Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 20:01
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2020-06-03 20:02:02
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 26928.12 | 581.34 | 581.34 |
Net Site Energy | 26928.12 | 581.34 | 581.34 |
Total Source Energy | 84080.08 | 1815.19 | 1815.19 |
Net Source Energy | 84080.08 | 1815.19 | 1815.19 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 41.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2482.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3172.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 339.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1955.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2049.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 342.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 984.30 | 0.00 | 0.00 | 0.00 | 0.00 | 4845.27 |
Humidification | 348.38 | 0.00 | 0.00 | 0.00 | 0.00 | 129.60 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 535.38 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 26351.42 | 576.70 | 0.00 | 0.00 | 0.00 | 7255.04 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 41.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1055.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 1427.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Lighting | LightsWired | 3172.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 339.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1895.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2049.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 342.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 114.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 869.32 | 0.00 | 0.00 | 0.00 | 0.00 | 4845.27 | |
Humidification | General | 348.38 | 0.00 | 0.00 | 0.00 | 0.00 | 129.60 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 535.38 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 75.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 134.01 | 12.45 | 0.00 | 0.00 | 0.00 | 0.16 |
Other | 359.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 568.89 | 12.45 | 0.00 | 0.00 | 0.00 | 0.16 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 75.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 134.01 | 12.45 | 0.00 | 0.00 | 0.00 | 0.16 |
Other | 359.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 568.89 | 12.45 | 0.00 | 0.00 | 0.00 | 0.16 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 26351.417 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 26351.417 | 100.00 |
Total On-Site and Utility Electric Sources | 26351.417 | 100.00 |
Total Electricity End Uses | 26351.417 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 7255.04 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 7255.04 | 100.00 |
Total Water End Uses | 7255.04 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 422.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1069.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | DUMMY BOILER |DXReportMonthly
| CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SHWSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| DATACENTER_EXTRAWATERHEATC | CORE_BOTTOM VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS_HEATC | VAV_BOT WITH REHEAT_HEATC | VAV_MID WITH REHEAT_HEATC | VAV_TOP WITH REHEAT_HEATC | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | DATACENTER_EXTRAELECHEATC | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |PlantLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | DATACENTER BASEMENT SUPPLY FAN | DATACENTER BOT SUPPLY FAN | DATACENTER MID SUPPLY FAN | DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SHWSYS1 PUMP | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 20:01 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 8.5035 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.5035 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.5035 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.5035 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.5035 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.5035 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.5035 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.5035 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.5035 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.5035 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.5035 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.5035 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.5035 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.5035 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.5035 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.5035 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.5035 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.5035 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.5035 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 8.5035 | 484.4232 | |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.5035 | 19.08 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.5035 | 19.08 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 18-AUG-15:00 | 12-JAN-06:19 | - | - | - | 16-OCT-11:09 |
Heating | 0.00 | 821255.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 456542.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 276093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 89246.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 114460.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 32894.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 79128.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7280.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1826736.82 | 828535.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 821255.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 310601.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 276093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3428.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 85555.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 114460.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 32894.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 29880.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 7280.88 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 44.79 | 0.00 | 0.00 | 0.00 |
Cooling | 7862.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10045.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1076.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46479.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6194.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6490.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1085.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3117.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1103.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 580.35 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 83454.94 | 625.14 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.97 | 0.00 | 0.00 | 0.00 |
Cooling | 169.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 216.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 133.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 140.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 67.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 23.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 12.53 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1801.69 | 13.50 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.97 | 0.00 | 0.00 | 0.00 |
Cooling | 169.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 216.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 133.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 140.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 67.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 23.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 12.53 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1801.69 | 13.50 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.44 |
DATACENTER BOT DIRECT AIR | 0.469975 |
DATACENTER MID DIRECT AIR | 4.48 |
DATACENTER TOP DIRECT AIR | 0.454921 |
DATACENTER BASEMENT DIRECT AIR | 21.54 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.74 | 0.331652 | 0.330000 | 1.89 | 0.884405 | 0.500000 | 0.001149 | 0.000413 | 1.89 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 53.95 | 0.352568 | 0.342000 | 18.45 | 0.940180 | 0.500000 | 0.001081 | 0.007467 | 18.45 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.27 | 0.360954 | 0.352000 | 1.85 | 0.962544 | 0.500000 | 0.001056 | 0.001276 | 1.85 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.790907 | 0.301958 | 0.300000 | 0.237272 | 0.805221 | 0.500000 | 0.001262 | 0.000099 | 0.237272 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.01 | 0.152278 | 0.200000 | 0.202137 | 0.406075 | 0.500000 | 0.002502 | 0.000085 | 0.202137 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.00 | 0.238332 | 0.237000 | 0.237491 | 0.635553 | 0.500000 | 0.001599 | 0.000140 | 0.237491 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.26 | 0.122061 | 0.200000 | 0.252177 | 0.325496 | 0.500000 | 0.003121 | 0.000063 | 0.252177 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 7.06 | 0.338277 | 0.328000 | 2.32 | 0.902072 | 0.500000 | 0.001126 | 0.002787 | 3.83 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 10.41 | 0.147869 | 0.200000 | 2.08 | 0.394318 | 0.500000 | 0.002577 | 0.001893 | 2.60 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 9.34 | 0.255745 | 0.248000 | 2.32 | 0.681986 | 0.500000 | 0.001490 | 0.002835 | 3.89 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 10.80 | 0.142508 | 0.200000 | 2.16 | 0.380022 | 0.500000 | 0.002674 | 0.001640 | 2.25 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.799887 | 0.298568 | 0.291000 | 0.232767 | 0.796181 | 0.500000 | 0.001276 | 0.000377 | 0.518056 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.03 | 0.149477 | 0.200000 | 0.205924 | 0.398606 | 0.500000 | 0.002549 | 0.000251 | 0.345284 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.02 | 0.234964 | 0.229000 | 0.232764 | 0.626570 | 0.500000 | 0.001622 | 0.000381 | 0.523168 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.14 | 0.134994 | 0.200000 | 0.228018 | 0.359984 | 0.500000 | 0.002822 | 0.000232 | 0.318278 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18701.63 | 0.000413 | 325.51 |
CORE_MID VAV BOX REHEAT COIL | 337977.85 | 0.007467 | 6291.27 |
CORE_TOP VAV BOX REHEAT COIL | 57741.41 | 0.001276 | 1185.46 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 4461.35 | 0.000099 | 83.30 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3826.97 | 0.000085 | 71.52 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6317.25 | 0.000140 | 124.86 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2869.62 | 0.000063 | 50.77 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 126129.16 | 0.002787 | 2632.28 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 85689.50 | 0.001893 | 1788.23 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 128311.06 | 0.002835 | 2677.77 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 74225.20 | 0.001640 | 1549.19 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 17058.37 | 0.000377 | 355.92 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11368.44 | 0.000251 | 237.20 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 17226.26 | 0.000381 | 359.42 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10481.23 | 0.000232 | 218.70 |
CAV_BAS_HEATC | 253165.35 | 0.005593 | 4740.17 |
VAV_BOT WITH REHEAT_HEATC | 28224.55 | 0.000624 | 429.51 |
VAV_MID WITH REHEAT_HEATC | 265371.50 | 0.005863 | 4036.31 |
VAV_TOP WITH REHEAT_HEATC | 27013.84 | 0.000597 | 410.88 |
DATACENTER_EXTRAWATERHEATC | 1021670.93 | 0.022573 | 19025.74 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
CAV_BAS | 5.44 | 5.44 | 5.44 | 5.44 | 5.44 | 5.44 | 1.00 | 1.00 | 5.44 |
VAV_BOT WITH REHEAT | 4.90 | 2.82 | 9.80 | 2.82 | 8.95 | 8.95 | 0.300000 | 0.315435 | 8.95 |
VAV_MID WITH REHEAT | 45.78 | 27.32 | 91.55 | 27.32 | 82.77 | 82.77 | 0.300000 | 0.330131 | 82.77 |
VAV_TOP WITH REHEAT | 4.63 | 2.75 | 9.26 | 3.41 | 8.43 | 8.43 | 0.300000 | 0.404155 | 8.43 |
AIRLOOP DATACENTER BASEMENT | 21.54 | 21.54 | 21.54 | 21.54 | 21.54 | 21.54 | 1.00 | 1.00 | 21.54 |
AIRLOOP DATACENTER BOT | 0.469975 | 0.469975 | 0.469975 | 0.469975 | 0.469975 | 0.469975 | 1.00 | 1.00 | 0.469975 |
AIRLOOP DATACENTER MID | 4.48 | 4.48 | 4.48 | 4.48 | 4.48 | 4.48 | 1.00 | 1.00 | 4.48 |
AIRLOOP DATACENTER TOP | 0.454921 | 0.454921 | 0.454921 | 0.454921 | 0.454921 | 0.454921 | 1.00 | 1.00 | 0.454921 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
CAV_BAS_OA_CONTROLLER | 5.44 | 1.20 |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.95 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 82.77 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 8.43 | |
AIRLOOP DATACENTER BASEMENT OA CONTROLLER | 21.54 | 0.338372 |
AIRLOOP DATACENTER BOT OA CONTROLLER | 0.469975 | |
AIRLOOP DATACENTER MID OA CONTROLLER | 4.48 | |
AIRLOOP DATACENTER TOP OA CONTROLLER | 0.454921 |
Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | |
CAV_BAS_COOLC | 96097.25 | 0.002748 | 5.44 | 0.008809 | 25.26 | 6.67 | 11.39 | 0.008436 |
VAV_BOT WITH REHEAT_COOLC | 168925.65 | 0.004831 | 8.95 | 0.008674 | 26.23 | 6.67 | 11.39 | 0.008436 |
VAV_MID WITH REHEAT_COOLC | 1592896.92 | 0.045557 | 82.77 | 0.008678 | 26.52 | 6.67 | 11.39 | 0.008436 |
VAV_TOP WITH REHEAT_COOLC | 158737.08 | 0.004540 | 8.43 | 0.008671 | 26.20 | 6.67 | 11.39 | 0.008436 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.44 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
CAV_BAS_COOLC_CONTROLLER | 0.002748 | 0.000173 |
CAV_BAS_HEATC_CONTROLLER | 0.005593 | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.004831 | 0.000099 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000624 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.045557 | 0.000010 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.005863 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.004540 | 0.000105 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000597 | |
DATACENTER_BAS_HEATC_CONTROLLER | 0.022573 | 0.000021 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.95 |
VAV_MID WITH REHEAT FAN | 82.77 |
VAV_TOP WITH REHEAT FAN | 8.43 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | 21.54 | 423349.74 | 301730.33 | 0.010368 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | 0.469975 | 9001.80 | 6498.24 | 0.000220 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | 4.48 | 85818.47 | 61942.75 | 0.002102 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | 0.454921 | 8718.08 | 6291.50 | 0.000214 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.54 | 21.54 | 21.54 | 21.54 | 423349.74 | 423349.74 | 14546.00 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.469975 | 0.469975 | 0.469975 | 0.469975 | 9001.80 | 9001.80 | 671.96 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.48 | 4.48 | 4.48 | 4.48 | 85818.47 | 85818.47 | 6719.65 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.454921 | 0.454921 | 0.454921 | 0.454921 | 8718.08 | 8718.08 | 671.96 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
DATACENTER BASEMENT SUPPLY FAN | 21.54 |
DATACENTER BOT SUPPLY FAN | 0.469975 |
DATACENTER MID SUPPLY FAN | 4.48 |
DATACENTER TOP SUPPLY FAN | 0.454921 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | 21.54 | 423349.74 | 0.010368 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | 0.469975 | 9001.80 | 0.000220 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | 4.48 | 85818.47 | 0.002102 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | 0.454921 | 8718.08 | 0.000214 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | 14546.00 | |
DATACENTER_EXTRAELECHEATC | 423349.74 | 10000000.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | 671.96 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | 6719.65 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | 671.96 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER BASEMENT HUMIDIFIER | 0.000084 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.057676 | 11032.72 |
HEATSYS1 PUMP | 0.055187 | 14099.45 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.057676 | 6.92 |
SHWSYS1 | 0.000440 | 0.052800 |
HEATSYS1 | 0.055187 | 6.62 |
COOLSYS1_SUPPLY | 0.057676 | 6.92 |
SINGLE WATER PLANT LOOP | 0.012903 | 1.55 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.057676 | 0.057676 | 242095.67 | 8.33 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SHWSYS1 PUMP | 0.000440 | 56.21 |
COOLSYS1 CHILLER1 PUMP | 0.028838 | 1838.79 |
COOLSYS1 CHILLER2 PUMP | 0.028838 | 1838.79 |
PLANT CIRC PUMP | 0.012903 | 3291.03 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000440 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2497831.47 | 1248915.74 | 0.055187 |
DUMMY BOILER | 531511.74 | 93894.07 | 0.012903 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.057676 | 0.029190 | 1021789.14 | 1028007.54 | 0.052118 |
COOLSYS1 CHILLER2 | 0.057676 | 0.029190 | 1021789.14 | 1028007.54 | 0.052118 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.012903 | 139666.47 | 60955.40 | 69833.23 | 7879.72 | 21575.63 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.104236 | 12.51 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.104236 | 22058.24 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 40.07 | 976416.06 | 8.01 | 122052.01 |
TOWERWATERSYS COOLTOWER 2 | 40.07 | 976416.06 | 8.01 | 122052.01 |
Design Water Flow Rate [m3/s] Equipment # 48 | |
WSHPPLANT OPERATION SCHEME | 0.042272 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 8.503 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.345 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 8.503 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 223.803 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 8.503 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 223.803 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 8.503 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 223.803 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | N/A | 0.000 | 8.503 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 492.927 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_SCH | BASEMENT | 2779.43 | 149.6 | 23634.824 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23634.824 |
2 | CORE_BOTTOM_LIGHTS | BLDG_LIGHT_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 21225.733 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21225.733 |
3 | CORE_MID_LIGHTS | BLDG_LIGHT_SCH | CORE_MID | 2496.12 | 134.4 | 21225.733 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21225.733 |
4 | CORE_TOP_LIGHTS | BLDG_LIGHT_SCH | CORE_TOP | 2496.12 | 134.4 | 21225.733 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21225.733 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2665.103 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2665.103 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1717.494 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1717.494 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2665.161 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2665.161 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1717.494 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1717.494 |
9 | PERIMETER_MID_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2665.103 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2665.103 |
10 | PERIMETER_MID_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1717.494 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1717.494 |
11 | PERIMETER_MID_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2665.161 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2665.161 |
12 | PERIMETER_MID_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1717.494 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1717.494 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2665.103 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2665.103 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1717.494 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1717.494 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2665.161 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2665.161 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1717.494 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1717.494 |
17 | DATACENTER_BASEMENT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 6664.009 | 8.503 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6664.009 |
18 | DATACENTER_BOT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 307.850 | 8.503 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 307.850 |
19 | DATACENTER_MID_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 307.850 | 8.503 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 307.850 |
20 | DATACENTER_TOP_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 307.850 | 8.503 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 307.850 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 379632.522 | 484.423 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL | 20 | 3 | 9 | 0.167 | 0.7800 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_EAST_CFACTOR | 30 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_SOUTH_CFACTOR | 31 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_NORTH_CFACTOR | 32 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 34 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 35 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.115 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1010000 | 2.1010000 | 2.1010000 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | -0.41768822E-14 | 0.27520919E-16 | -0.15672466E-09 | 0.83927561E-16 |
51 | 8 | 0.22856702E-07 | 0.10578700E-12 | 0.38803401E-03 | -0.25988854E-09 |
52 | 7 | -0.12546900E-01 | 0.54357740E-08 | -0.23525379E-01 | 0.14266284E-03 |
53 | 6 | 0.41364683 | 0.18861797E-05 | 0.47915075 | -0.48455579E-02 |
54 | 5 | -5.2715232 | 0.70271773E-04 | -4.4954566 | 0.64187715E-01 |
55 | 4 | 33.360936 | 0.57369956E-03 | 21.652120 | -0.42687724 |
56 | 3 | -111.98802 | 0.12481219E-02 | -56.042688 | 1.5262008 |
57 | 2 | 197.88617 | 0.70096321E-03 | 78.258916 | -2.9127067 |
58 | 1 | -171.44340 | 0.74721452E-04 | -55.366563 | 2.7504751 |
59 | 0 | 57.057407 | 0.42462867E-06 | 15.540328 | |
60 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
61 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
62 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
63 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
64 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
65 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
66 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
67 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
68 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
69 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
70 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
71 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
72 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
73 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
74 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
75 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
76 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
77 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
78 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
79 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
80 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
81 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
82 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
83 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
84 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
85 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
86 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
87 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
88 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
89 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
90 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
91 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
92 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
93 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
94 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
95 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
96 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
97 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
98 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
99 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
100 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
101 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
102 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
103 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
104 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
105 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
106 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
107 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.45_SHGC_0.25 | 29 | 1 | VerySmooth | 2.557 | 0.252 | 0.162 | 0.276 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.741E-005 | 4.376E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 74211.91763 | 74211.91763 | 5.44371 | 5.44371 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.20219E-003 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20008 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80000 | 5.05843E-003 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 78187.73298 | 78187.73298 | 5.73506 | 5.73506 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.20219E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07776 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 | |
5 | CORE_MID | Cooling | 735690.11682 | 735690.11682 | 53.94833 | 53.94833 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.20219E-003 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
6 | CORE_MID | Heating | 155659.02074 | 155659.02074 | 6.62714 | 10.77757 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
7 | CORE_TOP | Cooling | 71863.12558 | 71863.12558 | 5.26949 | 5.26949 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.20219E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
8 | CORE_TOP | Heating | 39412.41818 | 39412.41818 | 1.70032 | 1.70032 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 10683.37276 | 10683.37276 | 0.79091 | 0.79091 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 31.30000 | 8.20219E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 2122.46357 | 2122.46357 | 9.11718E-002 | 0.13532 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 13749.83722 | 13749.83722 | 1.01068 | 1.01068 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.20219E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 1833.91511 | 1833.91511 | 7.85555E-002 | 8.72074E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 13535.74159 | 13535.74159 | 1.00207 | 1.00207 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:40:00 | 30.61767 | 8.20219E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 3974.32795 | 3974.32795 | 0.17106 | 0.17106 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 17031.89293 | 17031.89293 | 1.26088 | 1.26088 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.20219E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 383.48302 | 383.48302 | 1.67484E-002 | 8.72074E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 95363.44650 | 95363.44650 | 7.05991 | 7.05991 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 31.30000 | 8.20219E-003 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 88335.80385 | 88335.80385 | 3.82769 | 3.82769 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 140593.18211 | 140593.18211 | 10.40819 | 10.40819 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 25.27767 | 8.20219E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 60007.70282 | 60007.70282 | 2.60084 | 2.60084 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 126141.64604 | 126141.64604 | 9.33844 | 9.33844 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 30.85500 | 8.20219E-003 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 89860.83297 | 89860.83297 | 3.89410 | 3.89410 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 145881.34098 | 145881.34098 | 10.79973 | 10.79973 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 30.29133 | 8.20219E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 51994.70455 | 51994.70455 | 2.25193 | 2.25193 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 10804.69566 | 10804.69566 | 0.79989 | 0.79989 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30000 | 8.20219E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 11941.21609 | 11941.21609 | 0.51806 | 0.51806 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 13908.00789 | 13908.00789 | 1.02962 | 1.02962 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 25.84133 | 8.20219E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 7957.76280 | 7957.76280 | 0.34528 | 0.34528 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 13729.82526 | 13729.82526 | 1.01644 | 1.01644 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.92917 | 8.20219E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 12058.55696 | 12058.55696 | 0.52317 | 0.52317 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 15400.20650 | 15400.20650 | 1.14009 | 1.14009 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 30.29133 | 8.20219E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 7337.68609 | 7337.68609 | 0.31828 | 0.31828 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8049.55477 | 8049.55477 | 0.46997 | 0.46997 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 28.94150 | 8.20219E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80000 | 5.05843E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 76726.47693 | 76726.47693 | 4.47969 | 4.47969 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 28.94150 | 8.20219E-003 | 36.20274 | 0.00000 | 0.15631 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15631 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80000 | 5.05843E-003 | 36.20274 | 0.00000 | 0.15631 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7791.73051 | 7791.73051 | 0.45492 | 0.45492 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 28.94150 | 8.20219E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80000 | 5.05843E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 368940.27652 | 368940.27652 | 21.54064 | 21.54064 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:10:00 | 22.68183 | 8.20219E-003 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33837 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80000 | 5.05843E-003 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | CAV_BAS | Cooling | Sensible | 74037.36 | 5.44371 | 5.44371 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | CAV_BAS | Heating | Sensible | 51589.39 | 1.20008 | 1.20008 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | VAV_BOT WITH REHEAT | Cooling | Sensible | 132405.80 | 8.94525 | 8.94525 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_BOT WITH REHEAT | Heating | Sensible | 16657.38 | 1.55856 | 1.55856 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
5 | VAV_MID WITH REHEAT | Cooling | Sensible | 1197102.29 | 82.76551 | 82.76551 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_MID WITH REHEAT | Heating | Sensible | 249580.27 | 23.35214 | 23.35214 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
7 | VAV_TOP WITH REHEAT | Cooling | Sensible | 133923.85 | 8.42522 | 8.42522 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
8 | VAV_TOP WITH REHEAT | Heating | Sensible | 27115.75 | 3.40510 | 3.40510 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:30:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 364380.97 | 21.54064 | 21.54064 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 14546.00 | 0.33837 | 0.33837 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 7961.12 | 0.46997 | 0.46997 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 671.96 | 1.56314E-002 | 1.56314E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 75900.42 | 4.47969 | 4.47969 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6719.65 | 0.15631 | 0.15631 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7710.24 | 0.45492 | 0.45492 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 671.96 | 1.56314E-002 | 1.56314E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.44371 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.73506 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33165 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.89257 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88440 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14880E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.13190E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.89257 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18701.62651 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.13190E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 325.50662 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 53.94833 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35257 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34200 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.45033 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.94018 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08064E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.46721E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.45033 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 337977.85099 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.46721E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6291.26833 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.26949 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36095 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35200 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.85486 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96254 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05554E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.27573E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.85486 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 57741.41339 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.27573E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1185.45781 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79091 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30196 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23727 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80522 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.26177E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.85681E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23727 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4461.35306 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.85681E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 83.30020 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.01068 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15228 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20214 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40608 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.50200E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.45523E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20214 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3826.97259 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.45523E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 71.51656 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.00207 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23833 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23700 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23749 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63555 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.59861E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.39572E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23749 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6317.25423 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.39572E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 124.85895 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.26088 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12206 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25218 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32550 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.12139E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.34007E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.25218 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2869.61569 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.34007E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 50.77274 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.05991 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33828 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32800 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.31565 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90207 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12630E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.78667E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.82769 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 126129.15997 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.78667E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2632.28027 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.40819 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14787 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.08164 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39432 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.57660E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.89320E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.60084 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 85689.49589 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.89320E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1788.23410 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.33844 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25574 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24800 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.31593 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68199 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.48977E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.83488E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.89410 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 128311.06074 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.83488E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2677.77466 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.79973 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14251 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.15995 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38002 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.67353E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.63992E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.25193 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 74225.20222 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.63992E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1549.18675 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79989 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29857 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29100 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23277 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79618 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.27609E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.76884E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.51806 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17058.37233 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.76884E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 355.92479 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.02962 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14948 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20592 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39861 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54888E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.51172E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34528 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11368.43656 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.51172E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 237.19755 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.01644 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23496 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22900 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23276 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62657 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.62153E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.80593E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.52317 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17226.25741 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.80593E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 359.42498 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.14009 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13499 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22802 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35998 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.82235E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.31570E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.31828 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10481.22759 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.31570E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 218.69878 |
212 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BOT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46997 |
213 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER MID DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.47969 |
214 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER TOP DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45492 |
215 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.54064 |
216 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.44371 |
217 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.44371 |
218 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.44371 |
219 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.44371 |
220 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.44371 |
221 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.44371 |
222 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
223 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.89980 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.82165 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.79961 |
227 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.82165 |
228 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.94525 |
229 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.94525 |
230 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31544 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 45.77730 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 27.32350 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 91.55460 |
235 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 27.32350 |
236 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 82.76551 |
237 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 82.76551 |
238 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.33013 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.62776 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.75433 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.25553 |
243 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.40510 |
244 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.42522 |
245 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.42522 |
246 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
247 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.40416 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.54064 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.54064 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.54064 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.54064 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.54064 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.54064 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46997 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46997 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46997 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46997 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46997 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.46997 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.47969 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.47969 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.47969 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.47969 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.47969 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.47969 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45492 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45492 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45492 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45492 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45492 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.45492 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.44371 |
281 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.94525 |
282 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 82.76551 |
283 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.42522 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.54064 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.46997 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.47969 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.45492 |
288 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.44371 |
289 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20008 |
290 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Coil Load [W] | 96097.25104 |
291 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 2.74837E-003 |
292 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 5.44371 |
293 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.80882E-003 |
294 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Temperature [C] | 25.25874 |
295 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
296 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Temperature [C] | 11.39498 |
297 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.43576E-003 |
298 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Rated Capacity [W] | 253165.35146 |
299 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 5.59338E-003 |
300 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 4740.17204 |
301 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.44371 |
302 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.74837E-003 |
303 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.73263E-004 |
304 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.59338E-003 |
305 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.94525 |
306 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 168925.65174 |
307 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 4.83125E-003 |
308 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 8.94525 |
309 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.67369E-003 |
310 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.23100 |
311 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
312 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.39463 |
313 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.43576E-003 |
314 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 28224.54933 |
315 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 6.23587E-004 |
316 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 429.50905 |
317 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.94525 |
318 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.83125E-003 |
319 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.85646E-005 |
320 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.23587E-004 |
321 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 82.76551 |
322 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 1592896.92401 |
323 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 4.55566E-002 |
324 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 82.76551 |
325 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.67753E-003 |
326 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.52103 |
327 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
328 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.39464 |
329 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.43576E-003 |
330 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 265371.49911 |
331 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 5.86306E-003 |
332 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 4036.30955 |
333 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 82.76551 |
334 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.55566E-002 |
335 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.04527E-005 |
336 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.86306E-003 |
337 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.42522 |
338 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 158737.07855 |
339 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 4.53986E-003 |
340 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 8.42522 |
341 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.67131E-003 |
342 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.20072 |
343 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
344 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.39462 |
345 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.43576E-003 |
346 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 27013.84015 |
347 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 5.96838E-004 |
348 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 410.88143 |
349 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.42522 |
350 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.53986E-003 |
351 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.04891E-004 |
352 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.96838E-004 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.54064 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33837 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.54064 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Total Cooling Capacity [W] | 423349.73790 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Sensible Cooling Capacity [W] | 301730.33336 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.03678E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.54064 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.54064 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.54064 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.54064 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 423349.73790 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 423349.73790 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 14545.99987 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.54064 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.54064 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Heating Capacity [W] | 423349.73790 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.03678E-002 |
371 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Design Size Nominal Capacity [W] | 14545.99987 |
372 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 8.43953E-005 |
373 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | Design Size Nominal Capacity [W] | 423349.73790 |
377 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | User-Specified Nominal Capacity [W] | 10000000.00000 |
378 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Rated Capacity [W] | 1021670.93110 |
379 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Maximum Water Flow Rate [m3/s] | 2.25726E-002 |
380 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size U-Factor Times Area Value [W/K] | 19025.74138 |
381 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.25726E-002 |
382 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Controller Convergence Tolerance | 2.10960E-005 |
383 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46997 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.46997 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Total Cooling Capacity [W] | 9001.79522 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Sensible Cooling Capacity [W] | 6498.24480 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.20453E-004 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46997 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46997 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46997 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46997 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9001.79522 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9001.79522 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 671.96493 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
396 | Fan:OnOff | DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46997 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.46997 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Heating Capacity [W] | 9001.79522 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.20453E-004 |
400 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Design Size Nominal Capacity [W] | 671.96493 |
401 | Controller:OutdoorAir | AIRLOOP DATACENTER MID OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.47969 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.47969 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Total Cooling Capacity [W] | 85818.46914 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Sensible Cooling Capacity [W] | 61942.74626 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.10169E-003 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.47969 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.47969 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.47969 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.47969 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 85818.46914 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 85818.46914 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6719.64934 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
414 | Fan:OnOff | DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.47969 |
415 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.47969 |
416 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Heating Capacity [W] | 85818.46914 |
417 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.10169E-003 |
418 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Design Size Nominal Capacity [W] | 6719.64934 |
419 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45492 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.45492 |
421 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Total Cooling Capacity [W] | 8718.08459 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Sensible Cooling Capacity [W] | 6291.50489 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.13505E-004 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45492 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45492 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45492 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45492 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 8718.08459 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 8718.08459 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 671.96493 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
432 | Fan:OnOff | DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45492 |
433 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.45492 |
434 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Heating Capacity [W] | 8718.08459 |
435 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.13505E-004 |
436 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Design Size Nominal Capacity [W] | 671.96493 |
437 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 5.76761E-002 |
438 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 11032.72348 |
439 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 5.76761E-002 |
440 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 6.92114 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 5.76761E-002 |
442 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 5.76761E-002 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 242095.66691 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
445 | PlantLoop | SHWSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
446 | PlantLoop | SHWSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
447 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
448 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Power Consumption [W] | 56.20535 |
449 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
450 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 5.51865E-002 |
451 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 6.62238 |
452 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 5.51865E-002 |
453 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 14099.45181 |
454 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2497831.47032 |
455 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1248915.73500 |
456 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 5.51865E-002 |
457 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 5.76761E-002 |
458 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 6.92114 |
459 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 2.88381E-002 |
460 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 1838.78725 |
461 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 2.88381E-002 |
462 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 1838.78725 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.76761E-002 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.91904E-002 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1021789.13924 |
466 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1028007.54000 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.21178E-002 |
468 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.76761E-002 |
469 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.91904E-002 |
470 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1021789.13924 |
471 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1028007.54000 |
472 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.21178E-002 |
473 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.29035E-002 |
474 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.54841 |
475 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.29035E-002 |
476 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3291.02638 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.29035E-002 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 60955.40265 |
480 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
481 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
482 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21575.62873 |
483 | Boiler:HotWater | DUMMY BOILER | Design Size Nominal Capacity [W] | 531511.73788 |
484 | Boiler:HotWater | DUMMY BOILER | User-Specified Nominal Capacity [W] | 93894.07000 |
485 | Boiler:HotWater | DUMMY BOILER | Design Size Design Water Flow Rate [m3/s] | 1.29035E-002 |
486 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10424 |
487 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.50827 |
488 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10424 |
489 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 22058.24281 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 40.06542 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 976416.05745 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 8.01308 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 122052.00718 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 40.06542 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 976416.05745 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 8.01308 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 122052.00718 |
498 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 4.22720E-002 |
499 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 4.22720E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 17742.69 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 320922.01 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 54789.14 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 4235.77 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3633.45 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 5995.57 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2722.04 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 119673.58 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 81303.72 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 121743.81 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 70426.17 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 16185.30 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 10786.58 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 16344.59 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 9944.78 |
16 | Coil:Heating:Water | CAV_BAS_HEATC | 205396.43 |
17 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | 23746.84 |
18 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | 222855.68 |
19 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | 22685.89 |
20 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | 821491.17 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | CAV_BAS_COOLC | 133964.28 | 95056.93 | 38907.35 | 0.71 | 35856.23 | 363.67 |
2 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | 228324.79 | 159508.38 | 68816.41 | 0.70 | 57578.61 | 583.99 |
3 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | 2126789.82 | 1481517.02 | 645272.80 | 0.70 | 517992.89 | 5253.77 |
4 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | 214870.84 | 150163.50 | 64707.35 | 0.70 | 54423.08 | 551.99 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.67 | 22.78 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.67 | 22.78 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 13 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.3963754059 | 0.4717516269 | Pass | Pass | 1.5199500977 | 2.2512689184 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.3586857181E-002 | 0.1060901422 | Pass | Pass | 2.1131606047E-002 | 0.1422113511 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.4235350738E-003 | 5.7890602686E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.5016782890E-002 | 9.4256037028E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.9550977648E-002 | 7.0155798408E-002 | Pass | Pass | 2.0874494079E-002 | 0.1406722413 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 7.1384731747E-002 | 0.1517218684 | Pass | Pass | 2.0869535126E-002 | 0.1413322048 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.5214119961E-002 | 9.9817636546E-002 | Pass | Pass | 2.0697342302E-002 | 0.1389071819 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.4376694330E-002 | 0.1149772303 | Pass | Pass | 2.1064435858E-002 | 0.1404479883 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.5101608963E-002 | 2.2390249843E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.1382147838E-002 | 0.1100446028 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.4578783597E-002 | 8.5825586482E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.8972818397E-002 | 3.5584600663E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.9157991443E-002 | 2.3576751472E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.0410833642E-002 | 0.1066201871 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.5717275463E-002 | 8.4904316365E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.3588761934E-002 | 3.6665901926E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.9154592242E-003 | 1.1003165696E-002 | Pass | Pass | 4.5043109616E-002 | 0.3293009206 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.1613428502E-003 | 6.7951585831E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.4639777274E-002 | 3.2558174566E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.7665575191E-014 | 3.5786475854E-014 | Pass | Pass | 2.5184536615E-003 | 1.7964358492E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.0329417162E-014 | 1.6093464249E-014 | Pass | Pass | 1.1235449471E-002 | 7.0682804226E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.0043161328E-002 | 3.3630313961E-002 | Pass | Pass | 0.1737487032 | 0.6492399030 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.5890426943E-004 | 2.2605395914E-004 | Pass | Pass | 4.4580046657E-005 | 3.7031178176E-005 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S | |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.45_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.557 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.45_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.557 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.45_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.557 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.45_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.557 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.45_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.557 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.45_SHGC_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.557 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.45_SHGC_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.557 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.45_SHGC_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.557 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.45_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.557 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.45_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.557 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.45_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.557 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.45_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.557 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.45_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.557 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.45_SHGC_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.557 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.45_SHGC_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.557 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.45_SHGC_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.557 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.45_SHGC_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.557 | 0.252 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.45_SHGC_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.557 | 0.252 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.45_SHGC_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.557 | 0.252 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.45_SHGC_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.557 | 0.252 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.45_SHGC_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.557 | 0.252 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.45_SHGC_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.557 | 0.252 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.45_SHGC_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.557 | 0.252 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.45_SHGC_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.557 | 0.252 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
Total or Average | 4635.80 | 2.557 | 0.252 | 0.276 | ||||||||||||
North Total or Average | 1390.74 | 2.557 | 0.252 | 0.276 | ||||||||||||
Non-North Total or Average | 3245.06 | 2.557 | 0.252 | 0.276 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 8.5035 | 2779.43 | 23634.82 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 48.39 | 0.0000 | Y | 214.69 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | 8.5035 | 2496.12 | 21225.73 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 48.39 | 0.0000 | Y | 192.81 |
CORE_MID_LIGHTS | CORE_MID | 8.5035 | 24961.20 | 212257.33 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 48.39 | 0.0000 | Y | 1928.09 |
CORE_TOP_LIGHTS | CORE_TOP | 8.5035 | 2496.12 | 21225.73 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 48.39 | 0.0000 | Y | 192.81 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | 8.5035 | 313.41 | 2665.10 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 28.03 | 0.0000 | Y | 14.02 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | 8.5035 | 201.98 | 1717.49 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.78 | 0.0000 | Y | 8.96 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | 8.5035 | 313.42 | 2665.16 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.43 | 0.0000 | Y | 13.72 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | 8.5035 | 201.98 | 1717.49 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.65 | 0.0000 | Y | 8.92 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | 8.5035 | 3134.13 | 26651.03 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.94 | 0.0000 | Y | 139.80 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | 8.5035 | 2019.75 | 17174.94 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.73 | 0.0000 | Y | 89.39 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | 8.5035 | 3134.20 | 26651.61 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.40 | 0.0000 | Y | 137.09 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | 8.5035 | 2019.75 | 17174.94 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.59 | 0.0000 | Y | 88.96 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | 8.5035 | 313.41 | 2665.10 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.94 | 0.0000 | Y | 13.98 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | 8.5035 | 201.98 | 1717.49 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.73 | 0.0000 | Y | 8.94 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | 8.5035 | 313.42 | 2665.16 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.40 | 0.0000 | Y | 13.71 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | 8.5035 | 201.98 | 1717.49 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.59 | 0.0000 | Y | 8.90 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | 8.5035 | 783.68 | 6664.01 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 62.55 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | 8.5035 | 36.20 | 307.85 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 2.89 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | 8.5035 | 362.03 | 3078.50 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 28.90 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | 8.5035 | 36.20 | 307.85 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 2.89 |
Interior Lighting Total | 8.5035 | 46320.38 | 393884.84 | 1001.01 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2665.10 | 1027.93 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2665.10 | 369.12 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1717.49 | 662.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1717.49 | 237.87 |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2665.16 | 1027.95 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2665.16 | 369.12 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1717.49 | 662.44 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1717.49 | 237.87 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2665.10 | 1027.93 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2665.10 | 369.12 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1717.49 | 662.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1717.49 | 237.87 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2665.16 | 1027.95 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2665.16 | 369.12 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1717.49 | 662.44 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1717.49 | 237.87 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2665.10 | 1027.93 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2665.10 | 369.12 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1717.49 | 662.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1717.49 | 237.87 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2665.16 | 1027.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2665.16 | 369.12 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1717.49 | 662.44 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1717.49 | 237.87 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12979.20 | AstronomicalClock | - | 42.14 | 42.14 | 102.68 | |
EXTERIOR_LIGHTS_B | 968.00 | AstronomicalClock | - | 83.75 | 62.95 | 11.44 | |
EXTERIOR_LIGHTS_C | 26027.00 | AstronomicalClock | - | 83.75 | 46.20 | 225.74 | |
Exterior Lighting Total | 39974.20 | 339.86 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2010445.42 | |||
HEATSYS1 BOILER | Boiler:HotWater | 1248915.74 | 0.81 | ||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1028007.54 | 5.33 | 6.67 | 22.78 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1028007.54 | 5.33 | 6.67 | 22.78 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||
DUMMY BOILER | Boiler:HotWater | 93894.07 | 0.80 | ||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 976416.06 | |||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 976416.06 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CAV_BAS_COOLC | Coil:Cooling:Water | 96097.25 | 133964.28 | 95056.93 | 38907.35 | 0.71 | - | 35856.23 | 363.67 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | 168925.65 | 228324.79 | 159508.38 | 68816.41 | 0.70 | - | 57578.61 | 583.99 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | 1592896.92 | 2126789.82 | 1481517.02 | 645272.80 | 0.70 | - | 517992.89 | 5253.77 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | 158737.08 | 214870.84 | 150163.50 | 64707.35 | 0.70 | - | 54423.08 | 551.99 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 423349.74 | 301730.33 | 121619.40 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9001.80 | 6498.24 | 2503.55 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Coil:Cooling:WaterToAirHeatPump:EquationFit | 85818.47 | 61942.75 | 23875.72 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Coil:Cooling:WaterToAirHeatPump:EquationFit | 8718.08 | 6291.50 | 2426.58 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 18701.63 | 17742.69 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 337977.85 | 320922.01 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 57741.41 | 54789.14 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 4461.35 | 4235.77 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 3826.97 | 3633.45 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6317.25 | 5995.57 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 2869.62 | 2722.04 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 126129.16 | 119673.58 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 85689.50 | 81303.72 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 128311.06 | 121743.81 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 74225.20 | 70426.17 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17058.37 | 16185.30 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11368.44 | 10786.58 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17226.26 | 16344.59 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 10481.23 | 9944.78 | - |
CAV_BAS_HEATC | Coil:Heating:Water | 253165.35 | 205396.43 | - |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | 28224.55 | 23746.84 | - |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | 265371.50 | 222855.68 | - |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | 27013.84 | 22685.89 | - |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Coil:Heating:WaterToAirHeatPump:EquationFit | 423349.74 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Coil:Heating:WaterToAirHeatPump:EquationFit | 9001.80 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Coil:Heating:WaterToAirHeatPump:EquationFit | 85818.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Coil:Heating:WaterToAirHeatPump:EquationFit | 8718.08 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | 14546.00 | 1.00 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | 10000000.00 | 1.00 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | 1021670.93 | 821491.17 | - |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | 671.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | 6719.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | 671.96 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.44 | 9230.66 | 1695.65 | 1.00 | 1.16 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.95 | 19330.20 | 2160.95 | 1.00 | 1.12 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 82.77 | 178851.87 | 2160.95 | 1.00 | 1.08 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.43 | 18206.46 | 2160.95 | 1.00 | 1.12 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.54 | 35713.80 | 1657.97 | 1.00 | 1.13 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 526.42 | 1120.11 | 1.00 | 1.63 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.48 | 5017.73 | 1120.11 | 1.00 | 1.16 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 509.56 | 1120.11 | 1.00 | 1.65 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 134283.83 | 0.057676 | 11032.72 | 191287.51 | 0.90 | General |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.055187 | 14099.45 | 255487.18 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 44761.28 | 0.028838 | 1838.79 | 63762.50 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 44761.28 | 0.028838 | 1838.79 | 63762.50 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.012903 | 3291.03 | 255050.01 | 0.90 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.104236 | 22058.24 | 211619.12 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 74211.92 | 74211.92 | 26.70 | 5.444 | 5.444 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00897 | 24.71 | 0.00820 | 1.200 | 0.00 |
CORE_BOTTOM | 78187.73 | 78187.73 | 31.32 | 5.735 | 5.735 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 24.71 | 0.00820 | 1.078 | 0.00 |
CORE_MID | 735690.12 | 735690.12 | 294.73 | 53.948 | 53.948 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 24.71 | 0.00820 | 10.778 | 0.00 |
CORE_TOP | 71863.13 | 71863.13 | 28.79 | 5.269 | 5.269 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 24.71 | 0.00820 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 10683.37 | 10683.37 | 34.09 | 0.791 | 0.791 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00885 | 31.30 | 0.00820 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 13749.84 | 13749.84 | 68.08 | 1.011 | 1.011 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00868 | 24.71 | 0.00820 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 13535.74 | 13535.74 | 43.19 | 1.002 | 1.002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:40:00 | 24.00 | 24.00 | 0.00878 | 30.62 | 0.00820 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 17031.89 | 17031.89 | 84.33 | 1.261 | 1.261 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00864 | 30.41 | 0.00820 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 95363.45 | 95363.45 | 304.27 | 7.060 | 7.060 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00889 | 31.30 | 0.00820 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 140593.18 | 140593.18 | 696.09 | 10.408 | 10.408 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 24.00 | 24.00 | 0.00867 | 25.28 | 0.00820 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 126141.65 | 126141.65 | 402.47 | 9.338 | 9.338 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 24.00 | 24.00 | 0.00879 | 30.86 | 0.00820 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 145881.34 | 145881.34 | 722.27 | 10.800 | 10.800 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 24.00 | 24.00 | 0.00866 | 30.29 | 0.00820 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 10804.70 | 10804.70 | 34.47 | 0.800 | 0.800 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00884 | 31.30 | 0.00820 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 13908.01 | 13908.01 | 68.86 | 1.030 | 1.030 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 24.00 | 24.00 | 0.00867 | 25.84 | 0.00820 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 13729.83 | 13729.83 | 43.81 | 1.016 | 1.016 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00877 | 30.93 | 0.00820 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 15400.21 | 15400.21 | 76.25 | 1.140 | 1.140 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 24.00 | 24.00 | 0.00866 | 30.29 | 0.00820 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8049.55 | 8049.55 | 222.35 | 0.470 | 0.470 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 27.00 | 27.00 | 0.00850 | 28.94 | 0.00820 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 76726.48 | 76726.48 | 2119.36 | 4.480 | 4.480 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 27.00 | 27.00 | 0.00850 | 28.94 | 0.00820 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7791.73 | 7791.73 | 215.22 | 0.455 | 0.455 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 27.00 | 27.00 | 0.00850 | 28.94 | 0.00820 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 368940.28 | 368940.28 | 470.78 | 21.541 | 21.541 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:10:00 | 27.00 | 27.00 | 0.00850 | 22.68 | 0.00820 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 1.078 | 0.00 | |
CORE_MID | 155659.02 | 155659.02 | 62.36 | 6.627 | 10.778 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 10.778 | 0.00 |
CORE_TOP | 39412.42 | 39412.42 | 15.79 | 1.700 | 1.700 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 2122.46 | 2122.46 | 6.77 | 0.091 | 0.135 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00671 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 1833.92 | 1833.92 | 9.08 | 0.079 | 0.087 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00687 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 3974.33 | 3974.33 | 12.68 | 0.171 | 0.171 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00717 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 383.48 | 383.48 | 1.90 | 0.017 | 0.087 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | 21.00 | 21.00 | 0.00675 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 88335.80 | 88335.80 | 281.85 | 3.828 | 3.828 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00763 | 3.80 | 0.00506 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 60007.70 | 60007.70 | 297.10 | 2.601 | 2.601 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00767 | 3.80 | 0.00506 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 89860.83 | 89860.83 | 286.71 | 3.894 | 3.894 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00765 | 3.80 | 0.00506 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 51994.70 | 51994.70 | 257.43 | 2.252 | 2.252 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00754 | 3.80 | 0.00506 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 11941.22 | 11941.22 | 38.10 | 0.518 | 0.518 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 7957.76 | 7957.76 | 39.40 | 0.345 | 0.345 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00784 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 12058.56 | 12058.56 | 38.47 | 0.523 | 0.523 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00783 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 7337.69 | 7337.69 | 36.33 | 0.318 | 0.318 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 3.80 | 0.00506 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 3.80 | 0.00506 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 3.80 | 0.00506 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 3.80 | 0.00506 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 3.80 | 0.00506 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CAV_BAS | 5.44 | 5.44 | 1.20 | 1.20 | 5.4437 | 5.4437 | 5.4437 | 1.0000 | 1.0000 |
VAV_BOT WITH REHEAT | 8.95 | 8.95 | 1.56 | 1.56 | 8.9452 | 2.8216 | 8.9452 | 0.3154 | 0.3000 |
VAV_MID WITH REHEAT | 82.77 | 82.77 | 23.35 | 23.35 | 82.7655 | 27.3235 | 82.7655 | 0.3301 | 0.3000 |
VAV_TOP WITH REHEAT | 8.43 | 8.43 | 3.41 | 3.41 | 8.4252 | 3.4051 | 8.4252 | 0.4042 | 0.3000 |
AIRLOOP DATACENTER BASEMENT | 21.54 | 21.54 | 0.34 | 0.34 | 21.5406 | 21.5406 | 21.5406 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.47 | 0.47 | 0.02 | 0.02 | 0.4700 | 0.4700 | 0.4700 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.48 | 4.48 | 0.16 | 0.16 | 4.4797 | 4.4797 | 4.4797 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.45 | 0.45 | 0.02 | 0.02 | 0.4549 | 0.4549 | 0.4549 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18701.627 | 18701.627 | 1.892570 | 0.00041319 | 325.507 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17742.69 | 18701.63 | 1.892570 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 18776.86 | 18776.86 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 337977.851 | 337977.851 | 18.450330 | 0.00746721 | 6291.268 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 320922.01 | 337977.85 | 18.450330 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 155659.02 | 0.00 | 339631.67 | 339631.67 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 57741.413 | 57741.413 | 1.854861 | 0.00127573 | 1185.458 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 54789.14 | 57741.41 | 1.854861 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 39412.42 | 0.00 | 58004.97 | 58004.97 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 4461.353 | 4461.353 | 0.237272 | 0.00009857 | 83.300 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4235.77 | 4461.35 | 0.237272 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00671500 | 42.6925 | 2122.46 | 0.00 | 4482.78 | 4482.78 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 3826.973 | 3826.973 | 0.202137 | 0.00008455 | 71.517 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3633.45 | 3826.97 | 0.202137 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00687046 | 43.6707 | 1833.92 | 0.00 | 3845.34 | 3845.34 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 6317.254 | 6317.254 | 0.237491 | 0.00013957 | 124.859 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5995.57 | 6317.25 | 0.237491 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00717333 | 45.5740 | 3974.33 | 0.00 | 6346.61 | 6346.61 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 2869.616 | 2869.616 | 0.252177 | 0.00006340 | 50.773 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | 2722.04 | 2869.62 | 0.252177 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00674634 | 42.8881 | 383.48 | 0.00 | 2880.86 | 2880.86 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 126129.160 | 126129.160 | 3.827689 | 0.00278667 | 2632.280 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 119673.58 | 126129.16 | 3.827689 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00763427 | 48.4669 | 88335.80 | 0.00 | 126705.01 | 126705.01 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 85689.496 | 85689.496 | 2.600845 | 0.00189320 | 1788.234 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 81303.72 | 85689.50 | 2.600845 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00767066 | 48.6949 | 60007.70 | 0.00 | 86080.72 | 86080.72 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 128311.061 | 128311.061 | 3.894103 | 0.00283488 | 2677.775 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 121743.81 | 128311.06 | 3.894103 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00764868 | 48.5572 | 89860.83 | 0.00 | 128896.88 | 128896.88 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 74225.202 | 74225.202 | 2.251927 | 0.00163992 | 1549.187 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 70426.17 | 74225.20 | 2.251927 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00753998 | 47.8760 | 51994.70 | 0.00 | 74564.09 | 74564.09 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 17058.372 | 17058.372 | 0.518056 | 0.00037688 | 355.925 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16185.30 | 17058.37 | 0.518056 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00782485 | 49.6605 | 11941.22 | 0.00 | 17136.25 | 17136.25 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 11368.437 | 11368.437 | 0.345284 | 0.00025117 | 237.198 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10786.58 | 11368.44 | 0.345284 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00783684 | 49.7355 | 7957.76 | 0.00 | 11420.34 | 11420.34 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 17226.257 | 17226.257 | 0.523168 | 0.00038059 | 359.425 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16344.59 | 17226.26 | 0.523168 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00782947 | 49.6894 | 12058.56 | 0.00 | 17304.90 | 17304.90 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 10481.228 | 10481.228 | 0.318278 | 0.00023157 | 218.699 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9944.78 | 10481.23 | 0.318278 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00778421 | 49.4061 | 7337.69 | 0.00 | 10529.08 | 10529.08 |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 96097.251 | -999.000 | 5.443713 | 0.00274837 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 96097.25 | 90125.55 | 5.443713 | 25.26 | 16.88 | 0.00880882 | 11.39 | 11.35 | 0.00843576 | 29.25 | 0.00820219 | 17.73 | 22.0453 | 24.00 | 0.00897177 | 47.3664 | 73246.55 | 0.00 | 108058.10 | 95258.80 |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 253165.351 | 253165.351 | 5.443713 | 0.00559338 | 4740.172 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 205396.43 | 237474.67 | 5.443713 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 22.0453 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 216760.71 | 216760.71 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 168925.652 | -999.000 | 8.945247 | 0.00483125 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 168925.65 | 162498.22 | 8.945247 | 26.23 | 17.10 | 0.00867369 | 11.39 | 11.93 | 0.00843576 | 31.30 | 0.00820219 | 18.40 | 28.3731 | 24.00 | 0.00882771 | 46.6159 | 112134.07 | 0.00 | 188678.31 | 168798.85 |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 28224.549 | 28224.549 | 2.683574 | 0.00062359 | 429.509 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 23746.84 | 28224.55 | 2.683574 | 3.80 | 3.80 | 0.00505843 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 94.5769 | 21.00 | 0.00766435 | 48.6530 | 8264.95 | 0.00 | 25118.05 | 25118.05 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1592896.924 | -999.000 | 82.765515 | 0.04555665 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1592896.92 | 1532458.56 | 82.765515 | 26.52 | 17.20 | 0.00867753 | 11.39 | 11.93 | 0.00843576 | 31.30 | 0.00820219 | 18.40 | 30.6654 | 24.00 | 0.00884914 | 46.7275 | 992390.92 | 0.00 | 1775794.05 | 1590653.78 |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 265371.499 | 265371.499 | 24.829654 | 0.00586306 | 4036.310 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 222855.68 | 265371.50 | 24.829654 | 3.80 | 3.80 | 0.00505843 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 102.2179 | 21.00 | 0.00780043 | 49.5072 | 445858.06 | 0.00 | 235729.57 | 235729.57 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 158737.079 | -999.000 | 8.425224 | 0.00453986 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 158737.08 | 152744.03 | 8.425224 | 26.20 | 17.09 | 0.00867131 | 11.39 | 11.93 | 0.00843576 | 31.30 | 0.00820219 | 18.40 | 30.1243 | 24.00 | 0.00884506 | 46.7062 | 113675.99 | 0.00 | 177343.31 | 158680.33 |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 27013.840 | 27013.840 | 2.527567 | 0.00059684 | 410.881 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22685.89 | 27013.84 | 2.527567 | 3.80 | 3.80 | 0.00505843 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 100.4143 | 21.00 | 0.00791044 | 50.1958 | 58090.93 | 0.00 | 23996.40 | 23996.40 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 423349.738 | 301730.333 | 21.540637 | 0.01036781 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:10:00 | 456263.49 | 456263.48 | -999.0 | 28.49 | 17.71 | 0.00849531 | 12.80 | 11.92 | 0.00849531 | 31.30 | 0.00820219 | 18.40 | -999.0000 | 27.00 | 0.00850000 | 37.5769 | 368349.02 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9001.795 | 6498.245 | 0.469975 | 0.00022045 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 9744.20 | 9744.20 | -999.0 | 28.03 | 17.55 | 0.00849009 | 12.80 | 11.92 | 0.00849009 | 28.94 | 0.00820219 | 17.62 | -999.0000 | 27.00 | 0.00850000 | 37.5769 | 8049.55 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 85818.469 | 61942.746 | 4.479688 | 0.00210169 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 92894.45 | 92894.45 | -999.0 | 28.03 | 17.56 | 0.00848961 | 12.80 | 11.92 | 0.00848961 | 28.94 | 0.00820219 | 17.62 | -999.0000 | 27.00 | 0.00850000 | 37.5769 | 76726.48 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 8718.085 | 6291.505 | 0.454921 | 0.00021351 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 9436.30 | 9436.30 | -999.0 | 28.04 | 17.56 | 0.00848977 | 12.80 | 11.92 | 0.00848977 | 29.16 | 0.00820219 | 17.70 | -999.0000 | 27.00 | 0.00850000 | 37.5769 | 7790.53 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 423349.738 | 423349.738 | 21.540637 | 0.01036781 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 423349.74 | 423349.74 | 21.540637 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 1.5709 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9001.795 | 9001.795 | 0.469975 | 0.00022045 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9001.80 | 9001.80 | 0.469975 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.3260 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 85818.469 | 85818.469 | 4.479688 | 0.00210169 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 85818.47 | 85818.47 | 4.479688 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.4894 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 8718.085 | 8718.085 | 0.454921 | 0.00021351 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8718.08 | 8718.08 | 0.454921 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.4361 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 14546.000 | 14546.000 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 14546.00 | 14546.00 | 21.540637 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 1.5709 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10000000.00 | 939681.36 | 21.540637 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 1.5709 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 1021670.931 | 1021670.931 | 21.540637 | 0.02257257 | 19025.741 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 821491.17 | 939681.36 | 21.540637 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 1.5709 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | 0.00 | 0.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 671.965 | 671.965 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 671.96 | 671.96 | 0.469975 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.3260 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6719.649 | 6719.649 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 6719.65 | 6719.65 | 4.479688 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.4894 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 671.965 | 671.965 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 671.96 | 671.96 | 0.454921 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.4361 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 18701.627 | 18701.627 | 1.892570 | 0.00041319 | 325.507 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.18090455 | 71.00 | 82.00 | 11.00 | 2548101.32 | 0.6963 | 0.748715 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17742.69 | 18701.63 | 1.0000 | 2.23659921 | 1.892570 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.41314744 | 60.00 | 49.00 | 11.00 | 0.000 | 17742.69 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 18776.86 | 18776.86 | 2.23659921 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 21.03 | 14.85 | 0.00800000 | 41455.1 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 337977.851 | 337977.851 | 18.450330 | 0.00746721 | 6291.268 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.18090455 | 71.00 | 82.00 | 11.00 | 2548101.32 | 12.5946 | 13.530851 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 320922.01 | 337977.85 | 1.0000 | 21.80420674 | 18.450330 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 7.46644590 | 60.00 | 49.00 | 11.00 | 0.000 | 320922.01 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.60 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 155659.02 | 0.00 | 339631.67 | 339631.67 | 21.80420674 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 28.08 | 17.37 | 0.00800000 | 48636.3 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 57741.413 | 57741.413 | 1.854861 | 0.00127573 | 1185.458 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.18090455 | 71.00 | 82.00 | 11.00 | 2548101.32 | 2.1502 | 2.311662 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 54789.14 | 57741.41 | 1.0000 | 2.19203480 | 1.854861 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 1.27559584 | 60.00 | 49.00 | 11.00 | 0.000 | 54789.14 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 39412.42 | 0.00 | 58004.97 | 58004.97 | 2.19203480 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 38.75 | 20.78 | 0.00800000 | 59521.5 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4461.353 | 4461.353 | 0.237272 | 0.00009857 | 83.300 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.18090455 | 71.00 | 82.00 | 11.00 | 2548101.32 | 0.1662 | 0.178609 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4235.77 | 4461.35 | 1.0000 | 0.28040325 | 0.237272 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.09855809 | 60.00 | 49.00 | 11.00 | 0.000 | 4235.77 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.88 | 0.00671500 | 21.00 | 0.00671500 | 42.6925 | 2122.46 | 0.00 | 4482.78 | 4482.78 | 0.28040325 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 28.48 | 17.50 | 0.00800000 | 49046.7 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3826.973 | 3826.973 | 0.202137 | 0.00008455 | 71.517 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.18090455 | 71.00 | 82.00 | 11.00 | 2548101.32 | 0.1426 | 0.153212 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3633.45 | 3826.97 | 1.0000 | 0.23888072 | 0.202137 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.08454366 | 60.00 | 49.00 | 11.00 | 0.000 | 3633.45 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.83 | 0.00687046 | 21.00 | 0.00687046 | 43.6707 | 1833.92 | 0.00 | 3845.34 | 3845.34 | 0.23888072 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 28.59 | 17.54 | 0.00800000 | 49157.2 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6317.254 | 6317.254 | 0.237491 | 0.00013957 | 124.859 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.18090455 | 71.00 | 82.00 | 11.00 | 2548101.32 | 0.2353 | 0.252910 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5995.57 | 6317.25 | 1.0000 | 0.28066151 | 0.237491 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.13955778 | 60.00 | 49.00 | 11.00 | 0.000 | 5995.57 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.87 | 0.00717333 | 21.00 | 0.00717333 | 45.5740 | 3974.33 | 0.00 | 6346.61 | 6346.61 | 0.28066151 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 34.98 | 19.62 | 0.00800000 | 55672.9 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2869.616 | 2869.616 | 0.252177 | 0.00006340 | 50.773 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.18090455 | 71.00 | 82.00 | 11.00 | 2548101.32 | 0.1068 | 0.114884 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | 2722.04 | 2869.62 | 1.0000 | 0.29801733 | 0.252177 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.06339418 | 60.00 | 49.00 | 11.00 | 0.000 | 2722.04 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00674634 | 21.00 | 0.00674634 | 42.8881 | 383.48 | 0.00 | 2880.86 | 2880.86 | 0.29801733 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 22.28 | 15.31 | 0.00800000 | 42726.6 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 126129.160 | 126129.160 | 3.827689 | 0.00278667 | 2632.280 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.18090455 | 71.00 | 82.00 | 11.00 | 2548101.32 | 4.6966 | 5.049546 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 119673.58 | 126129.16 | 1.0000 | 4.52348174 | 3.827689 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 2.78638540 | 60.00 | 49.00 | 11.00 | 0.000 | 119673.58 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00763427 | 21.00 | 0.00763427 | 48.4669 | 88335.80 | 0.00 | 126705.01 | 126705.01 | 4.52348174 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.27 | 21.23 | 0.00800000 | 61070.3 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 85689.496 | 85689.496 | 2.600845 | 0.00189320 | 1788.234 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.18090455 | 71.00 | 82.00 | 11.00 | 2548101.32 | 3.1908 | 3.430556 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 81303.72 | 85689.50 | 1.0000 | 3.07362272 | 2.600845 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 1.89301158 | 60.00 | 49.00 | 11.00 | 0.000 | 81303.72 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00767066 | 21.00 | 0.00767066 | 48.6949 | 60007.70 | 0.00 | 86080.72 | 86080.72 | 3.07362272 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.26 | 21.23 | 0.00800000 | 61066.1 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 128311.061 | 128311.061 | 3.894103 | 0.00283488 | 2677.775 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.18090455 | 71.00 | 82.00 | 11.00 | 2548101.32 | 4.7778 | 5.136898 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 121743.81 | 128311.06 | 1.0000 | 4.60196773 | 3.894103 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 2.83458691 | 60.00 | 49.00 | 11.00 | 0.000 | 121743.81 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00764868 | 21.00 | 0.00764868 | 48.5572 | 89860.83 | 0.00 | 128896.88 | 128896.88 | 4.60196773 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.27 | 21.23 | 0.00800000 | 61068.9 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 74225.202 | 74225.202 | 2.251927 | 0.00163992 | 1549.187 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.18090455 | 71.00 | 82.00 | 11.00 | 2548101.32 | 2.7639 | 2.971586 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 70426.17 | 74225.20 | 1.0000 | 2.66127945 | 2.251927 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 1.63974786 | 60.00 | 49.00 | 11.00 | 0.000 | 70426.17 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00753998 | 21.00 | 0.00753998 | 47.8760 | 51994.70 | 0.00 | 74564.09 | 74564.09 | 2.66127945 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.28 | 21.23 | 0.00800000 | 61078.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17058.372 | 17058.372 | 0.518056 | 0.00037688 | 355.925 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.18090455 | 71.00 | 82.00 | 11.00 | 2548101.32 | 0.6352 | 0.682927 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16185.30 | 17058.37 | 1.0000 | 0.61222714 | 0.518056 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.37684545 | 60.00 | 49.00 | 11.00 | 0.000 | 16185.30 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00782485 | 21.00 | 0.00782485 | 49.6605 | 11941.22 | 0.00 | 17136.25 | 17136.25 | 0.61222714 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61049.9 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11368.437 | 11368.437 | 0.345284 | 0.00025117 | 237.198 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.18090455 | 71.00 | 82.00 | 11.00 | 2548101.32 | 0.4233 | 0.455132 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10786.58 | 11368.44 | 1.0000 | 0.40804947 | 0.345284 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.25114609 | 60.00 | 49.00 | 11.00 | 0.000 | 10786.58 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00783684 | 21.00 | 0.00783684 | 49.7355 | 7957.76 | 0.00 | 11420.34 | 11420.34 | 0.40804947 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61047.5 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17226.257 | 17226.257 | 0.523168 | 0.00038059 | 359.425 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.18090455 | 71.00 | 82.00 | 11.00 | 2548101.32 | 0.6414 | 0.689649 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16344.59 | 17226.26 | 1.0000 | 0.61826822 | 0.523168 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.38055428 | 60.00 | 49.00 | 11.00 | 0.000 | 16344.59 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00782947 | 21.00 | 0.00782947 | 49.6894 | 12058.56 | 0.00 | 17304.90 | 17304.90 | 0.61826822 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61049.1 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10481.228 | 10481.228 | 0.318278 | 0.00023157 | 218.699 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.18090455 | 71.00 | 82.00 | 11.00 | 2548101.32 | 0.3903 | 0.419613 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9944.78 | 10481.23 | 1.0000 | 0.37613369 | 0.318278 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.23154629 | 60.00 | 49.00 | 11.00 | 0.000 | 9944.78 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00778421 | 21.00 | 0.00778421 | 49.4061 | 7337.69 | 0.00 | 10529.08 | 10529.08 | 0.37613369 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61052.7 | |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 96097.251 | -999.000 | 5.443713 | 0.00274837 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2151 | 1004.8586 | 1.1818 | CAV_BAS FAN | Fan:ConstantVolume | 5.443713 | 6.43326371 | 4197.9300 | 999.8980 | 57.67024865 | 15.00 | 6.67 | 8.33 | 2016656.91 | 4.7652 | 4.765176 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 96097.25 | 90125.55 | 1.0000 | 6.43326371 | 5.443713 | 25.26 | 16.88 | 0.00880882 | 47824.9 | 11.39 | 11.35 | 0.00843576 | 32888.2 | 2.74808885 | 6.67 | 13.38 | 8.33 | 9230.655 | 86866.60 | 29.25 | 0.00820219 | 17.73 | 1.20008137 | 22.0453 | 24.00 | 0.00900019 | 24.00 | 0.00897177 | 47.3664 | 73246.55 | 0.00 | 108058.10 | 95258.80 | 6.43326371 | 25.26 | 17.08 | 0.00880882 | 47824.9 | 10.76 | 10.75 | 0.00801961 | 31028.1 | |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 253165.351 | 253165.351 | 5.443713 | 0.00559338 | 4740.172 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | CAV_BAS FAN | Fan:ConstantVolume | 5.443713 | 6.43326371 | 4197.9300 | 999.8980 | 55.18090455 | 71.00 | 82.00 | 11.00 | 2548101.32 | 8.0608 | 10.135406 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 205396.43 | 237474.67 | 1.0000 | 6.43326371 | 5.443713 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 5.59280851 | 60.00 | 49.00 | 11.00 | 0.000 | 205396.43 | 3.80 | 0.00505843 | 3.80 | 1.20008137 | 22.0453 | 0.00 | 0.00000000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 216760.71 | 216760.71 | 6.43326371 | 12.80 | 3.49 | 0.00111515 | 15677.4 | 46.26 | 17.75 | 0.00111515 | 49371.1 | |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 168925.652 | -999.000 | 8.945247 | 0.00483125 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9640 | 1004.8586 | 1.1818 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.945247 | 10.57130200 | 4197.9300 | 999.8980 | 57.67024865 | 15.00 | 6.67 | 8.33 | 2016656.91 | 8.3765 | 8.376519 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 168925.65 | 162498.22 | 1.0000 | 10.57130200 | 8.945247 | 26.23 | 17.10 | 0.00867369 | 48473.3 | 11.39 | 11.93 | 0.00843576 | 34322.2 | 4.83075942 | 6.67 | 13.38 | 8.33 | 19330.202 | 149595.45 | 31.30 | 0.00820219 | 18.40 | 2.53804000 | 28.3731 | 24.00 | 0.00888133 | 24.00 | 0.00882771 | 46.6159 | 112134.07 | 0.00 | 188678.31 | 168798.85 | 10.57130200 | 26.23 | 17.30 | 0.00867369 | 48473.3 | 10.59 | 10.58 | 0.00792764 | 30625.1 | |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 28224.549 | 28224.549 | 2.683574 | 0.00062359 | 429.509 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.945247 | 10.57130200 | 4197.9300 | 999.8980 | 55.18090455 | 71.00 | 82.00 | 11.00 | 2548101.32 | 0.9319 | 1.129962 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 23746.84 | 28224.55 | 1.0000 | 3.17139060 | 2.683574 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 0.62352332 | 60.00 | 49.00 | 11.00 | 0.000 | 23746.84 | 3.80 | 0.00505843 | 3.80 | 2.53804000 | 94.5769 | 6.44 | 0.00209455 | 21.00 | 0.00766435 | 48.6530 | 8264.95 | 0.00 | 25118.05 | 25118.05 | 3.17139060 | 12.80 | 8.22 | 0.00489770 | 25227.3 | 20.61 | 11.68 | 0.00489770 | 33147.5 | |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1592896.924 | -999.000 | 82.765515 | 0.04555665 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9711 | 1004.8586 | 1.1818 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 82.765515 | 97.81051925 | 4197.9300 | 999.8980 | 57.67024865 | 15.00 | 6.67 | 8.33 | 2016656.91 | 78.9870 | 78.987007 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1592896.92 | 1532458.56 | 1.0000 | 97.81051925 | 82.765515 | 26.52 | 17.20 | 0.00867753 | 48779.2 | 11.39 | 11.93 | 0.00843576 | 34322.2 | 45.55200314 | 6.67 | 13.38 | 8.33 | 178851.869 | 1414045.05 | 31.30 | 0.00820219 | 18.40 | 25.38036000 | 30.6654 | 24.00 | 0.00892840 | 24.00 | 0.00884914 | 46.7275 | 992390.92 | 0.00 | 1775794.05 | 1590653.78 | 97.81051925 | 26.52 | 17.40 | 0.00867753 | 48779.2 | 10.59 | 10.58 | 0.00792659 | 30623.7 | |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 265371.499 | 265371.499 | 24.829654 | 0.00586306 | 4036.310 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 82.765515 | 97.81051925 | 4197.9300 | 999.8980 | 55.18090455 | 71.00 | 82.00 | 11.00 | 2548101.32 | 8.7460 | 10.624075 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 222855.68 | 265371.50 | 1.0000 | 29.34315577 | 24.829654 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 5.86246091 | 60.00 | 49.00 | 11.00 | 0.000 | 222855.68 | 3.80 | 0.00505843 | 3.80 | 25.38036000 | 102.2179 | 20.77 | 0.00780043 | 21.00 | 0.00780043 | 49.5072 | 445858.06 | 0.00 | 235729.57 | 235729.57 | 29.34315577 | 12.80 | 8.41 | 0.00505843 | 25633.1 | 20.72 | 11.89 | 0.00505843 | 33666.7 | |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 158737.079 | -999.000 | 8.425224 | 0.00453986 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9595 | 1004.8586 | 1.1818 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.425224 | 9.95675022 | 4197.9300 | 999.8980 | 57.67024865 | 15.00 | 6.67 | 8.33 | 2016656.91 | 7.8713 | 7.871298 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 158737.08 | 152744.03 | 1.0000 | 9.95675022 | 8.425224 | 26.20 | 17.09 | 0.00867131 | 48436.3 | 11.39 | 11.93 | 0.00843576 | 34322.2 | 4.53939724 | 6.67 | 13.38 | 8.33 | 18206.461 | 140530.62 | 31.30 | 0.00820219 | 18.40 | 2.53804000 | 30.1243 | 24.00 | 0.00887388 | 24.00 | 0.00884506 | 46.7062 | 113675.99 | 0.00 | 177343.31 | 158680.33 | 9.95675022 | 26.20 | 17.28 | 0.00867131 | 48436.3 | 10.59 | 10.58 | 0.00792768 | 30624.9 | |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 27013.840 | 27013.840 | 2.527567 | 0.00059684 | 410.881 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.425224 | 9.95675022 | 4197.9300 | 999.8980 | 55.18090455 | 71.00 | 82.00 | 11.00 | 2548101.32 | 0.8903 | 1.081492 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:30:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22685.89 | 27013.84 | 1.0000 | 2.98702507 | 2.527567 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 0.59677691 | 60.00 | 49.00 | 11.00 | 0.000 | 22685.89 | 3.80 | 0.00505843 | 3.80 | 2.53804000 | 100.4143 | 21.00 | 0.00794956 | 21.00 | 0.00791044 | 50.1958 | 58090.93 | 0.00 | 23996.40 | 23996.40 | 2.98702507 | 12.80 | 8.41 | 0.00505843 | 25633.1 | 20.72 | 11.89 | 0.00505843 | 33666.7 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 423349.738 | 301730.333 | 21.540637 | 0.01036781 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6324 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:10:00 | 456263.49 | 456263.48 | 0.9279 | -999.0 | -999.0 | 28.49 | 17.71 | 0.00849531 | 50328.8 | 12.80 | 11.92 | 0.00849531 | 34310.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 456263.49 | 31.30 | 0.00820219 | 18.40 | 0.33837161 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 368349.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9001.795 | 6498.245 | 0.469975 | 0.00022045 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6227 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 9744.20 | 9744.20 | 0.9238 | -999.0 | -999.0 | 28.03 | 17.55 | 0.00849009 | 49839.8 | 12.80 | 11.92 | 0.00849009 | 34297.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9744.20 | 28.94 | 0.00820219 | 17.62 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 8049.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 85818.469 | 61942.746 | 4.479688 | 0.00210169 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6218 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 92894.45 | 92894.45 | 0.9238 | -999.0 | -999.0 | 28.03 | 17.56 | 0.00848961 | 49841.8 | 12.80 | 11.92 | 0.00848961 | 34296.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92894.45 | 28.94 | 0.00820219 | 17.62 | 0.15631366 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 76726.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 8718.085 | 6291.505 | 0.454921 | 0.00021351 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6220 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 9436.30 | 9436.30 | 0.9239 | -999.0 | -999.0 | 28.04 | 17.56 | 0.00848977 | 49849.0 | 12.80 | 11.92 | 0.00848977 | 34296.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9436.30 | 29.16 | 0.00820219 | 17.70 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 7790.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 423349.738 | 423349.738 | 21.540637 | 0.01036781 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 423349.74 | 423349.74 | 1.0000 | 25.45626494 | 21.540637 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 423349.74 | 3.80 | 0.00505843 | 3.80 | 0.33837161 | 1.5709 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9001.795 | 9001.795 | 0.469975 | 0.00022045 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9001.80 | 9001.80 | 1.0000 | 0.55540588 | 0.469975 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9001.80 | 3.80 | 0.00505843 | 3.80 | 0.01563137 | 3.3260 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 85818.469 | 85818.469 | 4.479688 | 0.00210169 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 85818.47 | 85818.47 | 1.0000 | 5.29399919 | 4.479688 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85818.47 | 3.80 | 0.00505843 | 3.80 | 0.15631366 | 3.4894 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8718.085 | 8718.085 | 0.454921 | 0.00021351 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8718.08 | 8718.08 | 1.0000 | 0.53761644 | 0.454921 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8718.08 | 3.80 | 0.00505843 | 3.80 | 0.01563137 | 3.4361 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14546.000 | 14546.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.540637 | 25.45626494 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 14546.00 | 14546.00 | 1.0000 | 25.45626494 | 21.540637 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14546.00 | 3.80 | 0.00505843 | 3.80 | 0.33837161 | 1.5709 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | No | No | unknown | No | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.540637 | 25.45626494 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10000000.00 | 939681.36 | 1.0000 | 25.45626494 | 21.540637 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10000000.00 | 3.80 | 0.00505843 | 3.80 | 0.33837161 | 1.5709 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1021670.931 | 1021670.931 | 21.540637 | 0.02257257 | 19025.741 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.540637 | 25.45626494 | 4197.9300 | 999.8980 | 55.18090455 | 71.00 | 82.00 | 11.00 | 2548101.32 | 32.2393 | 40.902316 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 821491.17 | 939681.36 | 1.0000 | 25.45626494 | 21.540637 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 22.57026817 | 60.00 | 49.00 | 11.00 | 0.000 | 821491.17 | 3.80 | 0.00505843 | 3.80 | 0.33837161 | 1.5709 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | 0.00 | 0.00 | 25.45626494 | 16.60 | 4.14 | 0.00007946 | 16881.5 | 16.60 | 4.14 | 0.00007946 | 16881.5 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 671.965 | 671.965 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.469975 | 0.55540588 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 671.96 | 671.96 | 1.0000 | 0.55540588 | 0.469975 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 671.96 | 3.80 | 0.00505843 | 3.80 | 0.01563137 | 3.3260 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6719.649 | 6719.649 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.479688 | 5.29399919 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 6719.65 | 6719.65 | 1.0000 | 5.29399919 | 4.479688 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6719.65 | 3.80 | 0.00505843 | 3.80 | 0.15631366 | 3.4894 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 671.965 | 671.965 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.454921 | 0.53761644 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 671.96 | 671.96 | 1.0000 | 0.53761644 | 0.454921 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 671.96 | 3.80 | 0.00505843 | 3.80 | 0.01563137 | 3.4361 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.44 | - | |||
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 8.95 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 82.77 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 8.43 | - | |||
AIRLOOP DATACENTER BASEMENT OA CONTROLLER | DifferentialDryBulb | 0.34 | 21.54 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 4313.50 | 544.17 | 419.00 |
CORE_BOTTOM | 4281.17 | 128.50 | 1.17 |
CORE_MID | 2433.83 | 1352.67 | 13.33 |
CORE_TOP | 1876.83 | 2865.50 | 17.50 |
PERIMETER_BOT_ZN_3 | 2470.67 | 1852.83 | 0.00 |
PERIMETER_BOT_ZN_2 | 2582.50 | 2118.83 | 63.67 |
PERIMETER_BOT_ZN_1 | 3357.33 | 1332.67 | 102.67 |
PERIMETER_BOT_ZN_4 | 4585.50 | 577.33 | 212.17 |
PERIMETER_MID_ZN_3 | 1173.67 | 3913.00 | 38.00 |
PERIMETER_MID_ZN_2 | 1420.00 | 2953.50 | 71.67 |
PERIMETER_MID_ZN_1 | 2545.00 | 2365.50 | 113.00 |
PERIMETER_MID_ZN_4 | 2244.50 | 2887.67 | 101.00 |
PERIMETER_TOP_ZN_3 | 1433.17 | 4248.17 | 355.17 |
PERIMETER_TOP_ZN_2 | 1893.33 | 3544.67 | 189.67 |
PERIMETER_TOP_ZN_1 | 2326.67 | 2879.67 | 166.33 |
PERIMETER_TOP_ZN_4 | 2076.17 | 3432.67 | 258.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5351.17 | 4807.50 | 1069.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 73.00 | 0.00 | 7.00 |
CORE_BOTTOM | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 14.83 | 0.00 | 14.83 |
PERIMETER_BOT_ZN_1 | 0.00 | 200.00 | 0.00 | 200.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 73.33 | 0.00 | 42.67 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 11.83 | 0.00 | 11.83 |
PERIMETER_MID_ZN_1 | 0.00 | 290.83 | 0.00 | 290.83 |
PERIMETER_MID_ZN_4 | 0.00 | 24.50 | 0.00 | 18.67 |
PERIMETER_TOP_ZN_3 | 2.33 | 0.00 | 0.17 | 0.00 |
PERIMETER_TOP_ZN_2 | 1.17 | 8.17 | 0.00 | 8.17 |
PERIMETER_TOP_ZN_1 | 0.50 | 116.33 | 0.00 | 116.33 |
PERIMETER_TOP_ZN_4 | 0.33 | 23.83 | 0.00 | 18.17 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 207.83 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 2.67 | 710.50 | 0.17 | 422.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 1.891 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 1.180 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.923 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.868 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 1.041 | 0.031 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 1.446 | 0.032 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 1.469 | 0.031 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 2.266 | 0.032 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.818 | 0.069 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 1.229 | 0.074 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 1.284 | 0.070 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 1.479 | 0.072 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.824 | 0.086 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 1.279 | 0.089 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 1.238 | 0.086 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 1.513 | 0.089 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 26351.42 | 295107.57 | 14-MAY-02:50 | 1826736.82 | 18-AUG-16:00 |
Electricity:Building | 17848.33 | 217354.51 | 28-MAY-17:30 | 1099403.99 | 01-DEC-16:20 |
Electricity:Zone:BASEMENT | 639.09 | 14055.89 | 01-JAN-00:10 | 32720.90 | 02-JAN-08:10 |
InteriorLights:Electricity | 3172.03 | 10070.85 | 25-JUN-17:20 | 321032.30 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:BASEMENT | 214.69 | 598.35 | 01-JAN-00:10 | 19263.35 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3172.03 | 10070.85 | 25-JUN-17:20 | 321032.30 | 02-JAN-16:50 |
Electricity:Zone:CORE_BOTTOM | 482.42 | 4990.59 | 01-JAN-00:10 | 34506.47 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 192.81 | 537.36 | 01-JAN-00:10 | 17299.84 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4824.17 | 49905.77 | 01-JAN-00:10 | 345064.06 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1928.10 | 5373.60 | 01-JAN-00:10 | 172998.44 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 482.42 | 4990.58 | 01-JAN-00:10 | 34506.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 192.81 | 537.36 | 01-JAN-00:10 | 17299.84 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 50.39 | 622.57 | 16-APR-17:10 | 4332.72 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.02 | 57.42 | 01-JAN-09:10 | 2172.17 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 32.39 | 401.21 | 18-JUN-17:10 | 2792.17 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.96 | 37.00 | 01-JAN-07:20 | 1399.83 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 50.09 | 622.58 | 16-APR-17:10 | 4332.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.72 | 57.42 | 01-JAN-07:30 | 2172.22 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 32.35 | 401.21 | 12-MAR-17:10 | 2792.16 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.92 | 37.00 | 01-JAN-09:00 | 1399.83 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 503.44 | 6225.74 | 16-APR-17:10 | 43327.20 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 139.80 | 574.18 | 01-JAN-09:00 | 21721.68 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 323.74 | 4012.10 | 21-MAY-17:10 | 27921.70 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 89.39 | 370.02 | 01-JAN-07:20 | 13998.28 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 500.74 | 6225.83 | 16-APR-17:10 | 43328.00 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 137.09 | 574.19 | 01-JAN-07:30 | 21722.16 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 323.31 | 4012.08 | 12-MAR-17:10 | 27921.60 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 88.96 | 370.02 | 01-JAN-08:50 | 13998.28 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 50.34 | 622.57 | 16-APR-17:10 | 4332.72 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 13.98 | 57.42 | 01-JAN-09:00 | 2172.17 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 32.37 | 401.21 | 21-MAY-17:10 | 2792.17 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.94 | 37.00 | 01-JAN-07:20 | 1399.83 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 50.07 | 622.58 | 16-APR-17:10 | 4332.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.71 | 57.42 | 01-JAN-07:30 | 2172.22 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 32.33 | 401.21 | 12-MAR-17:10 | 2792.16 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.90 | 37.00 | 01-JAN-08:50 | 1399.83 | 02-JAN-16:50 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7557.41 | 95209.88 | 01-JAN-06:10 | 385063.96 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.55 | 301.75 | 01-JAN-06:10 | 5431.44 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 156.77 | 1962.54 | 01-JAN-06:10 | 8045.33 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 2.89 | 13.94 | 01-JAN-06:10 | 250.91 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1567.70 | 19625.45 | 01-JAN-06:10 | 80453.32 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 28.90 | 139.39 | 01-JAN-06:10 | 2509.10 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 156.77 | 1962.54 | 01-JAN-06:10 | 8045.33 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 2.89 | 13.94 | 01-JAN-06:10 | 250.91 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.31 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.88 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.07 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.36 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.43 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.43 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.65 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.36 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.43 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.43 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 01-APR-00:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
Electricity:HVAC | 3879.89 | 46488.13 | 14-MAY-05:40 | 352190.99 | 05-DEC-15:00 |
ExteriorEquipment:Electricity | 1955.89 | 13239.62 | 01-JAN-00:10 | 126040.41 | 24-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.99 | 979.82 | 01-JAN-00:10 | 3452.33 | 01-DEC-16:30 |
ElectricityPurchased:Facility | 26351.42 | 295107.57 | 14-MAY-02:50 | 1826736.82 | 18-AUG-16:00 |
ElectricityPurchased:Plant | 26351.42 | 295107.57 | 14-MAY-02:50 | 1826736.82 | 18-AUG-16:00 |
Cogeneration:ElectricityPurchased | 26351.42 | 295107.57 | 14-MAY-02:50 | 1826736.82 | 18-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 26351.42 | 295107.57 | 14-MAY-02:50 | 1826736.82 | 18-AUG-16:00 |
ElectricityNet:Plant | 26351.42 | 295107.57 | 14-MAY-02:50 | 1826736.82 | 18-AUG-16:00 |
Cogeneration:ElectricityNet | 26351.42 | 295107.57 | 14-MAY-02:50 | 1826736.82 | 18-AUG-16:00 |
Fans:Electricity | 2049.32 | 41767.51 | 01-JAN-12:10 | 133554.25 | 29-SEP-15:30 |
General:Fans:Electricity | 2049.32 | 41767.51 | 01-JAN-12:10 | 133554.25 | 29-SEP-15:30 |
ExteriorLights:Electricity | 339.86 | 0.00 | 01-JAN-07:00 | 39974.20 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 339.86 | 0.00 | 01-JAN-07:00 | 39974.20 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1895.08 | 12222.20 | 01-JAN-00:10 | 122221.98 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 2482.56 | 3445.10 | 23-JAN-08:00 | 456542.05 | 18-AUG-16:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 348.38 | 0.00 | 01-JAN-00:40 | 100000.00 | 07-JAN-04:10 |
Electricity:Plant | 2382.44 | 3914.68 | 03-JAN-07:10 | 422623.78 | 18-AUG-16:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:Electricity | 1055.37 | 0.00 | 01-JAN-00:10 | 310601.20 | 18-AUG-16:00 |
HeatRejection:Electricity | 984.30 | 525.41 | 03-JAN-07:00 | 79128.34 | 17-JAN-12:20 |
General:HeatRejection:Electricity | 114.98 | 0.00 | 01-JAN-00:10 | 29880.07 | 17-JAN-12:20 |
Pumps:Electricity | 342.77 | 3291.03 | 01-JAN-00:10 | 39272.68 | 30-OCT-13:40 |
General:Pumps:Electricity | 342.77 | 3291.03 | 01-JAN-00:10 | 39272.68 | 30-OCT-13:40 |
WIRED_LTG_ELECTRICITY | 89.13 | 0.00 | 01-JAN-00:10 | 9021.01 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 5334.88 | 88964.76 | 01-APR-00:10 | 305206.10 | 03-APR-07:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 576.70 | 7280.88 | 01-JAN-01:00 | 828535.99 | 12-JAN-06:20 |
Gas:Plant | 576.70 | 7280.88 | 01-JAN-01:00 | 828535.99 | 12-JAN-06:20 |
WaterSystems:Gas | 535.38 | 7280.88 | 01-JAN-01:00 | 72100.92 | 30-JAN-13:00 |
Water Heater:WaterSystems:Gas | 535.38 | 7280.88 | 01-JAN-01:00 | 72100.92 | 30-JAN-13:00 |
Heating:Gas | 41.32 | 0.00 | 01-JAN-00:10 | 821255.11 | 12-JAN-06:20 |
Boiler:Heating:Gas | 41.32 | 0.00 | 01-JAN-00:10 | 821255.11 | 12-JAN-06:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 12914.90 | 12891.71 | 01-JAN-07:00 | 2476055.06 | 18-AUG-15:50 |
PlantLoopCoolingDemand:HVAC | 12914.90 | 12891.71 | 01-JAN-07:00 | 2476055.06 | 18-AUG-15:50 |
CoolingCoils:PlantLoopCoolingDemand | 12914.90 | 12891.71 | 01-JAN-07:00 | 2476055.06 | 18-AUG-15:50 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 7255.04 | 0.00 | 01-JAN-00:40 | 0.00 | 16-OCT-11:10 |
Water:Plant | 7125.44 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
MainsWater:Facility | 7255.04 | 0.00 | 01-JAN-00:40 | 0.00 | 16-OCT-11:10 |
MainsWater:Plant | 7125.44 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:HVAC | 129.60 | 0.00 | 01-JAN-00:40 | 0.00 | 07-JAN-04:10 |
Humidifier:Water | 129.60 | 0.00 | 01-JAN-00:40 | 0.00 | 07-JAN-04:10 |
MainsWater:HVAC | 129.60 | 0.00 | 01-JAN-00:40 | 0.00 | 07-JAN-04:10 |
Humidifier:MainsWater | 129.60 | 0.00 | 01-JAN-00:40 | 0.00 | 07-JAN-04:10 |
HeatRejection:Water | 4845.27 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
HeatRejection:MainsWater | 4845.27 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 409.26 | 0.00 | 01-JAN-00:10 | 239226.71 | 09-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 379.65 | 0.00 | 01-JAN-00:10 | 43841.05 | 02-FEB-12:30 |
WaterSystems:PlantLoopHeatingDemand | 379.65 | 0.00 | 01-JAN-00:10 | 43841.05 | 02-FEB-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 52548.04 | 106015.67 | 01-JAN-05:30 | 9398203.30 | 18-AUG-15:50 |
EnergyTransfer:Building | 18916.12 | 93363.51 | 08-JAN-07:40 | 1391236.11 | 18-AUG-15:40 |
EnergyTransfer:Zone:BASEMENT | 700.40 | 0.00 | 01-JAN-00:10 | 78638.89 | 13-NOV-06:10 |
Heating:EnergyTransfer | 23.45 | 0.00 | 02-JAN-17:30 | 158423.79 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 6.72 | 0.00 | 01-JAN-00:10 | 56718.04 | 14-AUG-02:10 |
Cooling:EnergyTransfer | 18892.67 | 92844.06 | 08-JAN-07:40 | 1391236.11 | 18-AUG-15:40 |
Cooling:EnergyTransfer:Zone:BASEMENT | 693.69 | 0.00 | 01-JAN-00:10 | 78638.89 | 13-NOV-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 660.83 | 0.00 | 01-JAN-00:10 | 53540.57 | 13-NOV-10:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 660.83 | 0.00 | 01-JAN-00:10 | 53540.57 | 13-NOV-10:10 |
EnergyTransfer:Zone:CORE_MID | 4842.62 | 0.00 | 01-JAN-00:10 | 422298.59 | 14-OCT-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4842.62 | 0.00 | 01-JAN-00:10 | 422298.59 | 14-OCT-05:10 |
EnergyTransfer:Zone:CORE_TOP | 440.78 | 0.00 | 01-JAN-00:10 | 46323.61 | 16-OCT-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.11 | 0.00 | 01-JAN-00:10 | 23872.38 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 440.67 | 0.00 | 01-JAN-00:10 | 46323.61 | 16-OCT-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 72.57 | 0.00 | 01-JAN-00:10 | 8530.86 | 16-OCT-11:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 72.57 | 0.00 | 01-JAN-00:10 | 8530.86 | 16-OCT-11:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 64.03 | 0.00 | 01-JAN-00:10 | 10419.81 | 16-OCT-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 64.03 | 0.00 | 01-JAN-00:10 | 10419.81 | 16-OCT-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 103.27 | 0.00 | 01-JAN-00:10 | 15471.28 | 31-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 103.27 | 0.00 | 01-JAN-00:10 | 15471.28 | 31-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 103.23 | 0.00 | 01-JAN-00:10 | 14791.16 | 18-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 103.23 | 0.00 | 01-JAN-00:10 | 14791.16 | 18-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 507.68 | 0.00 | 01-JAN-00:10 | 72588.87 | 29-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.62 | 0.00 | 01-JAN-00:10 | 36249.17 | 30-MAR-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 507.06 | 0.00 | 01-JAN-00:10 | 72588.87 | 29-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 535.90 | 0.00 | 01-JAN-00:10 | 102445.59 | 19-JUL-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.31 | 0.00 | 01-JAN-00:10 | 28696.22 | 30-MAR-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 535.59 | 0.00 | 01-JAN-00:10 | 102445.59 | 19-JUL-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 868.77 | 0.00 | 01-JAN-00:10 | 151803.07 | 31-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.11 | 0.00 | 01-JAN-00:10 | 28692.39 | 30-MAR-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 868.66 | 0.00 | 01-JAN-00:10 | 151803.07 | 31-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 615.25 | 0.00 | 01-JAN-00:10 | 121305.12 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.09 | 0.00 | 01-JAN-00:10 | 23498.73 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 615.17 | 0.00 | 01-JAN-00:10 | 121305.12 | 29-SEP-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 49.16 | 0.00 | 01-JAN-00:10 | 9664.88 | 09-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 1.57 | 0.00 | 01-JAN-00:10 | 9664.88 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 47.60 | 0.00 | 01-JAN-00:10 | 7979.37 | 29-SEP-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 51.18 | 0.00 | 01-JAN-00:10 | 10134.12 | 19-JUL-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.67 | 0.00 | 01-JAN-00:10 | 6558.61 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 50.52 | 0.00 | 01-JAN-00:10 | 10134.12 | 19-JUL-09:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 81.33 | 0.00 | 01-JAN-00:10 | 15956.00 | 31-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.60 | 0.00 | 01-JAN-00:10 | 7983.47 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 80.72 | 0.00 | 01-JAN-00:10 | 15956.00 | 31-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 60.21 | 0.00 | 01-JAN-00:10 | 12636.00 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.38 | 0.00 | 01-JAN-00:10 | 4743.68 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 59.83 | 0.00 | 01-JAN-00:10 | 12636.00 | 29-SEP-15:30 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 65.73 | 0.00 | 01-JAN-00:10 | 7052.08 | 16-OCT-15:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.73 | 0.00 | 01-JAN-00:10 | 2664.89 | 26-FEB-15:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 65.01 | 0.00 | 01-JAN-00:10 | 7052.08 | 16-OCT-15:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 385.89 | 0.00 | 01-JAN-00:10 | 48182.37 | 17-OCT-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.57 | 0.00 | 01-JAN-00:10 | 18533.09 | 23-APR-14:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 381.32 | 0.00 | 01-JAN-00:10 | 48182.37 | 17-OCT-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 62.60 | 0.00 | 01-JAN-00:10 | 14158.33 | 16-OCT-13:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 6.83 | 0.00 | 01-JAN-00:10 | 9195.02 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 55.77 | 0.00 | 01-JAN-00:10 | 14158.33 | 16-OCT-13:10 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.49 | 1108.23 | 09-JAN-07:40 | 7963.94 | 06-AUG-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.49 | 1108.23 | 09-JAN-07:40 | 7963.94 | 06-AUG-18:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1247.21 | 3864.22 | 09-JAN-07:00 | 73384.31 | 06-AUG-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1247.21 | 3864.22 | 09-JAN-07:00 | 73384.31 | 06-AUG-18:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 117.30 | 0.01 | 05-JAN-05:40 | 7429.02 | 20-AUG-17:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.15 | 0.00 | 02-JAN-10:40 | 530.31 | 09-JAN-04:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 117.15 | 0.00 | 01-JAN-00:10 | 7429.02 | 20-AUG-17:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7140.68 | 87291.83 | 14-MAY-07:00 | 368098.47 | 18-AUG-19:30 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7140.68 | 87291.83 | 14-MAY-07:00 | 368098.47 | 18-AUG-19:30 |
EnergyTransfer:Plant | 21928.21 | 0.00 | 01-JAN-00:10 | 5678939.97 | 18-AUG-15:50 |
WaterSystems:EnergyTransfer | 379.65 | 0.00 | 01-JAN-00:10 | 43841.05 | 02-FEB-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 379.65 | 0.00 | 01-JAN-00:10 | 43841.05 | 02-FEB-12:30 |
EnergyTransfer:HVAC | 11703.71 | 10647.58 | 01-JAN-06:50 | 2328540.53 | 18-AUG-15:50 |
HeatingCoils:EnergyTransfer | 29.61 | 0.00 | 01-JAN-00:10 | 224371.41 | 09-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 29.61 | 0.00 | 01-JAN-00:10 | 224371.41 | 09-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 29.61 | 0.00 | 01-JAN-00:10 | 224371.41 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 11674.10 | 10646.85 | 01-JAN-07:00 | 2328540.53 | 18-AUG-15:50 |
LoopToLoop:EnergyTransfer | 6832.29 | 0.00 | 01-JAN-00:10 | 1806236.20 | 18-AUG-15:50 |
Boilers:EnergyTransfer | 29.18 | 0.00 | 01-JAN-00:10 | 666912.25 | 12-JAN-06:20 |
Chillers:EnergyTransfer | 6815.86 | 0.00 | 01-JAN-00:10 | 1774561.16 | 18-AUG-16:00 |
HeatRejection:EnergyTransfer | 7871.23 | 0.00 | 01-JAN-00:10 | 2085162.37 | 18-AUG-16:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 6.716 | -693.694 | 0.000 | 0.000 | 92.700 | 214.693 | 424.397 | 0.000 | 0.000 | 0.000 | 0.008 | 0.000 | 0.000 | 0.000 | 0.000 | -44.812 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -660.835 | 0.000 | 0.000 | 83.444 | 192.810 | 289.609 | 0.000 | 0.000 | 0.000 | 94.973 | 0.000 | 0.000 | 0.000 | 0.000 | -0.005 |
CORE_MID | 0.000 | 0.000 | 0.000 | -4842.629 | 0.000 | 0.000 | 838.973 | 1928.097 | 2896.074 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -820.516 |
CORE_TOP | 0.000 | 0.000 | 0.107 | -440.670 | 0.000 | 0.000 | 85.457 | 192.810 | 289.607 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -127.311 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -72.568 | 0.000 | 0.000 | 10.555 | 14.023 | 36.365 | 17.612 | 0.000 | 0.022 | 49.498 | 0.000 | -52.782 | 0.000 | -2.725 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -64.034 | 0.000 | 0.000 | 6.812 | 8.956 | 23.435 | 45.633 | 0.000 | 0.014 | 13.370 | 0.000 | -32.413 | 0.000 | -1.774 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -103.274 | 0.000 | 0.000 | 10.484 | 13.723 | 36.365 | 87.070 | 0.000 | 0.018 | 9.150 | 0.000 | -50.755 | 0.000 | -2.782 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -103.228 | 0.000 | 0.000 | 6.755 | 8.916 | 23.435 | 51.427 | 0.000 | 0.013 | 53.587 | 0.000 | -38.854 | 0.000 | -2.051 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.622 | -507.059 | 0.000 | 0.000 | 109.148 | 139.797 | 363.647 | 194.564 | 0.000 | 0.590 | 222.928 | 0.000 | -470.765 | 0.000 | -53.473 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.309 | -535.591 | 0.000 | 0.000 | 51.138 | 89.394 | 234.348 | 459.917 | 0.000 | 0.310 | 40.627 | 0.000 | -303.120 | 0.000 | -37.333 | -0.005 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.110 | -868.673 | 0.000 | 0.000 | 105.581 | 137.091 | 363.653 | 869.124 | 0.000 | 0.395 | 0.020 | 0.000 | -488.461 | 0.000 | -59.734 | -59.085 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.089 | -615.168 | 0.000 | 0.000 | 70.005 | 88.964 | 234.347 | 529.983 | 0.000 | 0.355 | 64.407 | 0.000 | -333.411 | 0.000 | -39.572 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 1.565 | -47.596 | 0.000 | 0.000 | 11.170 | 13.979 | 36.365 | 20.215 | 0.000 | 0.080 | 14.040 | 0.000 | -43.731 | 0.000 | -6.087 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.666 | -50.517 | 0.000 | 0.000 | 7.030 | 8.939 | 23.435 | 46.547 | 0.000 | 0.039 | 0.000 | 0.000 | -28.567 | 0.000 | -4.307 | -3.264 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.603 | -80.725 | 0.000 | 0.000 | 10.751 | 13.709 | 36.365 | 87.674 | 0.000 | 0.050 | 0.001 | 0.000 | -46.014 | 0.000 | -6.905 | -15.507 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.384 | -59.826 | 0.000 | 0.000 | 7.150 | 8.896 | 23.435 | 53.269 | 0.000 | 0.047 | 2.695 | 0.000 | -31.446 | 0.000 | -4.602 | -0.002 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -139.486 | 0.000 | 0.000 | 0.000 | 2.890 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -17.284 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1247.212 | 0.000 | 0.000 | 0.000 | 28.897 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -320.490 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.149 | -117.152 | 0.000 | 0.000 | 0.000 | 2.890 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -39.768 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7140.698 | 0.000 | 0.000 | 0.000 | 62.553 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -416.712 |
GROUNDFLOOR_PLENUM | 0.728 | -65.005 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.033 | 70.013 | 0.000 | 0.000 | 0.000 | -5.768 | 0.000 |
MIDFLOOR_PLENUM | 4.573 | -381.314 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.677 | 473.102 | 0.000 | 0.000 | 0.000 | -97.037 | 0.000 |
TOPFLOOR_PLENUM | 6.833 | -55.770 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.061 | 59.155 | 0.000 | 0.000 | 0.000 | -10.279 | -0.000 |
Total Facility | 12.134 | -502.090 | 11.320 | -18390.635 | 0.000 | 0.000 | 1507.154 | 3172.025 | 14676.305 | 2463.036 | 0.000 | 2.704 | 1167.574 | 0.000 | -1920.320 | 0.000 | -334.429 | -1864.763 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 30-OCT-03:33 | 0.00 | 0.00 | 0.00 | -116986.96 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 102931.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 04-OCT-04:12 | 0.00 | 0.00 | 0.00 | -85755.96 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 79280.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-OCT-04:11 | 0.00 | 0.00 | 0.00 | -774354.72 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 709604.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | -76878.16 | 0.00 | 0.00 | 846.25 | 537.36 | 7647.36 | 0.00 | 0.00 | 0.00 | 67847.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 05-OCT-04:11 | 0.00 | 0.00 | 0.00 | -9360.86 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 9705.39 | 0.00 | -1157.56 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 23-JUL-08:22 | 0.00 | 0.00 | 0.00 | -17923.59 | 0.00 | 0.00 | 23.93 | 37.00 | 464.11 | 12880.95 | 0.00 | 0.00 | 4543.88 | 0.00 | -0.00 | 0.00 | -26.28 | 0.00 |
PERIMETER_BOT_ZN_1 | 25-DEC-13:22 | 0.00 | 0.00 | 0.00 | -19064.57 | 0.00 | 0.00 | 33.95 | 57.42 | 720.19 | 21569.78 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -114.78 | -3201.99 |
PERIMETER_BOT_ZN_4 | 06-AUG-16:32 | 0.00 | 0.00 | 0.00 | -22508.10 | 0.00 | 0.00 | 18.81 | 37.00 | 464.11 | 12460.07 | 0.00 | 0.00 | 9616.27 | 0.00 | -0.00 | 0.00 | -88.16 | 0.00 |
PERIMETER_MID_ZN_3 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | -80254.58 | 0.00 | 0.00 | 1131.42 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 78552.38 | 0.00 | -9699.13 | 0.00 | -7.25 | 0.00 |
PERIMETER_MID_ZN_2 | 23-JUL-08:52 | 0.00 | 0.00 | 0.00 | -184992.34 | 0.00 | 0.00 | 236.68 | 370.02 | 4641.14 | 114263.82 | 0.00 | 0.00 | 66386.11 | 0.00 | -0.00 | 0.00 | -905.44 | 0.00 |
PERIMETER_MID_ZN_1 | 15-OCT-13:01 | 0.00 | 0.00 | 0.00 | -184641.97 | 0.00 | 0.00 | 322.07 | 574.19 | 7201.95 | 180044.82 | 0.00 | 2132.82 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5633.88 |
PERIMETER_MID_ZN_4 | 15-OCT-15:41 | 0.00 | 0.00 | 0.00 | -202416.94 | 0.00 | 0.00 | 214.11 | 370.02 | 4641.11 | 130855.17 | 0.00 | 531.76 | 65804.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | -9633.69 | 0.00 | 0.00 | 111.25 | 67.47 | 960.25 | 0.00 | 0.00 | 0.00 | 9469.83 | 0.00 | -974.38 | 0.00 | -0.73 | 0.00 |
PERIMETER_TOP_ZN_2 | 15-OCT-08:32 | 0.00 | 0.00 | 0.00 | -17974.53 | 0.00 | 0.00 | 24.28 | 37.00 | 464.11 | 13111.31 | 0.00 | 227.76 | 4110.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 19-NOV-12:52 | 0.00 | 0.00 | 0.00 | -19426.70 | 0.00 | 0.00 | 34.51 | 57.42 | 720.19 | 20567.01 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -158.66 | -1793.78 |
PERIMETER_TOP_ZN_4 | 15-OCT-15:51 | 0.00 | 0.00 | 0.00 | -21429.13 | 0.00 | 0.00 | 20.98 | 37.00 | 464.11 | 12333.96 | 0.00 | 48.85 | 8524.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 06-AUG-18:03 | 0.00 | 0.00 | 0.00 | -7980.15 | 0.00 | 0.00 | 0.00 | 15.39 | 7794.42 | 0.00 | 0.00 | 0.00 | 170.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 06-AUG-17:58 | 0.00 | 0.00 | 0.00 | -73384.31 | 0.00 | 0.00 | 0.00 | 153.92 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4713.84 |
DATACENTER_TOP_ZN_6 | 20-AUG-17:40 | 0.00 | 0.00 | 0.00 | -7429.02 | 0.00 | 0.00 | 0.00 | 15.39 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -380.80 |
DATACENTER_BASEMENT_ZN_6 | 26-DEC-01:11 | 0.00 | 0.00 | 0.00 | -375817.01 | 0.00 | 0.00 | 0.00 | 333.20 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4148.71 |
GROUNDFLOOR_PLENUM | 16-OCT-05:01 | 0.00 | -8478.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8540.89 | 0.00 | -0.00 | 0.00 | -61.99 | 0.00 |
MIDFLOOR_PLENUM | 17-OCT-16:00 | 0.00 | -48193.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.65 | 47786.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 16-OCT-13:10 | 0.00 | -14159.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.17 | 13888.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:03 | 0.00 | 36323.92 | 0.00 | -1552894.22 | 0.00 | 0.00 | 15870.88 | 10647.58 | 616289.16 | 0.00 | 0.00 | 0.00 | 934435.30 | 0.00 | -59400.18 | 0.00 | -1272.42 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-AUG-18:30 | 0.00 | 0.00 | 122437.55 | 0.00 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -136493.45 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-05:11 | 0.00 | 0.00 | 53857.96 | -0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -60332.94 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 30-MAR-05:02 | 0.00 | 0.00 | 83163.42 | -0.00 | 0.00 | 0.00 | 1473.39 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -40935.75 | 0.00 | -2783.70 | -51194.52 |
PERIMETER_MID_ZN_2 | 30-MAR-05:02 | 0.00 | 0.00 | 91458.93 | -0.00 | 0.00 | 0.00 | 959.82 | 434.81 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -27519.23 | 0.00 | -1865.14 | -69657.37 |
PERIMETER_MID_ZN_1 | 30-MAR-05:02 | 0.00 | 0.00 | 108474.91 | -0.00 | 0.00 | 0.00 | 1463.62 | 674.72 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -42306.94 | 0.00 | -2837.04 | -75071.86 |
PERIMETER_MID_ZN_4 | 09-JAN-06:03 | 0.00 | 0.00 | 75923.26 | -0.00 | 0.00 | 0.00 | 941.50 | 434.81 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -32695.63 | 0.00 | -1683.88 | -49108.21 |
PERIMETER_TOP_ZN_3 | 09-JAN-05:11 | 0.00 | 0.00 | 10931.42 | -0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3554.54 | 0.00 | -770.20 | -7419.71 |
PERIMETER_TOP_ZN_2 | 09-JAN-05:11 | 0.00 | 0.00 | 12330.93 | -0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2456.77 | 0.00 | -535.83 | -9862.28 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 13448.75 | -0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1877.48 | 0.00 | -869.58 | -11514.74 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:11 | 0.00 | 0.00 | 11597.91 | -0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1365.66 | 0.00 | -631.24 | -10124.96 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 11-JAN-05:12 | 0.00 | 0.00 | 541.09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2520.48 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 12-NOV-10:21 | 10244.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -105.64 | -10138.50 |
MIDFLOOR_PLENUM | 28-FEB-06:02 | 56423.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2801.42 | -53622.17 |
TOPFLOOR_PLENUM | 22-JUN-05:03 | 13268.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -87.69 | -13180.39 |
Total Facility | 30-MAR-05:02 | -961686.21 | 998902.52 | 384218.79 | -998902.52 | 0.00 | 0.00 | 17628.63 | 10647.58 | 497997.76 | 0.00 | 0.00 | 0.00 | 235788.30 | 0.00 | -167715.11 | 0.00 | -16879.73 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.4437 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.4437 | 0.2205 | 1.0000 | 1.2001 | 0.2205 | ||
VAV_BOT WITH REHEAT | 9.7996 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 8.9452 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 91.5546 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 82.7655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 9.2555 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 8.4252 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.5406 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.5406 | 0.0157 | 1.0000 | 0.3384 | 0.0157 | ||
AIRLOOP DATACENTER BOT | 0.4700 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4700 | 0.0333 | 1.0000 | 0.0156 | 0.0333 | ||
AIRLOOP DATACENTER MID | 4.4797 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.4797 | 0.0349 | 1.0000 | 0.1563 | 0.0349 | ||
AIRLOOP DATACENTER TOP | 0.4549 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4549 | 0.0344 | 1.0000 | 0.0156 | 0.0344 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.4437 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.4437 | 1.0000 | 1.0000 | 1.2001 | 0.2205 | ||
VAV_BOT WITH REHEAT | 4.8998 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.8216 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 45.7773 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 27.3235 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.6278 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.7543 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.5406 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.5406 | 1.0000 | 1.0000 | 0.3384 | 0.0157 | ||
AIRLOOP DATACENTER BOT | 0.4700 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4700 | 1.0000 | 1.0000 | 0.0156 | 0.0333 | ||
AIRLOOP DATACENTER MID | 4.4797 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.4797 | 1.0000 | 1.0000 | 0.1563 | 0.0349 | ||
AIRLOOP DATACENTER TOP | 0.4549 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4549 | 1.0000 | 1.0000 | 0.0156 | 0.0344 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2001 | 1.0000 | 1.2001 | 1.000 | 1.2001 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 0.0000 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 0.0000 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2001 | 1.2001 | 1.2001 |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
AIRLOOP DATACENTER BASEMENT | 0.00 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 | |
AIRLOOP DATACENTER BOT | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 | |
AIRLOOP DATACENTER MID | 0.00 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 | |
AIRLOOP DATACENTER TOP | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.4437 | 5.4437 | 5.4437 | 1.2001 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7351 | 5.7351 | 1.8926 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 53.9483 | 53.9483 | 18.4503 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2695 | 5.2695 | 1.8549 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7909 | 0.7909 | 0.2373 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0107 | 1.0107 | 0.2021 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0021 | 1.0021 | 0.2375 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2609 | 1.2609 | 0.2522 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.0599 | 7.0599 | 2.3157 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.4082 | 10.4082 | 2.0816 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.3384 | 9.3384 | 2.3159 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.7997 | 10.7997 | 2.1599 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7999 | 0.7999 | 0.2328 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0296 | 1.0296 | 0.2059 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0164 | 1.0164 | 0.2328 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1401 | 1.1401 | 0.2280 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4700 | 0.4700 | 0.4700 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.4797 | 4.4797 | 4.4797 | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4549 | 0.4549 | 0.4549 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.5406 | 21.5406 | 21.5406 | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.4437 | 5.4437 | 5.4437 | 5.4437 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 9.7996 | 8.9452 | 9.7996 | 2.8216 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 91.5546 | 82.7655 | 91.5546 | 27.3235 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 9.2555 | 8.4252 | 9.2555 | 2.7543 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.5406 | 21.5406 | 21.5406 | 21.5406 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4700 | 0.4700 | 0.4700 | 0.4700 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4797 | 4.4797 | 4.4797 | 4.4797 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4549 | 0.4549 | 0.4549 | 0.4549 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.4437 | 5.4437 | 5.4437 | 1.2001 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8675 | 2.8675 | 1.8926 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 26.9742 | 26.9742 | 18.4503 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6347 | 2.6347 | 1.8549 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3955 | 0.3955 | 0.2373 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5053 | 0.5053 | 0.2021 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5010 | 0.5010 | 0.2375 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6304 | 0.6304 | 0.2522 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.5300 | 3.5300 | 2.3157 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2041 | 5.2041 | 2.0816 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.6692 | 4.6692 | 2.3159 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3999 | 5.3999 | 2.1599 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3999 | 0.3999 | 0.2328 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5148 | 0.5148 | 0.2059 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5082 | 0.5082 | 0.2328 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5700 | 0.5700 | 0.2280 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4700 | 0.4700 | 0.4700 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.4797 | 4.4797 | 4.4797 | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4549 | 0.4549 | 0.4549 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.5406 | 21.5406 | 21.5406 | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.4437 | 5.4437 | 5.4437 | 5.4437 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 4.8998 | 2.8216 | 2.8216 | 2.8216 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 45.7773 | 27.3235 | 27.3235 | 27.3235 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.6278 | 2.7543 | 2.7543 | 2.7543 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.5406 | 21.5406 | 21.5406 | 21.5406 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4700 | 0.4700 | 0.4700 | 0.4700 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4797 | 4.4797 | 4.4797 | 4.4797 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4549 | 0.4549 | 0.4549 | 0.4549 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:02
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 422.33 |
Number of hours not met | 422.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 41.32 | 821255.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1055.37 | 310601.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Other | 1427.20 | 145940.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3172.03 | 321032.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 339.86 | 39974.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.88 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.99 | 3452.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1895.08 | 122221.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2049.32 | 133554.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 342.77 | 39272.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 114.98 | 29880.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Other | 869.32 | 49248.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 348.38 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 535.38 | 72100.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.31 | 26351.42 |
Natural Gas | 0.00 | 576.70 |
Additional | 0.00 | 0.00 |
Total | 14676.31 | 26928.12 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 68.48 |
Space Heating | 0.00 |
Space Cooling | 53.60 |
Fans (All) | 44.24 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.84 |
Miscellaneous (All) | 568.89 |
Subtotal | 568.89 |
Natural Gas [MJ/m2] | |
Space Heating | 0.89 |
Service Water Heating | 11.56 |
Miscellaneous (All) | 12.45 |
Subtotal | 12.45 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.78 |
Space Heating | 0.15 |
Space Cooling | 9.22 |
Fans (All) | 7.61 |
Service Water Heating | 1.99 |
Receptacle Equipment | 54.50 |
Miscellaneous | 14.75 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
BLDG_LIGHT_SCH | 2676. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.139865E+11 |
February | 0.000 | 0.464445E+10 |
March | 0.000 | 0.762870E+10 |
April | 0.000 | 0.160044E+10 |
May | 0.000 | 0.861053E+09 |
June | 0.000 | 0.155166E+09 |
July | 0.000 | 0.875667E+09 |
August | 0.000 | 0.609759E+09 |
September | 0.000 | 0.476501E+09 |
October | 0.000 | 0.140707E+10 |
November | 0.000 | 0.187417E+10 |
December | 0.000 | 0.720052E+10 |
Annual Sum or Average | 0.413200E+11 | |
Minimum of Months | 0.000 | 0.155166E+09 |
Maximum of Months | 0.000 | 0.139865E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.139865E+11 |
February | 0.000 | 0.464445E+10 |
March | 0.000 | 0.762870E+10 |
April | 0.000 | 0.160044E+10 |
May | 0.000 | 0.861053E+09 |
June | 0.000 | 0.155166E+09 |
July | 0.000 | 0.875667E+09 |
August | 0.000 | 0.609759E+09 |
September | 0.000 | 0.476501E+09 |
October | 0.000 | 0.140707E+10 |
November | 0.000 | 0.187417E+10 |
December | 0.000 | 0.720052E+10 |
Annual Sum or Average | 0.413200E+11 | |
Minimum of Months | 0.000 | 0.155166E+09 |
Maximum of Months | 0.000 | 0.139865E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Meter
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.139865E+11 |
February | 0.000 | 0.464445E+10 |
March | 0.000 | 0.762870E+10 |
April | 0.000 | 0.160044E+10 |
May | 0.000 | 0.861053E+09 |
June | 0.000 | 0.155166E+09 |
July | 0.000 | 0.875667E+09 |
August | 0.000 | 0.609759E+09 |
September | 0.000 | 0.476501E+09 |
October | 0.000 | 0.140707E+10 |
November | 0.000 | 0.187417E+10 |
December | 0.000 | 0.720052E+10 |
Annual Sum or Average | 0.413200E+11 | |
Minimum of Months | 0.000 | 0.155166E+09 |
Maximum of Months | 0.000 | 0.139865E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.139865E+11 |
February | 0.000 | 0.464445E+10 |
March | 0.000 | 0.762870E+10 |
April | 0.000 | 0.160044E+10 |
May | 0.000 | 0.861053E+09 |
June | 0.000 | 0.155166E+09 |
July | 0.000 | 0.875667E+09 |
August | 0.000 | 0.609759E+09 |
September | 0.000 | 0.476501E+09 |
October | 0.000 | 0.140707E+10 |
November | 0.000 | 0.187417E+10 |
December | 0.000 | 0.720052E+10 |
Annual Sum or Average | 0.413200E+11 | |
Minimum of Months | 0.000 | 0.155166E+09 |
Maximum of Months | 0.000 | 0.139865E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Meter
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.139865E+11 |
February | 0.000 | 0.464445E+10 |
March | 0.000 | 0.762870E+10 |
April | 0.000 | 0.160044E+10 |
May | 0.000 | 0.861053E+09 |
June | 0.000 | 0.155166E+09 |
July | 0.000 | 0.875667E+09 |
August | 0.000 | 0.609759E+09 |
September | 0.000 | 0.476501E+09 |
October | 0.000 | 0.140707E+10 |
November | 0.000 | 0.187417E+10 |
December | 0.000 | 0.720052E+10 |
Annual Sum or Average | 0.413200E+11 | |
Minimum of Months | 0.000 | 0.155166E+09 |
Maximum of Months | 0.000 | 0.139865E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.139865E+11 |
February | 0.000 | 0.464445E+10 |
March | 0.000 | 0.762870E+10 |
April | 0.000 | 0.160044E+10 |
May | 0.000 | 0.861053E+09 |
June | 0.000 | 0.155166E+09 |
July | 0.000 | 0.875667E+09 |
August | 0.000 | 0.609759E+09 |
September | 0.000 | 0.476501E+09 |
October | 0.000 | 0.140707E+10 |
November | 0.000 | 0.187417E+10 |
December | 0.000 | 0.720052E+10 |
Annual Sum or Average | 0.413200E+11 | |
Minimum of Months | 0.000 | 0.155166E+09 |
Maximum of Months | 0.000 | 0.139865E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.139865E+11 |
February | 0.000 | 0.464445E+10 |
March | 0.000 | 0.762870E+10 |
April | 0.000 | 0.160044E+10 |
May | 0.000 | 0.861053E+09 |
June | 0.000 | 0.155166E+09 |
July | 0.000 | 0.875667E+09 |
August | 0.000 | 0.609759E+09 |
September | 0.000 | 0.476501E+09 |
October | 0.000 | 0.140707E+10 |
November | 0.000 | 0.187417E+10 |
December | 0.000 | 0.720052E+10 |
Annual Sum or Average | 0.413200E+11 | |
Minimum of Months | 0.000 | 0.155166E+09 |
Maximum of Months | 0.000 | 0.139865E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Meter
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.139865E+11 |
February | 0.000 | 0.464445E+10 |
March | 0.000 | 0.762870E+10 |
April | 0.000 | 0.160044E+10 |
May | 0.000 | 0.861053E+09 |
June | 0.000 | 0.155166E+09 |
July | 0.000 | 0.875667E+09 |
August | 0.000 | 0.609759E+09 |
September | 0.000 | 0.476501E+09 |
October | 0.000 | 0.140707E+10 |
November | 0.000 | 0.187417E+10 |
December | 0.000 | 0.720052E+10 |
Annual Sum or Average | 0.413200E+11 | |
Minimum of Months | 0.000 | 0.155166E+09 |
Maximum of Months | 0.000 | 0.139865E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Meter
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.139865E+11 |
February | 0.000 | 0.464445E+10 |
March | 0.000 | 0.762870E+10 |
April | 0.000 | 0.160044E+10 |
May | 0.000 | 0.861053E+09 |
June | 0.000 | 0.155166E+09 |
July | 0.000 | 0.875667E+09 |
August | 0.000 | 0.609759E+09 |
September | 0.000 | 0.476501E+09 |
October | 0.000 | 0.140707E+10 |
November | 0.000 | 0.187417E+10 |
December | 0.000 | 0.720052E+10 |
Annual Sum or Average | 0.413200E+11 | |
Minimum of Months | 0.000 | 0.155166E+09 |
Maximum of Months | 0.000 | 0.139865E+11 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.581510E+11 | 114337.57 | 01-JAN-15:42 | 13.00 | 9.26 | 0.566860E+10 | 7499.45 | 10-JAN-14:20 | 16.67 | 11.78 |
February | 0.499793E+11 | 116082.45 | 20-FEB-17:40 | 15.00 | 11.00 | 0.513925E+10 | 7500.27 | 01-FEB-14:20 | 19.00 | 15.51 |
March | 0.586048E+11 | 115859.34 | 06-MAR-04:20 | 10.93 | 10.05 | 0.613279E+10 | 7499.46 | 01-MAR-14:20 | 18.00 | 14.20 |
April | 0.553676E+11 | 116581.64 | 09-APR-23:50 | 13.00 | 10.87 | 0.544960E+10 | 7499.39 | 13-APR-09:00 | 23.00 | 15.73 |
May | 0.556186E+11 | 113507.79 | 30-MAY-02:32 | 12.00 | 11.09 | 0.589952E+10 | 7499.46 | 05-MAY-13:00 | 18.00 | 16.13 |
June | 0.563619E+11 | 110468.44 | 12-JUN-02:51 | 13.00 | 11.87 | 0.587970E+10 | 7499.15 | 21-JUN-13:20 | 23.67 | 16.90 |
July | 0.580620E+11 | 111061.47 | 10-JUL-03:50 | 17.00 | 14.03 | 0.547211E+10 | 7499.07 | 11-JUL-13:20 | 22.00 | 17.21 |
August | 0.635005E+11 | 106924.44 | 27-AUG-22:53 | 15.00 | 15.00 | 0.613577E+10 | 7499.17 | 31-AUG-09:20 | 23.00 | 18.42 |
September | 0.562015E+11 | 110360.54 | 30-SEP-03:53 | 23.90 | 13.89 | 0.545051E+10 | 7499.43 | 21-SEP-09:30 | 20.00 | 18.02 |
October | 0.613764E+11 | 117005.89 | 30-OCT-03:33 | 9.00 | 6.70 | 0.567101E+10 | 7500.42 | 31-OCT-13:00 | 26.00 | 15.80 |
November | 0.603833E+11 | 116169.87 | 24-NOV-04:33 | 7.67 | 1.06 | 0.561566E+10 | 7499.84 | 30-NOV-14:00 | 21.00 | 13.06 |
December | 0.600811E+11 | 116680.52 | 25-DEC-17:23 | 15.00 | 9.39 | 0.547262E+10 | 7500.08 | 20-DEC-14:00 | 19.00 | 12.36 |
Annual Sum or Average | 0.693688E+12 | 0.679871E+11 | ||||||||
Minimum of Months | 0.499793E+11 | 106924.44 | 7.67 | 1.06 | 0.513925E+10 | 7499.07 | 16.67 | 11.78 | ||
Maximum of Months | 0.635005E+11 | 117005.89 | 23.90 | 15.00 | 0.613577E+10 | 7500.42 | 26.00 | 18.42 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.475560E+11 | 76911.07 | 25-JAN-05:12 | 16.00 | 11.05 | 0.507493E+10 | 6735.05 | 10-JAN-14:09 | 16.83 | 11.84 |
February | 0.448988E+11 | 74829.11 | 01-FEB-05:12 | 14.67 | 8.63 | 0.460253E+10 | 6735.31 | 01-FEB-14:09 | 19.00 | 15.69 |
March | 0.552682E+11 | 74536.58 | 21-MAR-04:12 | 13.00 | 12.44 | 0.549848E+10 | 6735.03 | 01-MAR-14:09 | 18.00 | 14.28 |
April | 0.576904E+11 | 78447.14 | 14-APR-03:02 | 14.00 | 13.37 | 0.487838E+10 | 6735.10 | 13-APR-09:00 | 23.00 | 15.73 |
May | 0.512260E+11 | 78571.48 | 25-MAY-04:12 | 15.67 | 13.66 | 0.528175E+10 | 6735.04 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.553472E+11 | 80974.39 | 26-JUN-04:12 | 17.67 | 15.32 | 0.526777E+10 | 6734.59 | 08-JUN-09:39 | 16.00 | 14.55 |
July | 0.614877E+11 | 81426.72 | 05-JUL-04:13 | 17.00 | 14.50 | 0.489147E+10 | 6734.40 | 10-JUL-09:09 | 21.00 | 15.41 |
August | 0.697782E+11 | 81445.03 | 30-AUG-04:12 | 18.00 | 15.43 | 0.549247E+10 | 6734.47 | 22-AUG-09:09 | 19.33 | 14.88 |
September | 0.509259E+11 | 83846.49 | 29-SEP-04:12 | 18.37 | 11.71 | 0.487637E+10 | 6734.67 | 15-SEP-09:09 | 18.17 | 14.34 |
October | 0.563808E+11 | 85761.54 | 04-OCT-04:12 | 20.00 | 18.02 | 0.507302E+10 | 6735.01 | 27-OCT-09:00 | 22.00 | 11.68 |
November | 0.542106E+11 | 83739.64 | 12-NOV-10:21 | 16.00 | 13.85 | 0.502823E+10 | 6735.46 | 30-NOV-14:00 | 21.00 | 13.06 |
December | 0.560618E+11 | 81600.06 | 19-DEC-04:02 | 16.00 | 5.12 | 0.489933E+10 | 6735.79 | 20-DEC-14:00 | 19.00 | 12.36 |
Annual Sum or Average | 0.660832E+12 | 0.608647E+11 | ||||||||
Minimum of Months | 0.448988E+11 | 74536.58 | 13.00 | 5.12 | 0.460253E+10 | 6734.40 | 16.00 | 11.68 | ||
Maximum of Months | 0.697782E+11 | 85761.54 | 20.00 | 18.02 | 0.549848E+10 | 6735.79 | 23.17 | 16.41 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.361487E+11 | 65621.02 | 17-JAN-06:03 | 15.83 | 13.52 | 0.502712E+10 | 6735.00 | 10-JAN-14:09 | 16.83 | 11.84 |
February | 0.329634E+11 | 60993.02 | 03-FEB-06:03 | 12.33 | 3.91 | 0.455901E+10 | 6735.32 | 01-FEB-14:09 | 19.00 | 15.69 |
March | 0.385748E+11 | 62836.12 | 24-MAR-05:02 | 12.00 | 12.00 | 0.545484E+10 | 6734.98 | 01-MAR-14:09 | 18.00 | 14.28 |
April | 0.389057E+11 | 67705.52 | 27-APR-04:11 | 15.00 | 14.40 | 0.484221E+10 | 6734.96 | 13-APR-13:50 | 20.17 | 15.45 |
May | 0.412875E+11 | 67197.01 | 25-MAY-05:02 | 14.83 | 13.74 | 0.524905E+10 | 6735.08 | 03-MAY-13:00 | 23.00 | 16.66 |
June | 0.435948E+11 | 71364.35 | 30-JUN-04:11 | 17.00 | 16.37 | 0.523595E+10 | 6734.60 | 08-JUN-09:39 | 16.00 | 14.55 |
July | 0.446622E+11 | 72939.06 | 03-JUL-05:02 | 17.17 | 15.13 | 0.485765E+10 | 6734.43 | 26-JUL-13:09 | 24.17 | 18.75 |
August | 0.478525E+11 | 73627.79 | 19-AUG-04:11 | 18.67 | 17.56 | 0.546188E+10 | 6734.46 | 22-AUG-09:09 | 19.33 | 14.88 |
September | 0.417829E+11 | 76589.03 | 30-SEP-05:02 | 23.80 | 13.82 | 0.484518E+10 | 6734.64 | 15-SEP-09:09 | 18.17 | 14.34 |
October | 0.434308E+11 | 77436.82 | 05-OCT-04:11 | 20.67 | 18.86 | 0.503877E+10 | 6734.91 | 27-OCT-09:00 | 22.00 | 11.68 |
November | 0.378845E+11 | 65100.67 | 10-NOV-06:03 | 15.17 | 13.96 | 0.499052E+10 | 6735.28 | 30-NOV-14:00 | 21.00 | 13.06 |
December | 0.371744E+11 | 64984.06 | 19-DEC-06:03 | 16.83 | 5.75 | 0.484896E+10 | 6735.61 | 20-DEC-14:00 | 19.00 | 12.36 |
Annual Sum or Average | 0.484262E+12 | 0.604111E+11 | ||||||||
Minimum of Months | 0.329634E+11 | 60993.02 | 12.00 | 3.91 | 0.455901E+10 | 6734.43 | 16.00 | 11.68 | ||
Maximum of Months | 0.478525E+11 | 77436.82 | 23.80 | 18.86 | 0.546188E+10 | 6735.61 | 24.17 | 18.75 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.287760E+11 | 35151.82 | 19-JAN-16:20 | 18.67 | 14.63 | 0.470818E+10 | 6734.81 | 27-JAN-14:09 | 16.83 | 12.83 |
February | 0.271756E+11 | 36824.88 | 16-FEB-16:20 | 16.47 | 13.30 | 0.434092E+10 | 6735.27 | 01-FEB-14:09 | 19.00 | 15.69 |
March | 0.324973E+11 | 45769.08 | 24-MAR-05:02 | 12.00 | 12.00 | 0.524451E+10 | 6734.84 | 01-MAR-14:09 | 18.00 | 14.28 |
April | 0.363767E+11 | 59825.88 | 27-APR-05:03 | 15.00 | 14.40 | 0.476213E+10 | 6734.96 | 13-APR-13:50 | 20.17 | 15.45 |
May | 0.388016E+11 | 60654.07 | 25-MAY-05:02 | 14.83 | 13.74 | 0.517436E+10 | 6735.04 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.432668E+11 | 65250.96 | 27-JUN-05:02 | 17.00 | 15.73 | 0.520450E+10 | 6734.55 | 08-JUN-09:39 | 16.00 | 14.55 |
July | 0.457774E+11 | 67375.98 | 03-JUL-05:02 | 17.17 | 15.13 | 0.484239E+10 | 6734.37 | 12-JUL-09:09 | 18.50 | 15.74 |
August | 0.484557E+11 | 67557.00 | 10-AUG-05:03 | 18.00 | 16.69 | 0.544304E+10 | 6734.43 | 22-AUG-09:09 | 19.33 | 14.88 |
September | 0.397346E+11 | 76880.75 | 30-SEP-05:02 | 23.80 | 13.82 | 0.480018E+10 | 6734.58 | 15-SEP-09:09 | 18.17 | 14.34 |
October | 0.396264E+11 | 71705.41 | 02-OCT-04:12 | 19.03 | 17.69 | 0.495038E+10 | 6734.83 | 31-OCT-13:09 | 26.83 | 16.90 |
November | 0.307104E+11 | 36413.01 | 01-NOV-16:00 | 16.80 | 12.57 | 0.479758E+10 | 6735.15 | 30-NOV-14:00 | 21.00 | 13.06 |
December | 0.294730E+11 | 35444.24 | 07-DEC-15:50 | 18.17 | 15.01 | 0.458321E+10 | 6735.47 | 20-DEC-14:00 | 19.00 | 12.36 |
Annual Sum or Average | 0.440671E+12 | 0.588514E+11 | ||||||||
Minimum of Months | 0.271756E+11 | 35151.82 | 12.00 | 12.00 | 0.434092E+10 | 6734.37 | 16.00 | 12.36 | ||
Maximum of Months | 0.484557E+11 | 76880.75 | 23.80 | 17.69 | 0.544304E+10 | 6735.47 | 26.83 | 16.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.431138E+10 | 5799.23 | 17-JAN-13:40 | 23.33 | 16.99 | 0.620354E+09 | 845.66 | 10-JAN-14:09 | 16.83 | 11.84 |
February | 0.419802E+10 | 5123.93 | 01-FEB-12:00 | 26.00 | 14.65 | 0.567119E+09 | 845.70 | 01-FEB-14:09 | 19.00 | 15.69 |
March | 0.521923E+10 | 5754.52 | 13-MAR-13:50 | 17.83 | 13.80 | 0.679536E+09 | 845.66 | 01-MAR-14:09 | 18.00 | 14.28 |
April | 0.627129E+10 | 7040.98 | 26-APR-13:40 | 26.33 | 16.85 | 0.608027E+09 | 845.67 | 13-APR-13:50 | 20.17 | 15.45 |
May | 0.592251E+10 | 6672.49 | 04-MAY-13:40 | 23.00 | 16.65 | 0.658022E+09 | 845.68 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.697727E+10 | 7128.15 | 19-JUN-05:01 | 16.17 | 14.82 | 0.659528E+09 | 845.61 | 07-JUN-13:00 | 19.00 | 14.24 |
July | 0.806541E+10 | 8933.13 | 03-JUL-05:01 | 17.17 | 15.13 | 0.613508E+09 | 845.59 | 05-JUL-13:09 | 22.00 | 16.40 |
August | 0.881840E+10 | 7619.22 | 07-AUG-14:00 | 26.00 | 19.97 | 0.688288E+09 | 845.59 | 22-AUG-09:09 | 19.33 | 14.88 |
September | 0.606266E+10 | 7985.22 | 29-SEP-13:10 | 35.67 | 18.12 | 0.608461E+09 | 845.61 | 15-SEP-09:09 | 18.17 | 14.34 |
October | 0.651275E+10 | 9361.22 | 05-OCT-04:11 | 20.67 | 18.86 | 0.632375E+09 | 845.65 | 31-OCT-13:09 | 26.83 | 16.90 |
November | 0.513030E+10 | 5666.57 | 13-NOV-11:40 | 18.33 | 14.17 | 0.623605E+09 | 845.70 | 30-NOV-14:00 | 21.00 | 13.06 |
December | 0.507838E+10 | 6126.22 | 05-DEC-15:00 | 25.00 | 13.20 | 0.605392E+09 | 845.74 | 20-DEC-14:00 | 19.00 | 12.36 |
Annual Sum or Average | 0.725676E+11 | 0.756422E+10 | ||||||||
Minimum of Months | 0.419802E+10 | 5123.93 | 16.17 | 13.20 | 0.567119E+09 | 845.59 | 16.83 | 11.84 | ||
Maximum of Months | 0.881840E+10 | 9361.22 | 35.67 | 19.97 | 0.688288E+09 | 845.74 | 26.83 | 16.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.389703E+10 | 11457.48 | 01-JAN-08:58 | 12.00 | 9.77 | 0.403009E+09 | 544.97 | 05-JAN-10:00 | 17.00 | 9.44 |
February | 0.364526E+10 | 10159.56 | 20-FEB-08:41 | 13.67 | 8.38 | 0.364361E+09 | 545.00 | 01-FEB-14:09 | 19.00 | 15.69 |
March | 0.455716E+10 | 14794.94 | 19-MAR-08:53 | 16.00 | 14.12 | 0.435729E+09 | 544.98 | 01-MAR-14:09 | 18.00 | 14.28 |
April | 0.579870E+10 | 17298.12 | 30-APR-09:13 | 23.00 | 15.73 | 0.390705E+09 | 545.01 | 13-APR-09:00 | 23.00 | 15.73 |
May | 0.544489E+10 | 16387.94 | 28-MAY-08:23 | 18.50 | 14.06 | 0.423602E+09 | 544.99 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.607432E+10 | 17268.92 | 18-JUN-08:43 | 21.50 | 16.59 | 0.423230E+09 | 544.95 | 02-JUN-09:50 | 21.50 | 15.57 |
July | 0.728951E+10 | 17925.33 | 23-JUL-08:22 | 24.00 | 19.31 | 0.394518E+09 | 544.94 | 10-JUL-09:00 | 21.00 | 15.41 |
August | 0.789845E+10 | 17287.99 | 13-AUG-08:23 | 23.00 | 18.71 | 0.442276E+09 | 544.94 | 22-AUG-09:09 | 19.33 | 14.88 |
September | 0.549730E+10 | 17119.36 | 10-SEP-09:13 | 22.33 | 17.54 | 0.390895E+09 | 544.96 | 15-SEP-09:09 | 18.17 | 14.34 |
October | 0.555970E+10 | 16810.59 | 09-OCT-08:23 | 20.00 | 15.17 | 0.406372E+09 | 544.99 | 27-OCT-09:00 | 22.00 | 11.68 |
November | 0.422358E+10 | 7513.33 | 13-NOV-08:25 | 15.50 | 12.90 | 0.401103E+09 | 545.00 | 30-NOV-14:00 | 21.00 | 13.06 |
December | 0.414750E+10 | 7344.65 | 25-DEC-08:51 | 14.00 | 8.11 | 0.388738E+09 | 545.02 | 20-DEC-14:00 | 19.00 | 12.36 |
Annual Sum or Average | 0.640334E+11 | 0.486454E+10 | ||||||||
Minimum of Months | 0.364526E+10 | 7344.65 | 12.00 | 8.11 | 0.364361E+09 | 544.94 | 17.00 | 9.44 | ||
Maximum of Months | 0.789845E+10 | 17925.33 | 24.00 | 19.31 | 0.442276E+09 | 545.02 | 23.17 | 16.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.975011E+10 | 16469.79 | 29-JAN-11:32 | 16.00 | 12.23 | 0.642324E+09 | 936.71 | 27-JAN-14:09 | 16.83 | 12.83 |
February | 0.744973E+10 | 16442.79 | 20-FEB-11:23 | 16.50 | 9.44 | 0.572866E+09 | 901.46 | 22-FEB-14:09 | 18.80 | 12.71 |
March | 0.751594E+10 | 16873.98 | 19-MAR-11:32 | 20.67 | 15.86 | 0.678618E+09 | 875.77 | 01-MAR-14:09 | 18.00 | 14.28 |
April | 0.749281E+10 | 10467.16 | 26-APR-13:00 | 27.00 | 17.11 | 0.607212E+09 | 845.70 | 13-APR-13:50 | 20.17 | 15.45 |
May | 0.589120E+10 | 7662.69 | 04-MAY-12:40 | 23.33 | 16.62 | 0.654366E+09 | 845.70 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.663681E+10 | 6895.86 | 27-JUN-13:10 | 23.83 | 18.66 | 0.657218E+09 | 845.63 | 07-JUN-13:00 | 19.00 | 14.24 |
July | 0.795590E+10 | 9413.12 | 31-JUL-12:30 | 28.00 | 21.18 | 0.612347E+09 | 845.61 | 05-JUL-13:09 | 22.00 | 16.40 |
August | 0.988993E+10 | 11878.48 | 30-AUG-12:30 | 23.50 | 17.68 | 0.688127E+09 | 845.61 | 29-AUG-13:39 | 24.67 | 17.71 |
September | 0.868916E+10 | 16195.76 | 04-SEP-10:37 | 21.00 | 16.51 | 0.610799E+09 | 927.30 | 29-SEP-13:20 | 35.33 | 18.07 |
October | 0.107188E+11 | 18698.51 | 29-OCT-13:12 | 22.00 | 15.67 | 0.643456E+09 | 977.64 | 31-OCT-13:09 | 26.83 | 16.90 |
November | 0.102238E+11 | 18438.24 | 19-NOV-13:42 | 25.33 | 15.06 | 0.638598E+09 | 929.78 | 27-NOV-14:09 | 22.83 | 9.18 |
December | 0.110578E+11 | 19064.64 | 25-DEC-13:22 | 22.00 | 9.47 | 0.630172E+09 | 953.15 | 19-DEC-14:09 | 22.83 | 9.76 |
Annual Sum or Average | 0.103272E+12 | 0.763610E+10 | ||||||||
Minimum of Months | 0.589120E+10 | 6895.86 | 16.00 | 9.44 | 0.572866E+09 | 845.61 | 16.83 | 9.18 | ||
Maximum of Months | 0.110578E+11 | 19064.64 | 28.00 | 21.18 | 0.688127E+09 | 977.64 | 35.33 | 18.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.532631E+10 | 10425.49 | 16-JAN-15:41 | 18.17 | 15.02 | 0.402662E+09 | 544.99 | 10-JAN-14:09 | 16.83 | 11.84 |
February | 0.570576E+10 | 20120.16 | 20-FEB-16:01 | 17.00 | 10.77 | 0.370703E+09 | 545.01 | 01-FEB-14:09 | 19.00 | 15.69 |
March | 0.788791E+10 | 20311.76 | 19-MAR-15:32 | 18.00 | 14.76 | 0.444701E+09 | 545.00 | 01-MAR-14:09 | 18.00 | 14.28 |
April | 0.104292E+11 | 22268.88 | 30-APR-15:52 | 22.00 | 15.82 | 0.396180E+09 | 545.00 | 13-APR-13:50 | 20.17 | 15.45 |
May | 0.750066E+10 | 21877.00 | 28-MAY-15:22 | 20.50 | 14.99 | 0.426359E+09 | 545.01 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.948095E+10 | 21631.45 | 18-JUN-14:22 | 23.00 | 17.85 | 0.427200E+09 | 544.95 | 07-JUN-13:00 | 19.00 | 14.24 |
July | 0.116707E+11 | 22195.34 | 23-JUL-16:32 | 24.00 | 18.91 | 0.397673E+09 | 544.93 | 05-JUL-13:09 | 22.00 | 16.40 |
August | 0.137258E+11 | 22508.98 | 06-AUG-16:32 | 23.33 | 19.29 | 0.445978E+09 | 544.93 | 22-AUG-09:09 | 19.33 | 14.88 |
September | 0.776222E+10 | 22133.22 | 10-SEP-16:12 | 21.67 | 16.72 | 0.394517E+09 | 544.95 | 15-SEP-09:09 | 18.17 | 14.34 |
October | 0.825040E+10 | 22039.90 | 15-OCT-15:22 | 30.50 | 15.16 | 0.411057E+09 | 544.98 | 27-OCT-09:00 | 22.00 | 11.68 |
November | 0.747909E+10 | 20982.45 | 23-NOV-14:12 | 21.00 | 8.01 | 0.407251E+09 | 545.07 | 30-NOV-14:00 | 21.00 | 13.06 |
December | 0.800792E+10 | 21528.93 | 25-DEC-14:02 | 22.00 | 9.83 | 0.397053E+09 | 545.09 | 20-DEC-14:50 | 19.20 | 11.86 |
Annual Sum or Average | 0.103227E+12 | 0.492133E+10 | ||||||||
Minimum of Months | 0.532631E+10 | 10425.49 | 17.00 | 8.01 | 0.370703E+09 | 544.93 | 16.83 | 11.68 | ||
Maximum of Months | 0.137258E+11 | 22508.98 | 30.50 | 19.29 | 0.445978E+09 | 545.09 | 23.17 | 16.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.313313E+10 | 3833.33 | 18-JAN-14:20 | 24.07 | 14.80 | 0.564552E+09 | 845.62 | 18-JAN-14:09 | 24.33 | 14.80 |
February | 0.291584E+10 | 3243.76 | 03-FEB-15:00 | 23.00 | 8.80 | 0.520667E+09 | 845.69 | 01-FEB-14:09 | 19.00 | 15.69 |
March | 0.342872E+10 | 3916.41 | 23-MAR-15:00 | 22.00 | 17.39 | 0.624594E+09 | 845.60 | 17-MAR-13:09 | 17.00 | 13.93 |
April | 0.395626E+10 | 5362.22 | 26-APR-14:00 | 26.00 | 16.72 | 0.582845E+09 | 845.65 | 13-APR-13:50 | 20.17 | 15.45 |
May | 0.445468E+10 | 5772.32 | 04-MAY-14:00 | 23.00 | 16.65 | 0.640285E+09 | 845.67 | 03-MAY-13:00 | 23.00 | 16.66 |
June | 0.520176E+10 | 5547.26 | 30-JUN-14:00 | 23.00 | 17.84 | 0.650140E+09 | 845.61 | 07-JUN-13:00 | 19.00 | 14.24 |
July | 0.565876E+10 | 6215.69 | 19-JUL-15:00 | 27.00 | 20.16 | 0.606378E+09 | 845.59 | 05-JUL-13:09 | 22.00 | 16.40 |
August | 0.582343E+10 | 6193.98 | 17-AUG-14:00 | 28.00 | 21.18 | 0.678539E+09 | 845.59 | 01-AUG-13:09 | 22.00 | 16.84 |
September | 0.471506E+10 | 8025.49 | 30-SEP-05:01 | 23.80 | 13.82 | 0.595413E+09 | 845.61 | 29-SEP-13:39 | 34.67 | 17.95 |
October | 0.479451E+10 | 7055.42 | 16-OCT-12:20 | 35.37 | 17.31 | 0.613284E+09 | 845.64 | 31-OCT-13:09 | 26.83 | 16.90 |
November | 0.338165E+10 | 3514.60 | 10-NOV-13:20 | 20.67 | 16.22 | 0.580188E+09 | 845.61 | 28-NOV-14:20 | 24.33 | 10.93 |
December | 0.324201E+10 | 3816.95 | 05-DEC-15:00 | 25.00 | 13.20 | 0.547642E+09 | 845.61 | 05-DEC-14:39 | 24.67 | 12.97 |
Annual Sum or Average | 0.507058E+11 | 0.720453E+10 | ||||||||
Minimum of Months | 0.291584E+10 | 3243.76 | 20.67 | 8.80 | 0.520667E+09 | 845.59 | 17.00 | 10.93 | ||
Maximum of Months | 0.582343E+10 | 8025.49 | 35.37 | 21.18 | 0.678539E+09 | 845.69 | 34.67 | 17.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.310829E+10 | 5709.08 | 20-JAN-09:10 | 17.33 | 14.09 | 0.279339E+09 | 521.21 | 24-JAN-11:20 | 23.00 | 14.45 |
February | 0.289136E+10 | 5675.51 | 21-FEB-09:30 | 15.50 | 10.46 | 0.253441E+09 | 521.27 | 01-FEB-13:50 | 19.83 | 15.74 |
March | 0.359761E+10 | 8624.68 | 23-MAR-09:00 | 19.00 | 14.75 | 0.303561E+09 | 521.25 | 10-MAR-08:09 | 14.67 | 11.27 |
April | 0.469690E+10 | 17780.93 | 30-APR-09:02 | 22.50 | 15.56 | 0.282777E+09 | 521.27 | 13-APR-10:09 | 22.83 | 15.57 |
May | 0.472438E+10 | 15794.76 | 28-MAY-08:53 | 19.00 | 14.24 | 0.304869E+09 | 521.29 | 24-MAY-10:50 | 21.00 | 14.87 |
June | 0.539871E+10 | 17711.07 | 18-JUN-08:32 | 21.00 | 16.34 | 0.306123E+09 | 521.21 | 02-JUN-10:09 | 22.00 | 15.75 |
July | 0.634546E+10 | 18501.17 | 23-JUL-08:52 | 25.00 | 19.59 | 0.288927E+09 | 521.21 | 05-JUL-07:10 | 18.33 | 15.08 |
August | 0.670227E+10 | 17834.66 | 13-AUG-08:53 | 24.00 | 19.31 | 0.322721E+09 | 521.20 | 22-AUG-10:20 | 21.33 | 15.74 |
September | 0.488761E+10 | 17796.46 | 10-SEP-08:53 | 22.00 | 17.39 | 0.281789E+09 | 521.21 | 29-SEP-07:10 | 24.00 | 14.15 |
October | 0.473771E+10 | 18460.85 | 15-OCT-09:02 | 32.67 | 15.99 | 0.292278E+09 | 521.26 | 27-OCT-10:30 | 22.00 | 13.02 |
November | 0.330142E+10 | 5320.48 | 13-NOV-09:00 | 17.00 | 13.47 | 0.281778E+09 | 521.21 | 08-NOV-11:00 | 23.00 | 13.43 |
December | 0.316720E+10 | 5699.69 | 05-DEC-09:00 | 24.00 | 11.77 | 0.270322E+09 | 521.23 | 07-DEC-11:00 | 21.00 | 14.98 |
Annual Sum or Average | 0.535589E+11 | 0.346792E+10 | ||||||||
Minimum of Months | 0.289136E+10 | 5320.48 | 15.50 | 10.46 | 0.253441E+09 | 521.20 | 14.67 | 11.27 | ||
Maximum of Months | 0.670227E+10 | 18501.17 | 32.67 | 19.59 | 0.322721E+09 | 521.29 | 24.00 | 15.75 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.923290E+10 | 15823.14 | 22-JAN-13:32 | 17.67 | 12.37 | 0.646253E+09 | 996.08 | 27-JAN-14:09 | 16.83 | 12.83 |
February | 0.659778E+10 | 15420.79 | 19-FEB-13:43 | 16.05 | 13.09 | 0.565436E+09 | 939.56 | 22-FEB-14:09 | 18.80 | 12.71 |
March | 0.606365E+10 | 14760.36 | 19-MAR-13:53 | 19.00 | 14.75 | 0.659678E+09 | 902.27 | 01-MAR-14:09 | 18.00 | 14.28 |
April | 0.551967E+10 | 9469.42 | 26-APR-13:00 | 27.00 | 17.11 | 0.594119E+09 | 845.70 | 13-APR-13:50 | 20.17 | 15.45 |
May | 0.477014E+10 | 6952.27 | 04-MAY-13:30 | 23.00 | 16.65 | 0.641103E+09 | 845.70 | 03-MAY-13:00 | 23.00 | 16.66 |
June | 0.521869E+10 | 5845.70 | 30-JUN-13:30 | 23.00 | 17.84 | 0.648009E+09 | 845.62 | 07-JUN-13:00 | 19.00 | 14.24 |
July | 0.587815E+10 | 8206.68 | 31-JUL-12:40 | 28.00 | 21.18 | 0.605814E+09 | 845.61 | 05-JUL-13:09 | 22.00 | 16.40 |
August | 0.723489E+10 | 11116.09 | 30-AUG-12:50 | 23.83 | 17.96 | 0.681871E+09 | 845.61 | 29-AUG-13:39 | 24.67 | 17.71 |
September | 0.782660E+10 | 14395.32 | 29-SEP-13:20 | 35.33 | 18.07 | 0.607062E+09 | 977.66 | 29-SEP-13:30 | 35.00 | 18.01 |
October | 0.969838E+10 | 18464.21 | 15-OCT-13:01 | 31.83 | 15.71 | 0.644662E+09 | 1036.42 | 31-OCT-13:20 | 26.67 | 16.68 |
November | 0.909019E+10 | 18141.89 | 19-NOV-12:02 | 26.17 | 15.35 | 0.637600E+09 | 971.94 | 27-NOV-14:09 | 22.83 | 9.18 |
December | 0.973483E+10 | 17379.45 | 17-DEC-13:12 | 23.33 | 10.57 | 0.630100E+09 | 997.45 | 19-DEC-14:09 | 22.83 | 9.76 |
Annual Sum or Average | 0.868659E+11 | 0.756171E+10 | ||||||||
Minimum of Months | 0.477014E+10 | 5845.70 | 16.05 | 10.57 | 0.565436E+09 | 845.61 | 16.83 | 9.18 | ||
Maximum of Months | 0.973483E+10 | 18464.21 | 35.33 | 21.18 | 0.681871E+09 | 1036.42 | 35.00 | 18.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.349953E+10 | 7516.87 | 26-JAN-15:30 | 16.00 | 12.29 | 0.369816E+09 | 544.96 | 27-JAN-14:20 | 16.67 | 12.78 |
February | 0.340769E+10 | 8541.02 | 22-FEB-16:00 | 16.00 | 11.99 | 0.339557E+09 | 545.01 | 01-FEB-14:09 | 19.00 | 15.69 |
March | 0.418293E+10 | 16857.02 | 19-MAR-16:33 | 17.33 | 14.66 | 0.406456E+09 | 544.96 | 01-MAR-14:20 | 18.00 | 14.20 |
April | 0.535509E+10 | 18705.15 | 30-APR-16:21 | 22.00 | 15.82 | 0.379545E+09 | 544.99 | 13-APR-13:50 | 20.17 | 15.45 |
May | 0.541274E+10 | 17369.08 | 21-MAY-16:53 | 18.00 | 13.87 | 0.411717E+09 | 545.01 | 03-MAY-13:00 | 23.00 | 16.66 |
June | 0.637885E+10 | 19158.75 | 18-JUN-16:32 | 21.33 | 17.26 | 0.418242E+09 | 544.94 | 07-JUN-13:00 | 19.00 | 14.24 |
July | 0.711052E+10 | 19594.24 | 02-JUL-16:22 | 21.50 | 16.68 | 0.392728E+09 | 544.93 | 05-JUL-13:09 | 22.00 | 16.40 |
August | 0.742009E+10 | 19030.35 | 20-AUG-16:11 | 21.60 | 17.27 | 0.439701E+09 | 544.93 | 01-AUG-13:09 | 22.00 | 16.84 |
September | 0.574994E+10 | 18065.16 | 04-SEP-15:42 | 20.17 | 16.12 | 0.384411E+09 | 544.94 | 29-SEP-13:00 | 34.00 | 17.82 |
October | 0.529816E+10 | 20241.98 | 15-OCT-15:41 | 30.17 | 14.96 | 0.394538E+09 | 544.97 | 31-OCT-13:09 | 26.83 | 16.90 |
November | 0.399472E+10 | 8186.75 | 07-NOV-15:30 | 19.00 | 14.50 | 0.378528E+09 | 545.04 | 30-NOV-14:00 | 21.00 | 13.06 |
December | 0.370636E+10 | 7988.38 | 18-DEC-15:30 | 22.00 | 8.95 | 0.361046E+09 | 545.06 | 20-DEC-14:00 | 19.00 | 12.36 |
Annual Sum or Average | 0.615166E+11 | 0.467628E+10 | ||||||||
Minimum of Months | 0.340769E+10 | 7516.87 | 16.00 | 8.95 | 0.339557E+09 | 544.93 | 16.67 | 12.36 | ||
Maximum of Months | 0.742009E+10 | 20241.98 | 30.17 | 17.27 | 0.439701E+09 | 545.06 | 34.00 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253277E+10 | 3336.22 | 18-JAN-15:30 | 22.50 | 15.10 | 0.527922E+09 | 845.62 | 18-JAN-14:00 | 23.00 | 14.77 |
February | 0.240166E+10 | 3078.07 | 03-FEB-15:50 | 21.33 | 9.83 | 0.490203E+09 | 845.59 | 16-FEB-14:00 | 17.10 | 13.79 |
March | 0.297589E+10 | 4136.30 | 23-MAR-15:20 | 21.67 | 17.33 | 0.591675E+09 | 845.59 | 24-MAR-13:09 | 19.00 | 15.87 |
April | 0.377374E+10 | 5949.47 | 26-APR-14:00 | 26.00 | 16.72 | 0.565927E+09 | 845.65 | 13-APR-13:50 | 20.17 | 15.45 |
May | 0.429328E+10 | 6432.36 | 04-MAY-13:50 | 23.00 | 16.65 | 0.623008E+09 | 845.67 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.524879E+10 | 6311.63 | 30-JUN-14:00 | 23.00 | 17.84 | 0.641178E+09 | 845.60 | 07-JUN-13:00 | 19.00 | 14.24 |
July | 0.585372E+10 | 7117.05 | 19-JUL-15:00 | 27.00 | 20.16 | 0.601827E+09 | 845.59 | 05-JUL-13:09 | 22.00 | 16.40 |
August | 0.595129E+10 | 6950.24 | 17-AUG-14:00 | 28.00 | 21.18 | 0.672575E+09 | 845.59 | 01-AUG-13:09 | 22.00 | 16.84 |
September | 0.459253E+10 | 9633.77 | 30-SEP-05:02 | 23.80 | 13.82 | 0.583403E+09 | 845.61 | 29-SEP-13:39 | 34.67 | 17.95 |
October | 0.448101E+10 | 8440.73 | 05-OCT-05:02 | 20.00 | 18.62 | 0.596195E+09 | 845.65 | 31-OCT-13:09 | 26.83 | 16.90 |
November | 0.286403E+10 | 3115.96 | 10-NOV-14:30 | 19.50 | 15.77 | 0.545241E+09 | 845.59 | 10-NOV-14:00 | 19.00 | 15.88 |
December | 0.262756E+10 | 3392.68 | 05-DEC-15:00 | 25.00 | 13.20 | 0.510616E+09 | 845.59 | 05-DEC-14:00 | 25.00 | 13.20 |
Annual Sum or Average | 0.475963E+11 | 0.694977E+10 | ||||||||
Minimum of Months | 0.240166E+10 | 3078.07 | 19.50 | 9.83 | 0.490203E+09 | 845.59 | 17.10 | 13.20 | ||
Maximum of Months | 0.595129E+10 | 9633.77 | 28.00 | 21.18 | 0.672575E+09 | 845.67 | 34.67 | 17.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259566E+10 | 4323.35 | 20-JAN-09:40 | 18.33 | 14.50 | 0.363826E+09 | 544.94 | 20-JAN-14:09 | 17.00 | 14.51 |
February | 0.238575E+10 | 4360.31 | 02-FEB-09:40 | 16.33 | 12.33 | 0.335703E+09 | 545.00 | 01-FEB-14:09 | 19.00 | 15.69 |
March | 0.311055E+10 | 7583.31 | 23-MAR-09:10 | 19.50 | 15.04 | 0.404532E+09 | 544.96 | 08-MAR-10:09 | 15.17 | 11.04 |
April | 0.446185E+10 | 14573.49 | 30-APR-09:02 | 22.50 | 15.56 | 0.383005E+09 | 545.01 | 13-APR-09:00 | 23.00 | 15.73 |
May | 0.454699E+10 | 9343.18 | 28-MAY-08:53 | 19.00 | 14.24 | 0.411986E+09 | 544.99 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.542539E+10 | 15429.06 | 18-JUN-09:02 | 22.00 | 16.84 | 0.416066E+09 | 544.95 | 02-JUN-09:50 | 21.50 | 15.57 |
July | 0.648587E+10 | 17679.68 | 04-JUL-08:43 | 21.50 | 15.67 | 0.392676E+09 | 544.93 | 10-JUL-09:00 | 21.00 | 15.41 |
August | 0.680340E+10 | 17449.06 | 06-AUG-08:53 | 24.00 | 19.31 | 0.440113E+09 | 544.93 | 22-AUG-09:09 | 19.33 | 14.88 |
September | 0.477587E+10 | 15695.44 | 10-SEP-08:43 | 21.50 | 17.27 | 0.381713E+09 | 544.95 | 15-SEP-09:09 | 18.17 | 14.34 |
October | 0.444253E+10 | 17977.27 | 15-OCT-08:32 | 31.67 | 15.27 | 0.394855E+09 | 544.99 | 27-OCT-09:00 | 22.00 | 11.68 |
November | 0.282422E+10 | 3740.16 | 01-NOV-09:20 | 14.67 | 12.52 | 0.371429E+09 | 544.97 | 20-NOV-10:09 | 16.33 | 14.27 |
December | 0.265930E+10 | 4091.95 | 05-DEC-09:30 | 25.00 | 12.42 | 0.350758E+09 | 544.95 | 19-DEC-10:09 | 23.33 | 10.02 |
Annual Sum or Average | 0.505174E+11 | 0.464666E+10 | ||||||||
Minimum of Months | 0.238575E+10 | 3740.16 | 14.67 | 12.33 | 0.335703E+09 | 544.93 | 15.17 | 10.02 | ||
Maximum of Months | 0.680340E+10 | 17977.27 | 31.67 | 19.31 | 0.440113E+09 | 545.01 | 23.33 | 16.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.799924E+10 | 17762.21 | 22-JAN-13:42 | 17.83 | 12.36 | 0.619473E+09 | 944.09 | 26-JAN-14:30 | 16.50 | 11.96 |
February | 0.566184E+10 | 16255.26 | 20-FEB-13:51 | 17.00 | 11.00 | 0.544602E+09 | 895.95 | 22-FEB-14:20 | 18.60 | 12.66 |
March | 0.533810E+10 | 13273.06 | 23-MAR-13:20 | 22.33 | 16.98 | 0.634416E+09 | 860.67 | 01-MAR-14:09 | 18.00 | 14.28 |
April | 0.525603E+10 | 9997.10 | 26-APR-13:10 | 26.83 | 17.05 | 0.580453E+09 | 845.70 | 13-APR-13:50 | 20.17 | 15.45 |
May | 0.458162E+10 | 7616.84 | 04-MAY-13:30 | 23.00 | 16.65 | 0.624925E+09 | 845.70 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.525650E+10 | 6588.88 | 30-JUN-13:40 | 23.00 | 17.84 | 0.638939E+09 | 845.62 | 07-JUN-13:00 | 19.00 | 14.24 |
July | 0.607363E+10 | 8939.67 | 31-JUL-12:50 | 28.00 | 21.18 | 0.601241E+09 | 845.61 | 05-JUL-13:09 | 22.00 | 16.40 |
August | 0.737284E+10 | 11689.27 | 30-AUG-12:50 | 23.83 | 17.96 | 0.676541E+09 | 845.61 | 29-AUG-13:39 | 24.67 | 17.71 |
September | 0.761096E+10 | 15432.12 | 29-SEP-13:20 | 35.33 | 18.07 | 0.597919E+09 | 961.55 | 29-SEP-13:30 | 35.00 | 18.01 |
October | 0.919310E+10 | 19412.47 | 15-OCT-11:12 | 32.00 | 16.52 | 0.630026E+09 | 996.55 | 31-OCT-13:20 | 26.67 | 16.68 |
November | 0.797151E+10 | 19427.42 | 19-NOV-12:52 | 27.00 | 14.94 | 0.617037E+09 | 917.70 | 30-NOV-14:09 | 22.67 | 10.90 |
December | 0.840861E+10 | 17495.86 | 25-DEC-13:32 | 22.00 | 9.62 | 0.603227E+09 | 951.06 | 19-DEC-14:09 | 22.83 | 9.76 |
Annual Sum or Average | 0.807240E+11 | 0.736880E+10 | ||||||||
Minimum of Months | 0.458162E+10 | 6588.88 | 17.00 | 9.62 | 0.544602E+09 | 845.61 | 16.50 | 9.76 | ||
Maximum of Months | 0.919310E+10 | 19427.42 | 35.33 | 21.18 | 0.676541E+09 | 996.55 | 35.00 | 18.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.308051E+10 | 7259.42 | 26-JAN-15:30 | 16.00 | 12.29 | 0.351760E+09 | 544.95 | 18-JAN-14:00 | 23.00 | 14.77 |
February | 0.303379E+10 | 8299.25 | 22-FEB-16:00 | 16.00 | 11.99 | 0.323736E+09 | 545.01 | 01-FEB-14:09 | 19.00 | 15.69 |
March | 0.389923E+10 | 11035.52 | 23-MAR-16:00 | 21.00 | 17.18 | 0.387837E+09 | 544.96 | 09-MAR-14:20 | 18.00 | 14.04 |
April | 0.530093E+10 | 19707.02 | 30-APR-16:21 | 22.00 | 15.82 | 0.367981E+09 | 544.99 | 13-APR-13:50 | 20.17 | 15.45 |
May | 0.537210E+10 | 18194.69 | 21-MAY-16:53 | 18.00 | 13.87 | 0.399631E+09 | 545.00 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.649636E+10 | 20244.35 | 18-JUN-16:32 | 21.33 | 17.26 | 0.410749E+09 | 544.94 | 07-JUN-13:00 | 19.00 | 14.24 |
July | 0.732279E+10 | 20102.95 | 23-JUL-17:22 | 23.50 | 18.57 | 0.388575E+09 | 544.93 | 10-JUL-13:09 | 22.00 | 16.40 |
August | 0.759098E+10 | 20981.94 | 20-AUG-16:02 | 21.80 | 17.33 | 0.434463E+09 | 544.93 | 01-AUG-13:09 | 22.00 | 16.84 |
September | 0.573331E+10 | 19754.32 | 10-SEP-16:12 | 21.67 | 16.72 | 0.375478E+09 | 544.95 | 29-SEP-13:00 | 34.00 | 17.82 |
October | 0.516048E+10 | 21429.49 | 15-OCT-15:51 | 30.00 | 14.86 | 0.382775E+09 | 544.97 | 31-OCT-13:09 | 26.83 | 16.90 |
November | 0.358932E+10 | 9472.33 | 12-NOV-15:51 | 17.00 | 13.93 | 0.361410E+09 | 545.03 | 30-NOV-14:00 | 21.00 | 13.06 |
December | 0.324587E+10 | 7635.28 | 19-DEC-15:30 | 21.50 | 8.90 | 0.342239E+09 | 545.05 | 20-DEC-14:00 | 19.00 | 12.36 |
Annual Sum or Average | 0.598257E+11 | 0.452663E+10 | ||||||||
Minimum of Months | 0.303379E+10 | 7259.42 | 16.00 | 8.90 | 0.323736E+09 | 544.93 | 18.00 | 12.36 | ||
Maximum of Months | 0.759098E+10 | 21429.49 | 30.00 | 18.57 | 0.434463E+09 | 545.05 | 34.00 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.420975E+10 | 7268.56 | 02-JAN-06:15 | 11.00 | 8.37 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.390713E+10 | 5949.95 | 21-FEB-06:15 | 8.00 | 6.97 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.474391E+10 | 5914.06 | 13-MAR-05:15 | 11.67 | 10.55 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.566293E+10 | 6027.66 | 17-APR-05:15 | 11.00 | 9.39 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.480302E+10 | 6194.62 | 01-MAY-05:13 | 13.33 | 12.00 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.573759E+10 | 7412.31 | 12-JUN-05:13 | 13.47 | 12.38 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.662739E+10 | 7048.00 | 05-JUL-05:01 | 17.00 | 14.41 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.732773E+10 | 6216.16 | 07-AUG-05:03 | 18.00 | 17.98 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.542571E+10 | 7368.95 | 05-SEP-05:13 | 16.00 | 14.76 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.601815E+10 | 8479.16 | 16-OCT-05:01 | 18.67 | 9.53 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.526439E+10 | 8265.36 | 13-NOV-06:15 | 11.33 | 10.62 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.527745E+10 | 7676.55 | 26-DEC-06:15 | 7.00 | 1.07 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.650052E+11 | 0.00 | ||||||||
Minimum of Months | 0.390713E+10 | 5914.06 | 7.00 | 1.07 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.732773E+10 | 8479.16 | 18.67 | 17.98 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214065E+10 | 4580.29 | 09-JAN-06:03 | 2.17 | -0.0 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.204842E+10 | 3908.81 | 03-FEB-06:10 | 12.33 | 3.91 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.224347E+10 | 4005.91 | 23-MAR-05:10 | 10.67 | 9.62 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.298755E+10 | 4022.88 | 26-APR-05:13 | 13.67 | 12.31 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.310018E+10 | 3995.22 | 06-MAY-05:10 | 14.17 | 13.59 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.376773E+10 | 4203.50 | 14-JUN-05:13 | 13.33 | 12.58 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.432454E+10 | 4152.28 | 14-JUL-05:17 | 16.33 | 15.30 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.466537E+10 | 4227.85 | 19-AUG-05:17 | 18.00 | 17.57 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.385023E+10 | 4438.35 | 29-SEP-16:00 | 32.00 | 16.83 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.393511E+10 | 4818.24 | 17-OCT-16:00 | 28.00 | 17.86 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.265209E+10 | 4212.50 | 14-NOV-06:10 | 10.17 | 9.48 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.241618E+10 | 3943.43 | 01-DEC-06:10 | 9.00 | 9.00 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.381315E+11 | 0.00 | ||||||||
Minimum of Months | 0.204842E+10 | 3908.81 | 2.17 | -0.0 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.466537E+10 | 4818.24 | 32.00 | 17.86 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185964E+10 | 6364.84 | 18-JAN-15:00 | 23.00 | 14.77 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.188494E+10 | 6630.52 | 01-FEB-14:10 | 19.00 | 15.69 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.279690E+10 | 9689.58 | 23-MAR-14:30 | 22.50 | 17.34 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.511927E+10 | 12561.01 | 26-APR-13:50 | 26.17 | 16.79 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.517097E+10 | 11747.55 | 03-MAY-13:30 | 23.50 | 15.89 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.688675E+10 | 11925.43 | 21-JUN-13:40 | 23.33 | 16.78 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.843638E+10 | 13353.39 | 19-JUL-14:00 | 27.00 | 20.83 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.858856E+10 | 12795.97 | 17-AUG-14:30 | 27.35 | 20.97 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.586970E+10 | 14129.10 | 29-SEP-13:50 | 34.33 | 17.89 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.505522E+10 | 14158.33 | 16-OCT-13:10 | 33.75 | 16.61 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.226376E+10 | 6455.69 | 10-NOV-14:10 | 19.83 | 15.68 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.183793E+10 | 5843.55 | 05-DEC-15:20 | 24.33 | 12.94 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.557700E+11 | 0.00 | ||||||||
Minimum of Months | 0.183793E+10 | 5843.55 | 19.00 | 12.94 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.858856E+10 | 14158.33 | 34.33 | 20.97 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.389008E+10 | 1973.15 | 30-JAN-16:50 | 14.00 | 11.29 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.821668E+10 | 4029.24 | 20-FEB-16:54 | 17.00 | 11.51 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.142557E+11 | 5994.01 | 19-MAR-17:13 | 16.00 | 13.98 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.188513E+11 | 7853.17 | 16-APR-17:33 | 15.00 | 11.12 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.416764E+10 | 2041.21 | 29-MAY-17:50 | 16.33 | 13.08 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.911747E+10 | 3901.72 | 25-JUN-17:47 | 19.33 | 15.99 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.145503E+11 | 5900.65 | 04-JUL-18:17 | 17.67 | 14.81 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.195886E+11 | 7980.15 | 06-AUG-18:03 | 20.67 | 18.88 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.416349E+10 | 2083.87 | 04-SEP-16:53 | 18.00 | 14.96 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.939496E+10 | 4161.76 | 15-OCT-16:57 | 27.00 | 14.31 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.139095E+11 | 5930.56 | 12-NOV-16:30 | 16.00 | 13.58 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.193802E+11 | 7901.81 | 25-DEC-16:13 | 19.33 | 9.93 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.139486E+12 | 0.00 | ||||||||
Minimum of Months | 0.389008E+10 | 1973.15 | 14.00 | 9.93 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.195886E+11 | 7980.15 | 27.00 | 18.88 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.263840E+10 | 1778.60 | 30-JAN-16:50 | 14.00 | 11.29 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.689601E+10 | 3701.07 | 22-FEB-17:00 | 14.00 | 12.23 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.126573E+11 | 5478.86 | 10-MAR-17:20 | 19.00 | 11.47 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.174198E+11 | 7295.61 | 27-APR-17:40 | 16.33 | 13.89 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.335125E+10 | 1789.89 | 28-MAY-17:45 | 17.33 | 14.00 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.822485E+10 | 3599.39 | 25-JUN-17:53 | 19.00 | 15.88 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.135323E+11 | 5493.25 | 04-JUL-18:13 | 17.67 | 14.81 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.183876E+11 | 7338.43 | 06-AUG-17:56 | 21.00 | 18.97 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.343595E+10 | 1921.16 | 29-SEP-16:40 | 30.67 | 16.79 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.832404E+10 | 3843.27 | 15-OCT-16:48 | 27.50 | 14.43 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.123906E+11 | 5454.75 | 07-NOV-16:30 | 18.00 | 14.12 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.174631E+11 | 7246.99 | 19-DEC-16:20 | 20.33 | 7.91 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.124721E+12 | 0.00 | ||||||||
Minimum of Months | 0.263840E+10 | 1778.60 | 14.00 | 7.91 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.183876E+11 | 7338.43 | 30.67 | 18.97 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149387E+10 | 1716.69 | 26-JAN-16:20 | 15.33 | 12.49 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.591130E+10 | 3695.79 | 22-FEB-17:00 | 14.00 | 12.23 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.117652E+11 | 5508.82 | 22-MAR-17:20 | 17.33 | 15.23 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.169230E+11 | 7345.61 | 27-APR-17:30 | 16.50 | 14.04 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.286283E+10 | 1861.84 | 29-MAY-17:43 | 16.33 | 13.08 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.798634E+10 | 3709.47 | 25-JUN-17:53 | 19.00 | 15.88 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.134077E+11 | 5599.20 | 09-JUL-17:54 | 18.00 | 14.96 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.182399E+11 | 7429.02 | 20-AUG-17:40 | 19.60 | 16.67 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.309702E+10 | 1991.59 | 29-SEP-16:40 | 30.67 | 16.79 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.778806E+10 | 3947.59 | 15-OCT-16:50 | 27.50 | 14.43 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.114380E+11 | 5432.48 | 07-NOV-16:30 | 18.00 | 14.12 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.162383E+11 | 7238.05 | 19-DEC-16:20 | 20.33 | 7.91 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.117152E+12 | 0.00 | ||||||||
Minimum of Months | 0.149387E+10 | 1716.69 | 14.00 | 7.91 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.182399E+11 | 7429.02 | 30.67 | 16.79 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238349E+12 | 90753.66 | 02-JAN-17:00 | 11.00 | 7.90 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.434539E+12 | 181660.68 | 21-FEB-17:00 | 16.00 | 13.02 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.726510E+12 | 273218.06 | 24-MAR-16:00 | 18.00 | 14.96 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.941259E+12 | 365249.49 | 26-APR-16:00 | 22.00 | 16.40 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.237859E+12 | 103005.91 | 01-MAY-00:10 | 15.20 | 14.50 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.466131E+12 | 181471.84 | 21-JUN-16:00 | 22.00 | 16.40 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.727924E+12 | 273617.91 | 19-JUL-14:20 | 27.00 | 20.61 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.972014E+12 | 370214.47 | 06-AUG-19:21 | 18.50 | 17.84 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.231907E+12 | 104376.46 | 01-SEP-00:10 | 16.07 | 14.82 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.483967E+12 | 182664.70 | 16-OCT-16:00 | 29.00 | 15.40 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.705779E+12 | 274400.25 | 13-NOV-17:00 | 15.00 | 13.80 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.974439E+12 | 376379.21 | 26-DEC-01:11 | 12.33 | 3.30 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.714068E+13 | 0.00 | ||||||||
Minimum of Months | 0.231907E+12 | 90753.66 | 11.00 | 3.30 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.974439E+12 | 376379.21 | 29.00 | 20.61 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.941344E+09 | 108950.18 | 23-JAN-04:50 | 9.00 |
February | 0.424784E+09 | 113479.15 | 20-FEB-15:20 | 17.00 |
March | 0.226566E+09 | 111041.67 | 06-MAR-04:17 | 10.93 |
April | 0.511735E+09 | 114183.46 | 09-APR-23:08 | 13.00 |
May | 0.441037E+09 | 113866.44 | 29-MAY-14:28 | 19.50 |
June | 0.293566E+09 | 120942.14 | 08-JUN-03:05 | 14.00 |
July | 0.726520E+09 | 116304.65 | 23-JUL-23:07 | 17.83 |
August | 0.618906E+09 | 122484.31 | 06-AUG-18:30 | 20.00 |
September | 0.526450E+09 | 118085.31 | 30-SEP-03:50 | 23.93 |
October | 0.876860E+09 | 121840.57 | 01-OCT-16:20 | 21.67 |
November | 0.573109E+09 | 113138.27 | 12-NOV-11:50 | 16.83 |
December | 0.555470E+09 | 114870.66 | 25-DEC-15:18 | 21.67 |
Annual Sum or Average | 0.671635E+10 | |||
Minimum of Months | 0.226566E+09 | 108950.18 | 9.00 | |
Maximum of Months | 0.941344E+09 | 122484.31 | 23.93 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 96743251.73 | 53864.98 | 02-JAN-05:11 | 11.00 |
February | 1683358.35 | 6871.98 | 27-FEB-06:03 | 11.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 8864201.60 | 50869.47 | 26-DEC-06:03 | 7.00 |
Annual Sum or Average | 0.107291E+09 | |||
Minimum of Months | 0.00 | 0.00 | 7.00 | |
Maximum of Months | 96743251.73 | 53864.98 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 37095535.82 | 8279.68 | 03-JAN-06:03 | 4.67 |
February | 2422933.88 | 5237.69 | 21-FEB-06:02 | 8.00 |
March | 14991053.05 | 8316.28 | 30-MAR-05:02 | 4.97 |
April | 229489.74 | 1912.41 | 01-APR-05:02 | 7.83 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 1539044.83 | 4536.67 | 24-NOV-06:03 | 8.92 |
December | 5899306.51 | 7673.47 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 62177363.83 | |||
Minimum of Months | 0.00 | 0.00 | 4.67 | |
Maximum of Months | 37095535.82 | 8316.28 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15914003.76 | 8771.32 | 03-JAN-06:03 | 4.67 |
February | 209249.80 | 1306.32 | 06-FEB-06:03 | 9.00 |
March | 10721946.13 | 9145.76 | 30-MAR-05:02 | 4.97 |
April | 266444.82 | 1890.75 | 01-APR-05:02 | 7.83 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 184405.03 | 1229.37 | 24-NOV-06:03 | 8.92 |
December | 3640817.11 | 7053.95 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 30936866.64 | |||
Minimum of Months | 0.00 | 0.00 | 4.67 | |
Maximum of Months | 15914003.76 | 9145.76 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1802203.53 | 5556.25 | 09-JAN-06:03 | 2.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 8484957.54 | 10847.40 | 30-MAR-05:02 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 753025.49 | 3913.00 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 11040186.56 | |||
Minimum of Months | 0.00 | 0.00 | 2.17 | |
Maximum of Months | 8484957.54 | 10847.40 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6554027.38 | 7592.49 | 09-JAN-06:03 | 2.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 2028753.14 | 5902.24 | 30-MAR-05:02 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 290913.95 | 1818.79 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 8873694.47 | |||
Minimum of Months | 0.00 | 0.00 | 2.17 | |
Maximum of Months | 6554027.38 | 7592.49 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.527648E+09 | 10931.33 | 09-JAN-05:11 | 4.67 |
February | 0.225625E+09 | 10190.10 | 06-FEB-05:12 | 8.33 |
March | 0.279045E+09 | 10374.60 | 30-MAR-04:11 | 4.57 |
April | 27319823.29 | 9730.96 | 01-APR-04:11 | 8.00 |
May | 7124469.22 | 9404.59 | 15-MAY-05:03 | 8.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 15663635.69 | 9554.15 | 30-OCT-05:02 | 10.83 |
November | 0.150676E+09 | 10096.40 | 24-NOV-05:12 | 8.33 |
December | 0.332249E+09 | 10210.92 | 13-DEC-05:11 | 6.67 |
Annual Sum or Average | 0.156535E+10 | |||
Minimum of Months | 0.00 | 0.00 | 4.57 | |
Maximum of Months | 0.527648E+09 | 10931.33 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230645E+09 | 12330.71 | 09-JAN-05:11 | 4.67 |
February | 0.102420E+09 | 11362.36 | 06-FEB-05:12 | 8.33 |
March | 0.121248E+09 | 11928.13 | 30-MAR-04:11 | 4.57 |
April | 10780345.96 | 10954.17 | 01-APR-04:11 | 8.00 |
May | 1795443.64 | 6931.77 | 15-MAY-05:03 | 8.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 6316402.05 | 10287.77 | 30-OCT-05:02 | 10.83 |
November | 55617321.69 | 11272.71 | 24-NOV-05:12 | 8.33 |
December | 0.136755E+09 | 11421.13 | 13-DEC-05:11 | 6.67 |
Annual Sum or Average | 0.665579E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.57 | |
Maximum of Months | 0.230645E+09 | 12330.71 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189201E+09 | 13448.21 | 02-JAN-05:11 | 11.00 |
February | 88848049.02 | 12288.73 | 13-FEB-05:11 | 14.33 |
March | 0.188004E+09 | 13038.26 | 30-MAR-04:11 | 4.57 |
April | 19191354.65 | 11882.81 | 01-APR-05:02 | 7.83 |
May | 9672093.95 | 11831.12 | 15-MAY-05:03 | 8.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 147497.07 | 983.31 | 12-OCT-05:03 | 9.00 |
November | 25488851.95 | 11988.51 | 06-NOV-06:01 | 10.17 |
December | 82284404.07 | 12705.81 | 13-DEC-05:11 | 6.67 |
Annual Sum or Average | 0.602837E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.57 | |
Maximum of Months | 0.189201E+09 | 13448.21 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168740E+09 | 11597.15 | 02-JAN-05:11 | 11.00 |
February | 43781119.93 | 10059.37 | 21-FEB-06:02 | 8.00 |
March | 71310136.91 | 11145.58 | 30-MAR-04:11 | 4.57 |
April | 6366247.43 | 10143.46 | 01-APR-05:02 | 7.83 |
May | 570953.51 | 3197.54 | 13-MAY-05:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 42431.69 | 353.60 | 30-OCT-05:02 | 10.83 |
November | 21063893.49 | 10370.84 | 06-NOV-06:01 | 10.17 |
December | 71753178.45 | 10798.94 | 13-DEC-05:11 | 6.67 |
Annual Sum or Average | 0.383628E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.57 | |
Maximum of Months | 0.168740E+09 | 11597.15 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43539320.94 | 7562.53 | 01-JAN-08:11 | 10.67 |
February | 47043825.36 | 8810.56 | 13-FEB-04:01 | 13.83 |
March | 58609462.97 | 8289.44 | 27-MAR-03:02 | 11.83 |
April | 81804047.36 | 9630.75 | 03-APR-03:02 | 12.00 |
May | 40631952.05 | 7730.63 | 01-MAY-03:02 | 13.50 |
June | 40952572.16 | 8200.54 | 19-JUN-03:01 | 16.00 |
July | 73715043.52 | 8393.93 | 13-JUL-03:01 | 17.00 |
August | 84277731.12 | 8841.17 | 29-AUG-03:01 | 16.00 |
September | 34915710.53 | 7935.91 | 01-SEP-03:01 | 15.25 |
October | 55739627.61 | 7509.24 | 05-OCT-03:01 | 21.00 |
November | 74289644.64 | 10243.45 | 12-NOV-10:21 | 16.00 |
December | 92086832.34 | 9546.97 | 18-DEC-04:03 | 18.00 |
Annual Sum or Average | 0.727606E+09 | |||
Minimum of Months | 34915710.53 | 7509.24 | 10.67 | |
Maximum of Months | 92086832.34 | 10243.45 | 21.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106797E+09 | 5388.01 | 17-JAN-06:03 | 15.83 |
February | 42621968.35 | 5642.17 | 28-FEB-06:02 | 10.17 |
March | 29584889.52 | 5548.83 | 06-MAR-06:02 | 11.17 |
April | 31724476.20 | 4692.11 | 18-APR-05:03 | 11.17 |
May | 30970212.18 | 4873.54 | 08-MAY-05:01 | 14.00 |
June | 20496734.30 | 4670.75 | 12-JUN-05:02 | 13.33 |
July | 26208943.41 | 4334.97 | 12-JUL-04:11 | 17.00 |
August | 19986188.73 | 4339.92 | 29-AUG-04:11 | 15.93 |
September | 21021017.65 | 4745.39 | 25-SEP-04:11 | 17.00 |
October | 36440383.56 | 4887.97 | 15-OCT-15:01 | 30.83 |
November | 42187200.07 | 5057.81 | 28-NOV-06:03 | 15.67 |
December | 49229849.17 | 5086.64 | 19-DEC-06:03 | 16.83 |
Annual Sum or Average | 0.457269E+09 | |||
Minimum of Months | 19986188.73 | 4334.97 | 10.17 | |
Maximum of Months | 0.106797E+09 | 5642.17 | 30.83 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141244E+10 | 10373.36 | 09-JAN-06:03 | 2.17 |
February | 0.916230E+09 | 6218.81 | 06-FEB-05:13 | 8.33 |
March | 0.110557E+10 | 9582.31 | 24-MAR-05:02 | 12.00 |
April | 0.384553E+09 | 12398.71 | 26-APR-05:02 | 13.83 |
May | 0.288441E+09 | 11911.95 | 04-MAY-05:03 | 14.33 |
June | 0.118547E+09 | 13267.40 | 22-JUN-05:03 | 14.00 |
July | 59131846.50 | 11590.17 | 17-JUL-05:01 | 15.83 |
August | 66803986.77 | 10590.90 | 31-AUG-05:03 | 15.17 |
September | 0.138744E+09 | 11648.69 | 12-SEP-05:02 | 15.00 |
October | 0.351718E+09 | 12618.94 | 18-OCT-05:03 | 15.00 |
November | 0.771055E+09 | 7821.85 | 01-NOV-05:02 | 12.83 |
December | 0.122010E+10 | 6799.65 | 26-DEC-06:03 | 7.00 |
Annual Sum or Average | 0.683334E+10 | |||
Minimum of Months | 59131846.50 | 6218.81 | 2.17 | |
Maximum of Months | 0.141244E+10 | 13267.40 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148736E+09 | 541.09 | 11-JAN-05:12 | 5.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 489277.72 | 355.41 | 14-MAY-04:45 | 8.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.149225E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.00 | |
Maximum of Months | 0.148736E+09 | 541.09 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.179018E+11 | 19263.35 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.162411E+11 | 19263.35 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.193470E+11 | 19263.35 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.172320E+11 | 19263.35 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.186244E+11 | 19263.35 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.185523E+11 | 19263.35 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.173042E+11 | 19263.35 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.193467E+11 | 19263.35 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.172320E+11 | 19263.35 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.179021E+11 | 19263.35 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.177053E+11 | 19263.35 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.173045E+11 | 19263.35 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.214693E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.162411E+11 | 19263.35 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.193470E+11 | 19263.35 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.160770E+11 | 17299.84 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.145856E+11 | 17299.84 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.173750E+11 | 17299.84 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.154756E+11 | 17299.84 | 03-APR-07:10 | 0.235253E+11 | 17206.63 | 03-APR-07:10 |
May | 0.167260E+11 | 17299.84 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.166612E+11 | 17299.84 | 01-JUN-07:10 | 0.244214E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.155404E+11 | 17299.84 | 03-JUL-07:10 | 0.239654E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.173747E+11 | 17299.84 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.154756E+11 | 17299.84 | 01-SEP-07:10 | 0.235253E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.160774E+11 | 17299.84 | 02-OCT-07:10 | 0.243681E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.159006E+11 | 17299.84 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.155407E+11 | 17299.84 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.192810E+12 | 0.289609E+12 | ||||
Minimum of Months | 0.145856E+11 | 17299.84 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.173750E+11 | 17299.84 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.160770E+11 | 17299.84 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.145856E+11 | 17299.84 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.173750E+11 | 17299.84 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.154756E+11 | 17299.84 | 03-APR-07:10 | 0.235252E+11 | 17206.56 | 03-APR-07:10 |
May | 0.167260E+11 | 17299.84 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.166612E+11 | 17299.84 | 01-JUN-07:10 | 0.244213E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.155404E+11 | 17299.84 | 03-JUL-07:10 | 0.239653E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.173747E+11 | 17299.84 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.154756E+11 | 17299.84 | 01-SEP-07:10 | 0.235252E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.160774E+11 | 17299.84 | 02-OCT-07:10 | 0.243680E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.159006E+11 | 17299.84 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.155407E+11 | 17299.84 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.192810E+12 | 0.289607E+12 | ||||
Minimum of Months | 0.145856E+11 | 17299.84 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.173750E+11 | 17299.84 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.160770E+11 | 17299.84 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.145856E+11 | 17299.84 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.173750E+11 | 17299.84 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.154756E+11 | 17299.84 | 03-APR-07:10 | 0.235252E+11 | 17206.56 | 03-APR-07:10 |
May | 0.167260E+11 | 17299.84 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.166612E+11 | 17299.84 | 01-JUN-07:10 | 0.244213E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.155404E+11 | 17299.84 | 03-JUL-07:10 | 0.239653E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.173747E+11 | 17299.84 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.154756E+11 | 17299.84 | 01-SEP-07:10 | 0.235252E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.160774E+11 | 17299.84 | 02-OCT-07:10 | 0.243680E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.159006E+11 | 17299.84 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.155407E+11 | 17299.84 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.192810E+12 | 0.289607E+12 | ||||
Minimum of Months | 0.145856E+11 | 17299.84 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.173750E+11 | 17299.84 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.129893E+10 | 2172.17 | 02-JAN-16:30 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.109467E+10 | 2172.17 | 27-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.125068E+10 | 1513.35 | 01-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.106565E+10 | 1513.35 | 21-APR-15:00 | 0.295395E+10 | 2160.55 | 03-APR-07:10 |
May | 0.112304E+10 | 1234.08 | 08-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.111133E+10 | 1234.08 | 09-JUN-07:10 | 0.306647E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.103941E+10 | 1133.80 | 11-JUL-07:10 | 0.300922E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.117553E+10 | 1234.08 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.109723E+10 | 1613.63 | 18-SEP-07:10 | 0.295395E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.122106E+10 | 1892.90 | 20-OCT-15:00 | 0.305979E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.126674E+10 | 2172.17 | 06-NOV-16:19 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.127903E+10 | 2172.17 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.140233E+11 | 0.363647E+11 | ||||
Minimum of Months | 0.103941E+10 | 1133.80 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.129893E+10 | 2172.17 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.814906E+09 | 1399.83 | 02-JAN-16:30 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.696623E+09 | 1399.83 | 27-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.799368E+09 | 975.26 | 01-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.687016E+09 | 975.26 | 21-APR-15:39 | 0.190364E+10 | 1392.34 | 03-APR-07:10 |
May | 0.728925E+09 | 730.66 | 08-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.722015E+09 | 730.66 | 08-JUN-07:10 | 0.197615E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.675081E+09 | 730.66 | 28-JUL-15:20 | 0.193926E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.760155E+09 | 730.66 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.702525E+09 | 975.26 | 18-SEP-07:10 | 0.190364E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.768195E+09 | 1219.86 | 20-OCT-15:50 | 0.197184E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.803427E+09 | 1399.83 | 06-NOV-16:19 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.798136E+09 | 1399.83 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.895637E+10 | 0.234348E+11 | ||||
Minimum of Months | 0.675081E+09 | 730.66 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.814906E+09 | 1399.83 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.122364E+10 | 2172.22 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.105759E+10 | 2172.22 | 27-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.123421E+10 | 1513.38 | 16-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.106640E+10 | 1513.38 | 21-APR-15:00 | 0.295400E+10 | 2160.58 | 03-APR-07:10 |
May | 0.113281E+10 | 1234.11 | 08-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.112326E+10 | 1234.11 | 08-JUN-07:10 | 0.306652E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.105002E+10 | 1133.82 | 11-JUL-07:10 | 0.300927E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.118267E+10 | 1234.11 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.108979E+10 | 1513.38 | 18-SEP-07:10 | 0.295400E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.115942E+10 | 1513.38 | 04-OCT-07:10 | 0.305983E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.120860E+10 | 2172.22 | 06-NOV-16:40 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.119429E+10 | 2172.22 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.137227E+11 | 0.363653E+11 | ||||
Minimum of Months | 0.105002E+10 | 1133.82 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.123421E+10 | 2172.22 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.807397E+09 | 1399.83 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.691227E+09 | 1399.83 | 27-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.799287E+09 | 1039.89 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.687775E+09 | 975.26 | 05-APR-07:10 | 0.190363E+10 | 1392.33 | 03-APR-07:10 |
May | 0.727966E+09 | 975.26 | 09-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.719353E+09 | 795.29 | 08-JUN-07:10 | 0.197614E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.672612E+09 | 795.29 | 11-JUL-07:10 | 0.193924E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.760861E+09 | 975.26 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.706468E+09 | 1219.86 | 18-SEP-07:10 | 0.190363E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.762085E+09 | 1219.86 | 05-OCT-07:10 | 0.197183E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.788669E+09 | 1399.83 | 06-NOV-16:40 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.792104E+09 | 1399.83 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.891580E+10 | 0.234347E+11 | ||||
Minimum of Months | 0.672612E+09 | 795.29 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.807397E+09 | 1399.83 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.129195E+10 | 2172.17 | 02-JAN-16:30 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.108952E+10 | 2172.17 | 27-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.124766E+10 | 1513.35 | 01-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.106413E+10 | 1513.35 | 21-APR-15:00 | 0.295395E+10 | 2160.55 | 03-APR-07:10 |
May | 0.112210E+10 | 1234.08 | 08-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.111040E+10 | 1133.80 | 08-JUN-07:10 | 0.306647E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.103895E+10 | 1133.80 | 11-JUL-07:10 | 0.300922E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.117398E+10 | 1234.08 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.109478E+10 | 1513.35 | 05-SEP-07:10 | 0.295395E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.121296E+10 | 1892.90 | 23-OCT-15:00 | 0.305979E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.126104E+10 | 2172.17 | 06-NOV-16:19 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.127226E+10 | 2172.17 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.139797E+11 | 0.363647E+11 | ||||
Minimum of Months | 0.103895E+10 | 1133.80 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.129195E+10 | 2172.17 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.812548E+09 | 1399.83 | 02-JAN-16:30 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.694932E+09 | 1399.83 | 27-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.797807E+09 | 975.26 | 01-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.686186E+09 | 975.26 | 21-APR-15:39 | 0.190364E+10 | 1392.34 | 03-APR-07:10 |
May | 0.727927E+09 | 730.66 | 08-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.721042E+09 | 730.66 | 09-JUN-07:10 | 0.197615E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.674314E+09 | 730.66 | 28-JUL-15:39 | 0.193926E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.759532E+09 | 730.66 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.701381E+09 | 975.26 | 18-SEP-07:10 | 0.190364E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.765255E+09 | 1219.86 | 20-OCT-15:50 | 0.197184E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.802307E+09 | 1399.83 | 06-NOV-16:19 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.796180E+09 | 1399.83 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.893941E+10 | 0.234348E+11 | ||||
Minimum of Months | 0.674314E+09 | 730.66 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.812548E+09 | 1399.83 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.122302E+10 | 2172.22 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.105679E+10 | 2172.22 | 27-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.123259E+10 | 1513.38 | 16-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.106481E+10 | 1513.38 | 21-APR-15:00 | 0.295400E+10 | 2160.58 | 03-APR-07:10 |
May | 0.113121E+10 | 1234.11 | 08-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.112207E+10 | 1234.11 | 09-JUN-07:10 | 0.306652E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.104922E+10 | 1133.82 | 11-JUL-07:10 | 0.300927E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.118126E+10 | 1234.11 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.108847E+10 | 1513.38 | 18-SEP-07:10 | 0.295400E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.115804E+10 | 1513.38 | 04-OCT-07:10 | 0.305983E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.120795E+10 | 2172.22 | 06-NOV-16:40 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.119366E+10 | 2172.22 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.137091E+11 | 0.363653E+11 | ||||
Minimum of Months | 0.104922E+10 | 1133.82 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.123259E+10 | 2172.22 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.805297E+09 | 1399.83 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.689833E+09 | 1399.83 | 27-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.797652E+09 | 975.26 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.686707E+09 | 975.26 | 05-APR-07:10 | 0.190363E+10 | 1392.33 | 03-APR-07:10 |
May | 0.726794E+09 | 975.26 | 09-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.718288E+09 | 795.29 | 08-JUN-07:10 | 0.197614E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.671712E+09 | 795.29 | 11-JUL-07:10 | 0.193924E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.759553E+09 | 975.26 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.705113E+09 | 1219.86 | 18-SEP-07:10 | 0.190363E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.759331E+09 | 1219.86 | 05-OCT-07:10 | 0.197183E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.786776E+09 | 1399.83 | 06-NOV-16:40 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.789392E+09 | 1399.83 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.889645E+10 | 0.234347E+11 | ||||
Minimum of Months | 0.671712E+09 | 795.29 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.805297E+09 | 1399.83 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.129194E+10 | 2172.17 | 02-JAN-16:30 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.108917E+10 | 2172.17 | 27-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.124766E+10 | 1513.35 | 01-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.106413E+10 | 1513.35 | 21-APR-15:00 | 0.295395E+10 | 2160.55 | 03-APR-07:10 |
May | 0.112207E+10 | 1234.08 | 08-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.111032E+10 | 1133.80 | 08-JUN-07:10 | 0.306647E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.103895E+10 | 1133.80 | 11-JUL-07:10 | 0.300922E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.117398E+10 | 1234.08 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.109475E+10 | 1513.35 | 05-SEP-07:10 | 0.295395E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.121280E+10 | 1892.90 | 23-OCT-15:00 | 0.305979E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.126104E+10 | 2172.17 | 06-NOV-16:19 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.127202E+10 | 2172.17 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.139788E+11 | 0.363647E+11 | ||||
Minimum of Months | 0.103895E+10 | 1133.80 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.129194E+10 | 2172.17 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.812470E+09 | 1399.83 | 02-JAN-16:30 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.694887E+09 | 1399.83 | 27-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.797768E+09 | 975.26 | 01-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.686020E+09 | 975.26 | 21-APR-15:50 | 0.190364E+10 | 1392.34 | 03-APR-07:10 |
May | 0.727925E+09 | 730.66 | 08-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.721003E+09 | 730.66 | 09-JUN-07:10 | 0.197615E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.674297E+09 | 730.66 | 28-JUL-15:39 | 0.193926E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.759519E+09 | 730.66 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.701306E+09 | 975.26 | 18-SEP-07:10 | 0.190364E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.765214E+09 | 1219.86 | 20-OCT-15:50 | 0.197184E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.802305E+09 | 1399.83 | 06-NOV-16:19 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.796084E+09 | 1399.83 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.893880E+10 | 0.234348E+11 | ||||
Minimum of Months | 0.674297E+09 | 730.66 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.812470E+09 | 1399.83 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.122296E+10 | 2172.22 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.105679E+10 | 2172.22 | 27-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.123257E+10 | 1513.38 | 16-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.106479E+10 | 1513.38 | 21-APR-15:00 | 0.295400E+10 | 2160.58 | 03-APR-07:10 |
May | 0.113112E+10 | 1234.11 | 08-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.112201E+10 | 1234.11 | 09-JUN-07:10 | 0.306652E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.104919E+10 | 1133.82 | 11-JUL-07:10 | 0.300927E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.118121E+10 | 1234.11 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.108840E+10 | 1513.38 | 18-SEP-07:10 | 0.295400E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.115799E+10 | 1513.38 | 04-OCT-07:10 | 0.305983E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.120795E+10 | 2172.22 | 06-NOV-16:40 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.119366E+10 | 2172.22 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.137086E+11 | 0.363653E+11 | ||||
Minimum of Months | 0.104919E+10 | 1133.82 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.123257E+10 | 2172.22 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.805220E+09 | 1399.83 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.689707E+09 | 1399.83 | 27-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.797574E+09 | 975.26 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.686632E+09 | 975.26 | 05-APR-07:10 | 0.190363E+10 | 1392.33 | 03-APR-07:10 |
May | 0.726717E+09 | 975.26 | 09-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.718194E+09 | 795.29 | 08-JUN-07:10 | 0.197614E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.671680E+09 | 795.29 | 11-JUL-07:10 | 0.193924E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.759514E+09 | 975.26 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.705068E+09 | 1219.86 | 18-SEP-07:10 | 0.190363E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.759241E+09 | 1219.86 | 05-OCT-07:10 | 0.197183E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.786629E+09 | 1399.83 | 06-NOV-16:40 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.789351E+09 | 1399.83 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.889553E+10 | 0.234347E+11 | ||||
Minimum of Months | 0.671680E+09 | 795.29 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.805220E+09 | 1399.83 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.522007E+10 | 5431.44 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.473481E+10 | 5431.44 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.562303E+10 | 5431.44 | 01-MAR-08:09 | 0.762606E+12 | 284724.39 | 01-MAR-00:10 |
April | 0.502580E+10 | 5431.44 | 03-APR-07:10 | 0.984007E+12 | 379632.52 | 01-APR-00:10 |
May | 0.542155E+10 | 5431.44 | 01-MAY-07:10 | 0.254202E+12 | 94908.13 | 01-MAY-00:10 |
June | 0.539412E+10 | 5431.44 | 01-JUN-07:10 | 0.492004E+12 | 189816.26 | 01-JUN-00:10 |
July | 0.505323E+10 | 5431.44 | 03-JUL-07:10 | 0.762606E+12 | 284724.39 | 01-JUL-00:10 |
August | 0.562303E+10 | 5431.44 | 01-AUG-07:10 | 0.101681E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.502580E+10 | 5431.44 | 01-SEP-07:10 | 0.246002E+12 | 94908.13 | 01-SEP-00:10 |
October | 0.522007E+10 | 5431.44 | 02-OCT-07:10 | 0.508404E+12 | 189816.26 | 01-OCT-00:10 |
November | 0.515799E+10 | 5431.44 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.505323E+10 | 5431.44 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.625527E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.473481E+10 | 5431.44 | 0.246002E+12 | 94908.13 | ||
Maximum of Months | 0.562303E+10 | 5431.44 | 0.101681E+13 | 379632.52 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.241145E+09 | 250.91 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.218729E+09 | 250.91 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.259761E+09 | 250.91 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.232171E+09 | 250.91 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.250453E+09 | 250.91 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.249186E+09 | 250.91 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.233438E+09 | 250.91 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.259761E+09 | 250.91 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.232171E+09 | 250.91 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.241145E+09 | 250.91 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.238278E+09 | 250.91 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.233438E+09 | 250.91 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.288968E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.218729E+09 | 250.91 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.259761E+09 | 250.91 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.241145E+09 | 250.91 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.218729E+09 | 250.91 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.259761E+09 | 250.91 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.232171E+09 | 250.91 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.250453E+09 | 250.91 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.249186E+09 | 250.91 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.233438E+09 | 250.91 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.259761E+09 | 250.91 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.232171E+09 | 250.91 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.241145E+09 | 250.91 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.238278E+09 | 250.91 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.233438E+09 | 250.91 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.288968E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.218729E+09 | 250.91 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.259761E+09 | 250.91 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.241145E+09 | 250.91 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.218729E+09 | 250.91 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.259761E+09 | 250.91 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.232171E+09 | 250.91 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.250453E+09 | 250.91 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.249186E+09 | 250.91 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.233438E+09 | 250.91 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.259761E+09 | 250.91 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.232171E+09 | 250.91 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.241145E+09 | 250.91 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.238278E+09 | 250.91 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.233438E+09 | 250.91 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.288968E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.218729E+09 | 250.91 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.259761E+09 | 250.91 | 0.208766E+11 | 7794.42 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.179018E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.162411E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.193470E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.172320E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.186244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.185523E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.173042E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.193467E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.172320E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.179021E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.177053E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.173045E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.214693E+12 | 0.424397E+12 | ||||||
Minimum of Months | 0.121482E+11 | 0.162411E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.193470E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.160770E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.145856E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.173750E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.154756E+11 | 0.235253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.167260E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.166612E+11 | 0.244214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.155404E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.173747E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.154756E+11 | 0.235253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.160774E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.159006E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.155407E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.192810E+12 | 0.289609E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.145856E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.173750E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.160770E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.145856E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.173750E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.154756E+11 | 0.235252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.167260E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.166612E+11 | 0.244213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.155404E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.173747E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.154756E+11 | 0.235252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.160774E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.159006E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.155407E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.192810E+12 | 0.289607E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.145856E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.173750E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.160770E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.145856E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.173750E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.154756E+11 | 0.235252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.167260E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.166612E+11 | 0.244213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.155404E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.173747E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.154756E+11 | 0.235252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.160774E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.159006E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.155407E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.192810E+12 | 0.289607E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.145856E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.173750E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.129893E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 306261.48 | 0.299162E+09 |
February | 0.136985E+10 | 0.109467E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47019.98 | 0.351241E+09 |
March | 0.163685E+10 | 0.125068E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11942.67 | 0.371858E+09 |
April | 0.145243E+10 | 0.106565E+10 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 436932.15 | 0.214223E+09 |
May | 0.157338E+10 | 0.112304E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.15 | 0.251730E+09 |
June | 0.156900E+10 | 0.111133E+10 | 0.306647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29288.53 | 0.133687E+09 |
July | 0.145680E+10 | 0.103941E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2095561.59 | 92312470.85 |
August | 0.163685E+10 | 0.117553E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2221457.70 | 0.114563E+09 |
September | 0.145243E+10 | 0.109723E+10 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3326360.67 | 0.115614E+09 |
October | 0.150991E+10 | 0.122106E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12569107.06 | 0.187151E+09 |
November | 0.149516E+10 | 0.126674E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 843584.48 | 0.282990E+09 |
December | 0.145680E+10 | 0.127903E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 203796.25 | 0.310567E+09 |
Annual Sum or Average | 0.181194E+11 | 0.140233E+11 | 0.363647E+11 | 22091373.71 | 0.272510E+10 | ||||
Minimum of Months | 0.136985E+10 | 0.103941E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.15 | 92312470.85 |
Maximum of Months | 0.163685E+10 | 0.129893E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12569107.06 | 0.371858E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.814906E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 216837.55 | 0.197531E+09 |
February | 0.882782E+09 | 0.696623E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31051.70 | 0.228829E+09 |
March | 0.105485E+10 | 0.799368E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7823.28 | 0.241398E+09 |
April | 0.936002E+09 | 0.687016E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 164861.00 | 0.138899E+09 |
May | 0.101394E+10 | 0.728925E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.94 | 0.167469E+09 |
June | 0.101113E+10 | 0.722015E+09 | 0.197615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19330.39 | 87146234.16 |
July | 0.938820E+09 | 0.675081E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1294157.32 | 60347150.56 |
August | 0.105485E+10 | 0.760155E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1419966.51 | 72255111.04 |
September | 0.936002E+09 | 0.702525E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2201361.74 | 76610333.19 |
October | 0.973041E+09 | 0.768195E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7818781.62 | 0.121312E+09 |
November | 0.963541E+09 | 0.803427E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 444462.07 | 0.183205E+09 |
December | 0.938820E+09 | 0.798136E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 149476.67 | 0.198839E+09 |
Annual Sum or Average | 0.116768E+11 | 0.895637E+10 | 0.234348E+11 | 13768148.80 | 0.177384E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.675081E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.94 | 60347150.56 |
Maximum of Months | 0.105485E+10 | 0.814906E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7818781.62 | 0.241398E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.122364E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 156990.81 | 0.310158E+09 |
February | 0.136988E+10 | 0.105759E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37732.60 | 0.358526E+09 |
March | 0.163688E+10 | 0.123421E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.29 | 0.371452E+09 |
April | 0.145246E+10 | 0.106640E+10 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 267479.43 | 0.215436E+09 |
May | 0.157341E+10 | 0.113281E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.41 | 0.245351E+09 |
June | 0.156904E+10 | 0.112326E+10 | 0.306652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29291.85 | 0.129290E+09 |
July | 0.145684E+10 | 0.105002E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2156347.59 | 90364684.91 |
August | 0.163688E+10 | 0.118267E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2070961.23 | 0.115681E+09 |
September | 0.145246E+10 | 0.108979E+10 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3204888.47 | 0.123376E+09 |
October | 0.150994E+10 | 0.115942E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10123397.13 | 0.199750E+09 |
November | 0.149520E+10 | 0.120860E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76909.49 | 0.296742E+09 |
December | 0.145684E+10 | 0.119429E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71501.61 | 0.325587E+09 |
Annual Sum or Average | 0.181198E+11 | 0.137227E+11 | 0.363653E+11 | 18195654.93 | 0.278171E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.105002E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.41 | 90364684.91 |
Maximum of Months | 0.163688E+10 | 0.123421E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10123397.13 | 0.371452E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.807397E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 174330.64 | 0.211161E+09 |
February | 0.882782E+09 | 0.691227E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31053.45 | 0.258591E+09 |
March | 0.105485E+10 | 0.799287E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.87 | 0.274001E+09 |
April | 0.936002E+09 | 0.687775E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 153117.62 | 0.166463E+09 |
May | 0.101394E+10 | 0.727966E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.79 | 0.185259E+09 |
June | 0.101113E+10 | 0.719353E+09 | 0.197614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19336.96 | 0.101124E+09 |
July | 0.938820E+09 | 0.672612E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1301511.39 | 76200142.48 |
August | 0.105485E+10 | 0.760861E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1349913.40 | 95941586.99 |
September | 0.936002E+09 | 0.706468E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2188437.69 | 88834536.87 |
October | 0.973041E+09 | 0.762085E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7505290.10 | 0.143933E+09 |
November | 0.963541E+09 | 0.788669E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 232730.02 | 0.212658E+09 |
December | 0.938820E+09 | 0.792104E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 125754.52 | 0.236903E+09 |
Annual Sum or Average | 0.116768E+11 | 0.891580E+10 | 0.234347E+11 | 13081579.43 | 0.205107E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.672612E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.79 | 76200142.48 |
Maximum of Months | 0.105485E+10 | 0.807397E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7505290.10 | 0.274001E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.129195E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1446336.69 | 0.577448E+09 |
February | 0.136985E+10 | 0.108952E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 125745.86 | 0.671762E+09 |
March | 0.163685E+10 | 0.124766E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 309601.62 | 0.730616E+09 |
April | 0.145243E+10 | 0.106413E+10 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1933531.55 | 0.426468E+09 |
May | 0.157338E+10 | 0.112210E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516183E+09 |
June | 0.156900E+10 | 0.111040E+10 | 0.306647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52701.57 | 0.275289E+09 |
July | 0.145680E+10 | 0.103895E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5527251.09 | 0.189378E+09 |
August | 0.163685E+10 | 0.117398E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6378464.67 | 0.237961E+09 |
September | 0.145243E+10 | 0.109478E+10 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7421653.07 | 0.230924E+09 |
October | 0.150991E+10 | 0.121296E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29718914.32 | 0.362982E+09 |
November | 0.149516E+10 | 0.126104E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3813572.00 | 0.546310E+09 |
December | 0.145680E+10 | 0.127226E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2254989.32 | 0.581993E+09 |
Annual Sum or Average | 0.181194E+11 | 0.139797E+11 | 0.363647E+11 | 58982761.76 | 0.534731E+10 | ||||
Minimum of Months | 0.136985E+10 | 0.103895E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189378E+09 |
Maximum of Months | 0.163685E+10 | 0.129195E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29718914.32 | 0.730616E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.812548E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 759682.28 | 0.399282E+09 |
February | 0.649041E+09 | 0.694932E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66379.07 | 0.462656E+09 |
March | 0.773965E+09 | 0.797807E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44385.23 | 0.503000E+09 |
April | 0.688021E+09 | 0.686186E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 317643.68 | 0.305304E+09 |
May | 0.744847E+09 | 0.727927E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361821E+09 |
June | 0.742030E+09 | 0.721042E+09 | 0.197615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35107.14 | 0.191108E+09 |
July | 0.690839E+09 | 0.674314E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2786228.89 | 0.140523E+09 |
August | 0.773965E+09 | 0.759532E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2911364.77 | 0.172999E+09 |
September | 0.688021E+09 | 0.701381E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4936587.10 | 0.164062E+09 |
October | 0.715730E+09 | 0.765255E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17229628.20 | 0.252955E+09 |
November | 0.708685E+09 | 0.802307E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1341941.14 | 0.377411E+09 |
December | 0.690839E+09 | 0.796180E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 583931.19 | 0.402224E+09 |
Annual Sum or Average | 0.858171E+10 | 0.893941E+10 | 0.234348E+11 | 31012878.69 | 0.373335E+10 | ||||
Minimum of Months | 0.649041E+09 | 0.674314E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140523E+09 |
Maximum of Months | 0.773965E+09 | 0.812548E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17229628.20 | 0.503000E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.122302E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 194150.04 | 0.676163E+09 |
February | 0.136988E+10 | 0.105679E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51616.92 | 0.762969E+09 |
March | 0.163688E+10 | 0.123259E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785475E+09 |
April | 0.145246E+10 | 0.106481E+10 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 779105.54 | 0.460623E+09 |
May | 0.157341E+10 | 0.113121E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521928E+09 |
June | 0.156904E+10 | 0.112207E+10 | 0.306652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52703.51 | 0.272365E+09 |
July | 0.145684E+10 | 0.104922E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5309197.72 | 0.191270E+09 |
August | 0.163688E+10 | 0.118126E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4656289.67 | 0.252916E+09 |
September | 0.145246E+10 | 0.108847E+10 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6815054.22 | 0.271294E+09 |
October | 0.150994E+10 | 0.115804E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21365092.87 | 0.435522E+09 |
November | 0.149520E+10 | 0.120795E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 121221.31 | 0.642405E+09 |
December | 0.145684E+10 | 0.119366E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 106004.51 | 0.700432E+09 |
Annual Sum or Average | 0.181198E+11 | 0.137091E+11 | 0.363653E+11 | 39450436.30 | 0.597336E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.104922E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191270E+09 |
Maximum of Months | 0.163688E+10 | 0.123259E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21365092.87 | 0.785475E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.805297E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 644224.60 | 0.409897E+09 |
February | 0.882782E+09 | 0.689833E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108193.95 | 0.483146E+09 |
March | 0.105485E+10 | 0.797652E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 142871.19 | 0.518950E+09 |
April | 0.936002E+09 | 0.686707E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1047164.40 | 0.327679E+09 |
May | 0.101394E+10 | 0.726794E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386149E+09 |
June | 0.101113E+10 | 0.718288E+09 | 0.197614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35131.66 | 0.206831E+09 |
July | 0.938820E+09 | 0.671712E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3637095.67 | 0.156388E+09 |
August | 0.105485E+10 | 0.759553E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3746357.46 | 0.192669E+09 |
September | 0.936002E+09 | 0.705113E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4966795.92 | 0.183660E+09 |
October | 0.973041E+09 | 0.759331E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18214241.30 | 0.274262E+09 |
November | 0.963541E+09 | 0.786776E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1923434.23 | 0.395770E+09 |
December | 0.938820E+09 | 0.789392E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1034561.17 | 0.421752E+09 |
Annual Sum or Average | 0.116768E+11 | 0.889645E+10 | 0.234347E+11 | 35500071.56 | 0.395715E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.671712E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156388E+09 |
Maximum of Months | 0.105485E+10 | 0.805297E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18214241.30 | 0.518950E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.129194E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2889196.25 | 0.624611E+09 |
February | 0.136985E+10 | 0.108917E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 253444.32 | 0.734375E+09 |
March | 0.163685E+10 | 0.124766E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 490444.67 | 0.829647E+09 |
April | 0.145243E+10 | 0.106413E+10 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2905262.18 | 0.499885E+09 |
May | 0.157338E+10 | 0.112207E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609121E+09 |
June | 0.156900E+10 | 0.111032E+10 | 0.306647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50719.47 | 0.335299E+09 |
July | 0.145680E+10 | 0.103895E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6566538.34 | 0.236996E+09 |
August | 0.163685E+10 | 0.117398E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7282064.48 | 0.292744E+09 |
September | 0.145243E+10 | 0.109475E+10 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9115798.09 | 0.276409E+09 |
October | 0.150991E+10 | 0.121280E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37453150.52 | 0.411324E+09 |
November | 0.149516E+10 | 0.126104E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6218821.73 | 0.604240E+09 |
December | 0.145680E+10 | 0.127202E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7186681.17 | 0.631852E+09 |
Annual Sum or Average | 0.181194E+11 | 0.139788E+11 | 0.363647E+11 | 80412121.22 | 0.608650E+10 | ||||
Minimum of Months | 0.136985E+10 | 0.103895E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236996E+09 |
Maximum of Months | 0.163685E+10 | 0.129194E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37453150.52 | 0.829647E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.812470E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1322088.08 | 0.436858E+09 |
February | 0.882782E+09 | 0.694887E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72594.77 | 0.514078E+09 |
March | 0.105485E+10 | 0.797768E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69555.88 | 0.578408E+09 |
April | 0.936002E+09 | 0.686020E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 388642.75 | 0.363328E+09 |
May | 0.101394E+10 | 0.727925E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432199E+09 |
June | 0.101113E+10 | 0.721003E+09 | 0.197615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33796.65 | 0.235207E+09 |
July | 0.938820E+09 | 0.674297E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3262015.00 | 0.176950E+09 |
August | 0.105485E+10 | 0.759519E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3338526.27 | 0.214712E+09 |
September | 0.936002E+09 | 0.701306E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6016922.50 | 0.199768E+09 |
October | 0.973041E+09 | 0.765214E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20661021.89 | 0.291170E+09 |
November | 0.963541E+09 | 0.802305E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2186169.35 | 0.423623E+09 |
December | 0.938820E+09 | 0.796084E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2144010.78 | 0.441165E+09 |
Annual Sum or Average | 0.116768E+11 | 0.893880E+10 | 0.234348E+11 | 39495343.93 | 0.430746E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.674297E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176950E+09 |
Maximum of Months | 0.105485E+10 | 0.812470E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20661021.89 | 0.578408E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.122296E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 492300.00 | 0.753095E+09 |
February | 0.136988E+10 | 0.105679E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102968.51 | 0.855914E+09 |
March | 0.163688E+10 | 0.123257E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901001E+09 |
April | 0.145246E+10 | 0.106479E+10 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1252755.44 | 0.543417E+09 |
May | 0.157341E+10 | 0.113112E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616568E+09 |
June | 0.156904E+10 | 0.112201E+10 | 0.306652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50721.38 | 0.331849E+09 |
July | 0.145684E+10 | 0.104919E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6380532.25 | 0.239214E+09 |
August | 0.163688E+10 | 0.118121E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5538087.06 | 0.310876E+09 |
September | 0.145246E+10 | 0.108840E+10 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8437389.61 | 0.327614E+09 |
October | 0.150994E+10 | 0.115799E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26939516.63 | 0.505239E+09 |
November | 0.149520E+10 | 0.120795E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 194210.23 | 0.733490E+09 |
December | 0.145684E+10 | 0.119366E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 238028.46 | 0.786609E+09 |
Annual Sum or Average | 0.181198E+11 | 0.137086E+11 | 0.363653E+11 | 49626509.59 | 0.690489E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.104919E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239214E+09 |
Maximum of Months | 0.163688E+10 | 0.123257E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26939516.63 | 0.901001E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.805220E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1198541.57 | 0.459988E+09 |
February | 0.882782E+09 | 0.689707E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 202437.94 | 0.546313E+09 |
March | 0.105485E+10 | 0.797574E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 230553.86 | 0.600519E+09 |
April | 0.936002E+09 | 0.686632E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1410241.16 | 0.389702E+09 |
May | 0.101394E+10 | 0.726717E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461511E+09 |
June | 0.101113E+10 | 0.718194E+09 | 0.197614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35418.07 | 0.251196E+09 |
July | 0.938820E+09 | 0.671680E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4444977.79 | 0.192185E+09 |
August | 0.105485E+10 | 0.759514E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4587316.34 | 0.234845E+09 |
September | 0.936002E+09 | 0.705068E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6146545.04 | 0.222420E+09 |
October | 0.973041E+09 | 0.759241E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22875421.44 | 0.318054E+09 |
November | 0.963541E+09 | 0.786629E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2917429.99 | 0.451927E+09 |
December | 0.938820E+09 | 0.789351E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2746549.33 | 0.473494E+09 |
Annual Sum or Average | 0.116768E+11 | 0.889553E+10 | 0.234347E+11 | 46795432.52 | 0.460215E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.671680E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192185E+09 |
Maximum of Months | 0.105485E+10 | 0.805220E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22875421.44 | 0.600519E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.522007E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.473481E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.562303E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.502580E+10 | 0.984007E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.542155E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.539412E+10 | 0.492004E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.505323E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.562303E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.502580E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.522007E+10 | 0.508404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.515799E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.505323E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.625527E+11 | 0.749486E+13 | |||||||
Minimum of Months | 0.00 | 0.473481E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.562303E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.241145E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.218729E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.259761E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.232171E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.250453E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.249186E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.233438E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.259761E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.232171E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.241145E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.238278E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.233438E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288968E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.218729E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.259761E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.241145E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.218729E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.259761E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.232171E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.250453E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.249186E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.233438E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.259761E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.232171E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.241145E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.238278E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.233438E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288968E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.218729E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.259761E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.241145E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.218729E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.259761E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.232171E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.250453E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.249186E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.233438E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.259761E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.232171E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.241145E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.238278E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.233438E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288968E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.218729E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.259761E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263807.03 | 0.635749E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44137.27 | 0.738367E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.773587E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399654.71 | 0.451852E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522237E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3946.30 | 0.278696E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2538590.75 | 0.200478E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2363336.16 | 0.253298E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5588192.08 | 0.248883E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21037334.32 | 0.402746E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788279.26 | 0.601254E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118710.36 | 0.660916E+09 |
Annual Sum or Average | 33145988.24 | 0.576806E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200478E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21037334.32 | 0.773587E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 867363.70 | 0.106595E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98906.71 | 0.123737E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29631.60 | 0.130865E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1481363.30 | 0.759377E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894009E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10078.21 | 0.471051E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5893992.63 | 0.333448E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5597954.25 | 0.428878E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10203439.95 | 0.419809E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40207862.38 | 0.674838E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2836590.51 | 0.101351E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455809.90 | 0.109685E+10 |
Annual Sum or Average | 67682993.14 | 0.970374E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333448E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40207862.38 | 0.130865E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1933217.23 | 0.102858E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27638.37 | 0.122515E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136527E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557674.46 | 0.863001E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102235E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579195E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1710827.79 | 0.438136E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1361317.04 | 0.513128E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10233960.95 | 0.495212E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40262499.75 | 0.693076E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3597769.79 | 0.100855E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1129679.14 | 0.104774E+10 |
Annual Sum or Average | 60814584.54 | 0.102794E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438136E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40262499.75 | 0.136527E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 19263.35 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 19263.35 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 19263.35 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 19263.35 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 19263.35 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 19263.35 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 19263.35 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 19263.35 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 19263.35 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 19263.35 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 19263.35 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 19263.35 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 17832.21 | 19263.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 19263.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17299.84 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17299.84 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17299.84 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17299.84 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17299.84 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17299.84 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17299.84 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17299.84 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17299.84 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17299.84 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17299.84 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17299.84 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 17299.84 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17299.84 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17299.84 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17299.84 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17299.84 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17299.84 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17299.84 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17299.84 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17299.84 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17299.84 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17299.84 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17299.84 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17299.84 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17299.84 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 17299.84 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17299.84 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17299.84 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17299.84 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17299.84 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17299.84 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17299.84 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17299.84 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17299.84 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17299.84 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17299.84 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17299.84 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17299.84 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17299.84 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 17299.84 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17299.84 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2172.17 | 02-JAN-16:30 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.28 | 14-JAN-15:00 | 763.23 | 02-JAN-02:51 |
February | 2010.79 | 01-FEB-10:09 | 2172.17 | 27-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 | 01-FEB-12:00 | 669.66 | 12-FEB-19:00 |
March | 2010.79 | 01-MAR-10:09 | 1513.35 | 01-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.64 | 11-MAR-14:00 | 716.96 | 28-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1513.35 | 21-APR-15:00 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.76 | 30-APR-10:43 | 441.54 | 17-APR-02:51 |
May | 2010.79 | 01-MAY-09:09 | 1234.08 | 08-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 03-MAY-12:00 | 390.78 | 27-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 1234.08 | 09-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.35 | 29-JUN-11:00 | 284.42 | 07-JUN-01:00 |
July | 2010.79 | 03-JUL-09:09 | 1133.80 | 11-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.08 | 23-JUL-10:50 | 216.39 | 13-JUL-03:00 |
August | 2010.79 | 01-AUG-09:09 | 1234.08 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.24 | 06-AUG-13:00 | 208.53 | 21-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 1613.63 | 18-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.30 | 29-SEP-14:00 | 232.21 | 04-SEP-18:00 |
October | 2010.79 | 02-OCT-09:09 | 1892.90 | 20-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.11 | 15-OCT-12:50 | 468.80 | 30-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 2172.17 | 06-NOV-16:19 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.70 | 19-NOV-12:52 | 629.04 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 2172.17 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.06 | 05-DEC-10:00 | 577.36 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1133.80 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 208.53 | |||||
Maximum of Months | 2010.79 | 2172.17 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 273.11 | 763.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1399.83 | 02-JAN-16:30 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.04 | 15-JAN-14:20 | 503.38 | 02-JAN-02:51 |
February | 1295.83 | 01-FEB-10:09 | 1399.83 | 27-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.78 | 01-FEB-12:00 | 422.92 | 12-FEB-19:00 |
March | 1295.83 | 01-MAR-10:09 | 975.26 | 01-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.68 | 11-MAR-14:00 | 454.79 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 975.26 | 21-APR-15:39 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.61 | 26-APR-13:00 | 282.44 | 17-APR-02:51 |
May | 1295.83 | 01-MAY-09:09 | 730.66 | 08-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:00 | 258.35 | 27-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 730.66 | 08-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 | 29-JUN-11:00 | 181.67 | 07-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 730.66 | 28-JUL-15:20 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.13 | 31-JUL-13:00 | 138.69 | 02-JUL-18:57 |
August | 1295.83 | 01-AUG-09:09 | 730.66 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 06-AUG-13:00 | 129.35 | 21-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 975.26 | 18-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.98 | 29-SEP-14:00 | 188.38 | 03-SEP-06:45 |
October | 1295.83 | 02-OCT-09:09 | 1219.86 | 20-OCT-15:50 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.49 | 15-OCT-12:50 | 306.64 | 30-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1399.83 | 06-NOV-16:19 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.27 | 19-NOV-13:10 | 413.17 | 23-NOV-07:00 |
December | 1295.83 | 01-DEC-10:09 | 1399.83 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 05-DEC-10:00 | 369.46 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 730.66 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 129.35 | |||||
Maximum of Months | 1295.83 | 1399.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 176.49 | 503.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2172.22 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 | 14-JAN-11:00 | 685.55 | 02-JAN-02:51 |
February | 2010.83 | 01-FEB-10:09 | 2172.22 | 27-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.58 | 01-FEB-12:00 | 641.86 | 25-FEB-03:00 |
March | 2010.83 | 01-MAR-10:09 | 1513.38 | 16-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 11-MAR-14:00 | 700.69 | 28-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1513.38 | 21-APR-15:00 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.12 | 26-APR-13:00 | 429.64 | 21-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 1234.11 | 08-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 03-MAY-12:00 | 376.88 | 27-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 1234.11 | 08-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.35 | 29-JUN-11:00 | 278.33 | 07-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 1133.82 | 11-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.24 | 23-JUL-10:50 | 209.76 | 13-JUL-03:00 |
August | 2010.83 | 01-AUG-09:09 | 1234.11 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.43 | 17-AUG-14:00 | 206.42 | 21-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 1513.38 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.40 | 29-SEP-14:00 | 253.25 | 04-SEP-13:50 |
October | 2010.83 | 02-OCT-09:09 | 1513.38 | 04-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.76 | 15-OCT-12:57 | 476.38 | 30-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 2172.22 | 06-NOV-16:40 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.42 | 18-NOV-14:10 | 631.28 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 2172.22 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 | 05-DEC-10:00 | 579.80 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1133.82 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 206.42 | |||||
Maximum of Months | 2010.83 | 2172.22 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 213.76 | 700.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1399.83 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.28 | 14-JAN-11:00 | 519.80 | 02-JAN-02:51 |
February | 1295.83 | 01-FEB-10:09 | 1399.83 | 27-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.78 | 01-FEB-12:00 | 501.31 | 12-FEB-19:00 |
March | 1295.83 | 01-MAR-10:09 | 1039.89 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 11-MAR-14:00 | 523.16 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 975.26 | 05-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.61 | 26-APR-13:00 | 376.70 | 16-APR-18:00 |
May | 1295.83 | 01-MAY-09:09 | 975.26 | 09-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:00 | 325.80 | 29-MAY-16:10 |
June | 1295.83 | 01-JUN-09:09 | 795.29 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 | 29-JUN-11:00 | 242.36 | 04-JUN-17:10 |
July | 1295.83 | 03-JUL-09:09 | 795.29 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.13 | 31-JUL-13:00 | 225.13 | 09-JUL-17:20 |
August | 1295.83 | 01-AUG-09:09 | 975.26 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.44 | 17-AUG-14:00 | 182.25 | 27-AUG-18:10 |
September | 1295.83 | 01-SEP-09:09 | 1219.86 | 18-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.98 | 29-SEP-14:00 | 236.87 | 03-SEP-16:40 |
October | 1295.83 | 02-OCT-09:09 | 1219.86 | 05-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.45 | 15-OCT-12:10 | 358.41 | 11-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1399.83 | 06-NOV-16:40 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.94 | 19-NOV-12:30 | 478.33 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1399.83 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 05-DEC-10:00 | 428.81 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 795.29 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 182.25 | |||||
Maximum of Months | 1295.83 | 1399.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 167.45 | 523.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2172.17 | 02-JAN-16:30 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 76.91 | 15-JAN-15:00 | 1236.17 | 02-JAN-02:51 |
February | 2010.79 | 01-FEB-10:09 | 2172.17 | 27-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.03 | 01-FEB-12:00 | 1274.09 | 25-FEB-03:00 |
March | 2010.79 | 01-MAR-10:09 | 1513.35 | 01-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.58 | 11-MAR-14:00 | 1402.26 | 28-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1513.35 | 21-APR-15:00 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.86 | 30-APR-10:50 | 865.84 | 21-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1234.08 | 08-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 813.20 | 27-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 1133.80 | 08-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.79 | 29-JUN-11:00 | 577.20 | 06-JUN-21:20 |
July | 2010.79 | 03-JUL-09:09 | 1133.80 | 11-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.06 | 23-JUL-11:00 | 427.97 | 02-JUL-18:53 |
August | 2010.79 | 01-AUG-09:09 | 1234.08 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.26 | 06-AUG-13:00 | 408.37 | 21-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 1513.35 | 05-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.39 | 29-SEP-14:00 | 453.93 | 24-SEP-14:53 |
October | 2010.79 | 02-OCT-09:09 | 1892.90 | 23-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 650.87 | 15-OCT-08:52 | 894.89 | 30-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 2172.17 | 06-NOV-16:19 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 285.38 | 19-NOV-12:52 | 1186.49 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 2172.17 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 168.15 | 25-DEC-11:51 | 1147.62 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1133.80 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.37 | |||||
Maximum of Months | 2010.79 | 2172.17 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 650.87 | 1402.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1399.83 | 02-JAN-16:30 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 55.92 | 15-JAN-15:00 | 851.64 | 02-JAN-02:51 |
February | 1239.33 | 01-FEB-08:09 | 1399.83 | 27-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.07 | 01-FEB-12:00 | 832.08 | 25-FEB-03:00 |
March | 1239.33 | 01-MAR-08:09 | 975.26 | 01-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.41 | 11-MAR-14:00 | 928.85 | 28-MAR-21:03 |
April | 1239.33 | 03-APR-07:10 | 975.26 | 21-APR-15:39 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.09 | 26-APR-13:00 | 574.89 | 21-APR-22:00 |
May | 1239.33 | 01-MAY-07:10 | 730.66 | 08-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 551.00 | 27-MAY-05:00 |
June | 1239.33 | 01-JUN-07:10 | 730.66 | 09-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.19 | 29-JUN-11:00 | 418.30 | 04-JUN-13:53 |
July | 1239.33 | 03-JUL-07:10 | 730.66 | 28-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.49 | 31-JUL-13:00 | 344.17 | 04-JUL-13:52 |
August | 1239.33 | 01-AUG-07:10 | 730.66 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.08 | 17-AUG-14:00 | 272.11 | 21-AUG-24:00 |
September | 1239.33 | 01-SEP-07:10 | 975.26 | 18-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.92 | 29-SEP-14:00 | 404.31 | 03-SEP-07:00 |
October | 1239.33 | 02-OCT-07:10 | 1219.86 | 20-OCT-15:50 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 377.29 | 15-OCT-12:50 | 614.45 | 30-OCT-03:00 |
November | 1239.33 | 01-NOV-07:10 | 1399.83 | 06-NOV-16:19 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.63 | 19-NOV-12:52 | 809.39 | 23-NOV-07:00 |
December | 1239.33 | 01-DEC-08:09 | 1399.83 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 55.01 | 17-DEC-13:00 | 767.51 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1239.33 | 730.66 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.11 | |||||
Maximum of Months | 1239.33 | 1399.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 377.29 | 928.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2172.22 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.72 | 14-JAN-11:00 | 1319.19 | 02-JAN-02:51 |
February | 2010.83 | 01-FEB-10:09 | 2172.22 | 27-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.39 | 01-FEB-12:00 | 1295.66 | 25-FEB-03:00 |
March | 2010.83 | 01-MAR-10:09 | 1513.38 | 16-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1425.29 | 28-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1513.38 | 21-APR-15:00 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.36 | 30-APR-10:43 | 872.31 | 21-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 1234.11 | 08-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 808.35 | 27-MAY-04:51 |
June | 2010.83 | 01-JUN-09:09 | 1234.11 | 09-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.79 | 29-JUN-11:00 | 576.27 | 07-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 1133.82 | 11-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.97 | 23-JUL-11:00 | 428.20 | 02-JUL-18:53 |
August | 2010.83 | 01-AUG-09:09 | 1234.11 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.63 | 17-AUG-14:00 | 417.75 | 21-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 1513.38 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.44 | 29-SEP-14:00 | 586.85 | 24-SEP-14:53 |
October | 2010.83 | 02-OCT-09:09 | 1513.38 | 04-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 467.13 | 15-OCT-08:52 | 1016.08 | 30-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 2172.22 | 06-NOV-16:40 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.19 | 18-NOV-14:00 | 1292.73 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 2172.22 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.46 | 05-DEC-10:00 | 1224.94 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1133.82 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.75 | |||||
Maximum of Months | 2010.83 | 2172.22 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 467.13 | 1425.29 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1399.83 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.12 | 14-JAN-12:50 | 865.91 | 02-JAN-02:51 |
February | 1295.83 | 01-FEB-10:09 | 1399.83 | 27-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.16 | 01-FEB-12:00 | 867.69 | 25-FEB-03:00 |
March | 1295.83 | 01-MAR-10:09 | 975.26 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.37 | 11-MAR-12:40 | 964.38 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 975.26 | 05-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.41 | 30-APR-10:50 | 740.20 | 16-APR-17:40 |
May | 1295.83 | 01-MAY-09:09 | 975.26 | 09-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 723.11 | 20-MAY-17:53 |
June | 1295.83 | 01-JUN-09:09 | 795.29 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.19 | 29-JUN-11:00 | 523.94 | 04-JUN-17:10 |
July | 1295.83 | 03-JUL-09:09 | 795.29 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.00 | 23-JUL-11:00 | 470.50 | 09-JUL-17:30 |
August | 1295.83 | 01-AUG-09:09 | 975.26 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.56 | 06-AUG-13:00 | 362.81 | 27-AUG-17:40 |
September | 1295.83 | 01-SEP-09:09 | 1219.86 | 18-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.93 | 29-SEP-14:00 | 516.68 | 03-SEP-16:50 |
October | 1295.83 | 02-OCT-09:09 | 1219.86 | 05-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 432.09 | 15-OCT-08:52 | 650.34 | 30-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1399.83 | 06-NOV-16:40 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.52 | 19-NOV-12:52 | 834.33 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1399.83 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.43 | 25-DEC-12:00 | 795.99 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 795.29 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.81 | |||||
Maximum of Months | 1295.83 | 1399.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 432.09 | 964.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2172.17 | 02-JAN-16:30 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 198.61 | 15-JAN-10:00 | 1394.71 | 27-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 2172.17 | 27-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.42 | 01-FEB-12:00 | 1416.96 | 25-FEB-03:00 |
March | 2010.79 | 01-MAR-10:09 | 1513.35 | 01-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 11-MAR-14:00 | 1726.64 | 28-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 1513.35 | 21-APR-15:00 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.81 | 30-APR-10:50 | 1014.46 | 21-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1234.08 | 08-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 999.78 | 20-MAY-18:00 |
June | 2010.79 | 01-JUN-09:09 | 1133.80 | 08-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.30 | 29-JUN-11:00 | 702.53 | 06-JUN-21:10 |
July | 2010.79 | 03-JUL-09:09 | 1133.80 | 11-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.33 | 23-JUL-10:53 | 547.70 | 02-JUL-18:53 |
August | 2010.79 | 01-AUG-09:09 | 1234.08 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.01 | 06-AUG-13:10 | 486.46 | 21-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 1513.35 | 05-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.83 | 29-SEP-14:00 | 585.36 | 24-SEP-14:53 |
October | 2010.79 | 02-OCT-09:09 | 1892.90 | 23-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 832.95 | 15-OCT-09:00 | 969.94 | 30-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 2172.17 | 06-NOV-16:19 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 366.36 | 19-NOV-13:00 | 1272.71 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 2172.17 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 406.88 | 25-DEC-11:51 | 1304.31 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1133.80 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 486.46 | |||||
Maximum of Months | 2010.79 | 2172.17 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 832.95 | 1726.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1399.83 | 02-JAN-16:30 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 92.83 | 15-JAN-10:00 | 940.21 | 06-JAN-23:00 |
February | 1295.83 | 01-FEB-10:09 | 1399.83 | 27-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.65 | 01-FEB-12:00 | 928.77 | 25-FEB-03:00 |
March | 1295.83 | 01-MAR-10:09 | 975.26 | 01-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.09 | 11-MAR-14:00 | 1149.24 | 28-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 975.26 | 21-APR-15:50 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.34 | 26-APR-13:00 | 677.02 | 21-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 730.66 | 08-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 685.40 | 29-MAY-12:53 |
June | 1295.83 | 01-JUN-09:09 | 730.66 | 09-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.20 | 29-JUN-11:00 | 523.35 | 04-JUN-13:43 |
July | 1295.83 | 03-JUL-09:09 | 730.66 | 28-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.55 | 31-JUL-13:00 | 427.91 | 04-JUL-13:30 |
August | 1295.83 | 01-AUG-09:09 | 730.66 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.00 | 17-AUG-14:00 | 338.80 | 27-AUG-18:10 |
September | 1295.83 | 01-SEP-09:09 | 975.26 | 18-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.22 | 29-SEP-14:00 | 445.01 | 03-SEP-07:00 |
October | 1295.83 | 02-OCT-09:09 | 1219.86 | 20-OCT-15:50 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 450.16 | 15-OCT-13:00 | 671.83 | 30-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1399.83 | 06-NOV-16:19 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.48 | 19-NOV-13:00 | 859.89 | 23-NOV-07:00 |
December | 1295.83 | 01-DEC-10:09 | 1399.83 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 162.65 | 25-DEC-12:00 | 875.62 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 730.66 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.80 | |||||
Maximum of Months | 1295.83 | 1399.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 450.16 | 1149.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2172.22 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.71 | 15-JAN-10:00 | 1532.91 | 06-JAN-23:00 |
February | 2010.83 | 01-FEB-10:09 | 2172.22 | 27-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.19 | 01-FEB-12:00 | 1546.83 | 20-FEB-15:10 |
March | 2010.83 | 01-MAR-10:09 | 1513.38 | 16-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1731.85 | 28-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 1513.38 | 21-APR-15:00 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.26 | 30-APR-10:43 | 1024.51 | 21-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 1234.11 | 08-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 988.10 | 20-MAY-18:00 |
June | 2010.83 | 01-JUN-09:09 | 1234.11 | 09-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.30 | 29-JUN-11:00 | 699.16 | 06-JUN-21:10 |
July | 2010.83 | 03-JUL-09:09 | 1133.82 | 11-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.18 | 23-JUL-10:53 | 547.66 | 02-JUL-18:53 |
August | 2010.83 | 01-AUG-09:09 | 1234.11 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.00 | 17-AUG-14:00 | 508.37 | 27-AUG-18:10 |
September | 2010.83 | 01-SEP-09:09 | 1513.38 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.20 | 29-SEP-14:00 | 749.63 | 24-SEP-14:53 |
October | 2010.83 | 02-OCT-09:09 | 1513.38 | 04-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 606.51 | 15-OCT-08:52 | 1131.70 | 30-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 2172.22 | 06-NOV-16:40 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.57 | 18-NOV-13:00 | 1409.30 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 2172.22 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.62 | 05-DEC-10:00 | 1405.43 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1133.82 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.37 | |||||
Maximum of Months | 2010.83 | 2172.22 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 606.51 | 1731.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1399.83 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 90.44 | 15-JAN-10:00 | 973.51 | 06-JAN-23:00 |
February | 1295.83 | 01-FEB-10:09 | 1399.83 | 27-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.03 | 01-FEB-12:00 | 978.82 | 25-FEB-03:00 |
March | 1295.83 | 01-MAR-10:09 | 975.26 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.08 | 11-MAR-12:40 | 1159.70 | 28-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 975.26 | 05-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.27 | 30-APR-10:50 | 905.45 | 16-APR-17:40 |
May | 1295.83 | 01-MAY-09:09 | 975.26 | 09-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 973.07 | 20-MAY-18:00 |
June | 1295.83 | 01-JUN-09:09 | 795.29 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.20 | 29-JUN-11:00 | 669.00 | 04-JUN-17:00 |
July | 1295.83 | 03-JUL-09:09 | 795.29 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.11 | 23-JUL-10:53 | 599.31 | 16-JUL-18:00 |
August | 1295.83 | 01-AUG-09:09 | 975.26 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.69 | 06-AUG-12:20 | 478.89 | 27-AUG-18:10 |
September | 1295.83 | 01-SEP-09:09 | 1219.86 | 18-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.22 | 29-SEP-14:00 | 646.00 | 03-SEP-16:50 |
October | 1295.83 | 02-OCT-09:09 | 1219.86 | 05-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 558.17 | 15-OCT-09:00 | 730.76 | 30-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1399.83 | 06-NOV-16:40 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.34 | 19-NOV-12:40 | 918.52 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1399.83 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 194.38 | 25-DEC-11:52 | 919.70 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 795.29 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.89 | |||||
Maximum of Months | 1295.83 | 1399.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 558.17 | 1159.70 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 5431.44 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 5431.44 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 5431.44 | 01-MAR-08:09 | 284724.39 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 5431.44 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 5431.44 | 01-MAY-07:10 | 94908.13 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 5431.44 | 01-JUN-07:10 | 189816.26 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 5431.44 | 03-JUL-07:10 | 284724.39 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 5431.44 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 5431.44 | 01-SEP-07:10 | 94908.13 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 5431.44 | 02-OCT-07:10 | 189816.26 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 5431.44 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 5431.44 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 5431.44 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 5431.44 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 250.91 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 250.91 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 250.91 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 250.91 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 250.91 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 250.91 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 250.91 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 250.91 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 250.91 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 250.91 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 250.91 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 250.91 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 250.91 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 250.91 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 250.91 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 250.91 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 250.91 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 250.91 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 250.91 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 250.91 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 250.91 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 250.91 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 250.91 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 250.91 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 250.91 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 250.91 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 250.91 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 250.91 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 250.91 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 250.91 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 250.91 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 250.91 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 250.91 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 250.91 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 250.91 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 250.91 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 250.91 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 250.91 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 250.91 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 250.91 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 250.91 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 250.91 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.15 | 14-JAN-15:00 | 1630.69 | 02-JAN-02:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.04 | 01-FEB-12:00 | 1406.07 | 12-FEB-19:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1491.34 | 28-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.49 | 30-APR-11:00 | 912.39 | 17-APR-02:51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 827.28 | 27-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 29-JUN-11:00 | 579.46 | 07-JUN-01:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.53 | 23-JUL-10:53 | 431.64 | 13-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.28 | 06-AUG-13:00 | 415.24 | 21-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.73 | 29-SEP-13:50 | 483.17 | 04-SEP-18:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.86 | 15-OCT-13:00 | 977.77 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.81 | 19-NOV-12:52 | 1357.76 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.69 | 05-DEC-10:00 | 1212.73 | 23-DEC-04:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.24 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.86 | 1630.69 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.68 | 15-JAN-10:00 | 2398.99 | 02-JAN-02:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.08 | 01-FEB-12:00 | 2389.62 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 11-MAR-13:50 | 2537.06 | 28-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.69 | 30-APR-10:53 | 1514.53 | 17-APR-02:51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1465.57 | 27-MAY-04:51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.96 | 29-JUN-11:00 | 997.23 | 07-JUN-01:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.33 | 23-JUL-11:00 | 729.21 | 13-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.11 | 06-AUG-12:53 | 707.46 | 21-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.25 | 29-SEP-13:50 | 817.60 | 02-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 951.11 | 15-OCT-12:51 | 1641.61 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.45 | 19-NOV-13:00 | 2311.93 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.76 | 05-DEC-10:00 | 2099.12 | 23-DEC-04:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 707.46 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 951.11 | 2537.06 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.38 | 15-JAN-10:00 | 2225.41 | 27-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.08 | 01-FEB-12:00 | 2354.68 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2729.65 | 28-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.34 | 30-APR-10:53 | 1630.94 | 16-APR-17:52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1698.03 | 07-MAY-14:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 1298.67 | 04-JUN-13:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.53 | 31-JUL-13:00 | 1040.93 | 09-JUL-16:52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.26 | 17-AUG-14:00 | 822.79 | 27-AUG-17:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.86 | 29-SEP-13:30 | 1073.36 | 24-SEP-14:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1121.66 | 15-OCT-08:52 | 1592.87 | 11-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.64 | 19-NOV-12:42 | 2070.59 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.90 | 25-DEC-11:51 | 2123.13 | 23-DEC-04:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 822.79 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1121.66 | 2729.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 114337.57 | 01-JAN-15:42 | 4488.06 | 5350.93 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 116082.45 | 20-FEB-17:40 | 2692.84 | 3210.56 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 115859.34 | 06-MAR-04:20 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 116581.64 | 09-APR-23:50 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 113507.79 | 30-MAY-02:32 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 110468.44 | 12-JUN-02:51 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 111061.47 | 10-JUL-03:50 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 106924.44 | 27-AUG-22:53 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 110360.54 | 30-SEP-03:53 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 117005.89 | 30-OCT-03:33 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 116169.87 | 24-NOV-04:33 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 116680.52 | 25-DEC-17:23 | 2692.84 | 3210.56 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 106924.44 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 117005.89 | 4488.06 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 76911.07 | 25-JAN-05:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 74829.11 | 01-FEB-05:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 74536.58 | 21-MAR-04:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78447.14 | 14-APR-03:02 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 78571.48 | 25-MAY-04:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 80974.39 | 26-JUN-04:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 81426.72 | 05-JUL-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 81445.03 | 30-AUG-04:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83846.49 | 29-SEP-04:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 85761.54 | 04-OCT-04:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 83739.64 | 12-NOV-10:21 | 8061.19 | 9611.02 | 57355.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 81600.06 | 19-DEC-04:02 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 74536.58 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 85761.54 | 8061.19 | 9611.02 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 65621.02 | 17-JAN-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 60993.02 | 03-FEB-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 62836.12 | 24-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 67705.52 | 27-APR-04:11 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 67197.01 | 25-MAY-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 71364.35 | 30-JUN-04:11 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 72939.06 | 03-JUL-05:02 | 16122.38 | 5373.60 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 73627.79 | 19-AUG-04:11 | 0.00 | 5373.60 | 44532.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76589.03 | 30-SEP-05:02 | 16122.38 | 5373.60 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 77436.82 | 05-OCT-04:11 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 65100.67 | 10-NOV-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 64984.06 | 19-DEC-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 60993.02 | 0.00 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 77436.82 | 16122.38 | 5373.60 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 35151.82 | 19-JAN-16:20 | 15316.26 | 17299.84 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 36824.88 | 16-FEB-16:20 | 15316.26 | 17299.84 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 45769.08 | 24-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 59825.88 | 27-APR-05:03 | 4836.72 | 1612.08 | 22942.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 60654.07 | 25-MAY-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 65250.96 | 27-JUN-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 67375.98 | 03-JUL-05:02 | 16122.38 | 5373.60 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 67557.00 | 10-AUG-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76880.75 | 30-SEP-05:02 | 16122.38 | 5373.60 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 71705.41 | 02-OCT-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36413.01 | 01-NOV-16:00 | 15316.26 | 17299.84 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 35444.24 | 07-DEC-15:50 | 15316.26 | 17299.84 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 35151.82 | 0.00 | 1612.08 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76880.75 | 16122.38 | 17299.84 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5799.23 | 17-JAN-13:40 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 |
February | 5123.93 | 01-FEB-12:00 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 | 0.00 |
March | 5754.52 | 13-MAR-13:50 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.03 |
April | 7040.98 | 26-APR-13:40 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 15.85 | 0.00 |
May | 6672.49 | 04-MAY-13:40 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 |
June | 7128.15 | 19-JUN-05:01 | 2024.33 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.42 |
July | 8933.13 | 03-JUL-05:01 | 2024.33 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7619.22 | 07-AUG-14:00 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 14.82 | 0.00 |
September | 7985.22 | 29-SEP-13:10 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 86.76 | 0.00 |
October | 9361.22 | 05-OCT-04:11 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5666.57 | 13-NOV-11:40 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.20 |
December | 6126.22 | 05-DEC-15:00 | 2010.79 | 1133.80 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 7.45 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5123.93 | 0.00 | 674.71 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9361.22 | 2024.33 | 1133.80 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 86.76 | 64.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11457.48 | 01-JAN-08:58 | 652.28 | 370.02 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.60 |
February | 10159.56 | 20-FEB-08:41 | 587.05 | 333.02 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.51 |
March | 14794.94 | 19-MAR-08:53 | 260.91 | 148.01 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17298.12 | 30-APR-09:13 | 260.91 | 148.01 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.63 |
May | 16387.94 | 28-MAY-08:23 | 260.91 | 148.01 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.03 |
June | 17268.92 | 18-JUN-08:43 | 260.91 | 148.01 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.23 |
July | 17925.33 | 23-JUL-08:22 | 326.14 | 185.01 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.28 |
August | 17287.99 | 13-AUG-08:23 | 260.91 | 148.01 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.42 |
September | 17119.36 | 10-SEP-09:13 | 260.91 | 148.01 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.62 |
October | 16810.59 | 09-OCT-08:23 | 260.91 | 148.01 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.76 |
November | 7513.33 | 13-NOV-08:25 | 2478.65 | 1332.08 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.38 |
December | 7344.65 | 25-DEC-08:51 | 652.28 | 370.02 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7344.65 | 260.91 | 148.01 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17925.33 | 2478.65 | 1332.08 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16469.79 | 29-JAN-11:32 | 404.87 | 229.68 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.12 |
February | 16442.79 | 20-FEB-11:23 | 404.87 | 229.68 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.72 |
March | 16873.98 | 19-MAR-11:32 | 404.87 | 229.68 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.17 |
April | 10467.16 | 26-APR-13:00 | 1923.15 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 22.12 | 0.00 |
May | 7662.69 | 04-MAY-12:40 | 1923.15 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 |
June | 6895.86 | 27-JUN-13:10 | 2010.83 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 |
July | 9413.12 | 31-JUL-12:30 | 1923.15 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 31.16 | 0.00 |
August | 11878.48 | 30-AUG-12:30 | 1923.15 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 |
September | 16195.76 | 04-SEP-10:37 | 1012.19 | 574.19 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.22 |
October | 18698.51 | 29-OCT-13:12 | 506.09 | 287.09 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.08 |
November | 18438.24 | 19-NOV-13:42 | 506.09 | 287.09 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.25 |
December | 19064.64 | 25-DEC-13:22 | 607.31 | 344.51 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.78 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6895.86 | 404.87 | 229.68 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19064.64 | 2010.83 | 1033.54 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 31.16 | 340.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10425.49 | 16-JAN-15:41 | 652.28 | 370.02 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.89 |
February | 20120.16 | 20-FEB-16:01 | 652.28 | 370.02 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.41 |
March | 20311.76 | 19-MAR-15:32 | 326.14 | 185.01 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.34 |
April | 22268.88 | 30-APR-15:52 | 391.37 | 222.01 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.33 |
May | 21877.00 | 28-MAY-15:22 | 326.14 | 185.01 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.20 |
June | 21631.45 | 18-JUN-14:22 | 326.14 | 185.01 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.13 |
July | 22195.34 | 23-JUL-16:32 | 391.37 | 222.01 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.24 |
August | 22508.98 | 06-AUG-16:32 | 391.37 | 222.01 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.16 |
September | 22133.22 | 10-SEP-16:12 | 326.14 | 185.01 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.99 |
October | 22039.90 | 15-OCT-15:22 | 391.37 | 222.01 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 50.87 | 0.00 |
November | 20982.45 | 23-NOV-14:12 | 326.14 | 185.01 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.82 |
December | 21528.93 | 25-DEC-14:02 | 391.37 | 222.01 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.38 |
Annual Sum or Average | |||||||||||
Minimum of Months | 10425.49 | 326.14 | 185.01 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22508.98 | 652.28 | 370.02 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 50.87 | 223.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3833.33 | 18-JAN-14:20 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
February | 3243.76 | 03-FEB-15:00 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.98 |
March | 3916.41 | 23-MAR-15:00 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.68 |
April | 5362.22 | 26-APR-14:00 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 27.74 | 0.00 |
May | 5772.32 | 04-MAY-14:00 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.59 |
June | 5547.26 | 30-JUN-14:00 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 |
July | 6215.69 | 19-JUL-15:00 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 | 0.00 |
August | 6193.98 | 17-AUG-14:00 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 64.63 | 0.00 |
September | 8025.49 | 30-SEP-05:01 | 2024.33 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
October | 7055.42 | 16-OCT-12:20 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 244.56 | 0.00 |
November | 3514.60 | 10-NOV-13:20 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.91 |
December | 3816.95 | 05-DEC-15:00 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 14.99 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3243.76 | 1923.11 | 674.71 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8025.49 | 2024.33 | 1033.52 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 244.56 | 72.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5709.08 | 20-JAN-09:10 | 1239.33 | 666.04 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 |
February | 5675.51 | 21-FEB-09:30 | 1239.33 | 666.04 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.55 |
March | 8624.68 | 23-MAR-09:00 | 1239.33 | 666.04 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17780.93 | 30-APR-09:02 | 260.91 | 148.01 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.91 |
May | 15794.76 | 28-MAY-08:53 | 260.91 | 148.01 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.10 |
June | 17711.07 | 18-JUN-08:32 | 260.91 | 148.01 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.81 |
July | 18501.17 | 23-JUL-08:52 | 326.14 | 185.01 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.54 |
August | 17834.66 | 13-AUG-08:53 | 260.91 | 148.01 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.78 |
September | 17796.46 | 10-SEP-08:53 | 260.91 | 148.01 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.95 |
October | 18460.85 | 15-OCT-09:02 | 326.14 | 185.01 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 223.78 | 0.00 |
November | 5320.48 | 13-NOV-09:00 | 1239.33 | 666.04 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.09 |
December | 5699.69 | 05-DEC-09:00 | 1239.33 | 666.04 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.68 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5320.48 | 260.91 | 148.01 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18501.17 | 1239.33 | 666.04 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 223.78 | 274.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15823.14 | 22-JAN-13:32 | 506.09 | 287.09 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.79 |
February | 15420.79 | 19-FEB-13:43 | 404.87 | 229.68 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813.21 |
March | 14760.36 | 19-MAR-13:53 | 404.87 | 229.68 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 746.92 |
April | 9469.42 | 26-APR-13:00 | 1923.15 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 48.13 | 0.00 |
May | 6952.27 | 04-MAY-13:30 | 2010.83 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.59 |
June | 5845.70 | 30-JUN-13:30 | 2010.83 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 |
July | 8206.68 | 31-JUL-12:40 | 1923.15 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 72.37 | 0.00 |
August | 11116.09 | 30-AUG-12:50 | 1923.15 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.99 |
September | 14395.32 | 29-SEP-13:20 | 2010.83 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 167.72 | 0.00 |
October | 18464.21 | 15-OCT-13:01 | 708.53 | 401.93 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 213.28 | 0.00 |
November | 18141.89 | 19-NOV-12:02 | 607.31 | 344.51 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.89 |
December | 17379.45 | 17-DEC-13:12 | 506.09 | 287.09 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.12 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5845.70 | 404.87 | 229.68 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18464.21 | 2010.83 | 1033.54 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 213.28 | 813.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7516.87 | 26-JAN-15:30 | 1239.33 | 666.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.86 |
February | 8541.02 | 22-FEB-16:00 | 1239.33 | 666.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.62 |
March | 16857.02 | 19-MAR-16:33 | 260.91 | 148.01 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.53 |
April | 18705.15 | 30-APR-16:21 | 521.82 | 296.02 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.47 |
May | 17369.08 | 21-MAY-16:53 | 260.91 | 148.01 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467.49 |
June | 19158.75 | 18-JUN-16:32 | 326.14 | 185.01 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.47 |
July | 19594.24 | 02-JUL-16:22 | 391.37 | 222.01 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.49 |
August | 19030.35 | 20-AUG-16:11 | 521.82 | 296.02 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.51 |
September | 18065.16 | 04-SEP-15:42 | 391.37 | 222.01 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.74 |
October | 20241.98 | 15-OCT-15:41 | 456.59 | 259.01 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 53.18 | 0.00 |
November | 8186.75 | 07-NOV-15:30 | 1239.33 | 666.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.71 |
December | 7988.38 | 18-DEC-15:30 | 1239.33 | 666.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.60 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7516.87 | 260.91 | 148.01 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20241.98 | 1239.33 | 666.04 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 53.18 | 467.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3336.22 | 18-JAN-15:30 | 1923.11 | 1133.80 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.19 |
February | 3078.07 | 03-FEB-15:50 | 1923.11 | 1133.80 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.40 |
March | 4136.30 | 23-MAR-15:20 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.30 |
April | 5949.47 | 26-APR-14:00 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 32.46 | 0.00 |
May | 6432.36 | 04-MAY-13:50 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.72 |
June | 6311.63 | 30-JUN-14:00 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.59 |
July | 7117.05 | 19-JUL-15:00 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 64.52 | 0.00 |
August | 6950.24 | 17-AUG-14:00 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 78.00 | 0.00 |
September | 9633.77 | 30-SEP-05:02 | 2024.33 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
October | 8440.73 | 05-OCT-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3115.96 | 10-NOV-14:30 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.61 |
December | 3392.68 | 05-DEC-15:00 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 16.35 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3078.07 | 1012.16 | 337.35 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9633.77 | 2024.33 | 1133.80 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 78.00 | 124.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4323.35 | 20-JAN-09:40 | 1239.33 | 666.04 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.49 |
February | 4360.31 | 02-FEB-09:40 | 1239.33 | 666.04 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.41 |
March | 7583.31 | 23-MAR-09:10 | 1295.83 | 666.04 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.71 |
April | 14573.49 | 30-APR-09:02 | 260.91 | 148.01 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.79 |
May | 9343.18 | 28-MAY-08:53 | 260.91 | 148.01 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.09 |
June | 15429.06 | 18-JUN-09:02 | 260.91 | 148.01 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.56 |
July | 17679.68 | 04-JUL-08:43 | 260.91 | 148.01 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.79 |
August | 17449.06 | 06-AUG-08:53 | 260.91 | 148.01 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.22 |
September | 15695.44 | 10-SEP-08:43 | 260.91 | 148.01 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.30 |
October | 17977.27 | 15-OCT-08:32 | 326.14 | 185.01 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 227.76 | 0.00 |
November | 3740.16 | 01-NOV-09:20 | 1295.83 | 666.04 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.59 |
December | 4091.95 | 05-DEC-09:30 | 1239.33 | 666.04 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 12.37 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3740.16 | 260.91 | 148.01 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17977.27 | 1295.83 | 666.04 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 227.76 | 341.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17762.21 | 22-JAN-13:42 | 506.09 | 287.09 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 681.93 |
February | 16255.26 | 20-FEB-13:51 | 1012.19 | 574.19 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1237.20 |
March | 13273.06 | 23-MAR-13:20 | 2010.83 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.04 |
April | 9997.10 | 26-APR-13:10 | 2010.83 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 52.99 | 0.00 |
May | 7616.84 | 04-MAY-13:30 | 2010.83 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.72 |
June | 6588.88 | 30-JUN-13:40 | 2010.83 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.60 |
July | 8939.67 | 31-JUL-12:50 | 1923.15 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 92.08 | 0.00 |
August | 11689.27 | 30-AUG-12:50 | 1923.15 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.66 |
September | 15432.12 | 29-SEP-13:20 | 2010.83 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 210.02 | 0.00 |
October | 19412.47 | 15-OCT-11:12 | 607.31 | 344.51 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 161.53 | 0.00 |
November | 19427.42 | 19-NOV-12:52 | 607.31 | 344.51 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.66 |
December | 17495.86 | 25-DEC-13:32 | 506.09 | 287.09 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.56 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6588.88 | 506.09 | 287.09 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19427.42 | 2010.83 | 1033.54 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 210.02 | 1237.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7259.42 | 26-JAN-15:30 | 1239.33 | 666.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.17 |
February | 8299.25 | 22-FEB-16:00 | 1239.33 | 666.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.64 |
March | 11035.52 | 23-MAR-16:00 | 1239.33 | 666.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.20 |
April | 19707.02 | 30-APR-16:21 | 521.82 | 296.02 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.85 |
May | 18194.69 | 21-MAY-16:53 | 260.91 | 148.01 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 581.02 |
June | 20244.35 | 18-JUN-16:32 | 326.14 | 185.01 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.20 |
July | 20102.95 | 23-JUL-17:22 | 0.00 | 204.30 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.82 |
August | 20981.94 | 20-AUG-16:02 | 391.37 | 222.01 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.15 |
September | 19754.32 | 10-SEP-16:12 | 326.14 | 185.01 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.52 |
October | 21429.49 | 15-OCT-15:51 | 456.59 | 259.01 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 48.85 | 0.00 |
November | 9472.33 | 12-NOV-15:51 | 652.28 | 370.02 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 497.12 |
December | 7635.28 | 19-DEC-15:30 | 1239.33 | 666.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.55 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7259.42 | 0.00 | 148.01 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21429.49 | 1239.33 | 666.04 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 48.85 | 581.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7268.56 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.40 |
February | 5949.95 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.32 |
March | 5914.06 | 13-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.90 |
April | 6027.66 | 17-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.62 |
May | 6194.62 | 01-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7412.31 | 12-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.98 |
July | 7048.00 | 05-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6216.16 | 07-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.62 |
September | 7368.95 | 05-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8479.16 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.99 |
November | 8265.36 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.68 |
December | 7676.55 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.03 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5914.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8479.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4580.29 | 09-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.81 |
February | 3908.81 | 03-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.46 |
March | 4005.91 | 23-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.56 |
April | 4022.88 | 26-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.72 |
May | 3995.22 | 06-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.15 |
June | 4203.50 | 14-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.38 |
July | 4152.28 | 14-JUL-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4227.85 | 19-AUG-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.95 |
September | 4438.35 | 29-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.42 | 0.00 |
October | 4818.24 | 17-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.77 | 0.00 |
November | 4212.50 | 14-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.23 |
December | 3943.43 | 01-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3908.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4818.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.42 | 427.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6364.84 | 18-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.78 |
February | 6630.52 | 01-FEB-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.32 |
March | 9689.58 | 23-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.36 |
April | 12561.01 | 26-APR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
May | 11747.55 | 03-MAY-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.71 |
June | 11925.43 | 21-JUN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.08 |
July | 13353.39 | 19-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.65 | 0.00 |
August | 12795.97 | 17-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.58 | 0.00 |
September | 14129.10 | 29-SEP-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.25 | 0.00 |
October | 14158.33 | 16-OCT-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.17 | 0.00 |
November | 6455.69 | 10-NOV-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.07 |
December | 5843.55 | 05-DEC-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.57 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5843.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14158.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.25 | 223.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1973.15 | 30-JAN-16:50 | 0.00 | 250.91 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4029.24 | 20-FEB-16:54 | 0.00 | 139.39 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5994.01 | 19-MAR-17:13 | 0.00 | 46.18 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7853.17 | 16-APR-17:33 | 0.00 | 46.18 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2041.21 | 29-MAY-17:50 | 0.00 | 46.18 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3901.72 | 25-JUN-17:47 | 0.00 | 61.57 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5900.65 | 04-JUL-18:17 | 0.00 | 46.18 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7980.15 | 06-AUG-18:03 | 0.00 | 61.57 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2083.87 | 04-SEP-16:53 | 0.00 | 41.82 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4161.76 | 15-OCT-16:57 | 0.00 | 55.76 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5930.56 | 12-NOV-16:30 | 0.00 | 41.82 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7901.81 | 25-DEC-16:13 | 0.00 | 41.82 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1973.15 | 0.00 | 41.82 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7980.15 | 0.00 | 250.91 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1778.60 | 30-JAN-16:50 | 0.00 | 250.91 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3701.07 | 22-FEB-17:00 | 0.00 | 250.91 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5478.86 | 10-MAR-17:20 | 0.00 | 139.39 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7295.61 | 27-APR-17:40 | 0.00 | 83.64 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1789.89 | 28-MAY-17:45 | 0.00 | 30.78 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3599.39 | 25-JUN-17:53 | 0.00 | 61.57 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5493.25 | 04-JUL-18:13 | 0.00 | 46.18 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7338.43 | 06-AUG-17:56 | 0.00 | 76.96 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1921.16 | 29-SEP-16:40 | 0.00 | 139.39 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3843.27 | 15-OCT-16:48 | 0.00 | 69.70 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5454.75 | 07-NOV-16:30 | 0.00 | 250.91 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7246.99 | 19-DEC-16:20 | 0.00 | 250.91 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1778.60 | 0.00 | 30.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7338.43 | 0.00 | 250.91 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1716.69 | 26-JAN-16:20 | 0.00 | 250.91 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3695.79 | 22-FEB-17:00 | 0.00 | 250.91 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5508.82 | 22-MAR-17:20 | 0.00 | 83.64 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7345.61 | 27-APR-17:30 | 0.00 | 83.64 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1861.84 | 29-MAY-17:43 | 0.00 | 46.18 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3709.47 | 25-JUN-17:53 | 0.00 | 61.57 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5599.20 | 09-JUL-17:54 | 0.00 | 76.96 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7429.02 | 20-AUG-17:40 | 0.00 | 92.35 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1991.59 | 29-SEP-16:40 | 0.00 | 139.39 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3947.59 | 15-OCT-16:50 | 0.00 | 69.70 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5432.48 | 07-NOV-16:30 | 0.00 | 250.91 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7238.05 | 19-DEC-16:20 | 0.00 | 250.91 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1716.69 | 0.00 | 46.18 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7429.02 | 0.00 | 250.91 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 90753.66 | 02-JAN-17:00 | 0.00 | 10862.88 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 181660.68 | 21-FEB-17:00 | 0.00 | 5431.44 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 273218.06 | 24-MAR-16:00 | 0.00 | 5431.44 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 365249.49 | 26-APR-16:00 | 0.00 | 5431.44 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 103005.91 | 01-MAY-00:10 | 0.00 | 333.20 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 181471.84 | 21-JUN-16:00 | 0.00 | 5431.44 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 273617.91 | 19-JUL-14:20 | 0.00 | 5431.44 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 370214.47 | 06-AUG-19:21 | 0.00 | 3332.00 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 104376.46 | 01-SEP-00:10 | 0.00 | 333.20 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 182664.70 | 16-OCT-16:00 | 0.00 | 5431.44 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 274400.25 | 13-NOV-17:00 | 0.00 | 5431.44 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 376379.21 | 26-DEC-01:11 | 0.00 | 3332.00 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 90753.66 | 0.00 | 333.20 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 376379.21 | 0.00 | 10862.88 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.157768E+13 | 1155911.97 | 18-JAN-11:00 | 0.608264E+11 | 828535.99 | 12-JAN-06:19 |
February | 0.173381E+13 | 1328667.04 | 01-FEB-09:00 | 0.471276E+11 | 532737.82 | 23-FEB-06:19 |
March | 0.230693E+13 | 1487760.75 | 23-MAR-15:09 | 0.564748E+11 | 395401.95 | 30-MAR-05:10 |
April | 0.265644E+13 | 1659596.26 | 26-APR-15:20 | 0.455687E+11 | 305106.71 | 03-APR-03:39 |
May | 0.156795E+13 | 1134526.50 | 04-MAY-13:39 | 0.466230E+11 | 163908.18 | 01-MAY-01:00 |
June | 0.197631E+13 | 1384448.71 | 29-JUN-15:00 | 0.442927E+11 | 101324.16 | 19-JUN-03:49 |
July | 0.255624E+13 | 1672359.81 | 31-JUL-15:00 | 0.429957E+11 | 147840.92 | 05-JUL-01:10 |
August | 0.311176E+13 | 1826736.82 | 18-AUG-15:00 | 0.457795E+11 | 145602.37 | 14-AUG-02:09 |
September | 0.163223E+13 | 1293638.03 | 29-SEP-15:09 | 0.424559E+11 | 147225.10 | 04-SEP-21:00 |
October | 0.215269E+13 | 1431370.94 | 03-OCT-13:30 | 0.457586E+11 | 159687.36 | 15-OCT-18:30 |
November | 0.230031E+13 | 1519393.47 | 28-NOV-14:09 | 0.463838E+11 | 184507.83 | 22-NOV-04:10 |
December | 0.277907E+13 | 1712068.18 | 05-DEC-16:10 | 0.524147E+11 | 396819.45 | 25-DEC-08:20 |
Annual Sum or Average | 0.263514E+14 | 0.576702E+12 | ||||
Minimum of Months | 0.156795E+13 | 1134526.50 | 0.424559E+11 | 101324.16 | ||
Maximum of Months | 0.311176E+13 | 1826736.82 | 0.608264E+11 | 828535.99 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.268546E+12 | 0.369377E+11 | 0.766053E+12 | 0.166080E+12 | 0.170552E+12 | 0.221086E+11 | 0.00 | 0.791731E+11 | 0.316479E+11 | 0.365860E+11 | 0.00 | 0.00 | 0.00 |
February | 0.241010E+12 | 0.303619E+11 | 0.978954E+12 | 0.150013E+12 | 0.153448E+12 | 0.186151E+11 | 0.00 | 0.933269E+11 | 0.328982E+11 | 0.351800E+11 | 0.00 | 0.00 | 0.00 |
March | 0.285503E+12 | 0.292627E+11 | 0.141645E+13 | 0.166252E+12 | 0.172312E+12 | 0.200792E+11 | 0.00 | 0.141331E+12 | 0.466110E+11 | 0.291319E+11 | 0.00 | 0.00 | 0.00 |
April | 0.252777E+12 | 0.242361E+11 | 0.166021E+13 | 0.160705E+12 | 0.167437E+12 | 0.250334E+11 | 0.00 | 0.255158E+12 | 0.100057E+12 | 0.108282E+11 | 0.00 | 0.00 | 0.00 |
May | 0.272265E+12 | 0.223184E+11 | 0.774418E+12 | 0.166164E+12 | 0.170079E+12 | 0.267622E+11 | 0.00 | 0.844472E+11 | 0.466213E+11 | 0.487851E+10 | 0.00 | 0.00 | 0.00 |
June | 0.270937E+12 | 0.205545E+11 | 0.106218E+13 | 0.160867E+12 | 0.169519E+12 | 0.321652E+11 | 0.00 | 0.178258E+12 | 0.814997E+11 | 0.325547E+09 | 0.00 | 0.00 | 0.00 |
July | 0.252856E+12 | 0.215258E+11 | 0.139289E+13 | 0.166002E+12 | 0.175496E+12 | 0.405351E+11 | 0.00 | 0.356775E+12 | 0.150164E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.283080E+12 | 0.237088E+11 | 0.173328E+13 | 0.166251E+12 | 0.182216E+12 | 0.450684E+11 | 0.00 | 0.513999E+12 | 0.164123E+12 | 34043422.82 | 0.00 | 0.00 | 0.00 |
September | 0.253833E+12 | 0.265029E+11 | 0.740378E+12 | 0.160705E+12 | 0.169546E+12 | 0.332482E+11 | 0.00 | 0.162738E+12 | 0.835039E+11 | 0.177511E+10 | 0.00 | 0.00 | 0.00 |
October | 0.265706E+12 | 0.318050E+11 | 0.108288E+13 | 0.166079E+12 | 0.176639E+12 | 0.340642E+11 | 0.00 | 0.239234E+12 | 0.107204E+12 | 0.490705E+11 | 0.00 | 0.00 | 0.00 |
November | 0.265236E+12 | 0.346498E+11 | 0.135889E+13 | 0.160772E+12 | 0.169190E+12 | 0.228117E+11 | 0.00 | 0.157278E+12 | 0.614557E+11 | 0.700208E+11 | 0.00 | 0.00 | 0.00 |
December | 0.260277E+12 | 0.379930E+11 | 0.170972E+13 | 0.166004E+12 | 0.172889E+12 | 0.222777E+11 | 0.00 | 0.220845E+12 | 0.785156E+11 | 0.110550E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317203E+13 | 0.339857E+12 | 0.146763E+14 | 0.195589E+13 | 0.204932E+13 | 0.342769E+12 | 0.00 | 0.248256E+13 | 0.984302E+12 | 0.348380E+12 | |||
Minimum of Months | 0.241010E+12 | 0.205545E+11 | 0.740378E+12 | 0.150013E+12 | 0.153448E+12 | 0.186151E+11 | 0.00 | 0.791731E+11 | 0.316479E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.285503E+12 | 0.379930E+11 | 0.173328E+13 | 0.166252E+12 | 0.182216E+12 | 0.450684E+11 | 0.00 | 0.513999E+12 | 0.164123E+12 | 0.110550E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.139865E+11 | 0.00 | 0.468399E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.464445E+10 | 0.00 | 0.424832E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.762870E+10 | 0.00 | 0.488461E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.160044E+10 | 0.00 | 0.439683E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.861053E+09 | 0.00 | 0.457620E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.155166E+09 | 0.00 | 0.441376E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.875667E+09 | 0.00 | 0.421201E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.609759E+09 | 0.00 | 0.451697E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.476501E+09 | 0.00 | 0.419794E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.140707E+10 | 0.00 | 0.443515E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.187417E+10 | 0.00 | 0.445097E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.720052E+10 | 0.00 | 0.452142E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.413200E+11 | 0.535382E+12 | |||||
Minimum of Months | 0.00 | 0.00 | 0.155166E+09 | 0.00 | 0.419794E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.139865E+11 | 0.00 | 0.488461E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 321032.30 | 02-JAN-16:49 | 39974.20 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 126033.08 | 31-JAN-08:20 | 112384.91 | 26-JAN-15:30 | 19640.14 | 18-JAN-14:20 | 0.00 | 01-JAN-00:10 |
February | 321032.30 | 27-FEB-16:00 | 39974.20 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 126030.52 | 10-FEB-08:20 | 114451.30 | 22-FEB-16:19 | 18592.91 | 01-FEB-11:00 | 0.00 | 01-FEB-00:10 |
March | 292935.83 | 16-MAR-07:10 | 39974.20 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 126035.29 | 16-MAR-07:19 | 112972.61 | 24-MAR-14:00 | 32671.54 | 22-MAR-12:00 | 0.00 | 01-MAR-00:10 |
April | 292871.20 | 21-APR-15:00 | 39974.20 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 126031.26 | 05-APR-07:19 | 114699.32 | 28-APR-15:30 | 32400.85 | 11-APR-15:39 | 0.00 | 01-APR-00:10 |
May | 285393.19 | 09-MAY-07:10 | 26960.70 | 01-MAY-18:30 | 423497.50 | 01-MAY-07:10 | 126031.26 | 09-MAY-07:19 | 105454.22 | 19-MAY-15:00 | 31191.90 | 04-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 282130.43 | 09-JUN-07:10 | 26960.70 | 01-JUN-18:49 | 541788.89 | 01-JUN-07:10 | 126029.52 | 09-JUN-07:19 | 107886.18 | 30-JUN-15:00 | 32441.29 | 14-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 280051.24 | 11-JUL-07:10 | 26960.70 | 01-JUL-18:00 | 660080.29 | 03-JUL-07:10 | 126028.41 | 11-JUL-07:19 | 113014.93 | 19-JUL-15:39 | 32644.49 | 31-JUL-15:50 | 0.00 | 01-JUL-00:10 |
August | 285393.19 | 21-AUG-07:10 | 39974.20 | 08-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 126031.26 | 21-AUG-07:19 | 115182.68 | 18-AUG-15:20 | 33057.47 | 18-AUG-15:50 | 0.00 | 01-AUG-00:10 |
September | 298066.30 | 18-SEP-07:10 | 39974.20 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 126038.03 | 18-SEP-07:19 | 133554.25 | 29-SEP-15:30 | 33196.76 | 29-SEP-10:39 | 0.00 | 01-SEP-00:10 |
October | 302520.62 | 23-OCT-15:00 | 39974.20 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 126040.41 | 24-OCT-07:19 | 131594.47 | 16-OCT-15:20 | 39272.68 | 30-OCT-13:39 | 0.00 | 01-OCT-00:10 |
November | 321032.30 | 06-NOV-16:40 | 39974.20 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 126031.35 | 24-NOV-08:20 | 114357.68 | 14-NOV-15:30 | 29969.46 | 28-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 321032.30 | 01-DEC-16:19 | 39974.20 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 126032.41 | 08-DEC-08:20 | 113593.76 | 21-DEC-15:39 | 30235.19 | 05-DEC-14:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 280051.24 | 26960.70 | 423497.50 | 126028.41 | 105454.22 | 18592.91 | 0.00 | |||||||
Maximum of Months | 321032.30 | 39974.20 | 778371.69 | 126040.41 | 133554.25 | 39272.68 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum}[W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum}[W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 161017.44 | 18-JAN-12:30 | 79128.34 | 17-JAN-12:20 | 100000.00 | 07-JAN-04:10 | 0.00 | 0.00 | 0.00 |
February | 216209.03 | 01-FEB-12:09 | 64188.31 | 01-FEB-11:09 | 100000.00 | 01-FEB-04:10 | 0.00 | 0.00 | 0.00 |
March | 274882.17 | 23-MAR-14:09 | 79128.34 | 22-MAR-12:09 | 100000.00 | 07-MAR-11:30 | 0.00 | 0.00 | 0.00 |
April | 327299.63 | 26-APR-12:00 | 79128.34 | 04-APR-11:00 | 100000.00 | 01-APR-04:00 | 0.00 | 0.00 | 0.00 |
May | 184710.40 | 04-MAY-13:39 | 79128.34 | 03-MAY-13:00 | 100000.00 | 24-MAY-05:49 | 0.00 | 0.00 | 0.00 |
June | 289321.39 | 29-JUN-12:00 | 79128.34 | 14-JUN-09:39 | 59529.04 | 12-JUN-09:00 | 0.00 | 0.00 | 0.00 |
July | 425624.51 | 31-JUL-15:00 | 79128.34 | 01-JUL-08:30 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 456542.05 | 18-AUG-15:00 | 79128.34 | 01-AUG-09:00 | 39271.84 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 286910.46 | 22-SEP-12:30 | 79128.34 | 05-SEP-12:09 | 100000.00 | 29-SEP-19:40 | 0.00 | 0.00 | 0.00 |
October | 350433.61 | 03-OCT-13:30 | 79128.34 | 01-OCT-11:39 | 100000.00 | 13-OCT-03:09 | 0.00 | 0.00 | 0.00 |
November | 262662.80 | 28-NOV-14:09 | 64188.31 | 10-NOV-10:00 | 100000.00 | 09-NOV-05:00 | 0.00 | 0.00 | 0.00 |
December | 303662.30 | 05-DEC-15:09 | 64188.31 | 04-DEC-13:00 | 100000.00 | 03-DEC-23:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 161017.44 | 64188.31 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 456542.05 | 79128.34 | 100000.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1155911.97 | 18-JAN-11:00 | 276093.44 | 423497.50 | 0.00 | 40207.72 | 91506.98 | 16674.60 | 0.00 | 143743.42 | 64188.31 |
February | 1328667.04 | 01-FEB-09:00 | 276093.44 | 541788.89 | 0.00 | 89246.91 | 86580.80 | 16571.73 | 0.00 | 166385.93 | 51999.34 |
March | 1487760.75 | 23-MAR-15:09 | 276093.44 | 660080.29 | 0.00 | 89246.91 | 107666.73 | 30546.56 | 0.00 | 244998.49 | 79128.34 |
April | 1659596.26 | 26-APR-15:20 | 276093.44 | 778371.69 | 0.00 | 89246.91 | 109240.28 | 31176.62 | 0.00 | 296338.98 | 79128.34 |
May | 1134526.50 | 04-MAY-13:39 | 276093.44 | 423497.50 | 0.00 | 40207.72 | 99941.49 | 30947.61 | 0.00 | 184710.40 | 79128.34 |
June | 1384448.71 | 29-JUN-15:00 | 276093.44 | 541788.89 | 0.00 | 89246.91 | 107078.76 | 31163.91 | 0.00 | 259948.45 | 79128.34 |
July | 1672359.81 | 31-JUL-15:00 | 276093.44 | 660080.29 | 0.00 | 89246.91 | 109620.30 | 32566.02 | 0.00 | 425624.51 | 79128.34 |
August | 1826736.82 | 18-AUG-15:00 | 276093.44 | 778371.69 | 0.00 | 89246.91 | 114460.15 | 32894.24 | 0.00 | 456542.05 | 79128.34 |
September | 1293638.03 | 29-SEP-15:09 | 276093.44 | 423497.50 | 0.00 | 89246.91 | 132791.82 | 32490.21 | 0.00 | 259876.00 | 79128.34 |
October | 1431370.94 | 03-OCT-13:30 | 276093.44 | 541788.89 | 0.00 | 40207.72 | 111506.28 | 32212.66 | 0.00 | 350433.61 | 79128.34 |
November | 1519393.47 | 28-NOV-14:09 | 276093.44 | 660080.29 | 0.00 | 40207.72 | 98523.66 | 29561.77 | 0.00 | 262662.80 | 52263.79 |
December | 1712068.18 | 05-DEC-16:10 | 293051.85 | 778371.69 | 0.00 | 89251.96 | 100170.47 | 29999.77 | 0.00 | 268647.33 | 53136.21 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1134526.50 | 276093.44 | 423497.50 | 0.00 | 40207.72 | 86580.80 | 16571.73 | 0.00 | 143743.42 | 51999.34 | |
Maximum of Months | 1826736.82 | 293051.85 | 778371.69 | 0.00 | 89251.96 | 132791.82 | 32894.24 | 0.00 | 456542.05 | 79128.34 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 821255.11 | 12-JAN-06:19 | 0.00 | 72100.92 | 30-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 525456.94 | 23-FEB-06:19 | 0.00 | 72098.50 | 06-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 388121.07 | 30-MAR-05:10 | 0.00 | 71843.90 | 02-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 297825.83 | 03-APR-03:39 | 0.00 | 70857.56 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 156627.30 | 01-MAY-01:00 | 0.00 | 69635.76 | 02-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 94043.28 | 19-JUN-03:49 | 0.00 | 68226.28 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 140560.04 | 05-JUL-01:10 | 0.00 | 66989.24 | 06-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 138321.49 | 14-AUG-02:09 | 0.00 | 66843.87 | 28-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 139944.22 | 04-SEP-21:00 | 0.00 | 67891.93 | 29-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 152406.48 | 15-OCT-18:30 | 0.00 | 69361.09 | 30-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 177226.95 | 22-NOV-04:10 | 0.00 | 70666.28 | 30-NOV-12:50 | 0.00 |
December | 0.00 | 0.00 | 389538.57 | 25-DEC-08:20 | 0.00 | 71676.46 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 94043.28 | 0.00 | 66843.87 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 821255.11 | 0.00 | 72100.92 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.18 | 2.00 | 27.85 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.85 | 0.50 | 27.68 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 26.39 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 26.41 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 26.99 | 0.17 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 26.60 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 26.70 | 0.17 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.35 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 26.62 | 1.17 | 27.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 26.70 | 0.83 | 27.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 26.48 | 0.83 | 28.02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 26.41 | 1.33 | 27.51 |
Annual Sum or Average | 0.00 | 0.00 | 73.00 | 26.64 | 7.00 | 27.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 26.35 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.18 | 2.00 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.44 | 0.67 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.63 | 2.00 | 27.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.56 | 1.50 | 27.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.74 | 1.67 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.74 | 3.83 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.76 | 2.50 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.77 | 1.33 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.82 | 1.33 | 27.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 14.83 | 27.71 | 14.83 | 27.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.82 | 3.83 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 47.67 | 25.03 | 47.67 | 25.03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 25.75 | 10.17 | 25.75 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.49 | 1.17 | 27.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 25.13 | 4.33 | 25.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 25.91 | 26.50 | 25.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 40.00 | 25.26 | 40.00 | 25.26 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 70.17 | 25.30 | 70.17 | 25.30 |
Annual Sum or Average | 0.00 | 0.00 | 200.00 | 25.34 | 200.00 | 25.34 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 70.17 | 27.49 | 70.17 | 27.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.47 | 0.17 | 27.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.64 | 2.17 | 27.64 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.93 | 2.00 | 27.92 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.65 | 4.50 | 28.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.86 | 3.83 | 27.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.92 | 3.00 | 28.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.57 | 6.33 | 28.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.33 | 6.33 | 28.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.90 | 3.17 | 28.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.10 | 4.50 | 28.15 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.80 | 3.00 | 27.80 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.84 | 3.67 | 27.84 |
Annual Sum or Average | 0.00 | 0.00 | 73.33 | 27.64 | 42.67 | 28.13 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.33 | 0.17 | 27.47 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 28.10 | 6.33 | 28.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.70 | 0.83 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.50 | 1.00 | 27.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.69 | 1.50 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.79 | 3.33 | 27.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.68 | 2.67 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.56 | 1.50 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.82 | 1.00 | 27.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.83 | 27.70 | 11.83 | 27.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.82 | 3.33 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 74.83 | 25.23 | 74.83 | 25.23 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 25.33 | 21.33 | 25.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.12 | 2.00 | 25.12 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 25.02 | 8.50 | 25.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 50.50 | 25.58 | 50.50 | 25.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 50.83 | 25.36 | 50.83 | 25.36 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 82.83 | 25.42 | 82.83 | 25.42 |
Annual Sum or Average | 0.00 | 0.00 | 290.83 | 25.37 | 290.83 | 25.37 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 82.83 | 25.58 | 82.83 | 25.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.62 | 0.33 | 27.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.84 | 3.00 | 27.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.81 | 2.00 | 27.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.78 | 2.00 | 27.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.94 | 4.50 | 28.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.01 | 2.67 | 28.10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.81 | 2.33 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.96 | 1.83 | 27.96 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 24.50 | 27.88 | 18.67 | 27.95 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.01 | 4.50 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 19.23 | 0.17 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 19.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 19.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.33 | 19.29 | 0.17 | 20.39 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 19.42 | 0.17 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 19.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 19.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.40 | 0.50 | 27.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.55 | 1.00 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.70 | 3.00 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.54 | 2.33 | 27.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.51 | 0.50 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.75 | 0.83 | 27.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 19.19 | 0.00 | 8.17 | 27.61 | 8.17 | 27.61 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.39 | 0.00 | 0.00 | 3.00 | 27.75 | 3.00 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.23 | 0.00 | 0.00 | 25.17 | 25.08 | 25.17 | 25.08 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 25.73 | 4.33 | 25.73 |
March | 0.17 | 19.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 24.94 | 6.50 | 24.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 25.81 | 25.00 | 25.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 25.32 | 18.17 | 25.32 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 25.18 | 37.17 | 25.18 |
Annual Sum or Average | 0.50 | 19.25 | 0.00 | 116.33 | 25.32 | 116.33 | 25.32 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.29 | 0.00 | 0.00 | 37.17 | 25.81 | 37.17 | 25.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.62 | 0.33 | 27.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.87 | 2.67 | 27.95 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.82 | 1.83 | 27.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.82 | 2.17 | 27.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.00 | 4.67 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.06 | 2.83 | 28.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.83 | 2.17 | 27.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.11 | 1.50 | 28.14 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 19.27 | 0.00 | 23.83 | 27.94 | 18.17 | 27.99 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.27 | 0.00 | 0.00 | 6.67 | 28.11 | 4.67 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.76 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.57 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 204.00 | 28.66 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.79 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 207.83 | 28.64 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 204.00 | 28.66 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.33 | 24.11 | 251.83 | 25.08 | 1.00 | 26.84 |
February | 26.67 | 24.01 | 231.33 | 24.96 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 309.00 | 24.67 | 0.00 | 0.00 |
April | 3.00 | 24.04 | 393.00 | 24.62 | 0.00 | 0.00 |
May | 0.50 | 24.00 | 375.17 | 24.62 | 0.00 | 0.00 |
June | 21.50 | 24.00 | 475.17 | 24.44 | 21.50 | 24.00 |
July | 152.00 | 24.78 | 497.00 | 24.58 | 152.00 | 24.78 |
August | 140.33 | 24.87 | 514.00 | 24.45 | 140.33 | 24.87 |
September | 67.83 | 24.71 | 451.17 | 24.56 | 67.83 | 24.71 |
October | 39.50 | 24.45 | 334.33 | 24.88 | 35.33 | 24.50 |
November | 25.50 | 24.11 | 279.17 | 25.02 | 0.83 | 26.79 |
December | 39.00 | 24.03 | 202.33 | 25.39 | 0.17 | 26.81 |
Annual Sum or Average | 544.17 | 24.58 | 4313.50 | 24.70 | 419.00 | 24.75 |
Minimum of Months | 0.00 | 0.00 | 202.33 | 24.44 | 0.00 | 0.00 |
Maximum of Months | 152.00 | 24.87 | 514.00 | 25.39 | 152.00 | 26.84 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 37.17 | 23.79 | 237.00 | 24.69 | 0.00 | 0.00 |
February | 20.67 | 23.86 | 241.33 | 24.52 | 0.00 | 0.00 |
March | 4.17 | 23.68 | 327.17 | 24.42 | 0.00 | 0.00 |
April | 6.50 | 23.65 | 422.33 | 24.29 | 0.00 | 0.00 |
May | 9.33 | 23.44 | 363.00 | 24.34 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 464.17 | 24.27 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 480.83 | 24.24 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 510.17 | 24.18 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 428.67 | 24.29 | 0.00 | 0.00 |
October | 7.50 | 23.76 | 330.83 | 24.43 | 0.00 | 0.00 |
November | 16.83 | 24.28 | 271.33 | 24.59 | 1.17 | 26.99 |
December | 26.33 | 24.01 | 204.33 | 24.75 | 0.00 | 0.00 |
Annual Sum or Average | 128.50 | 23.87 | 4281.17 | 24.37 | 1.17 | 26.99 |
Minimum of Months | 0.00 | 0.00 | 204.33 | 24.18 | 0.00 | 0.00 |
Maximum of Months | 37.17 | 24.28 | 510.17 | 24.75 | 1.17 | 26.99 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 198.17 | 23.53 | 95.33 | 24.26 | 13.33 | 24.07 |
February | 159.33 | 23.43 | 96.17 | 24.23 | 0.00 | 0.00 |
March | 141.33 | 23.40 | 159.83 | 24.24 | 0.00 | 0.00 |
April | 83.17 | 23.25 | 218.00 | 24.26 | 0.00 | 0.00 |
May | 81.33 | 23.27 | 221.50 | 24.27 | 0.00 | 0.00 |
June | 42.83 | 23.03 | 304.00 | 24.22 | 0.00 | 0.00 |
July | 51.17 | 23.11 | 297.00 | 24.22 | 0.00 | 0.00 |
August | 40.67 | 23.12 | 326.50 | 24.18 | 0.00 | 0.00 |
September | 51.17 | 23.16 | 291.67 | 24.23 | 0.00 | 0.00 |
October | 119.17 | 23.43 | 204.83 | 24.31 | 0.00 | 0.00 |
November | 153.50 | 23.56 | 151.67 | 24.39 | 0.00 | 0.00 |
December | 230.83 | 23.51 | 67.33 | 24.39 | 0.00 | 0.00 |
Annual Sum or Average | 1352.67 | 23.40 | 2433.83 | 24.25 | 13.33 | 24.07 |
Minimum of Months | 40.67 | 23.03 | 67.33 | 24.18 | 0.00 | 0.00 |
Maximum of Months | 230.83 | 23.56 | 326.50 | 24.39 | 13.33 | 24.07 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 402.83 | 22.60 | 39.00 | 22.71 | 14.00 | 20.43 |
February | 336.67 | 22.70 | 35.17 | 24.00 | 0.00 | 0.00 |
March | 338.00 | 22.91 | 79.50 | 24.02 | 0.00 | 0.00 |
April | 201.83 | 22.93 | 163.00 | 24.08 | 0.00 | 0.00 |
May | 191.67 | 22.99 | 174.00 | 24.10 | 0.00 | 0.00 |
June | 116.00 | 23.10 | 282.17 | 24.13 | 0.00 | 0.00 |
July | 80.83 | 23.16 | 301.83 | 24.15 | 0.00 | 0.00 |
August | 83.33 | 23.15 | 325.00 | 24.12 | 0.00 | 0.00 |
September | 141.00 | 23.09 | 241.17 | 24.12 | 0.00 | 0.00 |
October | 234.00 | 23.06 | 150.33 | 24.15 | 0.00 | 0.00 |
November | 319.00 | 22.87 | 67.17 | 24.08 | 1.33 | 21.95 |
December | 420.33 | 22.69 | 18.50 | 23.64 | 2.17 | 21.02 |
Annual Sum or Average | 2865.50 | 22.85 | 1876.83 | 24.08 | 17.50 | 20.62 |
Minimum of Months | 80.83 | 22.60 | 18.50 | 22.71 | 0.00 | 0.00 |
Maximum of Months | 420.33 | 23.16 | 325.00 | 24.15 | 14.00 | 21.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 331.33 | 23.18 | 36.33 | 24.38 | 0.00 | 0.00 |
February | 275.33 | 23.29 | 49.17 | 24.06 | 0.00 | 0.00 |
March | 223.00 | 23.25 | 114.67 | 24.10 | 0.00 | 0.00 |
April | 103.50 | 23.43 | 209.00 | 24.12 | 0.00 | 0.00 |
May | 136.67 | 23.40 | 204.33 | 24.19 | 0.00 | 0.00 |
June | 13.50 | 23.46 | 374.17 | 24.20 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 441.33 | 24.22 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 430.33 | 24.14 | 0.00 | 0.00 |
September | 60.17 | 23.35 | 292.50 | 24.19 | 0.00 | 0.00 |
October | 122.00 | 23.52 | 207.67 | 24.29 | 0.00 | 0.00 |
November | 257.17 | 23.51 | 85.83 | 24.30 | 0.00 | 0.00 |
December | 330.17 | 23.52 | 25.33 | 24.18 | 0.00 | 0.00 |
Annual Sum or Average | 1852.83 | 23.37 | 2470.67 | 24.19 | 0.00 | |
Minimum of Months | 0.00 | 0.00 | 25.33 | 24.06 | 0.00 | 0.00 |
Maximum of Months | 331.33 | 23.52 | 441.33 | 24.38 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 278.50 | 23.03 | 78.83 | 24.63 | 0.00 | 0.00 |
February | 254.83 | 22.98 | 80.67 | 24.38 | 0.33 | 26.51 |
March | 243.83 | 22.97 | 161.33 | 24.26 | 2.33 | 26.64 |
April | 152.17 | 23.22 | 249.17 | 24.27 | 6.33 | 26.80 |
May | 144.17 | 23.27 | 254.00 | 24.40 | 5.17 | 26.70 |
June | 92.67 | 23.45 | 325.00 | 24.28 | 8.83 | 26.75 |
July | 62.33 | 24.11 | 389.50 | 24.33 | 16.33 | 26.80 |
August | 78.83 | 23.69 | 369.17 | 24.20 | 12.33 | 26.73 |
September | 116.17 | 23.27 | 302.17 | 24.26 | 6.67 | 26.78 |
October | 150.00 | 23.28 | 225.00 | 24.39 | 5.33 | 26.82 |
November | 244.00 | 23.21 | 113.50 | 24.34 | 0.00 | 0.00 |
December | 301.33 | 23.15 | 34.17 | 24.78 | 0.00 | 0.00 |
Annual Sum or Average | 2118.83 | 23.19 | 2582.50 | 24.32 | 63.67 | 26.76 |
Minimum of Months | 62.33 | 22.97 | 34.17 | 24.20 | 0.00 | 0.00 |
Maximum of Months | 301.33 | 24.11 | 389.50 | 24.78 | 16.33 | 26.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 166.83 | 23.46 | 227.17 | 24.70 | 10.83 | 26.96 |
February | 191.00 | 23.35 | 164.00 | 24.56 | 9.67 | 26.93 |
March | 202.50 | 23.21 | 190.83 | 24.27 | 5.17 | 26.78 |
April | 112.17 | 23.29 | 252.33 | 24.24 | 0.00 | 0.00 |
May | 183.00 | 23.23 | 184.00 | 24.17 | 0.00 | 0.00 |
June | 61.50 | 23.32 | 311.00 | 24.15 | 0.00 | 0.00 |
July | 3.50 | 23.36 | 395.67 | 24.21 | 0.00 | 0.00 |
August | 2.17 | 23.42 | 432.83 | 24.17 | 0.00 | 0.00 |
September | 50.17 | 23.67 | 356.67 | 24.34 | 5.83 | 26.56 |
October | 92.17 | 24.62 | 331.17 | 24.63 | 33.33 | 26.78 |
November | 121.67 | 23.99 | 270.67 | 24.67 | 16.00 | 26.96 |
December | 146.00 | 24.00 | 241.00 | 24.90 | 21.83 | 26.94 |
Annual Sum or Average | 1332.67 | 23.55 | 3357.33 | 24.40 | 102.67 | 26.86 |
Minimum of Months | 2.17 | 23.21 | 164.00 | 24.15 | 0.00 | 0.00 |
Maximum of Months | 202.50 | 24.62 | 432.83 | 24.90 | 33.33 | 26.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 189.33 | 23.26 | 161.83 | 24.50 | 0.17 | 26.39 |
February | 69.83 | 23.76 | 234.67 | 24.49 | 6.33 | 26.70 |
March | 30.33 | 24.40 | 373.67 | 24.45 | 8.17 | 26.83 |
April | 28.50 | 26.67 | 472.00 | 24.56 | 26.00 | 26.97 |
May | 51.50 | 24.54 | 376.17 | 24.46 | 18.33 | 26.77 |
June | 19.17 | 26.87 | 491.67 | 24.44 | 19.17 | 26.87 |
July | 40.17 | 26.85 | 497.00 | 24.59 | 40.17 | 26.85 |
August | 36.50 | 26.81 | 514.00 | 24.47 | 36.50 | 26.81 |
September | 17.50 | 26.32 | 443.17 | 24.40 | 15.00 | 26.80 |
October | 36.83 | 25.29 | 391.50 | 24.59 | 18.83 | 26.89 |
November | 27.33 | 25.11 | 328.00 | 24.63 | 11.50 | 26.70 |
December | 30.33 | 25.09 | 301.83 | 24.78 | 12.00 | 26.80 |
Annual Sum or Average | 577.33 | 24.66 | 4585.50 | 24.52 | 212.17 | 26.84 |
Minimum of Months | 17.50 | 23.26 | 161.83 | 24.40 | 0.17 | 26.39 |
Maximum of Months | 189.33 | 26.87 | 514.00 | 24.78 | 40.17 | 26.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 469.17 | 22.20 | 20.17 | 21.80 | 13.17 | 20.64 |
February | 428.67 | 22.31 | 6.33 | 21.42 | 5.17 | 20.84 |
March | 455.00 | 22.39 | 21.83 | 23.82 | 1.17 | 20.98 |
April | 334.83 | 22.73 | 61.33 | 24.01 | 0.00 | 0.00 |
May | 299.67 | 22.90 | 87.67 | 24.04 | 0.00 | 0.00 |
June | 175.67 | 23.16 | 214.17 | 24.05 | 0.00 | 0.00 |
July | 115.33 | 23.18 | 263.00 | 24.08 | 0.00 | 0.00 |
August | 162.33 | 23.11 | 234.17 | 24.03 | 0.00 | 0.00 |
September | 243.67 | 23.03 | 150.17 | 24.03 | 0.00 | 0.00 |
October | 307.17 | 22.91 | 90.33 | 24.15 | 0.00 | 0.00 |
November | 434.83 | 22.53 | 11.50 | 22.49 | 5.50 | 20.85 |
December | 486.67 | 22.25 | 13.00 | 20.75 | 13.00 | 20.75 |
Annual Sum or Average | 3913.00 | 22.59 | 1173.67 | 23.95 | 38.00 | 20.74 |
Minimum of Months | 115.33 | 22.20 | 6.33 | 20.75 | 0.00 | 0.00 |
Maximum of Months | 486.67 | 23.18 | 263.00 | 24.15 | 13.17 | 20.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 366.50 | 22.42 | 23.00 | 23.40 | 5.67 | 20.65 |
February | 318.83 | 22.29 | 24.33 | 24.31 | 1.33 | 20.74 |
March | 317.00 | 22.33 | 62.17 | 24.27 | 1.83 | 22.47 |
April | 208.50 | 22.71 | 150.33 | 24.53 | 3.67 | 26.78 |
May | 216.50 | 22.81 | 144.33 | 24.58 | 2.67 | 26.65 |
June | 163.00 | 23.05 | 189.33 | 24.38 | 7.00 | 26.71 |
July | 108.67 | 23.58 | 264.50 | 24.50 | 18.00 | 26.77 |
August | 130.00 | 23.42 | 250.33 | 24.35 | 16.67 | 26.77 |
September | 190.67 | 22.91 | 165.50 | 24.30 | 5.67 | 26.78 |
October | 222.83 | 22.81 | 111.33 | 24.54 | 2.50 | 26.89 |
November | 325.83 | 22.60 | 26.00 | 24.29 | 1.33 | 20.97 |
December | 385.17 | 22.47 | 8.83 | 22.28 | 5.33 | 20.73 |
Annual Sum or Average | 2953.50 | 22.65 | 1420.00 | 24.40 | 71.67 | 25.50 |
Minimum of Months | 108.67 | 22.29 | 8.83 | 22.28 | 1.33 | 20.65 |
Maximum of Months | 385.17 | 23.58 | 264.50 | 24.58 | 18.00 | 26.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 213.33 | 23.19 | 210.50 | 24.88 | 18.00 | 26.33 |
February | 242.17 | 22.80 | 138.83 | 24.72 | 10.00 | 26.93 |
March | 291.00 | 22.62 | 136.00 | 24.27 | 3.00 | 25.68 |
April | 235.17 | 22.86 | 168.33 | 24.27 | 0.00 | 0.00 |
May | 280.17 | 22.87 | 118.17 | 24.09 | 0.00 | 0.00 |
June | 198.33 | 23.10 | 192.33 | 24.06 | 0.00 | 0.00 |
July | 122.33 | 23.15 | 262.67 | 24.12 | 0.00 | 0.00 |
August | 105.17 | 23.12 | 304.17 | 24.12 | 0.00 | 0.00 |
September | 110.67 | 23.25 | 291.50 | 24.34 | 4.83 | 26.46 |
October | 161.33 | 24.02 | 285.33 | 24.75 | 38.83 | 26.74 |
November | 193.50 | 23.44 | 224.00 | 24.83 | 16.67 | 26.92 |
December | 212.33 | 23.40 | 213.17 | 25.11 | 21.67 | 26.85 |
Annual Sum or Average | 2365.50 | 23.09 | 2545.00 | 24.47 | 113.00 | 26.70 |
Minimum of Months | 105.17 | 22.62 | 118.17 | 24.06 | 0.00 | 0.00 |
Maximum of Months | 291.00 | 24.02 | 304.17 | 25.11 | 38.83 | 26.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 400.00 | 22.33 | 46.33 | 23.88 | 2.83 | 20.41 |
February | 351.50 | 22.40 | 61.67 | 24.33 | 0.00 | 0.00 |
March | 375.17 | 22.52 | 87.83 | 24.23 | 2.00 | 26.30 |
April | 204.33 | 23.04 | 188.17 | 24.44 | 12.50 | 26.89 |
May | 217.17 | 23.08 | 191.83 | 24.42 | 11.17 | 26.77 |
June | 105.17 | 23.40 | 319.33 | 24.27 | 12.17 | 26.77 |
July | 63.83 | 24.54 | 387.83 | 24.40 | 25.17 | 26.84 |
August | 70.67 | 23.89 | 385.50 | 24.27 | 16.17 | 26.86 |
September | 128.00 | 23.23 | 268.17 | 24.33 | 10.17 | 26.83 |
October | 227.00 | 23.05 | 184.33 | 24.42 | 8.50 | 26.82 |
November | 345.50 | 22.65 | 87.50 | 24.28 | 0.33 | 26.54 |
December | 399.33 | 22.47 | 36.00 | 24.29 | 0.00 | 0.00 |
Annual Sum or Average | 2887.67 | 22.75 | 2244.50 | 24.33 | 101.00 | 26.64 |
Minimum of Months | 63.83 | 22.33 | 36.00 | 23.88 | 0.00 | 0.00 |
Maximum of Months | 400.00 | 24.54 | 387.83 | 24.44 | 25.17 | 26.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 488.67 | 21.47 | 99.00 | 20.11 | 99.00 | 20.11 |
February | 437.83 | 21.63 | 48.83 | 20.27 | 48.83 | 20.27 |
March | 477.83 | 21.84 | 52.33 | 21.38 | 37.33 | 20.33 |
April | 355.33 | 22.30 | 72.67 | 23.64 | 7.33 | 20.40 |
May | 335.33 | 22.49 | 88.67 | 23.91 | 2.33 | 20.04 |
June | 217.50 | 22.92 | 197.17 | 24.03 | 0.00 | 0.00 |
July | 147.50 | 23.05 | 264.17 | 24.07 | 0.00 | 0.00 |
August | 195.33 | 22.96 | 234.00 | 24.04 | 0.00 | 0.00 |
September | 281.00 | 22.72 | 133.67 | 24.02 | 0.00 | 0.00 |
October | 337.33 | 22.45 | 85.67 | 23.86 | 5.83 | 20.11 |
November | 480.33 | 21.95 | 51.17 | 20.59 | 48.67 | 20.41 |
December | 494.17 | 21.47 | 105.83 | 20.24 | 105.83 | 20.24 |
Annual Sum or Average | 4248.17 | 22.09 | 1433.17 | 23.10 | 355.17 | 20.24 |
Minimum of Months | 147.50 | 21.47 | 48.83 | 20.11 | 0.00 | 0.00 |
Maximum of Months | 494.17 | 23.05 | 264.17 | 24.07 | 105.83 | 20.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 458.83 | 21.89 | 62.17 | 21.00 | 50.17 | 20.29 |
February | 386.67 | 21.87 | 40.50 | 22.22 | 18.83 | 20.21 |
March | 388.33 | 21.98 | 77.00 | 23.43 | 16.00 | 20.24 |
April | 225.67 | 22.32 | 202.33 | 24.25 | 3.50 | 21.90 |
May | 246.83 | 22.47 | 179.67 | 24.32 | 0.67 | 23.09 |
June | 182.33 | 22.90 | 246.50 | 24.26 | 7.00 | 26.76 |
July | 117.00 | 23.61 | 341.50 | 24.37 | 21.83 | 26.75 |
August | 142.50 | 23.34 | 331.50 | 24.25 | 16.67 | 26.72 |
September | 219.83 | 22.65 | 224.17 | 24.20 | 3.00 | 26.58 |
October | 268.67 | 22.54 | 131.17 | 24.27 | 3.83 | 22.74 |
November | 428.33 | 22.26 | 21.67 | 21.66 | 15.17 | 20.50 |
December | 479.67 | 21.92 | 35.17 | 20.54 | 33.00 | 20.32 |
Annual Sum or Average | 3544.67 | 22.28 | 1893.33 | 23.99 | 189.67 | 22.04 |
Minimum of Months | 117.00 | 21.87 | 21.67 | 20.54 | 0.67 | 20.21 |
Maximum of Months | 479.67 | 23.61 | 341.50 | 24.37 | 50.17 | 26.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 265.50 | 22.36 | 185.83 | 24.00 | 31.33 | 21.57 |
February | 278.67 | 22.10 | 125.83 | 24.01 | 20.17 | 21.59 |
March | 350.50 | 22.13 | 135.33 | 23.58 | 25.33 | 20.71 |
April | 267.17 | 22.41 | 162.50 | 24.10 | 5.17 | 20.59 |
May | 318.67 | 22.47 | 112.50 | 23.96 | 2.67 | 19.92 |
June | 230.50 | 22.85 | 181.50 | 24.04 | 0.00 | 0.00 |
July | 154.83 | 23.02 | 256.83 | 24.12 | 0.00 | 0.00 |
August | 146.17 | 22.98 | 279.67 | 24.12 | 0.00 | 0.00 |
September | 167.67 | 22.96 | 254.33 | 24.33 | 6.00 | 26.68 |
October | 199.50 | 23.32 | 247.17 | 24.66 | 29.50 | 26.66 |
November | 241.50 | 22.68 | 198.83 | 24.41 | 17.67 | 23.16 |
December | 259.00 | 22.53 | 186.33 | 24.27 | 28.50 | 21.83 |
Annual Sum or Average | 2879.67 | 22.57 | 2326.67 | 24.17 | 166.33 | 22.69 |
Minimum of Months | 146.17 | 22.10 | 112.50 | 23.58 | 0.00 | 0.00 |
Maximum of Months | 350.50 | 23.32 | 279.67 | 24.66 | 31.33 | 26.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 437.67 | 21.76 | 87.83 | 21.89 | 52.33 | 20.38 |
February | 372.50 | 21.81 | 68.67 | 23.11 | 21.00 | 20.43 |
March | 409.33 | 22.00 | 92.17 | 23.50 | 19.17 | 21.03 |
April | 269.00 | 22.65 | 164.17 | 24.38 | 15.17 | 25.75 |
May | 278.83 | 22.68 | 170.83 | 24.41 | 10.83 | 26.77 |
June | 162.83 | 23.05 | 273.17 | 24.25 | 12.67 | 26.77 |
July | 103.17 | 23.83 | 353.17 | 24.38 | 25.17 | 26.85 |
August | 111.33 | 23.39 | 344.17 | 24.25 | 16.50 | 26.83 |
September | 198.00 | 22.90 | 218.17 | 24.32 | 10.00 | 26.81 |
October | 280.33 | 22.62 | 152.00 | 24.39 | 7.50 | 26.81 |
November | 379.17 | 22.07 | 88.17 | 23.27 | 23.17 | 20.72 |
December | 430.50 | 21.84 | 63.67 | 21.55 | 44.83 | 20.49 |
Annual Sum or Average | 3432.67 | 22.30 | 2076.17 | 24.02 | 258.33 | 22.86 |
Minimum of Months | 103.17 | 21.76 | 63.67 | 21.55 | 7.50 | 20.38 |
Maximum of Months | 437.67 | 23.83 | 353.17 | 24.41 | 52.33 | 26.85 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.54515 | 34.81806 | 0.46961 | 10.27027 |
February | 454.00000 | 24.49282 | 37.46399 | 0.47071 | 10.18749 |
March | 514.00000 | 24.40322 | 40.50526 | 0.47619 | 10.16277 |
April | 485.00000 | 24.49605 | 44.21632 | 0.52343 | 11.18908 |
May | 508.00000 | 24.45754 | 43.69282 | -0.3521 | 8.40860 |
June | 496.00000 | 24.41523 | 50.61673 | -0.3096 | 7.71279 |
July | 497.00000 | 24.57438 | 57.58862 | -0.2049 | 7.00387 |
August | 514.00000 | 24.44295 | 59.14195 | -0.2258 | 6.95086 |
September | 485.00000 | 24.50870 | 52.51818 | -0.2625 | 7.50319 |
October | 502.00000 | 24.58100 | 42.10065 | 0.53566 | 11.81283 |
November | 489.00000 | 24.58984 | 35.82298 | 0.49431 | 10.93818 |
December | 497.00000 | 24.58146 | 31.01517 | 0.45682 | 10.24206 |
Annual Sum or Average | 5943.00000 | 24.50691 | 44.18848 | 0.16963 | 9.35388 |
Minimum of Months | 454.00000 | 24.40322 | 31.01517 | -0.3521 | 6.95086 |
Maximum of Months | 514.00000 | 24.58984 | 59.14195 | 0.53566 | 11.81283 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.31643 | 36.85862 | 0.43566 | 9.41083 |
February | 454.00000 | 24.27511 | 39.06531 | 0.44657 | 9.48605 |
March | 514.00000 | 24.26357 | 41.91125 | 0.47192 | 9.92203 |
April | 485.00000 | 24.24384 | 45.20634 | 0.50217 | 10.50327 |
May | 508.00000 | 24.21648 | 45.53223 | -0.3935 | 8.62771 |
June | 496.00000 | 24.22683 | 49.66893 | -0.3446 | 7.87494 |
July | 497.00000 | 24.21956 | 50.19920 | -0.3306 | 7.59466 |
August | 514.00000 | 24.17449 | 50.36407 | -0.3329 | 7.52703 |
September | 485.00000 | 24.22548 | 49.60569 | -0.3521 | 8.03399 |
October | 502.00000 | 24.27337 | 41.31992 | 0.47791 | 10.13314 |
November | 489.00000 | 24.35051 | 37.07482 | 0.46471 | 10.01342 |
December | 497.00000 | 24.33976 | 31.91657 | 0.42833 | 9.26676 |
Annual Sum or Average | 5943.00000 | 24.26007 | 43.26130 | 0.11958 | 9.02619 |
Minimum of Months | 454.00000 | 24.17449 | 31.91657 | -0.3935 | 7.52703 |
Maximum of Months | 514.00000 | 24.35051 | 50.36407 | 0.50217 | 10.50327 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.89627 | 40.00222 | 0.32433 | 7.61240 |
February | 454.00000 | 23.86753 | 41.14366 | 0.32612 | 7.52380 |
March | 514.00000 | 23.91131 | 43.83135 | 0.35757 | 7.91867 |
April | 485.00000 | 23.92605 | 46.98908 | 0.39231 | 8.53862 |
May | 508.00000 | 23.95269 | 46.78900 | -0.5115 | 10.91197 |
June | 496.00000 | 23.95775 | 51.05804 | -0.4664 | 9.96830 |
July | 497.00000 | 23.92352 | 51.78407 | -0.4685 | 10.02259 |
August | 514.00000 | 23.93202 | 51.86345 | -0.4584 | 9.76125 |
September | 485.00000 | 23.95183 | 50.86215 | -0.4705 | 10.07676 |
October | 502.00000 | 23.95373 | 42.87450 | 0.38057 | 8.36602 |
November | 489.00000 | 23.98777 | 39.13494 | 0.34958 | 8.03692 |
December | 497.00000 | 23.85636 | 34.21772 | 0.28115 | 7.05655 |
Annual Sum or Average | 5943.00000 | 23.92671 | 45.07854 | -0.0002 | 8.82700 |
Minimum of Months | 454.00000 | 23.85636 | 34.21772 | -0.5115 | 7.05655 |
Maximum of Months | 514.00000 | 23.98777 | 51.86345 | 0.39231 | 10.91197 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.84861 | 42.66618 | 0.05929 | 6.40656 |
February | 454.00000 | 23.01740 | 43.85189 | 0.11403 | 6.38093 |
March | 514.00000 | 23.26225 | 46.01264 | 0.19291 | 6.64331 |
April | 485.00000 | 23.56290 | 48.25503 | 0.30493 | 7.69313 |
May | 508.00000 | 23.63504 | 47.89608 | -0.6204 | 14.20630 |
June | 496.00000 | 23.82199 | 51.54422 | -0.5077 | 10.99339 |
July | 497.00000 | 23.87494 | 51.86884 | -0.4749 | 10.18060 |
August | 514.00000 | 23.86595 | 52.03513 | -0.4733 | 10.13162 |
September | 485.00000 | 23.74237 | 51.76600 | -0.5429 | 11.86455 |
October | 502.00000 | 23.57577 | 44.18130 | 0.28669 | 7.41344 |
November | 489.00000 | 23.25920 | 41.50065 | 0.16459 | 6.70916 |
December | 497.00000 | 22.87065 | 37.09994 | 0.03506 | 6.26154 |
Annual Sum or Average | 5943.00000 | 23.44784 | 46.57940 | -0.1244 | 8.76063 |
Minimum of Months | 454.00000 | 22.84861 | 37.09994 | -0.6204 | 6.26154 |
Maximum of Months | 514.00000 | 23.87494 | 52.03513 | 0.30493 | 14.20630 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.49380 | 37.64123 | 0.19966 | 6.49616 |
February | 454.00000 | 23.57218 | 39.92106 | 0.24103 | 6.65409 |
March | 514.00000 | 23.68817 | 42.67159 | 0.29416 | 7.29996 |
April | 485.00000 | 23.91772 | 45.46426 | 0.39081 | 8.42483 |
May | 508.00000 | 23.89221 | 45.50673 | -0.5335 | 11.51493 |
June | 496.00000 | 24.08147 | 49.25776 | -0.4172 | 8.92664 |
July | 497.00000 | 24.16724 | 49.82014 | -0.3662 | 8.03011 |
August | 514.00000 | 24.07354 | 50.24517 | -0.3933 | 8.41421 |
September | 485.00000 | 23.96504 | 49.80398 | -0.4702 | 10.02855 |
October | 502.00000 | 23.97630 | 41.38565 | 0.37981 | 8.41194 |
November | 489.00000 | 23.78159 | 37.74454 | 0.28601 | 7.18784 |
December | 497.00000 | 23.68716 | 32.46528 | 0.22377 | 6.40483 |
Annual Sum or Average | 5943.00000 | 23.85982 | 43.52384 | -0.0165 | 8.16053 |
Minimum of Months | 454.00000 | 23.49380 | 32.46528 | -0.5335 | 6.40483 |
Maximum of Months | 514.00000 | 24.16724 | 50.24517 | 0.39081 | 11.51493 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.55240 | 36.95626 | 0.24019 | 7.11197 |
February | 454.00000 | 23.47178 | 39.79803 | 0.24404 | 7.08359 |
March | 514.00000 | 23.55699 | 42.64774 | 0.29412 | 7.81386 |
April | 485.00000 | 23.82131 | 45.39576 | 0.41201 | 9.40956 |
May | 508.00000 | 23.92233 | 45.06441 | -0.4700 | 11.30673 |
June | 496.00000 | 23.97382 | 49.26437 | -0.4008 | 9.73966 |
July | 497.00000 | 24.11991 | 49.55313 | -0.3158 | 8.56235 |
August | 514.00000 | 23.96465 | 50.12618 | -0.3610 | 9.03875 |
September | 485.00000 | 23.89518 | 49.56720 | -0.4387 | 10.37395 |
October | 502.00000 | 23.88883 | 41.29957 | 0.39125 | 8.95012 |
November | 489.00000 | 23.66720 | 37.70310 | 0.28401 | 7.42542 |
December | 497.00000 | 23.51526 | 32.45901 | 0.20818 | 6.60688 |
Annual Sum or Average | 5943.00000 | 23.78122 | 43.34852 | 0.00475 | 8.62884 |
Minimum of Months | 454.00000 | 23.47178 | 32.45901 | -0.4700 | 6.60688 |
Maximum of Months | 514.00000 | 24.11991 | 50.12618 | 0.41201 | 11.30673 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.06939 | 35.60576 | 0.41119 | 10.09976 |
February | 454.00000 | 23.86174 | 38.81405 | 0.36075 | 9.06724 |
March | 514.00000 | 23.75050 | 42.05154 | 0.34097 | 8.54261 |
April | 485.00000 | 23.94183 | 45.18739 | 0.41435 | 9.13754 |
May | 508.00000 | 23.75611 | 45.88282 | -0.5791 | 12.92517 |
June | 496.00000 | 23.95418 | 49.71180 | -0.4671 | 9.94877 |
July | 497.00000 | 24.09868 | 50.05111 | -0.3919 | 8.52739 |
August | 514.00000 | 24.09044 | 50.02578 | -0.3668 | 8.18211 |
September | 485.00000 | 24.14042 | 48.86456 | -0.3570 | 8.82766 |
October | 502.00000 | 24.33755 | 40.13954 | 0.52323 | 12.02390 |
November | 489.00000 | 24.27054 | 36.10911 | 0.47430 | 11.01628 |
December | 497.00000 | 24.31656 | 30.69538 | 0.45680 | 10.99020 |
Annual Sum or Average | 5943.00000 | 24.04908 | 42.79700 | 0.06490 | 9.94784 |
Minimum of Months | 454.00000 | 23.75050 | 30.69538 | -0.5791 | 8.18211 |
Maximum of Months | 514.00000 | 24.33755 | 50.05111 | 0.52323 | 12.92517 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.85725 | 35.94883 | 0.33931 | 8.19963 |
February | 454.00000 | 24.16221 | 37.67829 | 0.44839 | 9.88105 |
March | 514.00000 | 24.29512 | 40.19645 | 0.52578 | 11.44043 |
April | 485.00000 | 24.52631 | 43.10158 | 0.66351 | 15.17093 |
May | 508.00000 | 24.24145 | 43.88536 | -0.3063 | 8.56258 |
June | 496.00000 | 24.41311 | 47.63173 | -0.1596 | 6.80562 |
July | 497.00000 | 24.57595 | 47.92845 | -0.0505 | 6.86184 |
August | 514.00000 | 24.45787 | 48.23922 | -0.0550 | 6.56306 |
September | 485.00000 | 24.32476 | 48.00654 | -0.2303 | 7.44442 |
October | 502.00000 | 24.43018 | 39.55569 | 0.56842 | 12.68270 |
November | 489.00000 | 24.43776 | 35.34489 | 0.52600 | 11.61524 |
December | 497.00000 | 24.46582 | 29.99786 | 0.50171 | 11.04016 |
Annual Sum or Average | 5943.00000 | 24.34951 | 41.49162 | 0.22851 | 9.67419 |
Minimum of Months | 454.00000 | 23.85725 | 29.99786 | -0.3063 | 6.56306 |
Maximum of Months | 514.00000 | 24.57595 | 48.23922 | 0.66351 | 15.17093 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.30075 | 40.14109 | -0.0926 | 6.48650 |
February | 454.00000 | 22.38867 | 43.03735 | -0.0482 | 6.07628 |
March | 514.00000 | 22.54634 | 46.03266 | 0.01099 | 6.13154 |
April | 485.00000 | 23.09517 | 48.39296 | 0.17465 | 6.49943 |
May | 508.00000 | 23.32860 | 47.45189 | -0.7432 | 17.85437 |
June | 496.00000 | 23.68111 | 51.12305 | -0.5784 | 12.62026 |
July | 497.00000 | 23.80156 | 52.13508 | -0.5200 | 11.13299 |
August | 514.00000 | 23.67110 | 53.03200 | -0.5601 | 12.15371 |
September | 485.00000 | 23.47894 | 52.08281 | -0.6520 | 14.76028 |
October | 502.00000 | 23.33924 | 43.54611 | 0.21330 | 6.83824 |
November | 489.00000 | 22.66735 | 40.74470 | 0.00840 | 6.14713 |
December | 497.00000 | 22.27220 | 35.38811 | -0.1250 | 6.35464 |
Annual Sum or Average | 5943.00000 | 23.05228 | 46.11908 | -0.2450 | 9.45384 |
Minimum of Months | 454.00000 | 22.27220 | 35.38811 | -0.7432 | 6.07628 |
Maximum of Months | 514.00000 | 23.80156 | 53.03200 | 0.21330 | 17.85437 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.63011 | 38.78017 | 0.00884 | 6.32295 |
February | 385.00000 | 22.59005 | 41.84715 | 0.02341 | 6.35400 |
March | 433.00000 | 22.78441 | 44.11113 | 0.09309 | 6.91037 |
April | 410.00000 | 23.47517 | 46.38958 | 0.30401 | 8.53615 |
May | 430.00000 | 23.53815 | 45.93622 | -0.6236 | 15.82758 |
June | 418.00000 | 23.70325 | 50.20792 | -0.5161 | 12.84933 |
July | 422.00000 | 24.03418 | 50.52031 | -0.3729 | 10.46367 |
August | 433.00000 | 23.86745 | 51.34983 | -0.4196 | 10.95627 |
September | 410.00000 | 23.52791 | 51.01112 | -0.5842 | 14.32030 |
October | 427.00000 | 23.46308 | 42.83379 | 0.27524 | 7.75431 |
November | 417.00000 | 22.90608 | 39.47321 | 0.08983 | 6.32438 |
December | 422.00000 | 22.58482 | 34.05280 | -0.0275 | 6.07787 |
Annual Sum or Average | 5034.00000 | 23.26279 | 44.71968 | -0.1473 | 9.40790 |
Minimum of Months | 385.00000 | 22.58482 | 34.05280 | -0.6236 | 6.07787 |
Maximum of Months | 433.00000 | 24.03418 | 51.34983 | 0.30401 | 15.82758 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.93018 | 35.83539 | 0.37443 | 10.45569 |
February | 454.00000 | 23.50168 | 39.87062 | 0.27046 | 8.83257 |
March | 514.00000 | 23.25957 | 43.56790 | 0.21479 | 7.89762 |
April | 485.00000 | 23.51554 | 46.76378 | 0.29587 | 7.96553 |
May | 508.00000 | 23.36990 | 47.19394 | -0.7226 | 17.44002 |
June | 496.00000 | 23.61023 | 51.31862 | -0.6012 | 13.33470 |
July | 497.00000 | 23.80112 | 52.05558 | -0.5156 | 11.20220 |
August | 514.00000 | 23.84121 | 52.05831 | -0.4758 | 10.50482 |
September | 485.00000 | 23.96800 | 49.86582 | -0.4254 | 10.50956 |
October | 502.00000 | 24.20203 | 40.81563 | 0.48325 | 11.78293 |
November | 489.00000 | 24.04188 | 36.83930 | 0.41154 | 10.61827 |
December | 497.00000 | 24.07946 | 31.22893 | 0.38936 | 10.82717 |
Annual Sum or Average | 5943.00000 | 23.76025 | 43.99002 | -0.0287 | 10.97215 |
Minimum of Months | 454.00000 | 23.25957 | 31.22893 | -0.7226 | 7.89762 |
Maximum of Months | 514.00000 | 24.20203 | 52.05831 | 0.48325 | 17.44002 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.66264 | 38.53994 | 0.02767 | 6.60129 |
February | 454.00000 | 22.77963 | 41.29289 | 0.08322 | 6.72810 |
March | 514.00000 | 22.91387 | 44.17008 | 0.14129 | 7.07008 |
April | 485.00000 | 23.63958 | 46.06356 | 0.36590 | 9.46448 |
May | 508.00000 | 23.65555 | 45.79734 | -0.5534 | 14.15622 |
June | 496.00000 | 23.91674 | 49.72671 | -0.4034 | 10.15261 |
July | 497.00000 | 24.16017 | 50.23559 | -0.2943 | 8.69792 |
August | 514.00000 | 24.02203 | 50.95009 | -0.3346 | 8.97069 |
September | 485.00000 | 23.83990 | 50.12334 | -0.4432 | 11.05311 |
October | 502.00000 | 23.62914 | 42.06209 | 0.33105 | 8.72560 |
November | 489.00000 | 23.07216 | 38.88509 | 0.14619 | 6.96842 |
December | 497.00000 | 22.77470 | 33.57967 | 0.03075 | 6.46117 |
Annual Sum or Average | 5943.00000 | 23.42616 | 44.31299 | -0.0774 | 8.76886 |
Minimum of Months | 454.00000 | 22.66264 | 33.57967 | -0.5534 | 6.46117 |
Maximum of Months | 514.00000 | 24.16017 | 50.95009 | 0.36590 | 14.15622 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.52372 | 41.89623 | -0.2951 | 8.97206 |
February | 454.00000 | 21.69672 | 44.72160 | -0.2256 | 7.76215 |
March | 514.00000 | 21.97221 | 47.49698 | -0.1361 | 7.11174 |
April | 485.00000 | 22.72056 | 49.37464 | 0.08531 | 6.71713 |
May | 508.00000 | 22.96844 | 48.36974 | -0.8627 | 22.98489 |
June | 496.00000 | 23.49612 | 51.63361 | -0.6343 | 14.69842 |
July | 497.00000 | 23.71154 | 52.43350 | -0.5397 | 11.95879 |
August | 514.00000 | 23.56832 | 53.47484 | -0.5860 | 13.22113 |
September | 485.00000 | 23.22334 | 53.00224 | -0.7356 | 17.99346 |
October | 502.00000 | 22.95883 | 44.53761 | 0.12039 | 6.96110 |
November | 489.00000 | 21.96866 | 42.28568 | -0.1680 | 7.33775 |
December | 497.00000 | 21.47000 | 37.03912 | -0.3312 | 9.00167 |
Annual Sum or Average | 5943.00000 | 22.61335 | 47.21073 | -0.3609 | 11.26206 |
Minimum of Months | 454.00000 | 21.47000 | 37.03912 | -0.8627 | 6.71713 |
Maximum of Months | 514.00000 | 23.71154 | 53.47484 | 0.12039 | 22.98489 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.05291 | 40.21884 | -0.1431 | 7.40482 |
February | 454.00000 | 22.16648 | 43.23668 | -0.0907 | 7.10820 |
March | 514.00000 | 22.47130 | 45.61750 | 0.01167 | 7.33563 |
April | 485.00000 | 23.29972 | 47.09135 | 0.26814 | 8.52990 |
May | 508.00000 | 23.33765 | 46.73264 | -0.6823 | 17.94250 |
June | 496.00000 | 23.63167 | 50.53066 | -0.5234 | 13.26567 |
July | 497.00000 | 24.00427 | 50.61918 | -0.3586 | 10.09120 |
August | 514.00000 | 23.85237 | 51.44868 | -0.4021 | 10.58135 |
September | 485.00000 | 23.42017 | 51.57686 | -0.6090 | 15.46864 |
October | 502.00000 | 23.26104 | 43.33236 | 0.22735 | 7.58939 |
November | 489.00000 | 22.44466 | 40.76239 | -0.0295 | 6.58255 |
December | 497.00000 | 21.97749 | 35.64265 | -0.1842 | 7.18973 |
Annual Sum or Average | 5943.00000 | 22.99948 | 45.58751 | -0.2112 | 9.94529 |
Minimum of Months | 454.00000 | 21.97749 | 35.64265 | -0.6823 | 6.58255 |
Maximum of Months | 514.00000 | 24.00427 | 51.57686 | 0.26814 | 17.94250 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.27180 | 37.38002 | 0.19703 | 9.50266 |
February | 454.00000 | 22.92482 | 41.40214 | 0.11679 | 8.67552 |
March | 514.00000 | 22.75349 | 44.95833 | 0.08220 | 8.10234 |
April | 485.00000 | 23.16749 | 47.73428 | 0.21225 | 7.91695 |
May | 508.00000 | 23.02157 | 48.10778 | -0.8387 | 22.38238 |
June | 496.00000 | 23.42986 | 51.81889 | -0.6559 | 15.47456 |
July | 497.00000 | 23.71115 | 52.36370 | -0.5353 | 12.06397 |
August | 514.00000 | 23.73190 | 52.55652 | -0.5035 | 11.57466 |
September | 485.00000 | 23.74533 | 50.71659 | -0.5002 | 12.98101 |
October | 502.00000 | 23.87053 | 41.71384 | 0.39980 | 10.91289 |
November | 489.00000 | 23.51994 | 38.09334 | 0.27125 | 9.46533 |
December | 497.00000 | 23.44181 | 32.56245 | 0.21673 | 9.50761 |
Annual Sum or Average | 5943.00000 | 23.38415 | 44.98567 | -0.1314 | 11.58203 |
Minimum of Months | 454.00000 | 22.75349 | 32.56245 | -0.8387 | 7.91695 |
Maximum of Months | 514.00000 | 23.87053 | 52.55652 | 0.39980 | 22.38238 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.03234 | 39.94568 | -0.1362 | 7.82052 |
February | 454.00000 | 22.20933 | 42.66119 | -0.0623 | 7.40777 |
March | 514.00000 | 22.39795 | 45.47587 | 0.01224 | 7.41494 |
April | 485.00000 | 23.26993 | 47.02376 | 0.28045 | 9.14594 |
May | 508.00000 | 23.30059 | 46.67416 | -0.6675 | 18.53896 |
June | 496.00000 | 23.69457 | 50.33315 | -0.4683 | 12.28262 |
July | 497.00000 | 24.01411 | 50.70095 | -0.3292 | 9.73359 |
August | 514.00000 | 23.86531 | 51.52642 | -0.3751 | 10.18480 |
September | 485.00000 | 23.57386 | 51.00648 | -0.5273 | 13.83625 |
October | 502.00000 | 23.25571 | 42.94094 | 0.24251 | 8.41453 |
November | 489.00000 | 22.50838 | 40.12210 | 0.00364 | 7.31187 |
December | 497.00000 | 22.11475 | 34.92109 | -0.1383 | 7.52738 |
Annual Sum or Average | 5943.00000 | 23.02508 | 45.30215 | -0.1823 | 9.98989 |
Minimum of Months | 454.00000 | 22.03234 | 34.92109 | -0.6675 | 7.31187 |
Maximum of Months | 514.00000 | 24.01411 | 51.52642 | 0.28045 | 18.53896 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.403504E+11 | 133548.79 | 17-JAN-13:30 | 281.74 | 0.246427E+12 | 0.00 | 0.286778E+12 | 1.92 | 7.51 | 24-JAN-13:30 | 0.00 | 0.00 |
February | 0.276531E+11 | 142073.47 | 01-FEB-12:10 | 227.11 | 0.155403E+12 | 0.00 | 0.183056E+12 | 1.59 | 7.37 | 01-FEB-09:20 | 0.00 | 0.00 |
March | 0.300230E+11 | 148502.94 | 23-MAR-12:30 | 234.15 | 0.175115E+12 | 0.00 | 0.205138E+12 | 1.49 | 7.49 | 22-MAR-15:30 | 0.00 | 0.00 |
April | 0.554709E+11 | 151821.45 | 26-APR-12:20 | 339.64 | 0.352013E+12 | 0.00 | 0.407483E+12 | 2.55 | 7.53 | 26-APR-16:50 | 0.00 | 0.00 |
May | 0.586361E+11 | 150454.03 | 04-MAY-12:40 | 379.33 | 0.361094E+12 | 0.00 | 0.419730E+12 | 2.74 | 7.51 | 02-MAY-13:00 | 0.00 | 0.00 |
June | 0.925008E+11 | 151730.18 | 27-JUN-09:10 | 446.20 | 0.600102E+12 | 0.00 | 0.692603E+12 | 3.62 | 7.55 | 19-JUN-08:40 | 0.00 | 0.00 |
July | 0.136773E+12 | 156728.20 | 14-JUL-16:10 | 523.90 | 0.905832E+12 | 0.00 | 0.104261E+13 | 4.26 | 7.55 | 11-JUL-11:50 | 0.00 | 0.00 |
August | 0.148960E+12 | 157922.68 | 09-AUG-16:20 | 570.78 | 0.981763E+12 | 0.00 | 0.113072E+13 | 4.57 | 7.52 | 18-AUG-04:13 | 0.00 | 0.00 |
September | 0.101687E+12 | 152162.56 | 13-SEP-09:00 | 438.48 | 0.672706E+12 | 0.00 | 0.774392E+12 | 3.65 | 7.54 | 11-SEP-16:10 | 0.00 | 0.00 |
October | 0.105937E+12 | 154120.01 | 01-OCT-13:00 | 441.90 | 0.701049E+12 | 0.00 | 0.806986E+12 | 3.58 | 7.55 | 03-OCT-04:12 | 0.00 | 0.00 |
November | 0.457834E+11 | 134014.18 | 28-NOV-13:40 | 302.80 | 0.279526E+12 | 0.00 | 0.325309E+12 | 2.18 | 7.46 | 10-NOV-12:30 | 0.00 | 0.00 |
December | 0.470748E+11 | 141193.36 | 05-DEC-15:50 | 285.15 | 0.299432E+12 | 0.00 | 0.346507E+12 | 2.02 | 7.37 | 20-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.890849E+12 | 4471.18 | 0.573046E+13 | 0.662131E+13 | 2.86 | |||||||
Minimum of Months | 0.276531E+11 | 133548.79 | 227.11 | 0.155403E+12 | 0.00 | 0.183056E+12 | 1.49 | 7.37 | 0.00 | 0.00 | ||
Maximum of Months | 0.148960E+12 | 157922.68 | 570.78 | 0.981763E+12 | 0.00 | 0.113072E+13 | 4.57 | 7.55 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.106992E+10 | 89165.21 | 23-MAR-14:10 | 4.17 | 0.753747E+10 | 0.00 | 0.860738E+10 | 0.04 | 7.36 | 22-MAR-12:20 | 0.00 | 0.00 |
April | 0.209780E+10 | 87069.33 | 26-APR-13:00 | 8.50 | 0.148516E+11 | 0.00 | 0.169494E+11 | 0.08 | 7.36 | 26-APR-16:00 | 0.00 | 0.00 |
May | 0.157459E+09 | 84343.42 | 04-MAY-13:40 | 1.17 | 0.107958E+10 | 0.00 | 0.123704E+10 | 0.01 | 7.37 | 04-MAY-14:00 | 0.00 | 0.00 |
June | 0.139270E+11 | 106949.25 | 29-JUN-13:00 | 47.00 | 0.945374E+11 | 0.00 | 0.108464E+12 | 0.44 | 7.37 | 19-JUN-15:20 | 0.00 | 0.00 |
July | 0.424956E+11 | 148019.40 | 31-JUL-16:00 | 128.81 | 0.276078E+12 | 0.00 | 0.318574E+12 | 1.12 | 7.36 | 07-JUL-14:10 | 0.00 | 0.00 |
August | 0.578089E+11 | 155300.60 | 18-AUG-16:00 | 172.25 | 0.375698E+12 | 0.00 | 0.433507E+12 | 1.50 | 7.35 | 21-AUG-14:10 | 0.00 | 0.00 |
September | 0.219194E+11 | 124075.60 | 22-SEP-12:30 | 72.00 | 0.148082E+12 | 0.00 | 0.170001E+12 | 0.67 | 7.37 | 11-SEP-15:40 | 0.00 | 0.00 |
October | 0.246587E+11 | 134985.33 | 03-OCT-13:40 | 79.33 | 0.164825E+12 | 0.00 | 0.189484E+12 | 0.71 | 7.37 | 30-OCT-14:10 | 0.00 | 0.00 |
November | 0.108210E+09 | 76551.64 | 28-NOV-14:10 | 0.50 | 0.743944E+09 | 0.00 | 0.852153E+09 | 0.00 | 7.35 | 28-NOV-14:10 | 0.00 | 0.00 |
December | 0.274329E+09 | 85876.49 | 19-DEC-13:15 | 1.08 | 0.196793E+10 | 0.00 | 0.224226E+10 | 0.01 | 7.37 | 05-DEC-15:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.164517E+12 | 514.81 | 0.108540E+13 | 0.124992E+13 | 0.39 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.578089E+11 | 155300.60 | 172.25 | 0.375698E+12 | 0.00 | 0.433507E+12 | 1.50 | 7.37 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.300448E+11 | 744.00 | 49248.27 | 03-JAN-12:10 | 188348.19 | 15-JAN-16:03 | 20.05 | 18.78 | 13.74 |
February | 0.323808E+11 | 672.00 | 49248.27 | 01-FEB-08:00 | 327696.11 | 12-FEB-14:30 | 21.00 | 18.52 | 13.74 |
March | 0.450417E+11 | 744.00 | 49248.27 | 01-MAR-10:10 | 446846.99 | 05-MAR-17:20 | 22.55 | 18.74 | 13.74 |
April | 0.960263E+11 | 720.00 | 49248.27 | 01-APR-08:20 | 643188.71 | 26-APR-11:10 | 27.94 | 20.05 | 13.74 |
May | 0.440032E+11 | 744.00 | 49248.27 | 01-MAY-09:40 | 191330.11 | 01-MAY-00:20 | 19.57 | 18.82 | 13.74 |
June | 0.694473E+11 | 720.00 | 49248.27 | 01-JUN-08:40 | 366214.12 | 29-JUN-11:00 | 21.91 | 19.82 | 13.74 |
July | 0.122862E+12 | 744.00 | 49248.27 | 01-JUL-02:50 | 647068.13 | 31-JUL-14:20 | 28.69 | 22.21 | 13.74 |
August | 0.131225E+12 | 744.00 | 49248.27 | 01-AUG-00:10 | 680719.99 | 18-AUG-12:10 | 35.72 | 24.25 | 13.74 |
September | 0.670964E+11 | 720.00 | 49248.27 | 01-SEP-08:40 | 246209.33 | 22-SEP-12:00 | 20.87 | 19.95 | 13.74 |
October | 0.930489E+11 | 744.00 | 49248.27 | 01-OCT-00:10 | 450065.88 | 01-OCT-12:00 | 24.54 | 21.22 | 13.74 |
November | 0.603686E+11 | 720.00 | 49248.27 | 01-NOV-11:10 | 487384.44 | 19-NOV-13:02 | 23.05 | 19.09 | 13.74 |
December | 0.777767E+11 | 744.00 | 49248.27 | 01-DEC-14:00 | 589098.18 | 26-DEC-01:05 | 26.28 | 19.61 | 13.74 |
Annual Sum or Average | 0.869321E+12 | 8760.00 | 24.39 | 20.11 | 13.74 | ||||
Minimum of Months | 0.300448E+11 | 672.00 | 49248.27 | 188348.19 | 19.57 | 18.52 | 13.74 | ||
Maximum of Months | 0.131225E+12 | 744.00 | 49248.27 | 680719.99 | 35.72 | 24.25 | 13.74 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.154596E+10 | 209.95 | 14940.04 | 13-JAN-12:40 | 963374.10 | 18-JAN-12:00 | 21.81 | 21.19 | 13.76 |
February | 0.510315E+09 | 164.21 | 14940.04 | 01-FEB-11:10 | 992608.04 | 03-FEB-15:00 | 21.54 | 21.10 | 12.32 |
March | 0.123698E+10 | 166.71 | 14940.04 | 22-MAR-10:30 | 873855.21 | 10-MAR-15:30 | 21.55 | 21.10 | 11.10 |
April | 0.329316E+10 | 273.13 | 14940.04 | 04-APR-10:40 | 790215.26 | 13-APR-10:40 | 22.03 | 21.14 | 18.17 |
May | 0.249933E+10 | 322.62 | 14940.04 | 02-MAY-10:50 | 855772.57 | 03-MAY-12:30 | 22.12 | 21.22 | 20.12 |
June | 0.852082E+10 | 413.62 | 14940.04 | 01-JUN-09:50 | 810621.50 | 29-JUN-13:00 | 23.00 | 21.51 | 25.19 |
July | 0.173391E+11 | 496.65 | 14940.04 | 01-JUL-07:30 | 1032006.01 | 31-JUL-16:00 | 24.25 | 22.15 | 28.19 |
August | 0.200724E+11 | 545.09 | 14940.04 | 01-AUG-09:10 | 1072114.01 | 18-AUG-16:00 | 24.47 | 22.16 | 30.76 |
September | 0.109567E+11 | 412.19 | 14940.04 | 01-SEP-10:20 | 892799.78 | 22-SEP-12:40 | 23.61 | 21.98 | 24.38 |
October | 0.929126E+10 | 411.52 | 14940.04 | 01-OCT-08:42 | 993751.08 | 25-OCT-11:00 | 23.51 | 21.86 | 23.85 |
November | 0.108150E+10 | 242.05 | 14940.04 | 10-NOV-11:00 | 974770.93 | 29-NOV-12:00 | 21.88 | 21.15 | 16.22 |
December | 0.705535E+09 | 216.99 | 14940.04 | 04-DEC-14:00 | 993490.21 | 18-DEC-14:30 | 21.86 | 21.11 | 14.00 |
Annual Sum or Average | 0.770530E+11 | 3874.73 | 22.65 | 21.48 | 19.89 | ||||
Minimum of Months | 0.510315E+09 | 164.21 | 14940.04 | 790215.26 | 21.54 | 21.10 | 11.10 | ||
Maximum of Months | 0.200724E+11 | 545.09 | 14940.04 | 1072114.01 | 24.47 | 22.16 | 30.76 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 57124474.69 | 2.17 | 14940.04 | 17-JAN-12:20 | 673258.37 | 17-JAN-13:50 | 21.81 | 21.79 | 0.08 |
February | 7023148.99 | 1.00 | 2834.81 | 01-FEB-13:10 | 643192.05 | 01-FEB-11:40 | 21.54 | 21.54 | 0.04 |
March | 0.332299E+09 | 7.50 | 14940.04 | 22-MAR-12:10 | 684982.64 | 23-MAR-11:00 | 21.55 | 21.50 | 0.36 |
April | 0.737859E+09 | 16.00 | 14940.04 | 04-APR-12:00 | 685233.37 | 26-APR-15:20 | 22.03 | 21.92 | 0.77 |
May | 0.118773E+09 | 4.33 | 14940.04 | 03-MAY-14:00 | 669616.57 | 04-MAY-13:40 | 22.12 | 22.09 | 0.17 |
June | 0.353154E+10 | 68.33 | 14940.04 | 14-JUN-09:40 | 810621.50 | 29-JUN-13:00 | 23.00 | 22.59 | 3.56 |
July | 0.996341E+10 | 187.88 | 14940.04 | 01-JUL-08:30 | 1032006.01 | 31-JUL-16:00 | 24.25 | 23.14 | 9.42 |
August | 0.128259E+11 | 240.60 | 14940.04 | 01-AUG-10:00 | 1072114.01 | 18-AUG-16:00 | 24.47 | 23.05 | 12.24 |
September | 0.545086E+10 | 104.49 | 14940.04 | 05-SEP-12:10 | 892799.78 | 22-SEP-12:40 | 23.61 | 22.99 | 5.45 |
October | 0.486396E+10 | 108.17 | 14940.04 | 01-OCT-10:58 | 976073.72 | 03-OCT-13:40 | 23.51 | 22.89 | 5.55 |
November | 5672487.34 | 0.83 | 3090.44 | 10-NOV-13:00 | 630146.70 | 28-NOV-14:10 | 21.88 | 21.88 | 0.04 |
December | 33354030.88 | 4.42 | 3015.48 | 05-DEC-10:40 | 716337.76 | 19-DEC-13:15 | 21.86 | 21.83 | 0.18 |
Annual Sum or Average | 0.379278E+11 | 745.73 | 22.65 | 22.27 | 3.19 | ||||
Minimum of Months | 5672487.34 | 0.83 | 2834.81 | 630146.70 | 21.54 | 21.50 | 0.04 | ||
Maximum of Months | 0.128259E+11 | 240.60 | 14940.04 | 1072114.01 | 24.47 | 23.14 | 12.24 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.987118E+10 | 0.00 | 134.60 | 1319183.92 | 12-JAN-06:20 | 0.00 | 59.75 | 64.37 | 0.04 | 0.00 | 0.00 | 1.06 | 12-JAN-06:20 |
February | 0.327415E+10 | 0.00 | 100.85 | 1498698.88 | 10-FEB-05:15 | 0.00 | 55.27 | 59.04 | 0.02 | 0.00 | 0.00 | 1.20 | 10-FEB-05:15 |
March | 0.512719E+10 | 0.00 | 98.91 | 1023997.74 | 30-MAR-05:02 | 0.00 | 49.59 | 53.80 | 0.02 | 0.00 | 0.00 | 0.82 | 30-MAR-05:02 |
April | 0.120904E+10 | 0.00 | 29.43 | 742208.66 | 03-APR-03:37 | 0.00 | 61.73 | 62.68 | 0.01 | 0.00 | 0.00 | 0.59 | 03-APR-03:37 |
May | 0.683825E+09 | 0.00 | 17.04 | 935082.45 | 15-MAY-04:12 | 0.00 | 71.61 | 71.85 | 0.01 | 0.00 | 0.00 | 0.75 | 15-MAY-04:12 |
June | 0.123607E+09 | 0.00 | 0.65 | 225078.24 | 08-JUN-03:05 | 0.00 | 72.42 | 72.42 | 0.00 | 0.00 | 0.00 | 0.18 | 08-JUN-03:05 |
July | 0.697198E+09 | 0.00 | 0.87 | 224122.42 | 03-JUL-03:47 | 0.00 | 72.47 | 72.48 | 0.01 | 0.00 | 0.00 | 0.18 | 03-JUL-03:47 |
August | 0.484800E+09 | 0.00 | 0.61 | 221533.52 | 06-AUG-18:30 | 0.00 | 72.59 | 72.60 | 0.00 | 0.00 | 0.00 | 0.18 | 06-AUG-18:30 |
September | 0.379161E+09 | 0.00 | 3.62 | 225854.94 | 30-SEP-03:50 | 0.00 | 72.45 | 72.50 | 0.00 | 0.00 | 0.00 | 0.18 | 30-SEP-03:50 |
October | 0.111755E+10 | 0.00 | 21.13 | 756671.92 | 18-OCT-03:02 | 0.00 | 73.22 | 73.46 | 0.01 | 0.00 | 0.00 | 0.61 | 18-OCT-03:02 |
November | 0.135545E+10 | 0.00 | 66.30 | 1452333.07 | 22-NOV-04:03 | 0.00 | 67.11 | 68.60 | 0.01 | 0.00 | 0.00 | 1.16 | 22-NOV-04:03 |
December | 0.485412E+10 | 0.00 | 118.37 | 1498698.88 | 11-DEC-02:12 | 0.00 | 51.70 | 56.46 | 0.02 | 0.00 | 0.00 | 1.20 | 11-DEC-02:12 |
Annual Sum or Average | 0.291773E+11 | 592.39 | 65.03 | 66.73 | 0.01 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.123607E+09 | 0.00 | 0.61 | 221533.52 | 0.00 | 49.59 | 53.80 | 0.00 | 0.00 | 0.00 | 0.18 | ||
Maximum of Months | 0.987118E+10 | 0.00 | 134.60 | 1498698.88 | 0.00 | 73.22 | 73.46 | 0.04 | 0.00 | 0.00 | 1.20 |
Report: BoilerReportMonthly
For: DUMMY BOILER
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 20.05 | 20.05 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 21.00 | 21.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 22.55 | 22.55 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 27.94 | 27.94 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 19.57 | 19.57 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 21.91 | 21.91 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 28.69 | 28.69 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 35.72 | 35.72 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 20.87 | 20.87 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 24.54 | 24.54 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 23.05 | 23.05 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 26.28 | 26.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 24.39 | 24.39 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.57 | 19.57 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.72 | 35.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.121068E+11 | 0.00 | 153.61 | 0.119468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85421.96 | 16-JAN-14:51 | 66751.05 | 17-JAN-12:00 | 0.00 | 0.00 | 0.00 |
February | 0.545688E+10 | 0.00 | 95.77 | 0.536838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74937.05 | 13-FEB-05:51 | 54972.78 | 20-FEB-13:51 | 0.00 | 0.00 | 0.00 |
March | 0.604915E+10 | 0.00 | 96.84 | 0.595727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55700.47 | 24-MAR-03:01 | 45789.96 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.158068E+11 | 0.00 | 193.72 | 0.155584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82966.32 | 30-APR-23:10 | 57626.75 | 26-APR-13:10 | 0.00 | 0.00 | 0.00 |
May | 0.151443E+11 | 0.00 | 209.41 | 0.149517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82478.99 | 29-MAY-14:30 | 63108.86 | 29-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.268395E+11 | 0.00 | 274.64 | 0.260177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95330.86 | 28-JUN-03:01 | 61896.31 | 26-JUN-10:00 | 0.00 | 0.00 | 0.00 |
July | 0.454068E+11 | 0.00 | 330.00 | 0.400346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105748.74 | 28-JUL-03:01 | 67393.85 | 31-JUL-12:10 | 0.00 | 0.00 | 0.00 |
August | 0.518765E+11 | 0.00 | 363.78 | 0.442754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120428.16 | 06-AUG-18:30 | 69538.83 | 14-AUG-11:00 | 0.00 | 0.00 | 0.00 |
September | 0.315283E+11 | 0.00 | 278.60 | 0.289108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105745.06 | 22-SEP-04:51 | 101156.82 | 30-SEP-03:01 | 0.00 | 0.00 | 0.00 |
October | 0.419918E+11 | 0.00 | 308.30 | 0.374177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124194.05 | 05-OCT-03:01 | 123487.35 | 15-OCT-15:19 | 0.00 | 0.00 | 0.00 |
November | 0.133721E+11 | 0.00 | 176.00 | 0.131940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83975.06 | 12-NOV-00:01 | 58405.59 | 27-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 0.163690E+11 | 0.00 | 161.16 | 0.163397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93595.60 | 25-DEC-11:51 | 93595.60 | 25-DEC-11:51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281948E+12 | 2641.85 | 0.259972E+12 | ||||||||||||
Minimum of Months | 0.545688E+10 | 0.00 | 95.77 | 0.536838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55700.47 | 45789.96 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.518765E+11 | 0.00 | 363.78 | 0.442754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124194.05 | 123487.35 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.233312E+11 | 0.00 | 244.27 | 0.231267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83762.90 | 18-JAN-13:50 | 83762.90 | 18-JAN-13:50 | 0.00 | 0.00 | 0.00 |
February | 0.156099E+11 | 0.00 | 202.32 | 0.150503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80554.46 | 01-FEB-12:00 | 80554.46 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.186911E+11 | 0.00 | 208.56 | 0.173055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103896.26 | 23-MAR-15:00 | 77218.95 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.384943E+11 | 0.00 | 313.17 | 0.360596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103840.41 | 26-APR-11:00 | 95428.95 | 26-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.342926E+11 | 0.00 | 354.79 | 0.335002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76516.27 | 04-MAY-13:50 | 71147.45 | 03-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.648715E+11 | 0.00 | 431.36 | 0.517851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125329.81 | 29-JUN-13:00 | 77950.40 | 26-JUN-10:00 | 0.00 | 0.00 | 0.00 |
July | 0.115272E+12 | 0.00 | 505.73 | 0.735293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 169012.37 | 31-JUL-15:40 | 96061.86 | 31-JUL-14:00 | 0.00 | 0.00 | 0.00 |
August | 0.141050E+12 | 0.00 | 558.96 | 0.844230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 173657.76 | 18-AUG-15:50 | 100170.49 | 17-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.732311E+11 | 0.00 | 418.32 | 0.530012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 142178.71 | 22-SEP-11:40 | 116270.07 | 30-SEP-03:01 | 0.00 | 0.00 | 0.00 |
October | 0.810878E+11 | 0.00 | 420.94 | 0.649061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 188362.51 | 05-OCT-04:11 | 123824.50 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 0.290306E+11 | 0.00 | 279.02 | 0.282493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90795.89 | 28-NOV-14:00 | 90795.89 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.312344E+11 | 0.00 | 257.17 | 0.311690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97195.85 | 05-DEC-15:00 | 97195.85 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.666196E+12 | 4194.61 | 0.512105E+12 | ||||||||||||
Minimum of Months | 0.156099E+11 | 0.00 | 202.32 | 0.150503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76516.27 | 71147.45 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.141050E+12 | 0.00 | 558.96 | 0.844230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 188362.51 | 123824.50 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.189321E+12 | 0.00 | 266.79 | 0.187976E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 675302.12 | 18-JAN-14:00 | 675302.12 | 18-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.120341E+12 | 0.00 | 215.39 | 0.116266E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 646570.18 | 01-FEB-12:00 | 646570.18 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.138602E+12 | 0.00 | 214.69 | 0.128359E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 849977.00 | 23-MAR-15:00 | 621299.46 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.271207E+12 | 0.00 | 303.14 | 0.255940E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 807866.36 | 26-APR-11:00 | 747096.21 | 26-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.278519E+12 | 0.00 | 358.04 | 0.272091E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 664799.02 | 04-MAY-14:00 | 610754.50 | 03-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.517198E+12 | 0.00 | 413.69 | 0.414943E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1051566.23 | 29-JUN-13:00 | 638407.52 | 29-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.872444E+12 | 0.00 | 438.06 | 0.560464E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1344285.93 | 31-JUL-15:50 | 800617.55 | 19-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.100669E+13 | 0.00 | 456.14 | 0.615006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1418285.81 | 18-AUG-15:50 | 820943.84 | 18-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.618168E+12 | 0.00 | 408.52 | 0.449651E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1194556.83 | 22-SEP-12:30 | 1153140.48 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 |
October | 0.652647E+12 | 0.00 | 403.96 | 0.525284E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1392966.25 | 05-OCT-04:11 | 1039845.00 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 0.212543E+12 | 0.00 | 279.49 | 0.207336E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 657756.77 | 28-NOV-14:10 | 657756.77 | 28-NOV-14:10 | 0.00 | 0.00 | 0.00 |
December | 0.221693E+12 | 0.00 | 262.32 | 0.221411E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 707162.92 | 05-DEC-15:00 | 707162.92 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.509937E+13 | 4020.24 | 0.395473E+13 | ||||||||||||
Minimum of Months | 0.120341E+12 | 0.00 | 214.69 | 0.116266E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 646570.18 | 610754.50 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.100669E+13 | 0.00 | 456.14 | 0.615006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1418285.81 | 1153140.48 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.164824E+11 | 0.00 | 228.67 | 0.163800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62113.72 | 18-JAN-13:20 | 62113.72 | 18-JAN-13:20 | 0.00 | 0.00 | 0.00 |
February | 0.106349E+11 | 0.00 | 188.75 | 0.102462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60191.22 | 03-FEB-15:00 | 60191.22 | 03-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.126544E+11 | 0.00 | 183.46 | 0.116293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89953.38 | 23-MAR-15:00 | 65212.17 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.270165E+11 | 0.00 | 279.96 | 0.254276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96513.94 | 26-APR-14:00 | 90491.95 | 26-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.277870E+11 | 0.00 | 336.14 | 0.271186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77388.95 | 03-MAY-14:00 | 70652.61 | 03-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.540263E+11 | 0.00 | 403.58 | 0.430272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120377.58 | 29-JUN-13:00 | 72300.34 | 29-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.930951E+11 | 0.00 | 431.35 | 0.596283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 166146.30 | 19-JUL-15:40 | 98780.19 | 19-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.107182E+12 | 0.00 | 445.28 | 0.647752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 169655.76 | 17-AUG-15:40 | 98380.08 | 17-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.616377E+11 | 0.00 | 388.74 | 0.448197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 127854.84 | 22-SEP-12:20 | 122623.24 | 29-SEP-13:50 | 0.00 | 0.00 | 0.00 |
October | 0.637254E+11 | 0.00 | 388.58 | 0.509907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 154690.91 | 05-OCT-05:02 | 120478.47 | 16-OCT-13:10 | 0.00 | 0.00 | 0.00 |
November | 0.184394E+11 | 0.00 | 254.25 | 0.179780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60774.74 | 28-NOV-14:00 | 60774.74 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.195179E+11 | 0.00 | 233.18 | 0.194942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69591.61 | 05-DEC-15:00 | 69591.61 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.512199E+12 | 3761.93 | 0.391515E+12 | ||||||||||||
Minimum of Months | 0.106349E+11 | 0.00 | 183.46 | 0.102462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60191.22 | 60191.22 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.107182E+12 | 0.00 | 445.28 | 0.647752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 169655.76 | 122623.24 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.821528E+11 | 0.269793E+11 | 467.77 | 0.820024E+11 | 0.150425E+09 | 0.00 | 0.79 | 07-JAN-15:00 | 0.00 | 09-JAN-18:00 | 135050.40 | 17-JAN-02:70 | 124083.51 | 15-JAN-15:37 | 15499.09 | 17-JAN-02:70 | 70980.64 | 07-JAN-16:00 | 0.00 |
February | 0.135071E+12 | 0.432693E+11 | 418.86 | 0.134386E+12 | 0.684094E+09 | 0.00 | 0.65 | 28-FEB-07:30 | 0.00 | 09-FEB-17:20 | 271307.29 | 12-FEB-14:10 | 211657.13 | 07-FEB-05:23 | 69319.06 | 11-FEB-14:10 | 63143.12 | 01-FEB-12:00 | 0.00 |
March | 0.228778E+12 | 0.729771E+11 | 493.57 | 0.214901E+12 | 0.138777E+11 | 0.00 | 0.79 | 19-MAR-08:27 | 0.01 | 15-MAR-04:55 | 331738.55 | 19-MAR-08:27 | 295271.31 | 08-MAR-22:03 | 88937.45 | 23-MAR-16:00 | 77998.77 | 23-MAR-14:00 | 0.00 |
April | 0.565517E+12 | 0.147554E+12 | 692.32 | 0.476919E+12 | 0.885986E+11 | 0.00 | 1.00 | 26-APR-10:20 | 0.01 | 16-APR-23:33 | 417003.10 | 11-APR-21:40 | 383573.29 | 28-APR-21:40 | 136889.67 | 30-APR-21:53 | 124645.69 | 26-APR-13:00 | 0.00 |
May | 0.168852E+11 | 0.117390E+11 | 213.47 | 0.164257E+11 | 0.459508E+09 | 0.00 | 0.72 | 23-MAY-06:10 | 0.00 | 01-MAY-03:02 | 147365.17 | 01-MAY-00:20 | 131940.35 | 01-MAY-00:20 | 22459.68 | 05-MAY-00:10 | 70531.72 | 18-MAY-15:20 | 0.00 |
June | 0.910115E+11 | 0.444198E+11 | 321.53 | 0.671037E+11 | 0.239077E+11 | 0.00 | 0.62 | 18-JUN-18:13 | 0.01 | 20-JUN-18:10 | 245784.94 | 14-JUN-24:00 | 206690.62 | 13-JUN-04:10 | 81534.71 | 29-JUN-11:10 | 70302.59 | 29-JUN-11:00 | 0.00 |
July | 0.482460E+12 | 0.133185E+12 | 727.83 | 0.289545E+12 | 0.192915E+12 | 0.00 | 1.00 | 18-JUL-11:10 | 0.01 | 09-JUL-00:30 | 422584.12 | 31-JUL-13:55 | 298475.53 | 31-JUL-11:40 | 165007.45 | 28-JUL-16:00 | 126902.73 | 31-JUL-11:30 | 0.00 |
August | 0.932016E+12 | 0.246975E+12 | 744.00 | 0.512373E+12 | 0.419643E+12 | 0.00 | 1.00 | 02-AUG-09:00 | 0.37 | 28-AUG-06:00 | 422438.88 | 07-AUG-07:15 | 347640.77 | 29-AUG-13:00 | 258404.29 | 18-AUG-07:00 | 128791.51 | 18-AUG-12:00 | 0.00 |
September | 0.304107E+11 | 0.245110E+11 | 170.69 | 0.270109E+11 | 0.339979E+10 | 0.00 | 0.59 | 01-SEP-00:10 | 0.00 | 01-SEP-22:10 | 190926.93 | 22-SEP-01:10 | 124781.90 | 29-SEP-13:00 | 82436.32 | 22-SEP-12:00 | 55761.34 | 29-SEP-13:00 | 0.00 |
October | 0.222204E+12 | 0.793668E+11 | 563.24 | 0.193288E+12 | 0.289154E+11 | 0.00 | 0.73 | 01-OCT-12:00 | 0.00 | 25-OCT-18:50 | 313018.31 | 01-OCT-03:40 | 214802.14 | 13-OCT-14:00 | 122140.77 | 01-OCT-11:52 | 95553.80 | 16-OCT-11:00 | 0.00 |
November | 0.234070E+12 | 0.746076E+11 | 558.21 | 0.220517E+12 | 0.135530E+11 | 0.00 | 0.85 | 19-NOV-13:00 | 0.01 | 05-NOV-22:24 | 369794.58 | 12-NOV-05:10 | 299157.66 | 19-NOV-13:00 | 74797.22 | 12-NOV-05:10 | 102649.35 | 19-NOV-13:00 | 0.00 |
December | 0.461455E+12 | 0.123850E+12 | 703.87 | 0.438880E+12 | 0.225743E+11 | 0.00 | 1.00 | 04-DEC-10:00 | 0.00 | 21-DEC-20:20 | 395567.33 | 26-DEC-04:50 | 395567.33 | 26-DEC-04:50 | 94602.70 | 07-DEC-16:00 | 120474.78 | 16-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.348203E+13 | 0.102943E+13 | 6075.35 | 0.267335E+13 | 0.808679E+12 | ||||||||||||||
Minimum of Months | 0.168852E+11 | 0.117390E+11 | 170.69 | 0.164257E+11 | 0.150425E+09 | 0.00 | 0.59 | 0.00 | 135050.40 | 124083.51 | 15499.09 | 55761.34 | 0.00 | ||||||
Maximum of Months | 0.932016E+12 | 0.246975E+12 | 744.00 | 0.512373E+12 | 0.419643E+12 | 0.00 | 1.00 | 0.37 | 422584.12 | 395567.33 | 258404.29 | 128791.51 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.510533E+10 | 0.128642E+10 | 744.00 | 0.510533E+10 | 0.00 | 0.00 | 0.32 | 30-JAN-16:50 | 0.21 | 09-JAN-07:40 | 2407.74 | 30-JAN-16:50 | 2407.74 | 30-JAN-16:50 | 0.00 | 01-JAN-00:05 | 686.29 | 18-JAN-13:00 | 0.00 |
February | 0.914152E+10 | 0.215304E+10 | 672.00 | 0.914152E+10 | 0.00 | 0.00 | 0.55 | 20-FEB-17:00 | 0.44 | 25-FEB-18:20 | 4388.28 | 20-FEB-17:00 | 4388.28 | 20-FEB-17:00 | 0.00 | 01-FEB-00:10 | 1238.29 | 01-FEB-12:00 | 0.00 |
March | 0.150901E+11 | 0.343111E+10 | 744.00 | 0.150901E+11 | 0.00 | 0.00 | 0.75 | 10-MAR-17:00 | 0.65 | 01-MAR-07:30 | 6280.86 | 19-MAR-17:20 | 6280.86 | 19-MAR-17:20 | 0.00 | 01-MAR-00:10 | 1673.84 | 23-MAR-14:00 | 0.00 |
April | 0.194730E+11 | 0.446182E+10 | 720.00 | 0.194730E+11 | 0.00 | 0.00 | 0.98 | 30-APR-17:02 | 0.84 | 01-APR-07:00 | 8071.73 | 16-APR-17:37 | 8071.73 | 16-APR-17:37 | 0.00 | 01-APR-00:10 | 2487.09 | 26-APR-13:00 | 0.00 |
May | 0.537269E+10 | 0.135324E+10 | 744.00 | 0.537269E+10 | 0.00 | 0.00 | 0.33 | 29-MAY-17:43 | 0.23 | 13-MAY-07:00 | 2473.30 | 29-MAY-17:43 | 2473.30 | 29-MAY-17:43 | 0.00 | 01-MAY-00:10 | 647.22 | 03-MAY-13:00 | 0.00 |
June | 0.100968E+11 | 0.248408E+10 | 720.00 | 0.100968E+11 | 0.00 | 0.00 | 0.54 | 25-JUN-17:02 | 0.46 | 01-JUN-06:30 | 4265.45 | 25-JUN-17:50 | 4265.45 | 25-JUN-17:50 | 0.00 | 01-JUN-00:10 | 1247.17 | 29-JUN-11:00 | 0.00 |
July | 0.153739E+11 | 0.392744E+10 | 744.00 | 0.153739E+11 | 0.00 | 0.00 | 0.79 | 23-JUL-17:32 | 0.68 | 08-JUL-06:55 | 6190.94 | 04-JUL-18:20 | 6190.94 | 04-JUL-18:20 | 0.00 | 01-JUL-00:10 | 1999.01 | 31-JUL-11:30 | 0.00 |
August | 0.202270E+11 | 0.530521E+10 | 744.00 | 0.202270E+11 | 0.00 | 0.00 | 1.00 | 06-AUG-16:55 | 0.86 | 21-AUG-21:17 | 8199.36 | 06-AUG-18:03 | 8199.36 | 06-AUG-18:03 | 0.00 | 01-AUG-00:10 | 2609.40 | 17-AUG-14:00 | 0.00 |
September | 0.532488E+10 | 0.139576E+10 | 720.00 | 0.532488E+10 | 0.00 | 0.00 | 0.36 | 29-SEP-16:40 | 0.24 | 16-SEP-07:00 | 2514.39 | 04-SEP-16:57 | 2514.39 | 04-SEP-16:57 | 0.00 | 01-SEP-00:10 | 958.73 | 29-SEP-13:00 | 0.00 |
October | 0.104080E+11 | 0.268953E+10 | 744.00 | 0.104080E+11 | 0.00 | 0.00 | 0.62 | 15-OCT-16:22 | 0.46 | 28-OCT-07:00 | 4515.94 | 15-OCT-16:55 | 4515.94 | 15-OCT-16:55 | 0.00 | 01-OCT-00:10 | 1754.24 | 16-OCT-11:00 | 0.00 |
November | 0.147128E+11 | 0.337998E+10 | 720.00 | 0.147128E+11 | 0.00 | 0.00 | 0.76 | 19-NOV-13:02 | 0.66 | 18-NOV-08:00 | 6219.75 | 12-NOV-16:30 | 6219.75 | 12-NOV-16:30 | 0.00 | 01-NOV-00:10 | 1878.58 | 19-NOV-13:00 | 0.00 |
December | 0.200263E+11 | 0.452185E+10 | 744.00 | 0.200263E+11 | 0.00 | 0.00 | 0.98 | 25-DEC-15:51 | 0.85 | 13-DEC-07:25 | 8118.57 | 25-DEC-16:17 | 8118.57 | 25-DEC-16:17 | 0.00 | 01-DEC-00:10 | 2377.52 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.150353E+12 | 0.363895E+11 | 8760.00 | 0.150353E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.510533E+10 | 0.128642E+10 | 672.00 | 0.510533E+10 | 0.00 | 0.00 | 0.32 | 0.21 | 2407.74 | 2407.74 | 0.00 | 647.22 | 0.00 | ||||||
Maximum of Months | 0.202270E+11 | 0.530521E+10 | 744.00 | 0.202270E+11 | 0.00 | 0.00 | 1.00 | 0.86 | 8199.36 | 8199.36 | 0.00 | 2609.40 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.383603E+11 | 0.986668E+10 | 744.00 | 0.383603E+11 | 0.00 | 0.00 | 0.30 | 30-JAN-16:50 | 0.13 | 09-JAN-07:00 | 21965.91 | 30-JAN-16:50 | 21965.91 | 30-JAN-16:50 | 0.00 | 01-JAN-00:05 | 6142.34 | 24-JAN-16:00 | 0.00 |
February | 0.781194E+11 | 0.185931E+11 | 672.00 | 0.781194E+11 | 0.00 | 0.00 | 0.53 | 22-FEB-17:00 | 0.36 | 26-FEB-06:20 | 40484.32 | 22-FEB-17:00 | 40484.32 | 22-FEB-17:00 | 0.00 | 01-FEB-00:10 | 11344.33 | 01-FEB-12:00 | 0.00 |
March | 0.134869E+12 | 0.309045E+11 | 744.00 | 0.134869E+12 | 0.00 | 0.00 | 0.75 | 10-MAR-17:00 | 0.58 | 30-MAR-06:00 | 57609.05 | 10-MAR-17:20 | 57609.05 | 10-MAR-17:20 | 0.00 | 01-MAR-00:10 | 15814.84 | 23-MAR-14:00 | 0.00 |
April | 0.180326E+12 | 0.415018E+11 | 720.00 | 0.180326E+12 | 0.00 | 0.00 | 0.97 | 26-APR-13:00 | 0.79 | 01-APR-07:00 | 75109.01 | 27-APR-17:40 | 75109.01 | 27-APR-17:40 | 0.00 | 01-APR-00:10 | 23639.07 | 26-APR-13:00 | 0.00 |
May | 0.452269E+11 | 0.115137E+11 | 744.00 | 0.452269E+11 | 0.00 | 0.00 | 0.31 | 28-MAY-17:45 | 0.17 | 14-MAY-05:30 | 22074.68 | 28-MAY-17:45 | 22074.68 | 28-MAY-17:45 | 0.00 | 01-MAY-00:10 | 5921.19 | 03-MAY-13:00 | 0.00 |
June | 0.917547E+11 | 0.226968E+11 | 720.00 | 0.917547E+11 | 0.00 | 0.00 | 0.54 | 29-JUN-17:40 | 0.42 | 01-JUN-07:00 | 39504.86 | 25-JUN-17:55 | 39504.86 | 25-JUN-17:55 | 0.00 | 01-JUN-00:10 | 11678.50 | 29-JUN-11:00 | 0.00 |
July | 0.143297E+12 | 0.367306E+11 | 744.00 | 0.143297E+12 | 0.00 | 0.00 | 0.78 | 19-JUL-15:00 | 0.65 | 08-JUL-06:55 | 57747.65 | 04-JUL-18:17 | 57747.65 | 04-JUL-18:17 | 0.00 | 01-JUL-00:10 | 18970.03 | 19-JUL-15:00 | 0.00 |
August | 0.190066E+12 | 0.499661E+11 | 744.00 | 0.190066E+12 | 0.00 | 0.00 | 0.99 | 17-AUG-14:10 | 0.84 | 22-AUG-06:40 | 75521.51 | 06-AUG-17:54 | 75521.51 | 06-AUG-17:54 | 0.00 | 01-AUG-00:10 | 24730.26 | 17-AUG-14:00 | 0.00 |
September | 0.456252E+11 | 0.120861E+11 | 720.00 | 0.456252E+11 | 0.00 | 0.00 | 0.36 | 29-SEP-16:40 | 0.21 | 20-SEP-06:55 | 23339.11 | 29-SEP-16:40 | 23339.11 | 29-SEP-16:40 | 0.00 | 01-SEP-00:10 | 8884.63 | 29-SEP-13:00 | 0.00 |
October | 0.931279E+11 | 0.242621E+11 | 744.00 | 0.931279E+11 | 0.00 | 0.00 | 0.60 | 15-OCT-16:32 | 0.41 | 30-OCT-07:00 | 41854.01 | 15-OCT-16:46 | 41854.01 | 15-OCT-16:46 | 0.00 | 01-OCT-00:10 | 16445.17 | 16-OCT-11:00 | 0.00 |
November | 0.131882E+12 | 0.305258E+11 | 720.00 | 0.131882E+12 | 0.00 | 0.00 | 0.74 | 28-NOV-14:10 | 0.60 | 27-NOV-07:40 | 57376.77 | 07-NOV-16:30 | 57376.77 | 07-NOV-16:30 | 0.00 | 01-NOV-00:10 | 16657.34 | 19-NOV-13:00 | 0.00 |
December | 0.181161E+12 | 0.412212E+11 | 744.00 | 0.181161E+12 | 0.00 | 0.00 | 0.96 | 05-DEC-15:50 | 0.79 | 24-DEC-06:55 | 74640.73 | 19-DEC-16:20 | 74640.73 | 19-DEC-16:20 | 0.00 | 01-DEC-00:10 | 22330.15 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.135381E+13 | 0.329869E+12 | 8760.00 | 0.135381E+13 | 0.00 | ||||||||||||||
Minimum of Months | 0.383603E+11 | 0.986668E+10 | 672.00 | 0.383603E+11 | 0.00 | 0.00 | 0.30 | 0.13 | 21965.91 | 21965.91 | 0.00 | 5921.19 | 0.00 | ||||||
Maximum of Months | 0.190066E+12 | 0.499661E+11 | 744.00 | 0.190066E+12 | 0.00 | 0.00 | 0.99 | 0.84 | 75521.51 | 75521.51 | 0.00 | 24730.26 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.260937E+10 | 0.690310E+09 | 669.67 | 0.260937E+10 | 0.00 | 0.00 | 0.30 | 18-JAN-16:10 | 0.00 | 01-JAN-00:05 | 2144.46 | 26-JAN-16:20 | 2144.46 | 26-JAN-16:20 | 0.00 | 01-JAN-00:05 | 610.28 | 24-JAN-16:00 | 0.00 |
February | 0.688156E+10 | 0.165830E+10 | 672.00 | 0.688156E+10 | 0.00 | 0.00 | 0.52 | 22-FEB-17:00 | 0.25 | 26-FEB-07:00 | 4050.85 | 22-FEB-17:00 | 4050.85 | 22-FEB-17:00 | 0.00 | 01-FEB-00:10 | 1100.14 | 01-FEB-12:00 | 0.00 |
March | 0.126477E+11 | 0.292509E+10 | 744.00 | 0.126477E+11 | 0.00 | 0.00 | 0.74 | 10-MAR-17:00 | 0.49 | 30-MAR-05:20 | 5797.27 | 22-MAR-17:20 | 5797.27 | 22-MAR-17:20 | 0.00 | 01-MAR-00:10 | 1597.58 | 23-MAR-14:00 | 0.00 |
April | 0.175735E+11 | 0.407126E+10 | 720.00 | 0.175735E+11 | 0.00 | 0.00 | 0.97 | 26-APR-13:10 | 0.72 | 01-APR-05:20 | 7566.57 | 27-APR-17:30 | 7566.57 | 27-APR-17:30 | 0.00 | 01-APR-00:10 | 2389.11 | 26-APR-13:00 | 0.00 |
May | 0.407187E+10 | 0.104766E+10 | 743.83 | 0.407187E+10 | 0.00 | 0.00 | 0.31 | 29-MAY-17:43 | 0.00 | 14-MAY-04:45 | 2284.27 | 29-MAY-17:43 | 2284.27 | 29-MAY-17:43 | 0.00 | 01-MAY-00:10 | 625.02 | 03-MAY-13:00 | 0.00 |
June | 0.896517E+10 | 0.222917E+10 | 720.00 | 0.896517E+10 | 0.00 | 0.00 | 0.54 | 29-JUN-17:30 | 0.37 | 01-JUN-06:50 | 4064.02 | 25-JUN-18:00 | 4064.02 | 25-JUN-18:00 | 0.00 | 01-JUN-00:10 | 1186.17 | 29-JUN-11:00 | 0.00 |
July | 0.142298E+11 | 0.366270E+10 | 744.00 | 0.142298E+11 | 0.00 | 0.00 | 0.78 | 19-JUL-15:00 | 0.61 | 06-JUL-06:50 | 5884.32 | 09-JUL-18:00 | 5884.32 | 09-JUL-18:00 | 0.00 | 01-JUL-00:10 | 1929.30 | 19-JUL-15:00 | 0.00 |
August | 0.188844E+11 | 0.498453E+10 | 744.00 | 0.188844E+11 | 0.00 | 0.00 | 0.99 | 17-AUG-14:10 | 0.81 | 06-AUG-05:00 | 7646.91 | 20-AUG-17:32 | 7646.91 | 20-AUG-17:32 | 0.00 | 01-AUG-00:10 | 2500.87 | 17-AUG-14:00 | 0.00 |
September | 0.425549E+10 | 0.113885E+10 | 720.00 | 0.425549E+10 | 0.00 | 0.00 | 0.37 | 29-SEP-16:40 | 0.14 | 03-SEP-06:25 | 2409.26 | 29-SEP-16:40 | 2409.26 | 29-SEP-16:40 | 0.00 | 01-SEP-00:10 | 927.93 | 29-SEP-13:00 | 0.00 |
October | 0.881659E+10 | 0.232000E+10 | 744.00 | 0.881659E+10 | 0.00 | 0.00 | 0.61 | 15-OCT-16:32 | 0.32 | 30-OCT-06:00 | 4293.39 | 15-OCT-16:42 | 4293.39 | 15-OCT-16:42 | 0.00 | 01-OCT-00:10 | 1669.49 | 16-OCT-11:10 | 0.00 |
November | 0.122900E+11 | 0.287354E+10 | 720.00 | 0.122900E+11 | 0.00 | 0.00 | 0.72 | 28-NOV-14:20 | 0.49 | 05-NOV-07:10 | 5723.72 | 07-NOV-16:30 | 5723.72 | 07-NOV-16:30 | 0.00 | 01-NOV-00:10 | 1654.84 | 28-NOV-14:00 | 0.00 |
December | 0.169564E+11 | 0.390288E+10 | 744.00 | 0.169564E+11 | 0.00 | 0.00 | 0.95 | 05-DEC-15:50 | 0.67 | 24-DEC-07:30 | 7462.96 | 19-DEC-16:20 | 7462.96 | 19-DEC-16:20 | 0.00 | 01-DEC-00:10 | 2225.87 | 05-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.128182E+12 | 0.315043E+11 | 8685.51 | 0.128182E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.260937E+10 | 0.690310E+09 | 669.67 | 0.260937E+10 | 0.00 | 0.00 | 0.30 | 0.00 | 2144.46 | 2144.46 | 0.00 | 610.28 | 0.00 | ||||||
Maximum of Months | 0.188844E+11 | 0.498453E+10 | 744.00 | 0.188844E+11 | 0.00 | 0.00 | 0.99 | 0.81 | 7646.91 | 7646.91 | 0.00 | 2500.87 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.87 | 0.00 | 103.87 | 38.97 | 465.91 | 0.00 | 0.00 | 744.00 |
February | 130.38 | 0.00 | 130.38 | 47.21 | 426.92 | 0.00 | 0.00 | 672.00 |
March | 159.78 | 0.00 | 159.78 | 76.61 | 432.52 | 0.00 | 0.00 | 744.00 |
April | 184.07 | 0.70 | 183.37 | 118.01 | 339.37 | 0.00 | 0.00 | 720.00 |
May | 221.17 | 10.26 | 210.91 | 147.78 | 287.30 | 0.00 | 0.00 | 744.00 |
June | 235.65 | 22.99 | 212.66 | 189.55 | 221.83 | 0.00 | 0.00 | 720.00 |
July | 223.12 | 18.65 | 204.47 | 205.45 | 195.49 | 0.00 | 0.00 | 744.00 |
August | 185.32 | 3.69 | 181.63 | 175.97 | 208.84 | 0.00 | 0.00 | 744.00 |
September | 156.87 | 0.02 | 156.85 | 138.77 | 251.37 | 0.00 | 0.00 | 720.00 |
October | 124.44 | 0.00 | 124.44 | 119.35 | 286.51 | 0.00 | 0.00 | 744.00 |
November | 112.67 | 0.00 | 112.67 | 46.50 | 426.77 | 0.00 | 0.00 | 720.00 |
December | 96.69 | 0.00 | 96.69 | 31.43 | 479.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 161.30 | 4.72 | 156.58 | 111.70 | 334.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.69 | 0.00 | 96.69 | 31.43 | 195.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 235.65 | 22.99 | 212.66 | 205.45 | 479.80 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.87 | 0.00 | 103.87 | 38.97 | 465.91 | 0.00 | 0.00 | 744.00 |
February | 130.38 | 0.00 | 130.38 | 47.21 | 426.92 | 0.00 | 0.00 | 672.00 |
March | 159.78 | 0.00 | 159.78 | 76.61 | 432.52 | 0.00 | 0.00 | 744.00 |
April | 184.07 | 0.70 | 183.37 | 118.01 | 339.37 | 0.00 | 0.00 | 720.00 |
May | 221.17 | 10.26 | 210.91 | 147.78 | 287.30 | 0.00 | 0.00 | 744.00 |
June | 235.65 | 22.99 | 212.66 | 189.55 | 221.83 | 0.00 | 0.00 | 720.00 |
July | 223.12 | 18.65 | 204.47 | 205.45 | 195.49 | 0.00 | 0.00 | 744.00 |
August | 185.32 | 3.69 | 181.63 | 175.97 | 208.84 | 0.00 | 0.00 | 744.00 |
September | 156.87 | 0.02 | 156.85 | 138.77 | 251.37 | 0.00 | 0.00 | 720.00 |
October | 124.44 | 0.00 | 124.44 | 119.35 | 286.51 | 0.00 | 0.00 | 744.00 |
November | 112.67 | 0.00 | 112.67 | 46.50 | 426.77 | 0.00 | 0.00 | 720.00 |
December | 96.69 | 0.00 | 96.69 | 31.43 | 479.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 161.30 | 4.72 | 156.58 | 111.70 | 334.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.69 | 0.00 | 96.69 | 31.43 | 195.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 235.65 | 22.99 | 212.66 | 205.45 | 479.80 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.87 | 0.00 | 103.87 | 38.97 | 465.91 | 0.00 | 0.00 | 744.00 |
February | 130.38 | 0.00 | 130.38 | 47.21 | 426.92 | 0.00 | 0.00 | 672.00 |
March | 159.78 | 0.00 | 159.78 | 76.61 | 432.52 | 0.00 | 0.00 | 744.00 |
April | 184.07 | 0.70 | 183.37 | 118.01 | 339.37 | 0.00 | 0.00 | 720.00 |
May | 221.17 | 10.26 | 210.91 | 147.78 | 287.30 | 0.00 | 0.00 | 744.00 |
June | 235.65 | 22.99 | 212.66 | 189.55 | 221.83 | 0.00 | 0.00 | 720.00 |
July | 223.12 | 18.65 | 204.47 | 205.45 | 195.49 | 0.00 | 0.00 | 744.00 |
August | 185.32 | 3.69 | 181.63 | 175.97 | 208.84 | 0.00 | 0.00 | 744.00 |
September | 156.87 | 0.02 | 156.85 | 138.77 | 251.37 | 0.00 | 0.00 | 720.00 |
October | 124.44 | 0.00 | 124.44 | 119.35 | 286.51 | 0.00 | 0.00 | 744.00 |
November | 112.67 | 0.00 | 112.67 | 46.50 | 426.77 | 0.00 | 0.00 | 720.00 |
December | 96.69 | 0.00 | 96.69 | 31.43 | 479.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 161.30 | 4.72 | 156.58 | 111.70 | 334.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.69 | 0.00 | 96.69 | 31.43 | 195.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 235.65 | 22.99 | 212.66 | 205.45 | 479.80 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.87 | 0.00 | 103.87 | 38.97 | 465.91 | 0.00 | 0.00 | 744.00 |
February | 130.38 | 0.00 | 130.38 | 47.21 | 426.92 | 0.00 | 0.00 | 672.00 |
March | 159.78 | 0.00 | 159.78 | 76.61 | 432.52 | 0.00 | 0.00 | 744.00 |
April | 184.07 | 0.70 | 183.37 | 118.01 | 339.37 | 0.00 | 0.00 | 720.00 |
May | 221.17 | 10.26 | 210.91 | 147.78 | 287.30 | 0.00 | 0.00 | 744.00 |
June | 235.65 | 22.99 | 212.66 | 189.55 | 221.83 | 0.00 | 0.00 | 720.00 |
July | 223.12 | 18.65 | 204.47 | 205.45 | 195.49 | 0.00 | 0.00 | 744.00 |
August | 185.32 | 3.69 | 181.63 | 175.97 | 208.84 | 0.00 | 0.00 | 744.00 |
September | 156.87 | 0.02 | 156.85 | 138.77 | 251.37 | 0.00 | 0.00 | 720.00 |
October | 124.44 | 0.00 | 124.44 | 119.35 | 286.51 | 0.00 | 0.00 | 744.00 |
November | 112.67 | 0.00 | 112.67 | 46.50 | 426.77 | 0.00 | 0.00 | 720.00 |
December | 96.69 | 0.00 | 96.69 | 31.43 | 479.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 161.30 | 4.72 | 156.58 | 111.70 | 334.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.69 | 0.00 | 96.69 | 31.43 | 195.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 235.65 | 22.99 | 212.66 | 205.45 | 479.80 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.87 | 0.00 | 103.87 | 38.96 | 465.89 | 0.00 | 0.00 | 744.00 |
February | 130.38 | 0.00 | 130.38 | 47.21 | 426.90 | 0.00 | 0.00 | 672.00 |
March | 159.77 | 0.00 | 159.77 | 76.61 | 432.50 | 0.00 | 0.00 | 744.00 |
April | 184.06 | 0.70 | 183.36 | 118.00 | 339.35 | 0.00 | 0.00 | 720.00 |
May | 221.16 | 10.26 | 210.90 | 147.78 | 287.29 | 0.00 | 0.00 | 744.00 |
June | 235.64 | 22.99 | 212.65 | 189.54 | 221.83 | 0.00 | 0.00 | 720.00 |
July | 223.11 | 18.65 | 204.46 | 205.44 | 195.48 | 0.00 | 0.00 | 744.00 |
August | 185.31 | 3.69 | 181.62 | 175.96 | 208.83 | 0.00 | 0.00 | 744.00 |
September | 156.87 | 0.02 | 156.84 | 138.77 | 251.36 | 0.00 | 0.00 | 720.00 |
October | 124.43 | 0.00 | 124.43 | 119.35 | 286.50 | 0.00 | 0.00 | 744.00 |
November | 112.66 | 0.00 | 112.66 | 46.50 | 426.75 | 0.00 | 0.00 | 720.00 |
December | 96.69 | 0.00 | 96.69 | 31.43 | 479.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 161.29 | 4.72 | 156.58 | 111.69 | 334.73 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.69 | 0.00 | 96.69 | 31.43 | 195.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 235.64 | 22.99 | 212.65 | 205.44 | 479.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 311.30 | 166.49 | 144.81 | 307.48 | 468.95 | 0.00 | 0.00 | 744.00 |
February | 328.39 | 150.43 | 177.96 | 309.44 | 429.87 | 0.00 | 0.00 | 672.00 |
March | 398.94 | 177.76 | 221.18 | 405.69 | 432.55 | 0.00 | 0.00 | 744.00 |
April | 510.03 | 255.80 | 254.22 | 607.41 | 343.85 | 0.00 | 0.00 | 720.00 |
May | 481.28 | 200.84 | 280.44 | 547.48 | 312.28 | 0.00 | 0.00 | 744.00 |
June | 478.28 | 207.51 | 270.77 | 586.73 | 246.80 | 0.00 | 0.00 | 720.00 |
July | 541.93 | 269.29 | 272.64 | 728.85 | 215.91 | 0.00 | 0.00 | 744.00 |
August | 535.22 | 284.29 | 250.93 | 733.49 | 216.23 | 0.00 | 0.00 | 744.00 |
September | 389.69 | 178.57 | 211.11 | 492.42 | 264.16 | 0.00 | 0.00 | 720.00 |
October | 344.94 | 177.29 | 167.65 | 446.38 | 291.87 | 0.00 | 0.00 | 744.00 |
November | 314.44 | 159.74 | 154.70 | 315.95 | 425.44 | 0.00 | 0.00 | 720.00 |
December | 299.97 | 166.67 | 133.31 | 292.44 | 468.87 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 411.75 | 199.95 | 211.80 | 482.34 | 342.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 299.97 | 150.43 | 133.31 | 292.44 | 215.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 541.93 | 284.29 | 280.44 | 733.49 | 468.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 311.30 | 166.49 | 144.81 | 307.48 | 468.95 | 0.00 | 0.00 | 744.00 |
February | 328.39 | 150.43 | 177.96 | 309.44 | 429.87 | 0.00 | 0.00 | 672.00 |
March | 398.94 | 177.76 | 221.18 | 405.69 | 432.55 | 0.00 | 0.00 | 744.00 |
April | 510.03 | 255.80 | 254.22 | 607.41 | 343.85 | 0.00 | 0.00 | 720.00 |
May | 481.28 | 200.84 | 280.44 | 547.48 | 312.28 | 0.00 | 0.00 | 744.00 |
June | 478.28 | 207.51 | 270.77 | 586.73 | 246.80 | 0.00 | 0.00 | 720.00 |
July | 541.93 | 269.29 | 272.64 | 728.85 | 215.91 | 0.00 | 0.00 | 744.00 |
August | 535.22 | 284.29 | 250.93 | 733.49 | 216.23 | 0.00 | 0.00 | 744.00 |
September | 389.69 | 178.57 | 211.11 | 492.42 | 264.16 | 0.00 | 0.00 | 720.00 |
October | 344.94 | 177.29 | 167.65 | 446.38 | 291.87 | 0.00 | 0.00 | 744.00 |
November | 314.44 | 159.74 | 154.70 | 315.95 | 425.44 | 0.00 | 0.00 | 720.00 |
December | 299.97 | 166.67 | 133.31 | 292.44 | 468.87 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 411.75 | 199.95 | 211.80 | 482.34 | 342.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 299.97 | 150.43 | 133.31 | 292.44 | 215.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 541.93 | 284.29 | 280.44 | 733.49 | 468.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 311.30 | 166.48 | 144.81 | 307.48 | 468.94 | 0.00 | 0.00 | 744.00 |
February | 328.38 | 150.43 | 177.95 | 309.44 | 429.87 | 0.00 | 0.00 | 672.00 |
March | 398.93 | 177.76 | 221.17 | 405.69 | 432.54 | 0.00 | 0.00 | 744.00 |
April | 510.02 | 255.80 | 254.22 | 607.40 | 343.84 | 0.00 | 0.00 | 720.00 |
May | 481.27 | 200.84 | 280.43 | 547.47 | 312.28 | 0.00 | 0.00 | 744.00 |
June | 478.27 | 207.50 | 270.77 | 586.72 | 246.80 | 0.00 | 0.00 | 720.00 |
July | 541.92 | 269.28 | 272.63 | 728.84 | 215.91 | 0.00 | 0.00 | 744.00 |
August | 535.21 | 284.29 | 250.92 | 733.47 | 216.22 | 0.00 | 0.00 | 744.00 |
September | 389.68 | 178.57 | 211.11 | 492.41 | 264.16 | 0.00 | 0.00 | 720.00 |
October | 344.93 | 177.28 | 167.65 | 446.37 | 291.87 | 0.00 | 0.00 | 744.00 |
November | 314.44 | 159.74 | 154.69 | 315.95 | 425.43 | 0.00 | 0.00 | 720.00 |
December | 299.97 | 166.66 | 133.31 | 292.43 | 468.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 411.74 | 199.95 | 211.80 | 482.34 | 342.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 299.97 | 150.43 | 133.31 | 292.43 | 215.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 541.92 | 284.29 | 280.43 | 733.47 | 468.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 685.66 | 503.01 | 182.65 | 940.93 | 421.43 | 0.00 | 0.00 | 744.00 |
February | 538.84 | 331.93 | 206.91 | 664.62 | 391.92 | 0.00 | 0.00 | 672.00 |
March | 429.43 | 207.40 | 222.03 | 480.63 | 413.26 | 0.00 | 0.00 | 744.00 |
April | 358.71 | 136.68 | 222.02 | 364.59 | 337.67 | 0.00 | 0.00 | 720.00 |
May | 255.41 | 31.33 | 224.09 | 204.42 | 299.04 | 0.00 | 0.00 | 744.00 |
June | 224.05 | 13.42 | 210.64 | 189.02 | 234.91 | 0.00 | 0.00 | 720.00 |
July | 237.31 | 26.58 | 210.73 | 229.44 | 204.95 | 0.00 | 0.00 | 744.00 |
August | 304.90 | 96.06 | 208.84 | 338.68 | 213.74 | 0.00 | 0.00 | 744.00 |
September | 424.37 | 214.98 | 209.39 | 544.00 | 252.10 | 0.00 | 0.00 | 720.00 |
October | 539.90 | 360.95 | 178.95 | 771.38 | 278.17 | 0.00 | 0.00 | 744.00 |
November | 656.33 | 463.41 | 192.92 | 886.75 | 391.18 | 0.00 | 0.00 | 720.00 |
December | 732.48 | 557.56 | 174.92 | 1015.57 | 428.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 448.57 | 244.98 | 203.59 | 552.20 | 321.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 224.05 | 13.42 | 174.92 | 189.02 | 204.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 732.48 | 557.56 | 224.09 | 1015.57 | 428.76 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 685.66 | 503.01 | 182.65 | 940.93 | 421.43 | 0.00 | 0.00 | 744.00 |
February | 538.84 | 331.93 | 206.91 | 664.62 | 391.92 | 0.00 | 0.00 | 672.00 |
March | 429.43 | 207.40 | 222.03 | 480.63 | 413.26 | 0.00 | 0.00 | 744.00 |
April | 358.71 | 136.68 | 222.02 | 364.59 | 337.67 | 0.00 | 0.00 | 720.00 |
May | 255.41 | 31.33 | 224.09 | 204.42 | 299.04 | 0.00 | 0.00 | 744.00 |
June | 224.05 | 13.42 | 210.64 | 189.02 | 234.91 | 0.00 | 0.00 | 720.00 |
July | 237.30 | 26.58 | 210.73 | 229.44 | 204.95 | 0.00 | 0.00 | 744.00 |
August | 304.90 | 96.06 | 208.84 | 338.68 | 213.74 | 0.00 | 0.00 | 744.00 |
September | 424.37 | 214.98 | 209.39 | 544.00 | 252.10 | 0.00 | 0.00 | 720.00 |
October | 539.90 | 360.95 | 178.95 | 771.38 | 278.17 | 0.00 | 0.00 | 744.00 |
November | 656.32 | 463.41 | 192.92 | 886.75 | 391.18 | 0.00 | 0.00 | 720.00 |
December | 732.48 | 557.56 | 174.92 | 1015.57 | 428.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 448.57 | 244.98 | 203.59 | 552.20 | 321.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 224.05 | 13.42 | 174.92 | 189.02 | 204.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 732.48 | 557.56 | 224.09 | 1015.57 | 428.76 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 685.66 | 503.01 | 182.65 | 940.93 | 421.43 | 0.00 | 0.00 | 744.00 |
February | 538.84 | 331.93 | 206.91 | 664.62 | 391.92 | 0.00 | 0.00 | 672.00 |
March | 429.43 | 207.40 | 222.03 | 480.63 | 413.26 | 0.00 | 0.00 | 744.00 |
April | 358.71 | 136.68 | 222.02 | 364.59 | 337.67 | 0.00 | 0.00 | 720.00 |
May | 255.41 | 31.33 | 224.09 | 204.42 | 299.04 | 0.00 | 0.00 | 744.00 |
June | 224.05 | 13.42 | 210.64 | 189.02 | 234.91 | 0.00 | 0.00 | 720.00 |
July | 237.31 | 26.58 | 210.73 | 229.44 | 204.95 | 0.00 | 0.00 | 744.00 |
August | 304.90 | 96.06 | 208.84 | 338.68 | 213.74 | 0.00 | 0.00 | 744.00 |
September | 424.37 | 214.98 | 209.39 | 544.00 | 252.10 | 0.00 | 0.00 | 720.00 |
October | 539.90 | 360.95 | 178.95 | 771.38 | 278.17 | 0.00 | 0.00 | 744.00 |
November | 656.33 | 463.41 | 192.92 | 886.75 | 391.18 | 0.00 | 0.00 | 720.00 |
December | 732.48 | 557.56 | 174.92 | 1015.57 | 428.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 448.57 | 244.98 | 203.59 | 552.20 | 321.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 224.05 | 13.42 | 174.92 | 189.02 | 204.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 732.48 | 557.56 | 224.09 | 1015.57 | 428.76 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 685.66 | 503.01 | 182.65 | 940.93 | 421.43 | 0.00 | 0.00 | 744.00 |
February | 538.84 | 331.93 | 206.91 | 664.62 | 391.92 | 0.00 | 0.00 | 672.00 |
March | 429.43 | 207.40 | 222.03 | 480.63 | 413.26 | 0.00 | 0.00 | 744.00 |
April | 358.71 | 136.68 | 222.02 | 364.59 | 337.67 | 0.00 | 0.00 | 720.00 |
May | 255.41 | 31.33 | 224.09 | 204.42 | 299.04 | 0.00 | 0.00 | 744.00 |
June | 224.05 | 13.42 | 210.64 | 189.02 | 234.91 | 0.00 | 0.00 | 720.00 |
July | 237.30 | 26.58 | 210.73 | 229.44 | 204.95 | 0.00 | 0.00 | 744.00 |
August | 304.90 | 96.06 | 208.84 | 338.68 | 213.74 | 0.00 | 0.00 | 744.00 |
September | 424.37 | 214.98 | 209.39 | 544.00 | 252.10 | 0.00 | 0.00 | 720.00 |
October | 539.90 | 360.95 | 178.95 | 771.38 | 278.17 | 0.00 | 0.00 | 744.00 |
November | 656.32 | 463.41 | 192.92 | 886.75 | 391.18 | 0.00 | 0.00 | 720.00 |
December | 732.48 | 557.56 | 174.92 | 1015.57 | 428.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 448.57 | 244.98 | 203.59 | 552.20 | 321.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 224.05 | 13.42 | 174.92 | 189.02 | 204.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 732.48 | 557.56 | 224.09 | 1015.57 | 428.76 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 685.63 | 502.99 | 182.64 | 940.89 | 421.41 | 0.00 | 0.00 | 744.00 |
February | 538.82 | 331.92 | 206.90 | 664.60 | 391.90 | 0.00 | 0.00 | 672.00 |
March | 429.41 | 207.39 | 222.02 | 480.61 | 413.25 | 0.00 | 0.00 | 744.00 |
April | 358.69 | 136.68 | 222.01 | 364.58 | 337.65 | 0.00 | 0.00 | 720.00 |
May | 255.40 | 31.32 | 224.08 | 204.42 | 299.03 | 0.00 | 0.00 | 744.00 |
June | 224.05 | 13.42 | 210.63 | 189.02 | 234.90 | 0.00 | 0.00 | 720.00 |
July | 237.30 | 26.57 | 210.72 | 229.43 | 204.95 | 0.00 | 0.00 | 744.00 |
August | 304.89 | 96.06 | 208.83 | 338.67 | 213.73 | 0.00 | 0.00 | 744.00 |
September | 424.36 | 214.98 | 209.38 | 543.98 | 252.09 | 0.00 | 0.00 | 720.00 |
October | 539.88 | 360.94 | 178.94 | 771.35 | 278.16 | 0.00 | 0.00 | 744.00 |
November | 656.30 | 463.39 | 192.91 | 886.71 | 391.17 | 0.00 | 0.00 | 720.00 |
December | 732.45 | 557.53 | 174.92 | 1015.53 | 428.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 448.56 | 244.97 | 203.58 | 552.18 | 321.88 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 224.05 | 13.42 | 174.92 | 189.02 | 204.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 732.45 | 557.53 | 224.08 | 1015.53 | 428.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 296.31 | 149.44 | 146.87 | 304.06 | 529.73 | 0.00 | 0.00 | 744.00 |
February | 353.50 | 163.19 | 190.31 | 353.22 | 504.85 | 0.00 | 0.00 | 672.00 |
March | 405.23 | 179.29 | 225.94 | 411.53 | 518.89 | 0.00 | 0.00 | 744.00 |
April | 558.62 | 290.88 | 267.74 | 665.56 | 429.55 | 0.00 | 0.00 | 720.00 |
May | 548.71 | 253.44 | 295.27 | 644.98 | 356.24 | 0.00 | 0.00 | 744.00 |
June | 581.28 | 290.61 | 290.67 | 729.28 | 292.52 | 0.00 | 0.00 | 720.00 |
July | 615.34 | 329.25 | 286.09 | 817.54 | 267.05 | 0.00 | 0.00 | 744.00 |
August | 577.34 | 312.90 | 264.44 | 774.50 | 282.96 | 0.00 | 0.00 | 744.00 |
September | 494.34 | 264.53 | 229.81 | 647.21 | 303.69 | 0.00 | 0.00 | 720.00 |
October | 377.87 | 206.30 | 171.57 | 494.96 | 352.33 | 0.00 | 0.00 | 744.00 |
November | 341.32 | 178.53 | 162.79 | 362.36 | 513.25 | 0.00 | 0.00 | 720.00 |
December | 301.45 | 161.68 | 139.77 | 306.77 | 582.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 454.67 | 231.96 | 222.70 | 543.58 | 410.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 296.31 | 149.44 | 139.77 | 304.06 | 267.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 615.34 | 329.25 | 295.27 | 817.54 | 582.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 296.31 | 149.44 | 146.87 | 304.06 | 529.73 | 0.00 | 0.00 | 744.00 |
February | 353.50 | 163.19 | 190.31 | 353.22 | 504.85 | 0.00 | 0.00 | 672.00 |
March | 405.23 | 179.29 | 225.94 | 411.53 | 518.89 | 0.00 | 0.00 | 744.00 |
April | 558.62 | 290.88 | 267.74 | 665.56 | 429.55 | 0.00 | 0.00 | 720.00 |
May | 548.71 | 253.44 | 295.27 | 644.98 | 356.24 | 0.00 | 0.00 | 744.00 |
June | 581.28 | 290.61 | 290.67 | 729.28 | 292.52 | 0.00 | 0.00 | 720.00 |
July | 615.34 | 329.25 | 286.09 | 817.54 | 267.05 | 0.00 | 0.00 | 744.00 |
August | 577.34 | 312.90 | 264.44 | 774.50 | 282.96 | 0.00 | 0.00 | 744.00 |
September | 494.34 | 264.53 | 229.81 | 647.21 | 303.69 | 0.00 | 0.00 | 720.00 |
October | 377.87 | 206.30 | 171.57 | 494.96 | 352.33 | 0.00 | 0.00 | 744.00 |
November | 341.32 | 178.53 | 162.79 | 362.36 | 513.25 | 0.00 | 0.00 | 720.00 |
December | 301.45 | 161.68 | 139.77 | 306.77 | 582.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 454.67 | 231.96 | 222.70 | 543.58 | 410.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 296.31 | 149.44 | 139.77 | 304.06 | 267.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 615.34 | 329.25 | 295.27 | 817.54 | 582.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 296.30 | 149.44 | 146.86 | 304.06 | 529.72 | 0.00 | 0.00 | 744.00 |
February | 353.49 | 163.18 | 190.31 | 353.21 | 504.84 | 0.00 | 0.00 | 672.00 |
March | 405.22 | 179.29 | 225.93 | 411.52 | 518.88 | 0.00 | 0.00 | 744.00 |
April | 558.61 | 290.88 | 267.73 | 665.54 | 429.54 | 0.00 | 0.00 | 720.00 |
May | 548.70 | 253.44 | 295.26 | 644.97 | 356.23 | 0.00 | 0.00 | 744.00 |
June | 581.27 | 290.61 | 290.66 | 729.26 | 292.51 | 0.00 | 0.00 | 720.00 |
July | 615.32 | 329.24 | 286.08 | 817.53 | 267.04 | 0.00 | 0.00 | 744.00 |
August | 577.33 | 312.89 | 264.44 | 774.49 | 282.95 | 0.00 | 0.00 | 744.00 |
September | 494.33 | 264.52 | 229.80 | 647.20 | 303.69 | 0.00 | 0.00 | 720.00 |
October | 377.87 | 206.30 | 171.57 | 494.95 | 352.32 | 0.00 | 0.00 | 744.00 |
November | 341.31 | 178.53 | 162.79 | 362.35 | 513.24 | 0.00 | 0.00 | 720.00 |
December | 301.44 | 161.68 | 139.77 | 306.76 | 582.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 454.66 | 231.96 | 222.70 | 543.57 | 410.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 296.30 | 149.44 | 139.77 | 304.06 | 267.04 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 615.32 | 329.24 | 295.26 | 817.53 | 582.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 519.34 | 0.00 | 519.34 | 253.82 | 2065.16 | 0.00 | 0.00 | 744.00 |
February | 651.91 | 0.00 | 651.91 | 299.40 | 1873.14 | 0.00 | 0.00 | 672.00 |
March | 798.87 | 0.00 | 798.87 | 453.27 | 1918.78 | 0.00 | 0.00 | 744.00 |
April | 920.35 | 3.50 | 916.85 | 661.60 | 1511.95 | 0.00 | 0.00 | 720.00 |
May | 1105.83 | 51.32 | 1054.52 | 789.30 | 1324.52 | 0.00 | 0.00 | 744.00 |
June | 1178.23 | 114.93 | 1063.30 | 992.83 | 1021.49 | 0.00 | 0.00 | 720.00 |
July | 1115.58 | 93.24 | 1022.34 | 1083.02 | 895.36 | 0.00 | 0.00 | 744.00 |
August | 926.58 | 18.44 | 908.14 | 931.58 | 953.24 | 0.00 | 0.00 | 744.00 |
September | 784.35 | 0.12 | 784.23 | 733.98 | 1144.58 | 0.00 | 0.00 | 720.00 |
October | 622.17 | 0.00 | 622.17 | 650.00 | 1280.54 | 0.00 | 0.00 | 744.00 |
November | 563.33 | 0.00 | 563.33 | 299.34 | 1876.37 | 0.00 | 0.00 | 720.00 |
December | 483.46 | 0.00 | 483.46 | 231.72 | 2071.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 806.49 | 23.59 | 782.90 | 616.96 | 1492.79 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 483.46 | 0.00 | 483.46 | 231.72 | 895.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1178.23 | 114.93 | 1063.30 | 1083.02 | 2071.64 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 933.89 | 499.46 | 434.44 | 951.83 | 1291.41 | 0.00 | 0.00 | 744.00 |
February | 985.16 | 451.30 | 533.87 | 953.85 | 1179.33 | 0.00 | 0.00 | 672.00 |
March | 1196.80 | 533.28 | 663.52 | 1238.16 | 1207.35 | 0.00 | 0.00 | 744.00 |
April | 1530.06 | 767.39 | 762.67 | 1824.64 | 978.17 | 0.00 | 0.00 | 720.00 |
May | 1443.82 | 602.51 | 841.31 | 1647.12 | 889.11 | 0.00 | 0.00 | 744.00 |
June | 1434.82 | 622.51 | 812.31 | 1759.62 | 704.02 | 0.00 | 0.00 | 720.00 |
July | 1625.77 | 807.86 | 817.91 | 2177.39 | 626.03 | 0.00 | 0.00 | 744.00 |
August | 1605.64 | 852.87 | 752.78 | 2188.73 | 641.04 | 0.00 | 0.00 | 744.00 |
September | 1169.05 | 535.72 | 633.34 | 1483.30 | 744.48 | 0.00 | 0.00 | 720.00 |
October | 1034.80 | 531.86 | 502.94 | 1349.76 | 819.06 | 0.00 | 0.00 | 744.00 |
November | 943.32 | 479.23 | 464.09 | 972.97 | 1179.48 | 0.00 | 0.00 | 720.00 |
December | 899.91 | 499.99 | 399.92 | 911.16 | 1288.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1235.24 | 599.85 | 635.39 | 1458.39 | 961.19 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 899.91 | 451.30 | 399.92 | 911.16 | 626.03 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1625.77 | 852.87 | 841.31 | 2188.73 | 1291.41 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3428.26 | 2515.04 | 913.22 | 4664.98 | 2076.67 | 0.00 | 0.00 | 744.00 |
February | 2694.16 | 1659.65 | 1034.51 | 3297.68 | 1889.35 | 0.00 | 0.00 | 672.00 |
March | 2147.13 | 1036.98 | 1110.15 | 2403.44 | 1972.87 | 0.00 | 0.00 | 744.00 |
April | 1793.51 | 683.41 | 1110.10 | 1838.56 | 1594.87 | 0.00 | 0.00 | 720.00 |
May | 1277.06 | 156.63 | 1120.43 | 1039.84 | 1431.28 | 0.00 | 0.00 | 744.00 |
June | 1120.26 | 67.08 | 1053.18 | 969.94 | 1107.81 | 0.00 | 0.00 | 720.00 |
July | 1186.51 | 132.88 | 1053.64 | 1179.08 | 961.68 | 0.00 | 0.00 | 744.00 |
August | 1524.50 | 480.32 | 1044.18 | 1713.92 | 1018.57 | 0.00 | 0.00 | 744.00 |
September | 2121.85 | 1074.91 | 1046.94 | 2706.33 | 1221.43 | 0.00 | 0.00 | 720.00 |
October | 2699.49 | 1804.75 | 894.74 | 3829.05 | 1355.09 | 0.00 | 0.00 | 744.00 |
November | 3281.59 | 2317.01 | 964.58 | 4400.37 | 1899.50 | 0.00 | 0.00 | 720.00 |
December | 3662.36 | 2787.75 | 874.61 | 5045.16 | 2078.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2242.84 | 1224.90 | 1017.95 | 2755.97 | 1548.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1120.26 | 67.08 | 874.61 | 969.94 | 961.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3662.36 | 2787.75 | 1120.43 | 5045.16 | 2078.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 888.91 | 448.32 | 440.59 | 958.90 | 1400.28 | 0.00 | 0.00 | 744.00 |
February | 1060.47 | 489.55 | 570.92 | 1115.35 | 1281.84 | 0.00 | 0.00 | 672.00 |
March | 1215.68 | 537.87 | 677.80 | 1302.42 | 1309.38 | 0.00 | 0.00 | 744.00 |
April | 1675.84 | 872.63 | 803.21 | 2061.14 | 1092.22 | 0.00 | 0.00 | 720.00 |
May | 1646.11 | 760.31 | 885.79 | 1959.77 | 979.18 | 0.00 | 0.00 | 744.00 |
June | 1743.82 | 871.83 | 871.99 | 2219.32 | 774.53 | 0.00 | 0.00 | 720.00 |
July | 1845.99 | 987.74 | 858.25 | 2497.08 | 699.49 | 0.00 | 0.00 | 744.00 |
August | 1731.99 | 938.68 | 793.32 | 2377.38 | 725.75 | 0.00 | 0.00 | 744.00 |
September | 1483.00 | 793.58 | 689.42 | 1962.58 | 823.18 | 0.00 | 0.00 | 720.00 |
October | 1133.61 | 618.90 | 514.70 | 1531.73 | 910.11 | 0.00 | 0.00 | 744.00 |
November | 1023.95 | 535.58 | 488.37 | 1151.41 | 1284.20 | 0.00 | 0.00 | 720.00 |
December | 904.33 | 485.03 | 419.30 | 996.68 | 1420.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1363.99 | 695.89 | 668.10 | 1680.57 | 1057.24 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 888.91 | 448.32 | 419.30 | 958.90 | 699.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1845.99 | 987.74 | 885.79 | 2497.08 | 1420.23 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 519.34 | 0.00 | 519.34 | 307.28 | 1854.84 | 0.00 | 0.00 | 744.00 |
February | 651.91 | 0.00 | 651.91 | 347.52 | 1694.09 | 0.00 | 0.00 | 672.00 |
March | 798.87 | 0.00 | 798.87 | 493.80 | 1777.15 | 0.00 | 0.00 | 744.00 |
April | 920.35 | 3.50 | 916.85 | 681.82 | 1430.71 | 0.00 | 0.00 | 720.00 |
May | 1105.83 | 51.32 | 1054.52 | 810.64 | 1254.86 | 0.00 | 0.00 | 744.00 |
June | 1178.23 | 114.93 | 1063.30 | 991.79 | 987.24 | 0.00 | 0.00 | 720.00 |
July | 1115.58 | 93.24 | 1022.34 | 1068.42 | 875.64 | 0.00 | 0.00 | 744.00 |
August | 926.58 | 18.44 | 908.14 | 920.69 | 929.98 | 0.00 | 0.00 | 744.00 |
September | 784.35 | 0.12 | 784.23 | 741.82 | 1090.88 | 0.00 | 0.00 | 720.00 |
October | 622.17 | 0.00 | 622.17 | 673.64 | 1196.21 | 0.00 | 0.00 | 744.00 |
November | 563.33 | 0.00 | 563.33 | 346.76 | 1706.46 | 0.00 | 0.00 | 720.00 |
December | 483.46 | 0.00 | 483.46 | 285.97 | 1861.37 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 806.49 | 23.59 | 782.90 | 641.01 | 1386.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 483.46 | 0.00 | 483.46 | 285.97 | 875.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1178.23 | 114.93 | 1063.30 | 1068.42 | 1861.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 933.89 | 499.46 | 434.44 | 999.97 | 1176.13 | 0.00 | 0.00 | 744.00 |
February | 985.16 | 451.30 | 533.87 | 989.15 | 1083.33 | 0.00 | 0.00 | 672.00 |
March | 1196.80 | 533.28 | 663.52 | 1266.31 | 1134.10 | 0.00 | 0.00 | 744.00 |
April | 1530.06 | 767.39 | 762.67 | 1834.79 | 937.64 | 0.00 | 0.00 | 720.00 |
May | 1443.82 | 602.51 | 841.31 | 1659.26 | 854.95 | 0.00 | 0.00 | 744.00 |
June | 1434.82 | 622.51 | 812.31 | 1756.39 | 687.81 | 0.00 | 0.00 | 720.00 |
July | 1625.77 | 807.86 | 817.91 | 2165.50 | 617.90 | 0.00 | 0.00 | 744.00 |
August | 1605.64 | 852.87 | 752.78 | 2178.86 | 631.45 | 0.00 | 0.00 | 744.00 |
September | 1169.05 | 535.72 | 633.34 | 1485.17 | 716.88 | 0.00 | 0.00 | 720.00 |
October | 1034.80 | 531.86 | 502.94 | 1363.11 | 775.80 | 0.00 | 0.00 | 744.00 |
November | 943.32 | 479.23 | 464.09 | 1011.35 | 1090.24 | 0.00 | 0.00 | 720.00 |
December | 899.91 | 499.99 | 399.92 | 961.03 | 1175.08 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1235.24 | 599.85 | 635.39 | 1476.01 | 905.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 899.91 | 451.30 | 399.92 | 961.03 | 617.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1625.77 | 852.87 | 841.31 | 2178.86 | 1176.13 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3428.26 | 2515.04 | 913.22 | 4728.82 | 1907.03 | 0.00 | 0.00 | 744.00 |
February | 2694.16 | 1659.65 | 1034.51 | 3344.03 | 1737.25 | 0.00 | 0.00 | 672.00 |
March | 2147.13 | 1036.98 | 1110.15 | 2439.49 | 1844.36 | 0.00 | 0.00 | 744.00 |
April | 1793.51 | 683.41 | 1110.10 | 1855.40 | 1517.74 | 0.00 | 0.00 | 720.00 |
May | 1277.06 | 156.63 | 1120.43 | 1059.87 | 1363.43 | 0.00 | 0.00 | 744.00 |
June | 1120.26 | 67.08 | 1053.18 | 970.74 | 1074.90 | 0.00 | 0.00 | 720.00 |
July | 1186.51 | 132.88 | 1053.64 | 1168.89 | 944.62 | 0.00 | 0.00 | 744.00 |
August | 1524.50 | 480.32 | 1044.18 | 1705.20 | 996.64 | 0.00 | 0.00 | 744.00 |
September | 2121.85 | 1074.91 | 1046.94 | 2707.59 | 1171.23 | 0.00 | 0.00 | 720.00 |
October | 2699.49 | 1804.75 | 894.74 | 3847.21 | 1282.49 | 0.00 | 0.00 | 744.00 |
November | 3281.59 | 2317.01 | 964.58 | 4444.68 | 1768.10 | 0.00 | 0.00 | 720.00 |
December | 3662.36 | 2787.75 | 874.61 | 5107.37 | 1918.57 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2242.84 | 1224.90 | 1017.95 | 2780.13 | 1459.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1120.26 | 67.08 | 874.61 | 970.74 | 944.62 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3662.36 | 2787.75 | 1120.43 | 5107.37 | 1918.57 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 888.91 | 448.32 | 440.59 | 985.74 | 1290.20 | 0.00 | 0.00 | 744.00 |
February | 1060.47 | 489.55 | 570.92 | 1137.96 | 1186.68 | 0.00 | 0.00 | 672.00 |
March | 1215.68 | 537.87 | 677.80 | 1320.37 | 1229.22 | 0.00 | 0.00 | 744.00 |
April | 1675.84 | 872.63 | 803.21 | 2065.88 | 1042.59 | 0.00 | 0.00 | 720.00 |
May | 1646.11 | 760.31 | 885.79 | 1964.41 | 935.93 | 0.00 | 0.00 | 744.00 |
June | 1743.82 | 871.83 | 871.99 | 2212.35 | 749.33 | 0.00 | 0.00 | 720.00 |
July | 1845.99 | 987.74 | 858.25 | 2483.96 | 682.31 | 0.00 | 0.00 | 744.00 |
August | 1731.99 | 938.68 | 793.32 | 2366.18 | 707.19 | 0.00 | 0.00 | 744.00 |
September | 1483.00 | 793.58 | 689.42 | 1961.40 | 789.87 | 0.00 | 0.00 | 720.00 |
October | 1133.61 | 618.90 | 514.70 | 1541.77 | 861.15 | 0.00 | 0.00 | 744.00 |
November | 1023.95 | 535.58 | 488.37 | 1173.05 | 1194.11 | 0.00 | 0.00 | 720.00 |
December | 904.33 | 485.03 | 419.30 | 1024.38 | 1308.81 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1363.99 | 695.89 | 668.10 | 1689.13 | 997.16 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 888.91 | 448.32 | 419.30 | 985.74 | 682.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1845.99 | 987.74 | 885.79 | 2483.96 | 1308.81 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.278205E+09 | 0.00 | 0.278205E+09 | 0.104366E+09 | 0.124789E+10 |
February | 0.315426E+09 | 0.00 | 0.315426E+09 | 0.114205E+09 | 0.103280E+10 |
March | 0.427944E+09 | 0.00 | 0.427944E+09 | 0.205198E+09 | 0.115847E+10 |
April | 0.477116E+09 | 1814966.41 | 0.475301E+09 | 0.305880E+09 | 0.879636E+09 |
May | 0.592380E+09 | 27490348.75 | 0.564889E+09 | 0.395821E+09 | 0.769514E+09 |
June | 0.610802E+09 | 59581668.43 | 0.551220E+09 | 0.491316E+09 | 0.574994E+09 |
July | 0.597602E+09 | 49946883.44 | 0.547655E+09 | 0.550283E+09 | 0.523608E+09 |
August | 0.496354E+09 | 9877225.53 | 0.486477E+09 | 0.471308E+09 | 0.559349E+09 |
September | 0.406610E+09 | 62069.80 | 0.406548E+09 | 0.359693E+09 | 0.651553E+09 |
October | 0.333289E+09 | 0.00 | 0.333289E+09 | 0.319673E+09 | 0.767400E+09 |
November | 0.292035E+09 | 0.00 | 0.292035E+09 | 0.120525E+09 | 0.110618E+10 |
December | 0.258985E+09 | 0.00 | 0.258985E+09 | 84180196.47 | 0.128510E+10 |
Annual Sum or Average | 0.508675E+10 | 0.148773E+09 | 0.493797E+10 | 0.352245E+10 | 0.105565E+11 |
Minimum of Months | 0.258985E+09 | 0.00 | 0.258985E+09 | 84180196.47 | 0.523608E+09 |
Maximum of Months | 0.610802E+09 | 59581668.43 | 0.564889E+09 | 0.550283E+09 | 0.128510E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.278205E+09 | 0.00 | 0.278205E+09 | 0.104366E+09 | 0.124789E+10 |
February | 0.315426E+09 | 0.00 | 0.315426E+09 | 0.114205E+09 | 0.103280E+10 |
March | 0.427943E+09 | 0.00 | 0.427943E+09 | 0.205198E+09 | 0.115847E+10 |
April | 0.477115E+09 | 1814964.24 | 0.475300E+09 | 0.305880E+09 | 0.879636E+09 |
May | 0.592379E+09 | 27490315.77 | 0.564889E+09 | 0.395820E+09 | 0.769514E+09 |
June | 0.610802E+09 | 59581596.94 | 0.551220E+09 | 0.491316E+09 | 0.574994E+09 |
July | 0.597601E+09 | 49946823.51 | 0.547654E+09 | 0.550282E+09 | 0.523608E+09 |
August | 0.496354E+09 | 9877213.68 | 0.486476E+09 | 0.471308E+09 | 0.559349E+09 |
September | 0.406610E+09 | 62069.72 | 0.406548E+09 | 0.359693E+09 | 0.651553E+09 |
October | 0.333289E+09 | 0.00 | 0.333289E+09 | 0.319673E+09 | 0.767400E+09 |
November | 0.292035E+09 | 0.00 | 0.292035E+09 | 0.120525E+09 | 0.110618E+10 |
December | 0.258985E+09 | 0.00 | 0.258985E+09 | 84180108.99 | 0.128510E+10 |
Annual Sum or Average | 0.508674E+10 | 0.148773E+09 | 0.493797E+10 | 0.352245E+10 | 0.105565E+11 |
Minimum of Months | 0.258985E+09 | 0.00 | 0.258985E+09 | 84180108.99 | 0.523608E+09 |
Maximum of Months | 0.610802E+09 | 59581596.94 | 0.564889E+09 | 0.550282E+09 | 0.128510E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.278205E+09 | 0.00 | 0.278205E+09 | 0.104366E+09 | 0.124789E+10 |
February | 0.315426E+09 | 0.00 | 0.315426E+09 | 0.114205E+09 | 0.103280E+10 |
March | 0.427944E+09 | 0.00 | 0.427944E+09 | 0.205198E+09 | 0.115847E+10 |
April | 0.477116E+09 | 1814966.41 | 0.475301E+09 | 0.305880E+09 | 0.879636E+09 |
May | 0.592380E+09 | 27490348.75 | 0.564889E+09 | 0.395821E+09 | 0.769514E+09 |
June | 0.610802E+09 | 59581668.43 | 0.551220E+09 | 0.491316E+09 | 0.574994E+09 |
July | 0.597602E+09 | 49946883.44 | 0.547655E+09 | 0.550283E+09 | 0.523608E+09 |
August | 0.496354E+09 | 9877225.53 | 0.486477E+09 | 0.471308E+09 | 0.559349E+09 |
September | 0.406610E+09 | 62069.80 | 0.406548E+09 | 0.359693E+09 | 0.651553E+09 |
October | 0.333289E+09 | 0.00 | 0.333289E+09 | 0.319673E+09 | 0.767400E+09 |
November | 0.292035E+09 | 0.00 | 0.292035E+09 | 0.120525E+09 | 0.110618E+10 |
December | 0.258985E+09 | 0.00 | 0.258985E+09 | 84180196.47 | 0.128510E+10 |
Annual Sum or Average | 0.508675E+10 | 0.148773E+09 | 0.493797E+10 | 0.352245E+10 | 0.105565E+11 |
Minimum of Months | 0.258985E+09 | 0.00 | 0.258985E+09 | 84180196.47 | 0.523608E+09 |
Maximum of Months | 0.610802E+09 | 59581668.43 | 0.564889E+09 | 0.550283E+09 | 0.128510E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.278205E+09 | 0.00 | 0.278205E+09 | 0.104366E+09 | 0.124789E+10 |
February | 0.315426E+09 | 0.00 | 0.315426E+09 | 0.114205E+09 | 0.103280E+10 |
March | 0.427943E+09 | 0.00 | 0.427943E+09 | 0.205198E+09 | 0.115847E+10 |
April | 0.477115E+09 | 1814964.24 | 0.475300E+09 | 0.305880E+09 | 0.879636E+09 |
May | 0.592379E+09 | 27490315.77 | 0.564889E+09 | 0.395820E+09 | 0.769514E+09 |
June | 0.610802E+09 | 59581596.94 | 0.551220E+09 | 0.491316E+09 | 0.574994E+09 |
July | 0.597601E+09 | 49946823.51 | 0.547654E+09 | 0.550282E+09 | 0.523608E+09 |
August | 0.496354E+09 | 9877213.68 | 0.486476E+09 | 0.471308E+09 | 0.559349E+09 |
September | 0.406610E+09 | 62069.72 | 0.406548E+09 | 0.359693E+09 | 0.651553E+09 |
October | 0.333289E+09 | 0.00 | 0.333289E+09 | 0.319673E+09 | 0.767400E+09 |
November | 0.292035E+09 | 0.00 | 0.292035E+09 | 0.120525E+09 | 0.110618E+10 |
December | 0.258985E+09 | 0.00 | 0.258985E+09 | 84180108.99 | 0.128510E+10 |
Annual Sum or Average | 0.508674E+10 | 0.148773E+09 | 0.493797E+10 | 0.352245E+10 | 0.105565E+11 |
Minimum of Months | 0.258985E+09 | 0.00 | 0.258985E+09 | 84180108.99 | 0.523608E+09 |
Maximum of Months | 0.610802E+09 | 59581596.94 | 0.564889E+09 | 0.550282E+09 | 0.128510E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.278194E+09 | 0.00 | 0.278194E+09 | 0.104362E+09 | 0.124784E+10 |
February | 0.315413E+09 | 0.00 | 0.315413E+09 | 0.114200E+09 | 0.103276E+10 |
March | 0.427927E+09 | 0.00 | 0.427927E+09 | 0.205190E+09 | 0.115842E+10 |
April | 0.477096E+09 | 1814893.26 | 0.475281E+09 | 0.305868E+09 | 0.879600E+09 |
May | 0.592356E+09 | 27489240.77 | 0.564867E+09 | 0.395805E+09 | 0.769483E+09 |
June | 0.610777E+09 | 59579267.02 | 0.551198E+09 | 0.491297E+09 | 0.574971E+09 |
July | 0.597578E+09 | 49944870.36 | 0.547633E+09 | 0.550261E+09 | 0.523587E+09 |
August | 0.496334E+09 | 9876827.44 | 0.486457E+09 | 0.471289E+09 | 0.559327E+09 |
September | 0.406594E+09 | 62067.29 | 0.406532E+09 | 0.359679E+09 | 0.651526E+09 |
October | 0.333276E+09 | 0.00 | 0.333276E+09 | 0.319661E+09 | 0.767369E+09 |
November | 0.292023E+09 | 0.00 | 0.292023E+09 | 0.120520E+09 | 0.110614E+10 |
December | 0.258975E+09 | 0.00 | 0.258975E+09 | 84176803.64 | 0.128505E+10 |
Annual Sum or Average | 0.508654E+10 | 0.148767E+09 | 0.493778E+10 | 0.352231E+10 | 0.105561E+11 |
Minimum of Months | 0.258975E+09 | 0.00 | 0.258975E+09 | 84176803.64 | 0.523587E+09 |
Maximum of Months | 0.610777E+09 | 59579267.02 | 0.564867E+09 | 0.550261E+09 | 0.128505E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.833788E+09 | 0.445919E+09 | 0.387869E+09 | 0.823558E+09 | 0.125604E+10 |
February | 0.794442E+09 | 0.363929E+09 | 0.430513E+09 | 0.748600E+09 | 0.103995E+10 |
March | 0.106852E+10 | 0.476118E+09 | 0.592400E+09 | 0.108661E+10 | 0.115855E+10 |
April | 0.132199E+10 | 0.663035E+09 | 0.658950E+09 | 0.157442E+10 | 0.891251E+09 |
May | 0.128906E+10 | 0.537929E+09 | 0.751128E+09 | 0.146636E+10 | 0.836424E+09 |
June | 0.123970E+10 | 0.537854E+09 | 0.701842E+09 | 0.152081E+10 | 0.639710E+09 |
July | 0.145150E+10 | 0.721262E+09 | 0.730237E+09 | 0.195215E+10 | 0.578291E+09 |
August | 0.143353E+10 | 0.761448E+09 | 0.672085E+09 | 0.196457E+10 | 0.579141E+09 |
September | 0.101007E+10 | 0.462865E+09 | 0.547208E+09 | 0.127635E+10 | 0.684711E+09 |
October | 0.923880E+09 | 0.474849E+09 | 0.449031E+09 | 0.119557E+10 | 0.781751E+09 |
November | 0.815034E+09 | 0.414058E+09 | 0.400976E+09 | 0.818954E+09 | 0.110274E+10 |
December | 0.803450E+09 | 0.446396E+09 | 0.357054E+09 | 0.783266E+09 | 0.125582E+10 |
Annual Sum or Average | 0.129850E+11 | 0.630566E+10 | 0.667929E+10 | 0.152112E+11 | 0.108044E+11 |
Minimum of Months | 0.794442E+09 | 0.363929E+09 | 0.357054E+09 | 0.748600E+09 | 0.578291E+09 |
Maximum of Months | 0.145150E+10 | 0.761448E+09 | 0.751128E+09 | 0.196457E+10 | 0.125604E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.833788E+09 | 0.445919E+09 | 0.387869E+09 | 0.823558E+09 | 0.125604E+10 |
February | 0.794442E+09 | 0.363929E+09 | 0.430513E+09 | 0.748600E+09 | 0.103995E+10 |
March | 0.106852E+10 | 0.476118E+09 | 0.592400E+09 | 0.108661E+10 | 0.115855E+10 |
April | 0.132199E+10 | 0.663035E+09 | 0.658950E+09 | 0.157442E+10 | 0.891251E+09 |
May | 0.128906E+10 | 0.537929E+09 | 0.751128E+09 | 0.146636E+10 | 0.836424E+09 |
June | 0.123970E+10 | 0.537854E+09 | 0.701842E+09 | 0.152081E+10 | 0.639710E+09 |
July | 0.145150E+10 | 0.721262E+09 | 0.730237E+09 | 0.195215E+10 | 0.578291E+09 |
August | 0.143353E+10 | 0.761448E+09 | 0.672085E+09 | 0.196457E+10 | 0.579141E+09 |
September | 0.101007E+10 | 0.462865E+09 | 0.547208E+09 | 0.127635E+10 | 0.684711E+09 |
October | 0.923880E+09 | 0.474849E+09 | 0.449031E+09 | 0.119557E+10 | 0.781751E+09 |
November | 0.815034E+09 | 0.414058E+09 | 0.400976E+09 | 0.818954E+09 | 0.110274E+10 |
December | 0.803450E+09 | 0.446396E+09 | 0.357054E+09 | 0.783266E+09 | 0.125582E+10 |
Annual Sum or Average | 0.129850E+11 | 0.630566E+10 | 0.667929E+10 | 0.152112E+11 | 0.108044E+11 |
Minimum of Months | 0.794442E+09 | 0.363929E+09 | 0.357054E+09 | 0.748600E+09 | 0.578291E+09 |
Maximum of Months | 0.145150E+10 | 0.761448E+09 | 0.751128E+09 | 0.196457E+10 | 0.125604E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.833773E+09 | 0.445911E+09 | 0.387862E+09 | 0.823543E+09 | 0.125601E+10 |
February | 0.794427E+09 | 0.363922E+09 | 0.430505E+09 | 0.748586E+09 | 0.103993E+10 |
March | 0.106850E+10 | 0.476110E+09 | 0.592389E+09 | 0.108659E+10 | 0.115852E+10 |
April | 0.132196E+10 | 0.663023E+09 | 0.658938E+09 | 0.157439E+10 | 0.891234E+09 |
May | 0.128903E+10 | 0.537919E+09 | 0.751114E+09 | 0.146634E+10 | 0.836409E+09 |
June | 0.123967E+10 | 0.537844E+09 | 0.701830E+09 | 0.152078E+10 | 0.639699E+09 |
July | 0.145147E+10 | 0.721249E+09 | 0.730224E+09 | 0.195212E+10 | 0.578280E+09 |
August | 0.143351E+10 | 0.761434E+09 | 0.672072E+09 | 0.196453E+10 | 0.579130E+09 |
September | 0.101005E+10 | 0.462857E+09 | 0.547198E+09 | 0.127633E+10 | 0.684699E+09 |
October | 0.923863E+09 | 0.474840E+09 | 0.449023E+09 | 0.119555E+10 | 0.781737E+09 |
November | 0.815019E+09 | 0.414050E+09 | 0.400968E+09 | 0.818939E+09 | 0.110272E+10 |
December | 0.803435E+09 | 0.446388E+09 | 0.357047E+09 | 0.783251E+09 | 0.125580E+10 |
Annual Sum or Average | 0.129847E+11 | 0.630555E+10 | 0.667917E+10 | 0.152109E+11 | 0.108042E+11 |
Minimum of Months | 0.794427E+09 | 0.363922E+09 | 0.357047E+09 | 0.748586E+09 | 0.578280E+09 |
Maximum of Months | 0.145147E+10 | 0.761434E+09 | 0.751114E+09 | 0.196453E+10 | 0.125601E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183647E+10 | 0.134727E+10 | 0.489199E+09 | 0.252018E+10 | 0.112876E+10 |
February | 0.130356E+10 | 0.803014E+09 | 0.500545E+09 | 0.160786E+10 | 0.948134E+09 |
March | 0.115019E+10 | 0.555498E+09 | 0.594693E+09 | 0.128732E+10 | 0.110688E+10 |
April | 0.929768E+09 | 0.354284E+09 | 0.575485E+09 | 0.945022E+09 | 0.875231E+09 |
May | 0.684103E+09 | 83902675.40 | 0.600200E+09 | 0.547531E+09 | 0.800944E+09 |
June | 0.580750E+09 | 34775604.69 | 0.545975E+09 | 0.489947E+09 | 0.608880E+09 |
July | 0.635598E+09 | 71179917.02 | 0.564418E+09 | 0.614540E+09 | 0.548949E+09 |
August | 0.816654E+09 | 0.257300E+09 | 0.559353E+09 | 0.907124E+09 | 0.572482E+09 |
September | 0.109998E+10 | 0.557238E+09 | 0.542741E+09 | 0.141006E+10 | 0.653450E+09 |
October | 0.144608E+10 | 0.966780E+09 | 0.479299E+09 | 0.206606E+10 | 0.745052E+09 |
November | 0.170120E+10 | 0.120115E+10 | 0.500044E+09 | 0.229846E+10 | 0.101394E+10 |
December | 0.196188E+10 | 0.149336E+10 | 0.468517E+09 | 0.272011E+10 | 0.114839E+10 |
Annual Sum or Average | 0.141462E+11 | 0.772576E+10 | 0.642047E+10 | 0.174142E+11 | 0.101511E+11 |
Minimum of Months | 0.580750E+09 | 34775604.69 | 0.468517E+09 | 0.489947E+09 | 0.548949E+09 |
Maximum of Months | 0.196188E+10 | 0.149336E+10 | 0.600200E+09 | 0.272011E+10 | 0.114839E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183647E+10 | 0.134727E+10 | 0.489199E+09 | 0.252018E+10 | 0.112876E+10 |
February | 0.130356E+10 | 0.803013E+09 | 0.500545E+09 | 0.160786E+10 | 0.948134E+09 |
March | 0.115019E+10 | 0.555497E+09 | 0.594692E+09 | 0.128732E+10 | 0.110688E+10 |
April | 0.929767E+09 | 0.354283E+09 | 0.575484E+09 | 0.945021E+09 | 0.875231E+09 |
May | 0.684102E+09 | 83902574.73 | 0.600199E+09 | 0.547530E+09 | 0.800944E+09 |
June | 0.580750E+09 | 34775562.96 | 0.545974E+09 | 0.489947E+09 | 0.608880E+09 |
July | 0.635598E+09 | 71179831.61 | 0.564418E+09 | 0.614539E+09 | 0.548949E+09 |
August | 0.816653E+09 | 0.257300E+09 | 0.559353E+09 | 0.907123E+09 | 0.572482E+09 |
September | 0.109998E+10 | 0.557238E+09 | 0.542741E+09 | 0.141006E+10 | 0.653450E+09 |
October | 0.144608E+10 | 0.966779E+09 | 0.479299E+09 | 0.206605E+10 | 0.745052E+09 |
November | 0.170119E+10 | 0.120115E+10 | 0.500043E+09 | 0.229845E+10 | 0.101394E+10 |
December | 0.196188E+10 | 0.149336E+10 | 0.468517E+09 | 0.272011E+10 | 0.114839E+10 |
Annual Sum or Average | 0.141462E+11 | 0.772575E+10 | 0.642046E+10 | 0.174142E+11 | 0.101511E+11 |
Minimum of Months | 0.580750E+09 | 34775562.96 | 0.468517E+09 | 0.489947E+09 | 0.548949E+09 |
Maximum of Months | 0.196188E+10 | 0.149336E+10 | 0.600199E+09 | 0.272011E+10 | 0.114839E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183647E+10 | 0.134727E+10 | 0.489199E+09 | 0.252018E+10 | 0.112876E+10 |
February | 0.130356E+10 | 0.803014E+09 | 0.500545E+09 | 0.160786E+10 | 0.948134E+09 |
March | 0.115019E+10 | 0.555498E+09 | 0.594693E+09 | 0.128732E+10 | 0.110688E+10 |
April | 0.929768E+09 | 0.354284E+09 | 0.575485E+09 | 0.945022E+09 | 0.875231E+09 |
May | 0.684103E+09 | 83902675.40 | 0.600200E+09 | 0.547531E+09 | 0.800944E+09 |
June | 0.580750E+09 | 34775604.69 | 0.545975E+09 | 0.489947E+09 | 0.608880E+09 |
July | 0.635598E+09 | 71179917.02 | 0.564418E+09 | 0.614540E+09 | 0.548949E+09 |
August | 0.816654E+09 | 0.257300E+09 | 0.559353E+09 | 0.907124E+09 | 0.572482E+09 |
September | 0.109998E+10 | 0.557238E+09 | 0.542741E+09 | 0.141006E+10 | 0.653450E+09 |
October | 0.144608E+10 | 0.966780E+09 | 0.479299E+09 | 0.206606E+10 | 0.745052E+09 |
November | 0.170120E+10 | 0.120115E+10 | 0.500044E+09 | 0.229846E+10 | 0.101394E+10 |
December | 0.196188E+10 | 0.149336E+10 | 0.468517E+09 | 0.272011E+10 | 0.114839E+10 |
Annual Sum or Average | 0.141462E+11 | 0.772576E+10 | 0.642047E+10 | 0.174142E+11 | 0.101511E+11 |
Minimum of Months | 0.580750E+09 | 34775604.69 | 0.468517E+09 | 0.489947E+09 | 0.548949E+09 |
Maximum of Months | 0.196188E+10 | 0.149336E+10 | 0.600200E+09 | 0.272011E+10 | 0.114839E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183647E+10 | 0.134727E+10 | 0.489199E+09 | 0.252018E+10 | 0.112876E+10 |
February | 0.130356E+10 | 0.803013E+09 | 0.500545E+09 | 0.160786E+10 | 0.948134E+09 |
March | 0.115019E+10 | 0.555497E+09 | 0.594692E+09 | 0.128732E+10 | 0.110688E+10 |
April | 0.929767E+09 | 0.354283E+09 | 0.575484E+09 | 0.945021E+09 | 0.875231E+09 |
May | 0.684102E+09 | 83902574.73 | 0.600199E+09 | 0.547530E+09 | 0.800944E+09 |
June | 0.580750E+09 | 34775562.96 | 0.545974E+09 | 0.489947E+09 | 0.608880E+09 |
July | 0.635598E+09 | 71179831.61 | 0.564418E+09 | 0.614539E+09 | 0.548949E+09 |
August | 0.816653E+09 | 0.257300E+09 | 0.559353E+09 | 0.907123E+09 | 0.572482E+09 |
September | 0.109998E+10 | 0.557238E+09 | 0.542741E+09 | 0.141006E+10 | 0.653450E+09 |
October | 0.144608E+10 | 0.966779E+09 | 0.479299E+09 | 0.206605E+10 | 0.745052E+09 |
November | 0.170119E+10 | 0.120115E+10 | 0.500043E+09 | 0.229845E+10 | 0.101394E+10 |
December | 0.196188E+10 | 0.149336E+10 | 0.468517E+09 | 0.272011E+10 | 0.114839E+10 |
Annual Sum or Average | 0.141462E+11 | 0.772575E+10 | 0.642046E+10 | 0.174142E+11 | 0.101511E+11 |
Minimum of Months | 0.580750E+09 | 34775562.96 | 0.468517E+09 | 0.489947E+09 | 0.548949E+09 |
Maximum of Months | 0.196188E+10 | 0.149336E+10 | 0.600199E+09 | 0.272011E+10 | 0.114839E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183640E+10 | 0.134722E+10 | 0.489180E+09 | 0.252008E+10 | 0.112871E+10 |
February | 0.130351E+10 | 0.802982E+09 | 0.500525E+09 | 0.160779E+10 | 0.948096E+09 |
March | 0.115014E+10 | 0.555476E+09 | 0.594669E+09 | 0.128727E+10 | 0.110684E+10 |
April | 0.929731E+09 | 0.354269E+09 | 0.575462E+09 | 0.944984E+09 | 0.875196E+09 |
May | 0.684075E+09 | 83899293.76 | 0.600176E+09 | 0.547509E+09 | 0.800912E+09 |
June | 0.580727E+09 | 34774203.08 | 0.545953E+09 | 0.489928E+09 | 0.608855E+09 |
July | 0.635572E+09 | 71177048.15 | 0.564395E+09 | 0.614515E+09 | 0.548927E+09 |
August | 0.816621E+09 | 0.257290E+09 | 0.559331E+09 | 0.907088E+09 | 0.572459E+09 |
September | 0.109994E+10 | 0.557216E+09 | 0.542719E+09 | 0.141000E+10 | 0.653423E+09 |
October | 0.144602E+10 | 0.966741E+09 | 0.479280E+09 | 0.206597E+10 | 0.745022E+09 |
November | 0.170113E+10 | 0.120110E+10 | 0.500024E+09 | 0.229836E+10 | 0.101390E+10 |
December | 0.196180E+10 | 0.149330E+10 | 0.468499E+09 | 0.272000E+10 | 0.114834E+10 |
Annual Sum or Average | 0.141457E+11 | 0.772545E+10 | 0.642021E+10 | 0.174135E+11 | 0.101507E+11 |
Minimum of Months | 0.580727E+09 | 34774203.08 | 0.468499E+09 | 0.489928E+09 | 0.548927E+09 |
Maximum of Months | 0.196180E+10 | 0.149330E+10 | 0.600176E+09 | 0.272000E+10 | 0.114834E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.793628E+09 | 0.400264E+09 | 0.393364E+09 | 0.814405E+09 | 0.141883E+10 |
February | 0.855175E+09 | 0.394781E+09 | 0.460394E+09 | 0.854509E+09 | 0.122132E+10 |
March | 0.108537E+10 | 0.480217E+09 | 0.605150E+09 | 0.110223E+10 | 0.138978E+10 |
April | 0.144794E+10 | 0.753962E+09 | 0.693977E+09 | 0.172512E+10 | 0.111338E+10 |
May | 0.146966E+10 | 0.678813E+09 | 0.790845E+09 | 0.172752E+10 | 0.954145E+09 |
June | 0.150668E+10 | 0.753273E+09 | 0.753406E+09 | 0.189028E+10 | 0.758206E+09 |
July | 0.164812E+10 | 0.881860E+09 | 0.766256E+09 | 0.218971E+10 | 0.715257E+09 |
August | 0.154634E+10 | 0.838061E+09 | 0.708279E+09 | 0.207443E+10 | 0.757867E+09 |
September | 0.128132E+10 | 0.685661E+09 | 0.595662E+09 | 0.167757E+10 | 0.787174E+09 |
October | 0.101209E+10 | 0.552564E+09 | 0.459531E+09 | 0.132569E+10 | 0.943678E+09 |
November | 0.884701E+09 | 0.462748E+09 | 0.421953E+09 | 0.939233E+09 | 0.133033E+10 |
December | 0.807395E+09 | 0.433040E+09 | 0.374354E+09 | 0.821650E+09 | 0.156136E+10 |
Annual Sum or Average | 0.143384E+11 | 0.731525E+10 | 0.702317E+10 | 0.171423E+11 | 0.129513E+11 |
Minimum of Months | 0.793628E+09 | 0.394781E+09 | 0.374354E+09 | 0.814405E+09 | 0.715257E+09 |
Maximum of Months | 0.164812E+10 | 0.881860E+09 | 0.790845E+09 | 0.218971E+10 | 0.156136E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.793628E+09 | 0.400264E+09 | 0.393364E+09 | 0.814405E+09 | 0.141883E+10 |
February | 0.855175E+09 | 0.394781E+09 | 0.460394E+09 | 0.854509E+09 | 0.122132E+10 |
March | 0.108537E+10 | 0.480217E+09 | 0.605150E+09 | 0.110223E+10 | 0.138978E+10 |
April | 0.144794E+10 | 0.753962E+09 | 0.693977E+09 | 0.172512E+10 | 0.111338E+10 |
May | 0.146966E+10 | 0.678813E+09 | 0.790845E+09 | 0.172752E+10 | 0.954145E+09 |
June | 0.150668E+10 | 0.753273E+09 | 0.753406E+09 | 0.189028E+10 | 0.758206E+09 |
July | 0.164812E+10 | 0.881860E+09 | 0.766256E+09 | 0.218971E+10 | 0.715257E+09 |
August | 0.154634E+10 | 0.838061E+09 | 0.708279E+09 | 0.207443E+10 | 0.757867E+09 |
September | 0.128132E+10 | 0.685661E+09 | 0.595662E+09 | 0.167757E+10 | 0.787174E+09 |
October | 0.101209E+10 | 0.552564E+09 | 0.459531E+09 | 0.132569E+10 | 0.943678E+09 |
November | 0.884701E+09 | 0.462748E+09 | 0.421953E+09 | 0.939233E+09 | 0.133033E+10 |
December | 0.807395E+09 | 0.433040E+09 | 0.374354E+09 | 0.821650E+09 | 0.156136E+10 |
Annual Sum or Average | 0.143384E+11 | 0.731525E+10 | 0.702317E+10 | 0.171423E+11 | 0.129513E+11 |
Minimum of Months | 0.793628E+09 | 0.394781E+09 | 0.374354E+09 | 0.814405E+09 | 0.715257E+09 |
Maximum of Months | 0.164812E+10 | 0.881860E+09 | 0.790845E+09 | 0.218971E+10 | 0.156136E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.793614E+09 | 0.400256E+09 | 0.393357E+09 | 0.814390E+09 | 0.141880E+10 |
February | 0.855160E+09 | 0.394774E+09 | 0.460386E+09 | 0.854493E+09 | 0.122130E+10 |
March | 0.108535E+10 | 0.480208E+09 | 0.605139E+09 | 0.110221E+10 | 0.138976E+10 |
April | 0.144791E+10 | 0.753949E+09 | 0.693964E+09 | 0.172509E+10 | 0.111336E+10 |
May | 0.146963E+10 | 0.678801E+09 | 0.790830E+09 | 0.172749E+10 | 0.954128E+09 |
June | 0.150665E+10 | 0.753259E+09 | 0.753392E+09 | 0.189025E+10 | 0.758192E+09 |
July | 0.164809E+10 | 0.881844E+09 | 0.766242E+09 | 0.218967E+10 | 0.715244E+09 |
August | 0.154631E+10 | 0.838046E+09 | 0.708266E+09 | 0.207439E+10 | 0.757853E+09 |
September | 0.128130E+10 | 0.685649E+09 | 0.595651E+09 | 0.167754E+10 | 0.787159E+09 |
October | 0.101208E+10 | 0.552554E+09 | 0.459523E+09 | 0.132567E+10 | 0.943660E+09 |
November | 0.884685E+09 | 0.462740E+09 | 0.421945E+09 | 0.939216E+09 | 0.133031E+10 |
December | 0.807380E+09 | 0.433033E+09 | 0.374348E+09 | 0.821635E+09 | 0.156133E+10 |
Annual Sum or Average | 0.143382E+11 | 0.731511E+10 | 0.702304E+10 | 0.171420E+11 | 0.129511E+11 |
Minimum of Months | 0.793614E+09 | 0.394774E+09 | 0.374348E+09 | 0.814390E+09 | 0.715244E+09 |
Maximum of Months | 0.164809E+10 | 0.881844E+09 | 0.790830E+09 | 0.218967E+10 | 0.156133E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139101E+10 | 0.00 | 0.139101E+10 | 0.679840E+09 | 0.553134E+10 |
February | 0.157711E+10 | 0.00 | 0.157711E+10 | 0.724297E+09 | 0.453151E+10 |
March | 0.213969E+10 | 0.00 | 0.213969E+10 | 0.121405E+10 | 0.513927E+10 |
April | 0.238555E+10 | 9074722.34 | 0.237647E+10 | 0.171488E+10 | 0.391898E+10 |
May | 0.296186E+10 | 0.137450E+09 | 0.282441E+10 | 0.211406E+10 | 0.354761E+10 |
June | 0.305397E+10 | 0.297905E+09 | 0.275607E+10 | 0.257342E+10 | 0.264769E+10 |
July | 0.298797E+10 | 0.249731E+09 | 0.273824E+10 | 0.290076E+10 | 0.239814E+10 |
August | 0.248174E+10 | 49385530.50 | 0.243235E+10 | 0.249515E+10 | 0.255316E+10 |
September | 0.203303E+10 | 310345.22 | 0.203272E+10 | 0.190249E+10 | 0.296674E+10 |
October | 0.166643E+10 | 0.00 | 0.166643E+10 | 0.174095E+10 | 0.342980E+10 |
November | 0.146016E+10 | 0.00 | 0.146016E+10 | 0.775882E+09 | 0.486355E+10 |
December | 0.129491E+10 | 0.00 | 0.129491E+10 | 0.620637E+09 | 0.554868E+10 |
Annual Sum or Average | 0.254334E+11 | 0.743857E+09 | 0.246896E+11 | 0.194564E+11 | 0.470765E+11 |
Minimum of Months | 0.129491E+10 | 0.00 | 0.129491E+10 | 0.620637E+09 | 0.239814E+10 |
Maximum of Months | 0.305397E+10 | 0.297905E+09 | 0.282441E+10 | 0.290076E+10 | 0.554868E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250134E+10 | 0.133774E+10 | 0.116360E+10 | 0.254937E+10 | 0.345891E+10 |
February | 0.238330E+10 | 0.109177E+10 | 0.129153E+10 | 0.230756E+10 | 0.285303E+10 |
March | 0.320552E+10 | 0.142834E+10 | 0.177718E+10 | 0.331628E+10 | 0.323378E+10 |
April | 0.396592E+10 | 0.198909E+10 | 0.197683E+10 | 0.472948E+10 | 0.253542E+10 |
May | 0.386713E+10 | 0.161377E+10 | 0.225336E+10 | 0.441164E+10 | 0.238138E+10 |
June | 0.371905E+10 | 0.161354E+10 | 0.210551E+10 | 0.456093E+10 | 0.182483E+10 |
July | 0.435445E+10 | 0.216376E+10 | 0.219069E+10 | 0.583192E+10 | 0.167676E+10 |
August | 0.430055E+10 | 0.228432E+10 | 0.201623E+10 | 0.586228E+10 | 0.171695E+10 |
September | 0.303019E+10 | 0.138858E+10 | 0.164161E+10 | 0.384471E+10 | 0.192970E+10 |
October | 0.277161E+10 | 0.142453E+10 | 0.134708E+10 | 0.361519E+10 | 0.219376E+10 |
November | 0.244508E+10 | 0.124216E+10 | 0.120291E+10 | 0.252194E+10 | 0.305722E+10 |
December | 0.241032E+10 | 0.133917E+10 | 0.107115E+10 | 0.244044E+10 | 0.345024E+10 |
Annual Sum or Average | 0.389545E+11 | 0.189168E+11 | 0.200377E+11 | 0.459917E+11 | 0.303120E+11 |
Minimum of Months | 0.238330E+10 | 0.109177E+10 | 0.107115E+10 | 0.230756E+10 | 0.167676E+10 |
Maximum of Months | 0.435445E+10 | 0.228432E+10 | 0.225336E+10 | 0.586228E+10 | 0.345891E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.918225E+10 | 0.673628E+10 | 0.244597E+10 | 0.124947E+11 | 0.556215E+10 |
February | 0.651772E+10 | 0.401502E+10 | 0.250270E+10 | 0.797774E+10 | 0.457071E+10 |
March | 0.575088E+10 | 0.277746E+10 | 0.297343E+10 | 0.643738E+10 | 0.528413E+10 |
April | 0.464879E+10 | 0.177140E+10 | 0.287739E+10 | 0.476554E+10 | 0.413391E+10 |
May | 0.342047E+10 | 0.419508E+09 | 0.300096E+10 | 0.278510E+10 | 0.383355E+10 |
June | 0.290372E+10 | 0.173876E+09 | 0.272984E+10 | 0.251409E+10 | 0.287144E+10 |
July | 0.317795E+10 | 0.355895E+09 | 0.282206E+10 | 0.315804E+10 | 0.257578E+10 |
August | 0.408322E+10 | 0.128649E+10 | 0.279673E+10 | 0.459057E+10 | 0.272813E+10 |
September | 0.549983E+10 | 0.278616E+10 | 0.271367E+10 | 0.701480E+10 | 0.316594E+10 |
October | 0.723031E+10 | 0.483384E+10 | 0.239647E+10 | 0.102557E+11 | 0.362946E+10 |
November | 0.850588E+10 | 0.600569E+10 | 0.250019E+10 | 0.114058E+11 | 0.492350E+10 |
December | 0.980928E+10 | 0.746672E+10 | 0.234256E+10 | 0.135130E+11 | 0.556745E+10 |
Annual Sum or Average | 0.707303E+11 | 0.386283E+11 | 0.321020E+11 | 0.869124E+11 | 0.488461E+11 |
Minimum of Months | 0.290372E+10 | 0.173876E+09 | 0.234256E+10 | 0.251409E+10 | 0.257578E+10 |
Maximum of Months | 0.980928E+10 | 0.746672E+10 | 0.300096E+10 | 0.135130E+11 | 0.556745E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238086E+10 | 0.120078E+10 | 0.118008E+10 | 0.256833E+10 | 0.375051E+10 |
February | 0.256550E+10 | 0.118433E+10 | 0.138117E+10 | 0.269825E+10 | 0.310104E+10 |
March | 0.325607E+10 | 0.144064E+10 | 0.181543E+10 | 0.348839E+10 | 0.350704E+10 |
April | 0.434377E+10 | 0.226186E+10 | 0.208191E+10 | 0.534248E+10 | 0.283103E+10 |
May | 0.440893E+10 | 0.203642E+10 | 0.237251E+10 | 0.524905E+10 | 0.262263E+10 |
June | 0.451999E+10 | 0.225979E+10 | 0.226019E+10 | 0.575249E+10 | 0.200757E+10 |
July | 0.494430E+10 | 0.264555E+10 | 0.229875E+10 | 0.668819E+10 | 0.187352E+10 |
August | 0.463897E+10 | 0.251416E+10 | 0.212482E+10 | 0.636757E+10 | 0.194386E+10 |
September | 0.384393E+10 | 0.205696E+10 | 0.178697E+10 | 0.508700E+10 | 0.213368E+10 |
October | 0.303625E+10 | 0.165767E+10 | 0.137858E+10 | 0.410260E+10 | 0.243764E+10 |
November | 0.265408E+10 | 0.138823E+10 | 0.126585E+10 | 0.298446E+10 | 0.332864E+10 |
December | 0.242216E+10 | 0.129911E+10 | 0.112305E+10 | 0.266950E+10 | 0.380395E+10 |
Annual Sum or Average | 0.430148E+11 | 0.219455E+11 | 0.210693E+11 | 0.529983E+11 | 0.333411E+11 |
Minimum of Months | 0.238086E+10 | 0.118433E+10 | 0.112305E+10 | 0.256833E+10 | 0.187352E+10 |
Maximum of Months | 0.494430E+10 | 0.264555E+10 | 0.237251E+10 | 0.668819E+10 | 0.380395E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139101E+10 | 0.00 | 0.139101E+10 | 0.823021E+09 | 0.496800E+10 |
February | 0.157711E+10 | 0.00 | 0.157711E+10 | 0.840717E+09 | 0.409835E+10 |
March | 0.213969E+10 | 0.00 | 0.213969E+10 | 0.132261E+10 | 0.475992E+10 |
April | 0.238555E+10 | 9074722.34 | 0.237647E+10 | 0.176728E+10 | 0.370839E+10 |
May | 0.296186E+10 | 0.137450E+09 | 0.282441E+10 | 0.217121E+10 | 0.336103E+10 |
June | 0.305397E+10 | 0.297905E+09 | 0.275607E+10 | 0.257071E+10 | 0.255891E+10 |
July | 0.298797E+10 | 0.249731E+09 | 0.273824E+10 | 0.286166E+10 | 0.234532E+10 |
August | 0.248174E+10 | 49385530.50 | 0.243235E+10 | 0.246599E+10 | 0.249085E+10 |
September | 0.203303E+10 | 310345.22 | 0.203272E+10 | 0.192280E+10 | 0.282755E+10 |
October | 0.166643E+10 | 0.00 | 0.166643E+10 | 0.180428E+10 | 0.320394E+10 |
November | 0.146016E+10 | 0.00 | 0.146016E+10 | 0.898800E+09 | 0.442316E+10 |
December | 0.129491E+10 | 0.00 | 0.129491E+10 | 0.765952E+09 | 0.498550E+10 |
Annual Sum or Average | 0.254334E+11 | 0.743857E+09 | 0.246896E+11 | 0.202150E+11 | 0.437309E+11 |
Minimum of Months | 0.129491E+10 | 0.00 | 0.129491E+10 | 0.765952E+09 | 0.234532E+10 |
Maximum of Months | 0.305397E+10 | 0.297905E+09 | 0.282441E+10 | 0.286166E+10 | 0.498550E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250134E+10 | 0.133774E+10 | 0.116360E+10 | 0.267833E+10 | 0.315014E+10 |
February | 0.238330E+10 | 0.109177E+10 | 0.129153E+10 | 0.239294E+10 | 0.262080E+10 |
March | 0.320552E+10 | 0.142834E+10 | 0.177718E+10 | 0.339170E+10 | 0.303756E+10 |
April | 0.396592E+10 | 0.198909E+10 | 0.197683E+10 | 0.475578E+10 | 0.243036E+10 |
May | 0.386713E+10 | 0.161377E+10 | 0.225336E+10 | 0.444415E+10 | 0.228989E+10 |
June | 0.371905E+10 | 0.161354E+10 | 0.210551E+10 | 0.455256E+10 | 0.178280E+10 |
July | 0.435445E+10 | 0.216376E+10 | 0.219069E+10 | 0.580008E+10 | 0.165499E+10 |
August | 0.430055E+10 | 0.228432E+10 | 0.201623E+10 | 0.583587E+10 | 0.169128E+10 |
September | 0.303019E+10 | 0.138858E+10 | 0.164161E+10 | 0.384955E+10 | 0.185816E+10 |
October | 0.277161E+10 | 0.142453E+10 | 0.134708E+10 | 0.365094E+10 | 0.207790E+10 |
November | 0.244508E+10 | 0.124216E+10 | 0.120291E+10 | 0.262142E+10 | 0.282590E+10 |
December | 0.241032E+10 | 0.133917E+10 | 0.107115E+10 | 0.257401E+10 | 0.314733E+10 |
Annual Sum or Average | 0.389545E+11 | 0.189168E+11 | 0.200377E+11 | 0.465473E+11 | 0.285671E+11 |
Minimum of Months | 0.238330E+10 | 0.109177E+10 | 0.107115E+10 | 0.239294E+10 | 0.165499E+10 |
Maximum of Months | 0.435445E+10 | 0.228432E+10 | 0.225336E+10 | 0.583587E+10 | 0.315014E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.918225E+10 | 0.673628E+10 | 0.244597E+10 | 0.126657E+11 | 0.510778E+10 |
February | 0.651772E+10 | 0.401502E+10 | 0.250270E+10 | 0.808987E+10 | 0.420276E+10 |
March | 0.575088E+10 | 0.277746E+10 | 0.297343E+10 | 0.653392E+10 | 0.493992E+10 |
April | 0.464879E+10 | 0.177140E+10 | 0.287739E+10 | 0.480919E+10 | 0.393399E+10 |
May | 0.342047E+10 | 0.419508E+09 | 0.300096E+10 | 0.283876E+10 | 0.365182E+10 |
June | 0.290372E+10 | 0.173876E+09 | 0.272984E+10 | 0.251615E+10 | 0.278613E+10 |
July | 0.317795E+10 | 0.355895E+09 | 0.282206E+10 | 0.313075E+10 | 0.253007E+10 |
August | 0.408322E+10 | 0.128649E+10 | 0.279673E+10 | 0.456721E+10 | 0.266940E+10 |
September | 0.549983E+10 | 0.278616E+10 | 0.271367E+10 | 0.701808E+10 | 0.303582E+10 |
October | 0.723031E+10 | 0.483384E+10 | 0.239647E+10 | 0.103044E+11 | 0.343501E+10 |
November | 0.850588E+10 | 0.600569E+10 | 0.250019E+10 | 0.115206E+11 | 0.458291E+10 |
December | 0.980928E+10 | 0.746672E+10 | 0.234256E+10 | 0.136796E+11 | 0.513870E+10 |
Annual Sum or Average | 0.707303E+11 | 0.386283E+11 | 0.321020E+11 | 0.876741E+11 | 0.460143E+11 |
Minimum of Months | 0.290372E+10 | 0.173876E+09 | 0.234256E+10 | 0.251615E+10 | 0.253007E+10 |
Maximum of Months | 0.980928E+10 | 0.746672E+10 | 0.300096E+10 | 0.136796E+11 | 0.513870E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238086E+10 | 0.120078E+10 | 0.118008E+10 | 0.264020E+10 | 0.345568E+10 |
February | 0.256550E+10 | 0.118433E+10 | 0.138117E+10 | 0.275295E+10 | 0.287082E+10 |
March | 0.325607E+10 | 0.144064E+10 | 0.181543E+10 | 0.353647E+10 | 0.329234E+10 |
April | 0.434377E+10 | 0.226186E+10 | 0.208191E+10 | 0.535475E+10 | 0.270240E+10 |
May | 0.440893E+10 | 0.203642E+10 | 0.237251E+10 | 0.526148E+10 | 0.250680E+10 |
June | 0.451999E+10 | 0.225979E+10 | 0.226019E+10 | 0.573442E+10 | 0.194227E+10 |
July | 0.494430E+10 | 0.264555E+10 | 0.229875E+10 | 0.665303E+10 | 0.182749E+10 |
August | 0.463897E+10 | 0.251416E+10 | 0.212482E+10 | 0.633759E+10 | 0.189414E+10 |
September | 0.384393E+10 | 0.205696E+10 | 0.178697E+10 | 0.508396E+10 | 0.204734E+10 |
October | 0.303625E+10 | 0.165767E+10 | 0.137858E+10 | 0.412947E+10 | 0.230649E+10 |
November | 0.265408E+10 | 0.138823E+10 | 0.126585E+10 | 0.304054E+10 | 0.309513E+10 |
December | 0.242216E+10 | 0.129911E+10 | 0.112305E+10 | 0.274369E+10 | 0.350550E+10 |
Annual Sum or Average | 0.430148E+11 | 0.219455E+11 | 0.210693E+11 | 0.532685E+11 | 0.314464E+11 |
Minimum of Months | 0.238086E+10 | 0.118433E+10 | 0.112305E+10 | 0.264020E+10 | 0.182749E+10 |
Maximum of Months | 0.494430E+10 | 0.264555E+10 | 0.237251E+10 | 0.665303E+10 | 0.350550E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 194.83 | 2329.52 | 519.34 | 0.00 | 519.34 | 0.00 | 0.00 |
February | 236.04 | 2134.57 | 651.92 | 0.00 | 651.92 | 0.00 | 0.00 |
March | 383.06 | 2162.59 | 798.87 | 0.00 | 798.87 | 0.00 | 0.00 |
April | 590.04 | 1696.81 | 920.35 | 3.50 | 916.85 | 0.00 | 0.00 |
May | 738.91 | 1436.51 | 1105.84 | 51.32 | 1054.52 | 0.00 | 0.00 |
June | 947.75 | 1109.16 | 1178.23 | 114.93 | 1063.30 | 0.00 | 0.00 |
July | 1027.25 | 977.46 | 1115.59 | 93.24 | 1022.35 | 0.00 | 0.00 |
August | 879.82 | 1044.18 | 926.58 | 18.44 | 908.14 | 0.00 | 0.00 |
September | 693.85 | 1256.84 | 784.35 | 0.12 | 784.23 | 0.00 | 0.00 |
October | 596.76 | 1432.56 | 622.17 | 0.00 | 622.17 | 0.00 | 0.00 |
November | 232.49 | 2133.83 | 563.33 | 0.00 | 563.33 | 0.00 | 0.00 |
December | 157.15 | 2398.98 | 483.47 | 0.00 | 483.47 | 0.00 | 0.00 |
Annual Sum or Average | 558.48 | 1673.71 | 806.49 | 23.59 | 782.90 | 0.00 | 0.00 |
Minimum of Months | 157.15 | 977.46 | 483.47 | 0.00 | 483.47 | 0.00 | 0.00 |
Maximum of Months | 1027.25 | 2398.98 | 1178.23 | 114.93 | 1063.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 922.44 | 1406.84 | 933.90 | 499.46 | 434.44 | 0.00 | 0.00 |
February | 928.32 | 1289.62 | 985.16 | 451.30 | 533.87 | 0.00 | 0.00 |
March | 1217.08 | 1297.65 | 1196.81 | 533.28 | 663.53 | 0.00 | 0.00 |
April | 1822.23 | 1031.53 | 1530.07 | 767.40 | 762.67 | 0.00 | 0.00 |
May | 1642.42 | 936.85 | 1443.83 | 602.52 | 841.31 | 0.00 | 0.00 |
June | 1760.18 | 740.40 | 1434.82 | 622.51 | 812.31 | 0.00 | 0.00 |
July | 2186.54 | 647.72 | 1625.77 | 807.86 | 817.91 | 0.00 | 0.00 |
August | 2200.44 | 648.68 | 1605.65 | 852.87 | 752.78 | 0.00 | 0.00 |
September | 1477.25 | 792.49 | 1169.06 | 535.72 | 633.34 | 0.00 | 0.00 |
October | 1339.12 | 875.61 | 1034.81 | 531.86 | 502.94 | 0.00 | 0.00 |
November | 947.86 | 1276.31 | 943.32 | 479.23 | 464.09 | 0.00 | 0.00 |
December | 877.31 | 1406.60 | 899.92 | 499.99 | 399.92 | 0.00 | 0.00 |
Annual Sum or Average | 1447.02 | 1027.81 | 1235.24 | 599.85 | 635.39 | 0.00 | 0.00 |
Minimum of Months | 877.31 | 647.72 | 899.92 | 451.30 | 399.92 | 0.00 | 0.00 |
Maximum of Months | 2200.44 | 1406.84 | 1625.77 | 852.87 | 841.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4704.60 | 2107.13 | 3428.27 | 2515.05 | 913.22 | 0.00 | 0.00 |
February | 3323.09 | 1959.59 | 2694.17 | 1659.65 | 1034.52 | 0.00 | 0.00 |
March | 2403.13 | 2066.30 | 2147.14 | 1036.99 | 1110.15 | 0.00 | 0.00 |
April | 1822.94 | 1688.32 | 1793.52 | 683.41 | 1110.11 | 0.00 | 0.00 |
May | 1022.11 | 1495.18 | 1277.06 | 156.63 | 1120.44 | 0.00 | 0.00 |
June | 945.11 | 1174.53 | 1120.26 | 67.08 | 1053.18 | 0.00 | 0.00 |
July | 1147.20 | 1024.76 | 1186.52 | 132.88 | 1053.64 | 0.00 | 0.00 |
August | 1693.39 | 1068.69 | 1524.50 | 480.32 | 1044.18 | 0.00 | 0.00 |
September | 2720.00 | 1260.50 | 2121.86 | 1074.91 | 1046.95 | 0.00 | 0.00 |
October | 3856.85 | 1390.84 | 2699.50 | 1804.76 | 894.74 | 0.00 | 0.00 |
November | 4433.71 | 1955.89 | 3281.60 | 2317.02 | 964.58 | 0.00 | 0.00 |
December | 5077.82 | 2143.78 | 3662.38 | 2787.76 | 874.61 | 0.00 | 0.00 |
Annual Sum or Average | 2760.98 | 1609.43 | 2242.85 | 1224.90 | 1017.95 | 0.00 | 0.00 |
Minimum of Months | 945.11 | 1024.76 | 1120.26 | 67.08 | 874.61 | 0.00 | 0.00 |
Maximum of Months | 5077.82 | 2143.78 | 3662.38 | 2787.76 | 1120.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 912.19 | 1589.18 | 888.91 | 448.32 | 440.59 | 0.00 | 0.00 |
February | 1059.65 | 1514.53 | 1060.48 | 489.56 | 570.92 | 0.00 | 0.00 |
March | 1234.57 | 1556.65 | 1215.68 | 537.87 | 677.81 | 0.00 | 0.00 |
April | 1996.66 | 1288.63 | 1675.85 | 872.64 | 803.21 | 0.00 | 0.00 |
May | 1934.93 | 1068.70 | 1646.11 | 760.32 | 885.80 | 0.00 | 0.00 |
June | 2187.81 | 877.55 | 1743.83 | 871.84 | 871.99 | 0.00 | 0.00 |
July | 2452.61 | 801.13 | 1846.00 | 987.74 | 858.26 | 0.00 | 0.00 |
August | 2323.49 | 848.86 | 1732.00 | 938.68 | 793.32 | 0.00 | 0.00 |
September | 1941.62 | 911.08 | 1483.00 | 793.58 | 689.42 | 0.00 | 0.00 |
October | 1484.86 | 1056.98 | 1133.61 | 618.91 | 514.70 | 0.00 | 0.00 |
November | 1087.07 | 1539.73 | 1023.95 | 535.59 | 488.37 | 0.00 | 0.00 |
December | 920.30 | 1748.82 | 904.33 | 485.03 | 419.30 | 0.00 | 0.00 |
Annual Sum or Average | 1630.73 | 1232.05 | 1364.00 | 695.89 | 668.11 | 0.00 | 0.00 |
Minimum of Months | 912.19 | 801.13 | 888.91 | 448.32 | 419.30 | 0.00 | 0.00 |
Maximum of Months | 2452.61 | 1748.82 | 1846.00 | 987.74 | 885.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 253.82 | 2065.16 | 519.34 | 0.00 | 519.34 | 0.00 | 0.00 |
February | 299.40 | 1873.14 | 651.91 | 0.00 | 651.91 | 0.00 | 0.00 |
March | 453.27 | 1918.78 | 798.87 | 0.00 | 798.87 | 0.00 | 0.00 |
April | 661.60 | 1511.95 | 920.35 | 3.50 | 916.85 | 0.00 | 0.00 |
May | 789.30 | 1324.52 | 1105.83 | 51.32 | 1054.52 | 0.00 | 0.00 |
June | 992.83 | 1021.49 | 1178.23 | 114.93 | 1063.30 | 0.00 | 0.00 |
July | 1083.02 | 895.36 | 1115.58 | 93.24 | 1022.34 | 0.00 | 0.00 |
August | 931.58 | 953.24 | 926.58 | 18.44 | 908.14 | 0.00 | 0.00 |
September | 733.98 | 1144.58 | 784.35 | 0.12 | 784.23 | 0.00 | 0.00 |
October | 650.00 | 1280.54 | 622.17 | 0.00 | 622.17 | 0.00 | 0.00 |
November | 299.34 | 1876.37 | 563.33 | 0.00 | 563.33 | 0.00 | 0.00 |
December | 231.72 | 2071.64 | 483.46 | 0.00 | 483.46 | 0.00 | 0.00 |
Annual Sum or Average | 616.96 | 1492.79 | 806.49 | 23.59 | 782.90 | 0.00 | 0.00 |
Minimum of Months | 231.72 | 895.36 | 483.46 | 0.00 | 483.46 | 0.00 | 0.00 |
Maximum of Months | 1083.02 | 2071.64 | 1178.23 | 114.93 | 1063.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 951.83 | 1291.41 | 933.89 | 499.46 | 434.44 | 0.00 | 0.00 |
February | 953.85 | 1179.33 | 985.16 | 451.30 | 533.87 | 0.00 | 0.00 |
March | 1238.16 | 1207.35 | 1196.80 | 533.28 | 663.52 | 0.00 | 0.00 |
April | 1824.64 | 978.17 | 1530.06 | 767.39 | 762.67 | 0.00 | 0.00 |
May | 1647.12 | 889.11 | 1443.82 | 602.51 | 841.31 | 0.00 | 0.00 |
June | 1759.62 | 704.02 | 1434.82 | 622.51 | 812.31 | 0.00 | 0.00 |
July | 2177.39 | 626.03 | 1625.77 | 807.86 | 817.91 | 0.00 | 0.00 |
August | 2188.73 | 641.04 | 1605.64 | 852.87 | 752.78 | 0.00 | 0.00 |
September | 1483.30 | 744.48 | 1169.05 | 535.72 | 633.34 | 0.00 | 0.00 |
October | 1349.76 | 819.06 | 1034.80 | 531.86 | 502.94 | 0.00 | 0.00 |
November | 972.97 | 1179.48 | 943.32 | 479.23 | 464.09 | 0.00 | 0.00 |
December | 911.16 | 1288.17 | 899.91 | 499.99 | 399.92 | 0.00 | 0.00 |
Annual Sum or Average | 1458.39 | 961.19 | 1235.24 | 599.85 | 635.39 | 0.00 | 0.00 |
Minimum of Months | 911.16 | 626.03 | 899.91 | 451.30 | 399.92 | 0.00 | 0.00 |
Maximum of Months | 2188.73 | 1291.41 | 1625.77 | 852.87 | 841.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4664.98 | 2076.67 | 3428.26 | 2515.04 | 913.22 | 0.00 | 0.00 |
February | 3297.68 | 1889.35 | 2694.16 | 1659.65 | 1034.51 | 0.00 | 0.00 |
March | 2403.44 | 1972.87 | 2147.13 | 1036.98 | 1110.15 | 0.00 | 0.00 |
April | 1838.56 | 1594.87 | 1793.51 | 683.41 | 1110.10 | 0.00 | 0.00 |
May | 1039.84 | 1431.28 | 1277.06 | 156.63 | 1120.43 | 0.00 | 0.00 |
June | 969.94 | 1107.81 | 1120.26 | 67.08 | 1053.18 | 0.00 | 0.00 |
July | 1179.08 | 961.68 | 1186.51 | 132.88 | 1053.64 | 0.00 | 0.00 |
August | 1713.92 | 1018.57 | 1524.50 | 480.32 | 1044.18 | 0.00 | 0.00 |
September | 2706.33 | 1221.43 | 2121.85 | 1074.91 | 1046.94 | 0.00 | 0.00 |
October | 3829.05 | 1355.09 | 2699.49 | 1804.75 | 894.74 | 0.00 | 0.00 |
November | 4400.37 | 1899.50 | 3281.59 | 2317.01 | 964.58 | 0.00 | 0.00 |
December | 5045.16 | 2078.65 | 3662.36 | 2787.75 | 874.61 | 0.00 | 0.00 |
Annual Sum or Average | 2755.97 | 1548.90 | 2242.84 | 1224.90 | 1017.95 | 0.00 | 0.00 |
Minimum of Months | 969.94 | 961.68 | 1120.26 | 67.08 | 874.61 | 0.00 | 0.00 |
Maximum of Months | 5045.16 | 2078.65 | 3662.36 | 2787.75 | 1120.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 958.90 | 1400.28 | 888.91 | 448.32 | 440.59 | 0.00 | 0.00 |
February | 1115.35 | 1281.84 | 1060.47 | 489.55 | 570.92 | 0.00 | 0.00 |
March | 1302.42 | 1309.38 | 1215.68 | 537.87 | 677.80 | 0.00 | 0.00 |
April | 2061.14 | 1092.22 | 1675.84 | 872.63 | 803.21 | 0.00 | 0.00 |
May | 1959.77 | 979.18 | 1646.11 | 760.31 | 885.79 | 0.00 | 0.00 |
June | 2219.32 | 774.53 | 1743.82 | 871.83 | 871.99 | 0.00 | 0.00 |
July | 2497.08 | 699.49 | 1845.99 | 987.74 | 858.25 | 0.00 | 0.00 |
August | 2377.38 | 725.75 | 1731.99 | 938.68 | 793.32 | 0.00 | 0.00 |
September | 1962.58 | 823.18 | 1483.00 | 793.58 | 689.42 | 0.00 | 0.00 |
October | 1531.73 | 910.11 | 1133.61 | 618.90 | 514.70 | 0.00 | 0.00 |
November | 1151.41 | 1284.20 | 1023.95 | 535.58 | 488.37 | 0.00 | 0.00 |
December | 996.68 | 1420.23 | 904.33 | 485.03 | 419.30 | 0.00 | 0.00 |
Annual Sum or Average | 1680.57 | 1057.24 | 1363.99 | 695.89 | 668.10 | 0.00 | 0.00 |
Minimum of Months | 958.90 | 699.49 | 888.91 | 448.32 | 419.30 | 0.00 | 0.00 |
Maximum of Months | 2497.08 | 1420.23 | 1845.99 | 987.74 | 885.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 307.28 | 1854.84 | 519.34 | 0.00 | 519.34 | 0.00 | 0.00 |
February | 347.52 | 1694.09 | 651.91 | 0.00 | 651.91 | 0.00 | 0.00 |
March | 493.80 | 1777.15 | 798.87 | 0.00 | 798.87 | 0.00 | 0.00 |
April | 681.82 | 1430.71 | 920.35 | 3.50 | 916.85 | 0.00 | 0.00 |
May | 810.64 | 1254.86 | 1105.83 | 51.32 | 1054.52 | 0.00 | 0.00 |
June | 991.79 | 987.24 | 1178.23 | 114.93 | 1063.30 | 0.00 | 0.00 |
July | 1068.42 | 875.64 | 1115.58 | 93.24 | 1022.34 | 0.00 | 0.00 |
August | 920.69 | 929.98 | 926.58 | 18.44 | 908.14 | 0.00 | 0.00 |
September | 741.82 | 1090.88 | 784.35 | 0.12 | 784.23 | 0.00 | 0.00 |
October | 673.64 | 1196.21 | 622.17 | 0.00 | 622.17 | 0.00 | 0.00 |
November | 346.76 | 1706.46 | 563.33 | 0.00 | 563.33 | 0.00 | 0.00 |
December | 285.97 | 1861.37 | 483.46 | 0.00 | 483.46 | 0.00 | 0.00 |
Annual Sum or Average | 641.01 | 1386.70 | 806.49 | 23.59 | 782.90 | 0.00 | 0.00 |
Minimum of Months | 285.97 | 875.64 | 483.46 | 0.00 | 483.46 | 0.00 | 0.00 |
Maximum of Months | 1068.42 | 1861.37 | 1178.23 | 114.93 | 1063.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 999.97 | 1176.13 | 933.89 | 499.46 | 434.44 | 0.00 | 0.00 |
February | 989.15 | 1083.33 | 985.16 | 451.30 | 533.87 | 0.00 | 0.00 |
March | 1266.31 | 1134.10 | 1196.80 | 533.28 | 663.52 | 0.00 | 0.00 |
April | 1834.79 | 937.64 | 1530.06 | 767.39 | 762.67 | 0.00 | 0.00 |
May | 1659.26 | 854.95 | 1443.82 | 602.51 | 841.31 | 0.00 | 0.00 |
June | 1756.39 | 687.81 | 1434.82 | 622.51 | 812.31 | 0.00 | 0.00 |
July | 2165.50 | 617.90 | 1625.77 | 807.86 | 817.91 | 0.00 | 0.00 |
August | 2178.86 | 631.45 | 1605.64 | 852.87 | 752.78 | 0.00 | 0.00 |
September | 1485.17 | 716.88 | 1169.05 | 535.72 | 633.34 | 0.00 | 0.00 |
October | 1363.11 | 775.80 | 1034.80 | 531.86 | 502.94 | 0.00 | 0.00 |
November | 1011.35 | 1090.24 | 943.32 | 479.23 | 464.09 | 0.00 | 0.00 |
December | 961.03 | 1175.08 | 899.91 | 499.99 | 399.92 | 0.00 | 0.00 |
Annual Sum or Average | 1476.01 | 905.86 | 1235.24 | 599.85 | 635.39 | 0.00 | 0.00 |
Minimum of Months | 961.03 | 617.90 | 899.91 | 451.30 | 399.92 | 0.00 | 0.00 |
Maximum of Months | 2178.86 | 1176.13 | 1625.77 | 852.87 | 841.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4728.82 | 1907.03 | 3428.26 | 2515.04 | 913.22 | 0.00 | 0.00 |
February | 3344.03 | 1737.25 | 2694.16 | 1659.65 | 1034.51 | 0.00 | 0.00 |
March | 2439.49 | 1844.36 | 2147.13 | 1036.98 | 1110.15 | 0.00 | 0.00 |
April | 1855.40 | 1517.74 | 1793.51 | 683.41 | 1110.10 | 0.00 | 0.00 |
May | 1059.87 | 1363.43 | 1277.06 | 156.63 | 1120.43 | 0.00 | 0.00 |
June | 970.74 | 1074.90 | 1120.26 | 67.08 | 1053.18 | 0.00 | 0.00 |
July | 1168.89 | 944.62 | 1186.51 | 132.88 | 1053.64 | 0.00 | 0.00 |
August | 1705.20 | 996.64 | 1524.50 | 480.32 | 1044.18 | 0.00 | 0.00 |
September | 2707.59 | 1171.23 | 2121.85 | 1074.91 | 1046.94 | 0.00 | 0.00 |
October | 3847.21 | 1282.49 | 2699.49 | 1804.75 | 894.74 | 0.00 | 0.00 |
November | 4444.68 | 1768.10 | 3281.59 | 2317.01 | 964.58 | 0.00 | 0.00 |
December | 5107.37 | 1918.57 | 3662.36 | 2787.75 | 874.61 | 0.00 | 0.00 |
Annual Sum or Average | 2780.13 | 1459.10 | 2242.84 | 1224.90 | 1017.95 | 0.00 | 0.00 |
Minimum of Months | 970.74 | 944.62 | 1120.26 | 67.08 | 874.61 | 0.00 | 0.00 |
Maximum of Months | 5107.37 | 1918.57 | 3662.36 | 2787.75 | 1120.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 985.74 | 1290.20 | 888.91 | 448.32 | 440.59 | 0.00 | 0.00 |
February | 1137.96 | 1186.68 | 1060.47 | 489.55 | 570.92 | 0.00 | 0.00 |
March | 1320.37 | 1229.22 | 1215.68 | 537.87 | 677.80 | 0.00 | 0.00 |
April | 2065.88 | 1042.59 | 1675.84 | 872.63 | 803.21 | 0.00 | 0.00 |
May | 1964.41 | 935.93 | 1646.11 | 760.31 | 885.79 | 0.00 | 0.00 |
June | 2212.35 | 749.33 | 1743.82 | 871.83 | 871.99 | 0.00 | 0.00 |
July | 2483.96 | 682.31 | 1845.99 | 987.74 | 858.25 | 0.00 | 0.00 |
August | 2366.18 | 707.19 | 1731.99 | 938.68 | 793.32 | 0.00 | 0.00 |
September | 1961.40 | 789.87 | 1483.00 | 793.58 | 689.42 | 0.00 | 0.00 |
October | 1541.77 | 861.15 | 1133.61 | 618.90 | 514.70 | 0.00 | 0.00 |
November | 1173.05 | 1194.11 | 1023.95 | 535.58 | 488.37 | 0.00 | 0.00 |
December | 1024.38 | 1308.81 | 904.33 | 485.03 | 419.30 | 0.00 | 0.00 |
Annual Sum or Average | 1689.13 | 997.16 | 1363.99 | 695.89 | 668.10 | 0.00 | 0.00 |
Minimum of Months | 985.74 | 682.31 | 888.91 | 448.32 | 419.30 | 0.00 | 0.00 |
Maximum of Months | 2483.96 | 1308.81 | 1845.99 | 987.74 | 885.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.521826E+09 | 0.623939E+10 | 0.139101E+10 | 0.00 | 0.139101E+10 | 0.00 | 0.00 |
February | 0.571020E+09 | 0.516396E+10 | 0.157712E+10 | 0.00 | 0.157712E+10 | 0.00 | 0.00 |
March | 0.102598E+10 | 0.579229E+10 | 0.213970E+10 | 0.00 | 0.213970E+10 | 0.00 | 0.00 |
April | 0.152939E+10 | 0.439814E+10 | 0.238556E+10 | 9074754.57 | 0.237648E+10 | 0.00 | 0.00 |
May | 0.197909E+10 | 0.384754E+10 | 0.296187E+10 | 0.137451E+09 | 0.282442E+10 | 0.00 | 0.00 |
June | 0.245656E+10 | 0.287495E+10 | 0.305398E+10 | 0.297906E+09 | 0.275608E+10 | 0.00 | 0.00 |
July | 0.275139E+10 | 0.261802E+10 | 0.298798E+10 | 0.249732E+09 | 0.273825E+10 | 0.00 | 0.00 |
August | 0.235652E+10 | 0.279672E+10 | 0.248175E+10 | 49385705.87 | 0.243236E+10 | 0.00 | 0.00 |
September | 0.179845E+10 | 0.325774E+10 | 0.203304E+10 | 310346.33 | 0.203273E+10 | 0.00 | 0.00 |
October | 0.159835E+10 | 0.383697E+10 | 0.166643E+10 | 0.00 | 0.166643E+10 | 0.00 | 0.00 |
November | 0.602621E+09 | 0.553088E+10 | 0.146016E+10 | 0.00 | 0.146016E+10 | 0.00 | 0.00 |
December | 0.420897E+09 | 0.642544E+10 | 0.129491E+10 | 0.00 | 0.129491E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.176121E+11 | 0.527820E+11 | 0.254335E+11 | 0.743859E+09 | 0.246897E+11 | 0.00 | 0.00 |
Minimum of Months | 0.420897E+09 | 0.261802E+10 | 0.129491E+10 | 0.00 | 0.129491E+10 | 0.00 | 0.00 |
Maximum of Months | 0.275139E+10 | 0.642544E+10 | 0.305398E+10 | 0.297906E+09 | 0.282442E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.247066E+10 | 0.376809E+10 | 0.250135E+10 | 0.133775E+10 | 0.116360E+10 | 0.00 | 0.00 |
February | 0.224579E+10 | 0.311984E+10 | 0.238331E+10 | 0.109178E+10 | 0.129153E+10 | 0.00 | 0.00 |
March | 0.325982E+10 | 0.347561E+10 | 0.320553E+10 | 0.142835E+10 | 0.177719E+10 | 0.00 | 0.00 |
April | 0.472323E+10 | 0.267374E+10 | 0.396593E+10 | 0.198909E+10 | 0.197684E+10 | 0.00 | 0.00 |
May | 0.439906E+10 | 0.250926E+10 | 0.386715E+10 | 0.161378E+10 | 0.225337E+10 | 0.00 | 0.00 |
June | 0.456239E+10 | 0.191912E+10 | 0.371907E+10 | 0.161355E+10 | 0.210551E+10 | 0.00 | 0.00 |
July | 0.585642E+10 | 0.173486E+10 | 0.435447E+10 | 0.216377E+10 | 0.219070E+10 | 0.00 | 0.00 |
August | 0.589366E+10 | 0.173741E+10 | 0.430057E+10 | 0.228433E+10 | 0.201624E+10 | 0.00 | 0.00 |
September | 0.382902E+10 | 0.205412E+10 | 0.303020E+10 | 0.138859E+10 | 0.164161E+10 | 0.00 | 0.00 |
October | 0.358669E+10 | 0.234524E+10 | 0.277162E+10 | 0.142454E+10 | 0.134708E+10 | 0.00 | 0.00 |
November | 0.245685E+10 | 0.330819E+10 | 0.244509E+10 | 0.124217E+10 | 0.120292E+10 | 0.00 | 0.00 |
December | 0.234978E+10 | 0.376745E+10 | 0.241033E+10 | 0.133918E+10 | 0.107115E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.456334E+11 | 0.324129E+11 | 0.389546E+11 | 0.189169E+11 | 0.200378E+11 | 0.00 | 0.00 |
Minimum of Months | 0.224579E+10 | 0.173486E+10 | 0.238331E+10 | 0.109178E+10 | 0.107115E+10 | 0.00 | 0.00 |
Maximum of Months | 0.589366E+10 | 0.376809E+10 | 0.435447E+10 | 0.228433E+10 | 0.225337E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.126008E+11 | 0.564373E+10 | 0.918228E+10 | 0.673630E+10 | 0.244598E+10 | 0.00 | 0.00 |
February | 0.803922E+10 | 0.474063E+10 | 0.651774E+10 | 0.401504E+10 | 0.250271E+10 | 0.00 | 0.00 |
March | 0.643653E+10 | 0.553438E+10 | 0.575090E+10 | 0.277747E+10 | 0.297344E+10 | 0.00 | 0.00 |
April | 0.472507E+10 | 0.437612E+10 | 0.464880E+10 | 0.177140E+10 | 0.287740E+10 | 0.00 | 0.00 |
May | 0.273763E+10 | 0.400469E+10 | 0.342048E+10 | 0.419510E+09 | 0.300097E+10 | 0.00 | 0.00 |
June | 0.244972E+10 | 0.304437E+10 | 0.290373E+10 | 0.173877E+09 | 0.272985E+10 | 0.00 | 0.00 |
July | 0.307267E+10 | 0.274472E+10 | 0.317796E+10 | 0.355897E+09 | 0.282207E+10 | 0.00 | 0.00 |
August | 0.453558E+10 | 0.286239E+10 | 0.408323E+10 | 0.128649E+10 | 0.279674E+10 | 0.00 | 0.00 |
September | 0.705023E+10 | 0.326722E+10 | 0.549985E+10 | 0.278617E+10 | 0.271368E+10 | 0.00 | 0.00 |
October | 0.103302E+11 | 0.372523E+10 | 0.723034E+10 | 0.483386E+10 | 0.239648E+10 | 0.00 | 0.00 |
November | 0.114922E+11 | 0.506967E+10 | 0.850591E+10 | 0.600571E+10 | 0.250020E+10 | 0.00 | 0.00 |
December | 0.136004E+11 | 0.574191E+10 | 0.980931E+10 | 0.746674E+10 | 0.234257E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.870703E+11 | 0.507551E+11 | 0.707305E+11 | 0.386285E+11 | 0.321021E+11 | 0.00 | 0.00 |
Minimum of Months | 0.244972E+10 | 0.274472E+10 | 0.290373E+10 | 0.173877E+09 | 0.234257E+10 | 0.00 | 0.00 |
Maximum of Months | 0.136004E+11 | 0.574191E+10 | 0.980931E+10 | 0.746674E+10 | 0.300097E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.244320E+10 | 0.425646E+10 | 0.238087E+10 | 0.120078E+10 | 0.118009E+10 | 0.00 | 0.00 |
February | 0.256351E+10 | 0.366395E+10 | 0.256551E+10 | 0.118434E+10 | 0.138117E+10 | 0.00 | 0.00 |
March | 0.330667E+10 | 0.416932E+10 | 0.325608E+10 | 0.144064E+10 | 0.181544E+10 | 0.00 | 0.00 |
April | 0.517534E+10 | 0.334013E+10 | 0.434379E+10 | 0.226187E+10 | 0.208192E+10 | 0.00 | 0.00 |
May | 0.518253E+10 | 0.286242E+10 | 0.440895E+10 | 0.203643E+10 | 0.237252E+10 | 0.00 | 0.00 |
June | 0.567081E+10 | 0.227460E+10 | 0.452001E+10 | 0.225980E+10 | 0.226020E+10 | 0.00 | 0.00 |
July | 0.656908E+10 | 0.214576E+10 | 0.494432E+10 | 0.264556E+10 | 0.229876E+10 | 0.00 | 0.00 |
August | 0.622324E+10 | 0.227359E+10 | 0.463899E+10 | 0.251417E+10 | 0.212482E+10 | 0.00 | 0.00 |
September | 0.503267E+10 | 0.236151E+10 | 0.384395E+10 | 0.205697E+10 | 0.178697E+10 | 0.00 | 0.00 |
October | 0.397706E+10 | 0.283102E+10 | 0.303627E+10 | 0.165768E+10 | 0.137859E+10 | 0.00 | 0.00 |
November | 0.281768E+10 | 0.399097E+10 | 0.265409E+10 | 0.138824E+10 | 0.126585E+10 | 0.00 | 0.00 |
December | 0.246494E+10 | 0.468405E+10 | 0.242217E+10 | 0.129911E+10 | 0.112306E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.514267E+11 | 0.388538E+11 | 0.430150E+11 | 0.219456E+11 | 0.210694E+11 | 0.00 | 0.00 |
Minimum of Months | 0.244320E+10 | 0.214576E+10 | 0.238087E+10 | 0.118434E+10 | 0.112306E+10 | 0.00 | 0.00 |
Maximum of Months | 0.656908E+10 | 0.468405E+10 | 0.494432E+10 | 0.264556E+10 | 0.237252E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.679840E+09 | 0.553134E+10 | 0.139101E+10 | 0.00 | 0.139101E+10 | 0.00 | 0.00 |
February | 0.724297E+09 | 0.453151E+10 | 0.157711E+10 | 0.00 | 0.157711E+10 | 0.00 | 0.00 |
March | 0.121405E+10 | 0.513927E+10 | 0.213969E+10 | 0.00 | 0.213969E+10 | 0.00 | 0.00 |
April | 0.171488E+10 | 0.391898E+10 | 0.238555E+10 | 9074722.34 | 0.237647E+10 | 0.00 | 0.00 |
May | 0.211406E+10 | 0.354761E+10 | 0.296186E+10 | 0.137450E+09 | 0.282441E+10 | 0.00 | 0.00 |
June | 0.257342E+10 | 0.264769E+10 | 0.305397E+10 | 0.297905E+09 | 0.275607E+10 | 0.00 | 0.00 |
July | 0.290076E+10 | 0.239814E+10 | 0.298797E+10 | 0.249731E+09 | 0.273824E+10 | 0.00 | 0.00 |
August | 0.249515E+10 | 0.255316E+10 | 0.248174E+10 | 49385530.50 | 0.243235E+10 | 0.00 | 0.00 |
September | 0.190249E+10 | 0.296674E+10 | 0.203303E+10 | 310345.22 | 0.203272E+10 | 0.00 | 0.00 |
October | 0.174095E+10 | 0.342980E+10 | 0.166643E+10 | 0.00 | 0.166643E+10 | 0.00 | 0.00 |
November | 0.775882E+09 | 0.486355E+10 | 0.146016E+10 | 0.00 | 0.146016E+10 | 0.00 | 0.00 |
December | 0.620637E+09 | 0.554868E+10 | 0.129491E+10 | 0.00 | 0.129491E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.194564E+11 | 0.470765E+11 | 0.254334E+11 | 0.743857E+09 | 0.246896E+11 | 0.00 | 0.00 |
Minimum of Months | 0.620637E+09 | 0.239814E+10 | 0.129491E+10 | 0.00 | 0.129491E+10 | 0.00 | 0.00 |
Maximum of Months | 0.290076E+10 | 0.554868E+10 | 0.305397E+10 | 0.297905E+09 | 0.282441E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.254937E+10 | 0.345891E+10 | 0.250134E+10 | 0.133774E+10 | 0.116360E+10 | 0.00 | 0.00 |
February | 0.230756E+10 | 0.285303E+10 | 0.238330E+10 | 0.109177E+10 | 0.129153E+10 | 0.00 | 0.00 |
March | 0.331628E+10 | 0.323378E+10 | 0.320552E+10 | 0.142834E+10 | 0.177718E+10 | 0.00 | 0.00 |
April | 0.472948E+10 | 0.253542E+10 | 0.396592E+10 | 0.198909E+10 | 0.197683E+10 | 0.00 | 0.00 |
May | 0.441164E+10 | 0.238138E+10 | 0.386713E+10 | 0.161377E+10 | 0.225336E+10 | 0.00 | 0.00 |
June | 0.456093E+10 | 0.182483E+10 | 0.371905E+10 | 0.161354E+10 | 0.210551E+10 | 0.00 | 0.00 |
July | 0.583192E+10 | 0.167676E+10 | 0.435445E+10 | 0.216376E+10 | 0.219069E+10 | 0.00 | 0.00 |
August | 0.586228E+10 | 0.171695E+10 | 0.430055E+10 | 0.228432E+10 | 0.201623E+10 | 0.00 | 0.00 |
September | 0.384471E+10 | 0.192970E+10 | 0.303019E+10 | 0.138858E+10 | 0.164161E+10 | 0.00 | 0.00 |
October | 0.361519E+10 | 0.219376E+10 | 0.277161E+10 | 0.142453E+10 | 0.134708E+10 | 0.00 | 0.00 |
November | 0.252194E+10 | 0.305722E+10 | 0.244508E+10 | 0.124216E+10 | 0.120291E+10 | 0.00 | 0.00 |
December | 0.244044E+10 | 0.345024E+10 | 0.241032E+10 | 0.133917E+10 | 0.107115E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.459917E+11 | 0.303120E+11 | 0.389545E+11 | 0.189168E+11 | 0.200377E+11 | 0.00 | 0.00 |
Minimum of Months | 0.230756E+10 | 0.167676E+10 | 0.238330E+10 | 0.109177E+10 | 0.107115E+10 | 0.00 | 0.00 |
Maximum of Months | 0.586228E+10 | 0.345891E+10 | 0.435445E+10 | 0.228432E+10 | 0.225336E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.124947E+11 | 0.556215E+10 | 0.918225E+10 | 0.673628E+10 | 0.244597E+10 | 0.00 | 0.00 |
February | 0.797774E+10 | 0.457071E+10 | 0.651772E+10 | 0.401502E+10 | 0.250270E+10 | 0.00 | 0.00 |
March | 0.643738E+10 | 0.528413E+10 | 0.575088E+10 | 0.277746E+10 | 0.297343E+10 | 0.00 | 0.00 |
April | 0.476554E+10 | 0.413391E+10 | 0.464879E+10 | 0.177140E+10 | 0.287739E+10 | 0.00 | 0.00 |
May | 0.278510E+10 | 0.383355E+10 | 0.342047E+10 | 0.419508E+09 | 0.300096E+10 | 0.00 | 0.00 |
June | 0.251409E+10 | 0.287144E+10 | 0.290372E+10 | 0.173876E+09 | 0.272984E+10 | 0.00 | 0.00 |
July | 0.315804E+10 | 0.257578E+10 | 0.317795E+10 | 0.355895E+09 | 0.282206E+10 | 0.00 | 0.00 |
August | 0.459057E+10 | 0.272813E+10 | 0.408322E+10 | 0.128649E+10 | 0.279673E+10 | 0.00 | 0.00 |
September | 0.701480E+10 | 0.316594E+10 | 0.549983E+10 | 0.278616E+10 | 0.271367E+10 | 0.00 | 0.00 |
October | 0.102557E+11 | 0.362946E+10 | 0.723031E+10 | 0.483384E+10 | 0.239647E+10 | 0.00 | 0.00 |
November | 0.114058E+11 | 0.492350E+10 | 0.850588E+10 | 0.600569E+10 | 0.250019E+10 | 0.00 | 0.00 |
December | 0.135130E+11 | 0.556745E+10 | 0.980928E+10 | 0.746672E+10 | 0.234256E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.869124E+11 | 0.488461E+11 | 0.707303E+11 | 0.386283E+11 | 0.321020E+11 | 0.00 | 0.00 |
Minimum of Months | 0.251409E+10 | 0.257578E+10 | 0.290372E+10 | 0.173876E+09 | 0.234256E+10 | 0.00 | 0.00 |
Maximum of Months | 0.135130E+11 | 0.556745E+10 | 0.980928E+10 | 0.746672E+10 | 0.300096E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.256833E+10 | 0.375051E+10 | 0.238086E+10 | 0.120078E+10 | 0.118008E+10 | 0.00 | 0.00 |
February | 0.269825E+10 | 0.310104E+10 | 0.256550E+10 | 0.118433E+10 | 0.138117E+10 | 0.00 | 0.00 |
March | 0.348839E+10 | 0.350704E+10 | 0.325607E+10 | 0.144064E+10 | 0.181543E+10 | 0.00 | 0.00 |
April | 0.534248E+10 | 0.283103E+10 | 0.434377E+10 | 0.226186E+10 | 0.208191E+10 | 0.00 | 0.00 |
May | 0.524905E+10 | 0.262263E+10 | 0.440893E+10 | 0.203642E+10 | 0.237251E+10 | 0.00 | 0.00 |
June | 0.575249E+10 | 0.200757E+10 | 0.451999E+10 | 0.225979E+10 | 0.226019E+10 | 0.00 | 0.00 |
July | 0.668819E+10 | 0.187352E+10 | 0.494430E+10 | 0.264555E+10 | 0.229875E+10 | 0.00 | 0.00 |
August | 0.636757E+10 | 0.194386E+10 | 0.463897E+10 | 0.251416E+10 | 0.212482E+10 | 0.00 | 0.00 |
September | 0.508700E+10 | 0.213368E+10 | 0.384393E+10 | 0.205696E+10 | 0.178697E+10 | 0.00 | 0.00 |
October | 0.410260E+10 | 0.243764E+10 | 0.303625E+10 | 0.165767E+10 | 0.137858E+10 | 0.00 | 0.00 |
November | 0.298446E+10 | 0.332864E+10 | 0.265408E+10 | 0.138823E+10 | 0.126585E+10 | 0.00 | 0.00 |
December | 0.266950E+10 | 0.380395E+10 | 0.242216E+10 | 0.129911E+10 | 0.112305E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.529983E+11 | 0.333411E+11 | 0.430148E+11 | 0.219455E+11 | 0.210693E+11 | 0.00 | 0.00 |
Minimum of Months | 0.256833E+10 | 0.187352E+10 | 0.238086E+10 | 0.118433E+10 | 0.112305E+10 | 0.00 | 0.00 |
Maximum of Months | 0.668819E+10 | 0.380395E+10 | 0.494430E+10 | 0.264555E+10 | 0.237251E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.823021E+09 | 0.496800E+10 | 0.139101E+10 | 0.00 | 0.139101E+10 | 0.00 | 0.00 |
February | 0.840717E+09 | 0.409835E+10 | 0.157711E+10 | 0.00 | 0.157711E+10 | 0.00 | 0.00 |
March | 0.132261E+10 | 0.475992E+10 | 0.213969E+10 | 0.00 | 0.213969E+10 | 0.00 | 0.00 |
April | 0.176728E+10 | 0.370839E+10 | 0.238555E+10 | 9074722.34 | 0.237647E+10 | 0.00 | 0.00 |
May | 0.217121E+10 | 0.336103E+10 | 0.296186E+10 | 0.137450E+09 | 0.282441E+10 | 0.00 | 0.00 |
June | 0.257071E+10 | 0.255891E+10 | 0.305397E+10 | 0.297905E+09 | 0.275607E+10 | 0.00 | 0.00 |
July | 0.286166E+10 | 0.234532E+10 | 0.298797E+10 | 0.249731E+09 | 0.273824E+10 | 0.00 | 0.00 |
August | 0.246599E+10 | 0.249085E+10 | 0.248174E+10 | 49385530.50 | 0.243235E+10 | 0.00 | 0.00 |
September | 0.192280E+10 | 0.282755E+10 | 0.203303E+10 | 310345.22 | 0.203272E+10 | 0.00 | 0.00 |
October | 0.180428E+10 | 0.320394E+10 | 0.166643E+10 | 0.00 | 0.166643E+10 | 0.00 | 0.00 |
November | 0.898800E+09 | 0.442316E+10 | 0.146016E+10 | 0.00 | 0.146016E+10 | 0.00 | 0.00 |
December | 0.765952E+09 | 0.498550E+10 | 0.129491E+10 | 0.00 | 0.129491E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.202150E+11 | 0.437309E+11 | 0.254334E+11 | 0.743857E+09 | 0.246896E+11 | 0.00 | 0.00 |
Minimum of Months | 0.765952E+09 | 0.234532E+10 | 0.129491E+10 | 0.00 | 0.129491E+10 | 0.00 | 0.00 |
Maximum of Months | 0.286166E+10 | 0.498550E+10 | 0.305397E+10 | 0.297905E+09 | 0.282441E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.267833E+10 | 0.315014E+10 | 0.250134E+10 | 0.133774E+10 | 0.116360E+10 | 0.00 | 0.00 |
February | 0.239294E+10 | 0.262080E+10 | 0.238330E+10 | 0.109177E+10 | 0.129153E+10 | 0.00 | 0.00 |
March | 0.339170E+10 | 0.303756E+10 | 0.320552E+10 | 0.142834E+10 | 0.177718E+10 | 0.00 | 0.00 |
April | 0.475578E+10 | 0.243036E+10 | 0.396592E+10 | 0.198909E+10 | 0.197683E+10 | 0.00 | 0.00 |
May | 0.444415E+10 | 0.228989E+10 | 0.386713E+10 | 0.161377E+10 | 0.225336E+10 | 0.00 | 0.00 |
June | 0.455256E+10 | 0.178280E+10 | 0.371905E+10 | 0.161354E+10 | 0.210551E+10 | 0.00 | 0.00 |
July | 0.580008E+10 | 0.165499E+10 | 0.435445E+10 | 0.216376E+10 | 0.219069E+10 | 0.00 | 0.00 |
August | 0.583587E+10 | 0.169128E+10 | 0.430055E+10 | 0.228432E+10 | 0.201623E+10 | 0.00 | 0.00 |
September | 0.384955E+10 | 0.185816E+10 | 0.303019E+10 | 0.138858E+10 | 0.164161E+10 | 0.00 | 0.00 |
October | 0.365094E+10 | 0.207790E+10 | 0.277161E+10 | 0.142453E+10 | 0.134708E+10 | 0.00 | 0.00 |
November | 0.262142E+10 | 0.282590E+10 | 0.244508E+10 | 0.124216E+10 | 0.120291E+10 | 0.00 | 0.00 |
December | 0.257401E+10 | 0.314733E+10 | 0.241032E+10 | 0.133917E+10 | 0.107115E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.465473E+11 | 0.285671E+11 | 0.389545E+11 | 0.189168E+11 | 0.200377E+11 | 0.00 | 0.00 |
Minimum of Months | 0.239294E+10 | 0.165499E+10 | 0.238330E+10 | 0.109177E+10 | 0.107115E+10 | 0.00 | 0.00 |
Maximum of Months | 0.583587E+10 | 0.315014E+10 | 0.435445E+10 | 0.228432E+10 | 0.225336E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.126657E+11 | 0.510778E+10 | 0.918225E+10 | 0.673628E+10 | 0.244597E+10 | 0.00 | 0.00 |
February | 0.808987E+10 | 0.420276E+10 | 0.651772E+10 | 0.401502E+10 | 0.250270E+10 | 0.00 | 0.00 |
March | 0.653392E+10 | 0.493992E+10 | 0.575088E+10 | 0.277746E+10 | 0.297343E+10 | 0.00 | 0.00 |
April | 0.480919E+10 | 0.393399E+10 | 0.464879E+10 | 0.177140E+10 | 0.287739E+10 | 0.00 | 0.00 |
May | 0.283876E+10 | 0.365182E+10 | 0.342047E+10 | 0.419508E+09 | 0.300096E+10 | 0.00 | 0.00 |
June | 0.251615E+10 | 0.278613E+10 | 0.290372E+10 | 0.173876E+09 | 0.272984E+10 | 0.00 | 0.00 |
July | 0.313075E+10 | 0.253007E+10 | 0.317795E+10 | 0.355895E+09 | 0.282206E+10 | 0.00 | 0.00 |
August | 0.456721E+10 | 0.266940E+10 | 0.408322E+10 | 0.128649E+10 | 0.279673E+10 | 0.00 | 0.00 |
September | 0.701808E+10 | 0.303582E+10 | 0.549983E+10 | 0.278616E+10 | 0.271367E+10 | 0.00 | 0.00 |
October | 0.103044E+11 | 0.343501E+10 | 0.723031E+10 | 0.483384E+10 | 0.239647E+10 | 0.00 | 0.00 |
November | 0.115206E+11 | 0.458291E+10 | 0.850588E+10 | 0.600569E+10 | 0.250019E+10 | 0.00 | 0.00 |
December | 0.136796E+11 | 0.513870E+10 | 0.980928E+10 | 0.746672E+10 | 0.234256E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.876741E+11 | 0.460143E+11 | 0.707303E+11 | 0.386283E+11 | 0.321020E+11 | 0.00 | 0.00 |
Minimum of Months | 0.251615E+10 | 0.253007E+10 | 0.290372E+10 | 0.173876E+09 | 0.234256E+10 | 0.00 | 0.00 |
Maximum of Months | 0.136796E+11 | 0.513870E+10 | 0.980928E+10 | 0.746672E+10 | 0.300096E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.264020E+10 | 0.345568E+10 | 0.238086E+10 | 0.120078E+10 | 0.118008E+10 | 0.00 | 0.00 |
February | 0.275295E+10 | 0.287082E+10 | 0.256550E+10 | 0.118433E+10 | 0.138117E+10 | 0.00 | 0.00 |
March | 0.353647E+10 | 0.329234E+10 | 0.325607E+10 | 0.144064E+10 | 0.181543E+10 | 0.00 | 0.00 |
April | 0.535475E+10 | 0.270240E+10 | 0.434377E+10 | 0.226186E+10 | 0.208191E+10 | 0.00 | 0.00 |
May | 0.526148E+10 | 0.250680E+10 | 0.440893E+10 | 0.203642E+10 | 0.237251E+10 | 0.00 | 0.00 |
June | 0.573442E+10 | 0.194227E+10 | 0.451999E+10 | 0.225979E+10 | 0.226019E+10 | 0.00 | 0.00 |
July | 0.665303E+10 | 0.182749E+10 | 0.494430E+10 | 0.264555E+10 | 0.229875E+10 | 0.00 | 0.00 |
August | 0.633759E+10 | 0.189414E+10 | 0.463897E+10 | 0.251416E+10 | 0.212482E+10 | 0.00 | 0.00 |
September | 0.508396E+10 | 0.204734E+10 | 0.384393E+10 | 0.205696E+10 | 0.178697E+10 | 0.00 | 0.00 |
October | 0.412947E+10 | 0.230649E+10 | 0.303625E+10 | 0.165767E+10 | 0.137858E+10 | 0.00 | 0.00 |
November | 0.304054E+10 | 0.309513E+10 | 0.265408E+10 | 0.138823E+10 | 0.126585E+10 | 0.00 | 0.00 |
December | 0.274369E+10 | 0.350550E+10 | 0.242216E+10 | 0.129911E+10 | 0.112305E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.532685E+11 | 0.314464E+11 | 0.430148E+11 | 0.219455E+11 | 0.210693E+11 | 0.00 | 0.00 |
Minimum of Months | 0.264020E+10 | 0.182749E+10 | 0.238086E+10 | 0.118433E+10 | 0.112305E+10 | 0.00 | 0.00 |
Maximum of Months | 0.665303E+10 | 0.350550E+10 | 0.494430E+10 | 0.264555E+10 | 0.237251E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.60 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.19 | 7.03 | 3.12 | 2.95 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.60 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.61 | 10.61 | 2.62 | 4.75 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.64 | 10.56 | 2.92 | 6.16 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.02 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.75 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.61 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.49 | 13.65 | 2.19 | 8.98 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.71 | 9.60 | 2.71 | 7.73 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.42 | 6.22 | 2.47 | 2.40 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.80 | 3.19 | 2.50 | 0.04 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.75 | 10.02 | 2.59 | 5.48 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.80 | 3.19 | 2.19 | 0.04 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.44 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.65 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.80 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.11 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.03 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.58 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.48 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.18 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.88 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.83 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.94 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.06 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.06 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.18 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.2 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.20 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.32 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.55 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.53 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.2 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.02 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.40 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.31 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.58 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.18 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.18 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.84 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.08 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.63 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.63 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.84 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.84 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.33 | 3.77 | 8.01 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.02 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.46 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.91 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.63 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.91 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHWSYS1 WATER HEATER
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.203568E+11 | -.332029E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.129865E+10 | 68.18 | 0.00 | 0.00 |
February | 0.186076E+11 | -.302054E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.116861E+10 | 67.95 | 0.00 | 0.00 |
March | 0.223777E+11 | -.351491E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.126651E+10 | 66.95 | 0.00 | 0.00 |
April | 0.187246E+11 | -.312393E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.124627E+10 | 67.78 | 0.00 | 0.00 |
May | 0.195810E+11 | -.324918E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.129132E+10 | 67.82 | 0.00 | 0.00 |
June | 0.189679E+11 | -.314832E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.123666E+10 | 67.34 | 0.00 | 0.00 |
July | 0.164139E+11 | -.295056E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.130445E+10 | 68.42 | 0.00 | 0.00 |
August | 0.192736E+11 | -.322343E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.127297E+10 | 67.24 | 0.00 | 0.00 |
September | 0.170060E+11 | -.296193E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.125350E+10 | 68.04 | 0.00 | 0.00 |
October | 0.182588E+11 | -.312347E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.130144E+10 | 68.32 | 0.00 | 0.00 |
November | 0.189684E+11 | -.314407E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.125981E+10 | 68.34 | 0.00 | 0.00 |
December | 0.190720E+11 | -.320082E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.129506E+10 | 68.12 | 0.00 | 0.00 |
Annual Sum or Average | 0.227608E+12 | -.379814E+12 | 8760.00 | -.151952E+11 | 67.87 | |||||
Minimum of Months | 0.164139E+11 | -.351491E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.130445E+10 | 66.95 | 0.00 | 0.00 |
Maximum of Months | 0.223777E+11 | -.295056E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.116861E+10 | 68.42 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:30 | 7849.68 | 37.54 | 285.17 | 281.00 | 1701.66 | 26.79 | 207.50 | 265.33 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:30 | 6967.49 | 35.76 | 275.67 | 274.67 | 1256.09 | 24.76 | 215.50 | 253.00 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-06:49 | 2071.19 | 20.41 | 97.17 | 315.50 | 1003.56 | 21.24 | 197.50 | 287.00 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:10 | 1364.95 | 19.60 | 35.33 | 332.67 | 828.26 | 20.96 | 156.83 | 297.67 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-06:49 | 1174.48 | 19.40 | 0.33 | 365.83 | 675.39 | 20.75 | 158.17 | 323.17 |
June | 381.00 | 0.52 | 0.48 | 01-JUN-06:49 | 1044.94 | 19.03 | 0.00 | 358.00 | 620.30 | 20.41 | 108.83 | 311.33 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-06:30 | 1054.64 | 19.06 | 0.67 | 368.17 | 645.95 | 20.46 | 138.67 | 332.33 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:19 | 1178.09 | 19.21 | 8.50 | 354.83 | 730.28 | 20.57 | 151.17 | 317.67 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:00 | 1710.39 | 20.23 | 52.50 | 309.83 | 952.85 | 21.00 | 150.83 | 278.00 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 3865.31 | 27.15 | 156.67 | 304.67 | 1172.43 | 21.73 | 137.33 | 276.33 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 7597.40 | 37.31 | 294.83 | 279.50 | 1529.88 | 26.36 | 218.00 | 270.17 |
December | 297.00 | 0.50 | 0.48 | 01-DEC-07:19 | 7723.95 | 38.42 | 293.33 | 283.17 | 2167.77 | 29.54 | 209.00 | 271.50 |
Annual Sum or Average | 4065.67 | 0.51 | 3313.85 | 25.19 | 1500.17 | 3827.83 | 1058.02 | 22.59 | 2049.33 | 3483.50 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1044.94 | 19.03 | 0.00 | 274.67 | 620.30 | 20.41 | 108.83 | 253.00 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 7849.68 | 38.42 | 294.83 | 368.17 | 2167.77 | 29.54 | 218.00 | 332.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-07:19 | 1745.34 | 23.78 | 89.83 | 266.50 | 886.84 | 23.56 | 111.50 | 229.67 |
February | 279.67 | 0.51 | 0.48 | 01-FEB-07:10 | 1907.85 | 23.85 | 87.00 | 268.50 | 997.51 | 23.91 | 118.50 | 224.50 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:40 | 2324.95 | 23.77 | 107.17 | 317.67 | 1268.41 | 23.97 | 140.67 | 280.17 |
April | 358.33 | 0.51 | 0.48 | 01-APR-05:00 | 2357.54 | 23.16 | 93.83 | 339.17 | 1248.25 | 23.51 | 103.33 | 308.83 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:19 | 2272.45 | 22.51 | 99.67 | 378.00 | 1238.66 | 23.10 | 125.33 | 333.67 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:19 | 2265.36 | 21.73 | 89.33 | 369.33 | 1202.79 | 22.39 | 89.00 | 327.50 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:30 | 2494.31 | 22.16 | 99.67 | 378.17 | 1315.51 | 22.67 | 93.50 | 343.33 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-06:49 | 2507.75 | 22.97 | 103.33 | 363.17 | 1279.78 | 23.21 | 89.00 | 329.83 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:40 | 2617.52 | 23.26 | 98.83 | 312.67 | 995.11 | 22.22 | 85.83 | 277.50 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 2366.84 | 23.17 | 89.17 | 286.33 | 975.96 | 22.10 | 88.67 | 241.50 |
November | 300.00 | 0.53 | 0.48 | 01-NOV-06:40 | 1988.82 | 24.02 | 98.00 | 265.00 | 1075.51 | 23.97 | 125.00 | 234.00 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-07:10 | 1744.36 | 24.23 | 97.50 | 267.50 | 908.40 | 23.91 | 107.00 | 227.00 |
Annual Sum or Average | 4065.67 | 0.52 | 2240.73 | 23.14 | 1153.33 | 3812.00 | 1133.32 | 23.18 | 1277.33 | 3357.50 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1744.36 | 21.73 | 87.00 | 265.00 | 886.84 | 22.10 | 85.83 | 224.50 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 2617.52 | 24.23 | 107.17 | 378.17 | 1315.51 | 23.97 | 140.67 | 343.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.56 | 0.48 | 01-JAN-09:09 | 555.61 | 16.90 | 0.00 | 237.67 | 359.09 | 18.66 | 0.00 | 165.33 |
February | 279.67 | 0.54 | 0.48 | 01-FEB-08:00 | 661.77 | 17.65 | 0.00 | 249.00 | 405.51 | 19.14 | 0.00 | 180.00 |
March | 338.17 | 0.54 | 0.48 | 01-MAR-08:30 | 773.79 | 17.97 | 0.00 | 306.50 | 462.09 | 19.30 | 5.33 | 252.33 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:19 | 863.97 | 19.13 | 0.00 | 336.33 | 548.23 | 20.50 | 62.17 | 297.83 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:40 | 1071.39 | 19.82 | 26.67 | 382.67 | 622.68 | 21.13 | 152.67 | 352.83 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:40 | 1132.12 | 21.50 | 82.50 | 375.33 | 672.32 | 22.69 | 179.17 | 342.17 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:49 | 1064.13 | 21.39 | 84.67 | 385.00 | 625.88 | 21.18 | 170.67 | 360.83 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:19 | 876.36 | 19.21 | 7.17 | 364.33 | 564.68 | 20.55 | 82.50 | 338.33 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-07:10 | 772.38 | 18.45 | 0.00 | 305.50 | 493.38 | 19.89 | 8.00 | 259.67 |
October | 296.17 | 0.55 | 0.48 | 01-OCT-09:39 | 591.60 | 17.08 | 0.00 | 263.67 | 386.43 | 18.67 | 0.33 | 185.67 |
November | 300.00 | 0.57 | 0.48 | 01-NOV-08:09 | 564.16 | 16.48 | 0.00 | 241.33 | 361.60 | 18.13 | 0.00 | 172.50 |
December | 297.00 | 0.58 | 0.48 | 01-DEC-08:50 | 506.21 | 16.17 | 0.00 | 230.50 | 332.89 | 18.00 | 0.00 | 146.33 |
Annual Sum or Average | 4065.67 | 0.53 | 811.34 | 18.68 | 201.00 | 3677.83 | 500.10 | 19.97 | 660.83 | 3053.83 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 506.21 | 16.17 | 0.00 | 230.50 | 332.89 | 18.00 | 0.00 | 146.33 | |
Maximum of Months | 408.67 | 0.58 | 0.48 | 1132.12 | 21.50 | 84.67 | 385.00 | 672.32 | 22.69 | 179.17 | 360.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.53 | 0.48 | 01-JAN-08:00 | 2260.65 | 24.56 | 107.00 | 254.17 | 851.88 | 22.80 | 117.83 | 216.33 |
February | 279.67 | 0.53 | 0.48 | 01-FEB-08:00 | 2082.30 | 23.91 | 90.00 | 257.00 | 1111.75 | 24.07 | 133.50 | 217.83 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-08:30 | 2321.33 | 23.31 | 101.00 | 311.17 | 1248.65 | 23.53 | 141.50 | 270.83 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:49 | 3195.00 | 22.05 | 82.33 | 333.00 | 1206.75 | 20.05 | 75.83 | 300.67 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-07:30 | 2998.73 | 20.07 | 52.83 | 368.83 | 1215.96 | 20.22 | 95.33 | 331.33 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-07:10 | 2543.85 | 17.86 | 0.00 | 362.17 | 1376.52 | 20.23 | 89.67 | 327.50 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-06:00 | 2683.46 | 17.92 | 5.67 | 372.17 | 1422.32 | 20.15 | 87.33 | 345.33 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:49 | 3313.39 | 21.74 | 88.33 | 356.33 | 1345.04 | 20.22 | 78.00 | 327.83 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-07:40 | 2953.94 | 24.50 | 106.67 | 306.67 | 1518.33 | 24.31 | 112.67 | 273.83 |
October | 296.17 | 0.52 | 0.48 | 01-OCT-09:39 | 2827.89 | 25.24 | 114.33 | 288.17 | 1122.80 | 23.51 | 103.50 | 245.17 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-08:09 | 2209.04 | 24.39 | 106.17 | 257.33 | 1204.21 | 24.33 | 134.67 | 219.50 |
December | 297.00 | 0.55 | 0.48 | 01-DEC-08:50 | 2006.94 | 24.38 | 109.83 | 249.33 | 1105.77 | 24.28 | 120.83 | 205.33 |
Annual Sum or Average | 4065.67 | 0.52 | 2652.52 | 22.21 | 964.17 | 3716.33 | 1241.38 | 22.09 | 1290.67 | 3281.50 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 2006.94 | 17.86 | 0.00 | 249.33 | 851.88 | 20.05 | 75.83 | 205.33 | |
Maximum of Months | 408.67 | 0.55 | 0.48 | 3313.39 | 25.24 | 114.33 | 372.17 | 1518.33 | 24.33 | 141.50 | 345.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:30 | 7919.58 | 37.01 | 284.83 | 281.17 | 1814.20 | 22.53 | 97.17 | 266.17 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:19 | 7010.25 | 35.33 | 275.00 | 274.67 | 1346.49 | 20.72 | 61.00 | 255.17 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 2106.91 | 14.14 | 11.17 | 316.00 | 1075.32 | 16.98 | 3.33 | 290.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:10 | 1401.03 | 13.53 | 0.00 | 333.17 | 889.06 | 17.09 | 0.00 | 305.17 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-06:49 | 1195.94 | 13.53 | 0.00 | 366.33 | 720.58 | 17.00 | 0.00 | 330.17 |
June | 381.00 | 0.52 | 0.48 | 01-JUN-06:49 | 1065.33 | 13.30 | 0.00 | 358.17 | 661.97 | 16.79 | 0.00 | 316.17 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-06:30 | 1078.00 | 13.46 | 0.00 | 368.83 | 690.35 | 16.98 | 0.00 | 336.17 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:19 | 1209.34 | 13.43 | 0.00 | 355.00 | 783.38 | 16.96 | 0.00 | 324.17 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:00 | 1753.89 | 14.07 | 14.00 | 309.83 | 1025.14 | 16.84 | 0.00 | 283.00 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 3926.40 | 23.13 | 141.67 | 304.67 | 1264.33 | 17.09 | 14.00 | 279.50 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 7658.01 | 36.91 | 294.67 | 279.67 | 1633.93 | 22.14 | 92.67 | 270.83 |
December | 297.00 | 0.50 | 0.48 | 01-DEC-07:19 | 7795.72 | 38.00 | 293.00 | 283.17 | 2283.64 | 25.95 | 142.67 | 273.00 |
Annual Sum or Average | 4065.67 | 0.51 | 3355.01 | 20.99 | 1314.33 | 3830.67 | 1130.22 | 18.66 | 410.83 | 3530.00 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1065.33 | 13.30 | 0.00 | 274.67 | 661.97 | 16.79 | 0.00 | 255.17 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 7919.58 | 38.00 | 294.67 | 368.83 | 2283.64 | 25.95 | 142.67 | 336.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-07:19 | 1778.97 | 21.03 | 85.00 | 266.50 | 931.52 | 21.52 | 55.00 | 235.33 |
February | 279.67 | 0.51 | 0.48 | 01-FEB-07:10 | 1913.82 | 19.66 | 70.83 | 268.67 | 1045.41 | 21.76 | 54.50 | 230.50 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 2368.67 | 20.96 | 106.50 | 318.33 | 1320.95 | 21.81 | 77.67 | 284.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-05:00 | 2399.89 | 19.94 | 93.67 | 339.83 | 1311.25 | 20.95 | 65.17 | 311.33 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:10 | 2303.40 | 19.29 | 99.17 | 378.83 | 1295.92 | 20.58 | 70.17 | 338.83 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:10 | 2302.16 | 18.45 | 88.83 | 370.00 | 1260.20 | 19.79 | 60.67 | 334.17 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:30 | 2530.86 | 18.95 | 99.67 | 379.00 | 1379.52 | 20.09 | 68.67 | 349.00 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-06:49 | 2542.50 | 19.80 | 103.33 | 363.50 | 1344.05 | 20.64 | 69.67 | 334.17 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:40 | 2664.30 | 20.42 | 98.83 | 313.83 | 1050.01 | 19.66 | 43.67 | 282.33 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 2410.23 | 20.30 | 88.83 | 287.33 | 1025.47 | 19.64 | 42.50 | 247.50 |
November | 300.00 | 0.53 | 0.48 | 01-NOV-06:40 | 2017.18 | 21.33 | 95.17 | 265.67 | 1120.21 | 22.10 | 68.33 | 238.83 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-07:10 | 1752.91 | 20.69 | 86.17 | 267.17 | 952.30 | 22.09 | 64.33 | 233.17 |
Annual Sum or Average | 4065.67 | 0.52 | 2274.06 | 19.99 | 1116.00 | 3818.67 | 1187.85 | 20.83 | 740.33 | 3419.67 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1752.91 | 18.45 | 70.83 | 265.67 | 931.52 | 19.64 | 42.50 | 230.50 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 2664.30 | 21.33 | 106.50 | 379.00 | 1379.52 | 22.10 | 77.67 | 349.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.56 | 0.48 | 01-JAN-08:00 | 564.95 | 11.10 | 0.00 | 239.00 | 382.56 | 14.95 | 0.00 | 180.00 |
February | 279.67 | 0.54 | 0.48 | 01-FEB-08:50 | 673.13 | 12.07 | 0.00 | 250.33 | 431.91 | 15.64 | 0.00 | 191.83 |
March | 338.17 | 0.54 | 0.48 | 01-MAR-08:20 | 787.99 | 12.53 | 0.00 | 306.83 | 492.32 | 15.93 | 0.00 | 260.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:10 | 883.78 | 13.71 | 0.00 | 336.50 | 585.62 | 17.29 | 0.00 | 304.50 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:40 | 1092.21 | 14.05 | 0.00 | 382.83 | 663.34 | 17.63 | 0.00 | 356.00 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:40 | 1155.51 | 16.25 | 42.50 | 375.67 | 715.75 | 19.50 | 40.83 | 347.50 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:49 | 1089.35 | 16.34 | 45.17 | 385.33 | 669.11 | 17.81 | 0.00 | 363.33 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:19 | 906.93 | 13.84 | 0.00 | 366.33 | 603.01 | 17.44 | 0.00 | 342.33 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-06:00 | 789.11 | 13.04 | 0.00 | 305.67 | 526.72 | 16.60 | 0.00 | 266.17 |
October | 296.17 | 0.55 | 0.48 | 01-OCT-09:39 | 604.54 | 11.50 | 0.00 | 266.00 | 412.59 | 15.22 | 0.00 | 201.33 |
November | 300.00 | 0.56 | 0.48 | 01-NOV-07:49 | 574.08 | 10.98 | 0.00 | 243.00 | 385.32 | 14.60 | 0.00 | 186.83 |
December | 297.00 | 0.57 | 0.48 | 01-DEC-08:39 | 514.43 | 10.45 | 0.00 | 231.50 | 354.64 | 14.26 | 0.00 | 161.33 |
Annual Sum or Average | 4065.67 | 0.53 | 829.03 | 13.20 | 87.67 | 3689.00 | 533.40 | 16.57 | 40.83 | 3161.67 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 514.43 | 10.45 | 0.00 | 231.50 | 354.64 | 14.26 | 0.00 | 161.33 | |
Maximum of Months | 408.67 | 0.57 | 0.48 | 1155.51 | 16.34 | 45.17 | 385.33 | 715.75 | 19.50 | 40.83 | 363.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.53 | 0.48 | 01-JAN-08:50 | 2293.14 | 22.12 | 105.33 | 255.17 | 896.63 | 20.67 | 45.33 | 222.00 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-08:50 | 2122.05 | 21.13 | 85.17 | 257.83 | 1162.19 | 21.94 | 60.00 | 223.33 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-08:20 | 2370.45 | 20.47 | 100.83 | 311.50 | 1302.45 | 21.29 | 71.50 | 275.67 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:40 | 3235.87 | 18.68 | 82.33 | 333.33 | 1274.00 | 16.69 | 0.00 | 304.50 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-07:19 | 3029.95 | 16.11 | 52.33 | 370.00 | 1279.82 | 16.83 | 0.00 | 337.17 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-07:10 | 2587.53 | 13.14 | 0.00 | 364.33 | 1441.89 | 16.74 | 0.00 | 330.83 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-06:49 | 2723.58 | 13.28 | 5.67 | 373.17 | 1491.76 | 16.66 | 0.00 | 348.83 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:49 | 3345.04 | 18.35 | 88.17 | 357.83 | 1413.17 | 16.90 | 7.00 | 331.17 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-07:30 | 3003.11 | 21.39 | 104.83 | 307.67 | 1584.90 | 21.96 | 73.67 | 277.83 |
October | 296.17 | 0.52 | 0.48 | 01-OCT-09:39 | 2858.24 | 21.86 | 107.83 | 289.00 | 1177.98 | 21.18 | 58.50 | 251.67 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-07:00 | 2244.15 | 21.95 | 104.33 | 258.50 | 1251.10 | 22.47 | 75.00 | 225.67 |
December | 297.00 | 0.55 | 0.48 | 01-DEC-08:39 | 2038.04 | 21.96 | 104.67 | 251.00 | 1149.88 | 22.52 | 74.67 | 212.17 |
Annual Sum or Average | 4065.67 | 0.52 | 2690.53 | 18.84 | 941.50 | 3729.33 | 1300.40 | 19.36 | 465.67 | 3340.83 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 2038.04 | 13.14 | 0.00 | 251.00 | 896.63 | 16.66 | 0.00 | 212.17 | |
Maximum of Months | 408.67 | 0.55 | 0.48 | 3345.04 | 22.12 | 107.83 | 373.17 | 1584.90 | 22.52 | 75.00 | 348.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:30 | 7920.93 | 37.00 | 284.83 | 281.17 | 1816.05 | 22.51 | 97.17 | 266.33 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:19 | 7012.60 | 35.32 | 275.00 | 274.67 | 1348.35 | 20.70 | 61.00 | 255.17 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 2109.43 | 14.11 | 11.17 | 316.00 | 1076.91 | 16.97 | 3.00 | 290.67 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:10 | 1402.64 | 13.50 | 0.00 | 333.17 | 890.15 | 17.08 | 0.00 | 305.50 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-06:49 | 1197.49 | 13.50 | 0.00 | 366.50 | 721.59 | 16.98 | 0.00 | 330.33 |
June | 381.00 | 0.52 | 0.48 | 01-JUN-06:49 | 1066.56 | 13.27 | 0.00 | 358.17 | 662.83 | 16.78 | 0.00 | 316.17 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-06:30 | 1079.08 | 13.43 | 0.00 | 368.83 | 691.17 | 16.96 | 0.00 | 336.33 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:19 | 1210.58 | 13.40 | 0.00 | 355.17 | 784.28 | 16.95 | 0.00 | 324.50 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:00 | 1755.81 | 14.04 | 14.00 | 309.83 | 1026.40 | 16.83 | 0.00 | 283.17 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 3928.29 | 23.11 | 141.67 | 304.67 | 1265.68 | 17.08 | 14.00 | 279.50 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 7659.67 | 36.90 | 294.67 | 279.67 | 1635.73 | 22.12 | 92.67 | 270.83 |
December | 297.00 | 0.50 | 0.48 | 01-DEC-07:19 | 7796.68 | 37.99 | 293.00 | 283.17 | 2285.38 | 25.94 | 142.67 | 273.00 |
Annual Sum or Average | 4065.67 | 0.51 | 3356.60 | 20.97 | 1314.33 | 3831.00 | 1131.52 | 18.65 | 410.50 | 3531.50 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1066.56 | 13.27 | 0.00 | 274.67 | 662.83 | 16.78 | 0.00 | 255.17 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 7920.93 | 37.99 | 294.67 | 368.83 | 2285.38 | 25.94 | 142.67 | 336.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-07:19 | 1779.64 | 21.00 | 85.00 | 266.50 | 932.36 | 21.50 | 55.00 | 235.50 |
February | 279.67 | 0.51 | 0.48 | 01-FEB-07:10 | 1914.89 | 19.63 | 70.83 | 268.83 | 1046.43 | 21.75 | 54.50 | 230.67 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 2370.16 | 20.94 | 106.50 | 318.33 | 1322.16 | 21.80 | 77.67 | 284.67 |
April | 358.33 | 0.51 | 0.48 | 01-APR-05:00 | 2401.12 | 19.91 | 93.67 | 340.00 | 1312.39 | 20.94 | 65.17 | 311.67 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:10 | 2304.92 | 19.26 | 99.17 | 378.83 | 1297.16 | 20.57 | 70.17 | 339.00 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:10 | 2303.50 | 18.42 | 88.83 | 370.00 | 1261.34 | 19.77 | 60.67 | 334.67 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:30 | 2532.03 | 18.92 | 99.67 | 379.17 | 1380.68 | 20.07 | 68.67 | 349.00 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-06:49 | 2543.51 | 19.77 | 103.33 | 363.50 | 1345.12 | 20.63 | 69.67 | 334.33 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:40 | 2665.38 | 20.40 | 98.83 | 313.83 | 1051.02 | 19.64 | 43.67 | 282.83 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 2411.05 | 20.27 | 88.83 | 287.33 | 1026.32 | 19.62 | 42.50 | 247.83 |
November | 300.00 | 0.53 | 0.48 | 01-NOV-06:40 | 2017.92 | 21.30 | 95.17 | 265.67 | 1121.06 | 22.09 | 68.33 | 239.00 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-07:10 | 1753.42 | 20.66 | 86.17 | 267.17 | 953.00 | 22.08 | 64.33 | 233.17 |
Annual Sum or Average | 4065.67 | 0.52 | 2275.14 | 19.96 | 1116.00 | 3819.17 | 1188.89 | 20.81 | 740.33 | 3422.33 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1753.42 | 18.42 | 70.83 | 265.67 | 932.36 | 19.62 | 42.50 | 230.67 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 2665.38 | 21.30 | 106.50 | 379.17 | 1380.68 | 22.09 | 77.67 | 349.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.56 | 0.48 | 01-JAN-08:00 | 565.26 | 11.07 | 0.00 | 239.00 | 382.97 | 14.93 | 0.00 | 180.33 |
February | 279.67 | 0.54 | 0.48 | 01-FEB-08:50 | 673.71 | 12.04 | 0.00 | 250.50 | 432.44 | 15.63 | 0.00 | 192.33 |
March | 338.17 | 0.54 | 0.48 | 01-MAR-08:20 | 788.80 | 12.50 | 0.00 | 306.83 | 492.97 | 15.91 | 0.00 | 260.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:10 | 884.46 | 13.68 | 0.00 | 336.50 | 586.27 | 17.27 | 0.00 | 304.50 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:40 | 1093.34 | 14.02 | 0.00 | 383.00 | 664.21 | 17.61 | 0.00 | 356.17 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:40 | 1156.62 | 16.22 | 42.50 | 375.83 | 716.63 | 19.48 | 40.83 | 347.67 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:49 | 1090.20 | 16.31 | 45.17 | 385.50 | 669.89 | 17.80 | 0.00 | 363.33 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:19 | 907.54 | 13.80 | 0.00 | 366.33 | 603.65 | 17.42 | 0.00 | 342.33 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-06:00 | 789.68 | 13.01 | 0.00 | 305.67 | 527.30 | 16.58 | 0.00 | 266.17 |
October | 296.17 | 0.55 | 0.48 | 01-OCT-09:39 | 604.93 | 11.47 | 0.00 | 266.17 | 413.02 | 15.20 | 0.00 | 201.50 |
November | 300.00 | 0.56 | 0.48 | 01-NOV-07:49 | 574.44 | 10.94 | 0.00 | 243.00 | 385.74 | 14.58 | 0.00 | 186.83 |
December | 297.00 | 0.57 | 0.48 | 01-DEC-08:39 | 514.67 | 10.41 | 0.00 | 231.50 | 355.00 | 14.25 | 0.00 | 161.50 |
Annual Sum or Average | 4065.67 | 0.53 | 829.69 | 13.17 | 87.67 | 3689.83 | 534.02 | 16.56 | 40.83 | 3163.17 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 514.67 | 10.41 | 0.00 | 231.50 | 355.00 | 14.25 | 0.00 | 161.50 | |
Maximum of Months | 408.67 | 0.57 | 0.48 | 1156.62 | 16.31 | 45.17 | 385.50 | 716.63 | 19.48 | 40.83 | 363.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.53 | 0.48 | 01-JAN-08:50 | 2293.86 | 22.09 | 105.33 | 255.17 | 897.54 | 20.65 | 45.33 | 222.00 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-08:50 | 2123.11 | 21.11 | 85.17 | 258.00 | 1163.31 | 21.92 | 60.00 | 223.33 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-08:20 | 2371.89 | 20.44 | 100.83 | 311.50 | 1303.72 | 21.28 | 71.50 | 275.83 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:40 | 3237.05 | 18.66 | 82.33 | 333.50 | 1275.25 | 16.68 | 0.00 | 304.50 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-07:19 | 3031.43 | 16.08 | 52.33 | 370.00 | 1281.12 | 16.81 | 0.00 | 337.33 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-07:10 | 2588.83 | 13.10 | 0.00 | 364.83 | 1443.20 | 16.72 | 0.00 | 331.17 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-06:49 | 2724.60 | 13.24 | 5.67 | 373.00 | 1493.01 | 16.64 | 0.00 | 349.00 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:49 | 3346.05 | 18.32 | 88.17 | 357.83 | 1414.34 | 16.88 | 7.00 | 331.33 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-07:30 | 3004.30 | 21.37 | 104.83 | 307.67 | 1586.16 | 21.94 | 73.67 | 278.00 |
October | 296.17 | 0.52 | 0.48 | 01-OCT-09:39 | 2859.08 | 21.83 | 107.83 | 289.00 | 1178.88 | 21.17 | 58.50 | 252.00 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-07:00 | 2244.92 | 21.92 | 104.33 | 258.50 | 1252.06 | 22.46 | 75.00 | 225.67 |
December | 297.00 | 0.55 | 0.48 | 01-DEC-08:39 | 2038.60 | 21.94 | 104.67 | 251.00 | 1150.70 | 22.50 | 74.67 | 212.50 |
Annual Sum or Average | 4065.67 | 0.52 | 2691.60 | 18.81 | 941.50 | 3730.00 | 1301.54 | 19.35 | 465.67 | 3342.67 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 2038.60 | 13.10 | 0.00 | 251.00 | 897.54 | 16.64 | 0.00 | 212.50 | |
Maximum of Months | 408.67 | 0.55 | 0.48 | 3346.05 | 22.09 | 107.83 | 373.00 | 1586.16 | 22.50 | 75.00 | 349.00 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAWATERHEATC
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.373583E+09 | 67448.01 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 94404867.62 | 19316.63 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 218337.34 | 363.90 | 06-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 57255960.47 | 8774.13 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133250E+09 | 67093.99 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.658712E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.373583E+09 | 67448.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.156433E+10 | 104411.74 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.451094E+09 | 65717.33 | 21-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.796105E+09 | 100655.92 | 08-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 77831845.94 | 32477.28 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 893374.31 | 1235.79 | 30-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180109E+09 | 58858.70 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.734868E+09 | 96101.79 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.380523E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.156433E+10 | 104411.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.783440E+09 | 117580.12 | 09-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.408462E+09 | 24974.12 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.473571E+09 | 116407.90 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35285446.41 | 30903.11 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 563418.64 | 939.03 | 30-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 77429974.61 | 24438.02 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.410109E+09 | 88241.65 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218886E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.783440E+09 | 117580.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.199842E+09 | 71100.97 | 09-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5075497.79 | 3129.48 | 13-FEB-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.390357E+09 | 132085.11 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 47265873.06 | 10578.78 | 01-APR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 45500033.40 | 52488.68 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.688040E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.390357E+09 | 132085.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.720445E+09 | 109724.55 | 09-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 69660968.56 | 6107.10 | 28-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.299510E+09 | 73215.99 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 48293857.35 | 13118.36 | 01-APR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 712836.47 | 468.42 | 30-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166723E+09 | 30648.15 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130535E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.720445E+09 | 109724.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.101754E+10 | 11960.37 | 02-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.583938E+09 | 12358.33 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.601625E+09 | 11987.38 | 28-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102147E+09 | 11833.19 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30031029.52 | 11732.18 | 15-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 340457.64 | 300.73 | 20-SEP-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86910597.00 | 11823.72 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.408628E+09 | 11994.85 | 07-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.752118E+09 | 12443.03 | 18-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.358328E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.101754E+10 | 12443.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.489843E+09 | 13695.16 | 02-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.360982E+09 | 13675.30 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.326334E+09 | 13625.84 | 29-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 44717858.75 | 13614.07 | 01-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7726574.72 | 8870.26 | 15-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 79613.11 | 72.39 | 01-JUN-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1896558.27 | 824.97 | 20-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 39026474.53 | 13655.72 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161041E+09 | 13631.22 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.343258E+09 | 13700.04 | 16-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177490E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.489843E+09 | 13700.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.368198E+09 | 15127.90 | 02-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.274224E+09 | 15710.22 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.402211E+09 | 15044.38 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70877255.28 | 14811.39 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40878517.74 | 14883.92 | 15-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16476031.50 | 2490.74 | 12-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 93055526.52 | 14963.26 | 06-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.215822E+09 | 15039.31 | 04-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148174E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.402211E+09 | 15710.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.486413E+09 | 13779.42 | 02-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.279180E+09 | 13623.30 | 21-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.273587E+09 | 13691.04 | 30-MAR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 38774096.99 | 13688.96 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16675944.41 | 4697.67 | 13-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30715217.97 | 1881.74 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180290E+09 | 13716.34 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.334733E+09 | 13439.71 | 13-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164037E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.486413E+09 | 13779.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_HEATC
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107598E+10 | 224250.53 | 16-JAN-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.384062E+09 | 223967.64 | 20-FEB-20:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 44649758.75 | 223246.79 | 06-MAR-04:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.403523E+09 | 224255.07 | 24-APR-01:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.560618E+09 | 224254.22 | 30-MAY-02:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.123237E+09 | 224255.15 | 08-JUN-03:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.697344E+09 | 224254.86 | 10-JUL-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.485481E+09 | 223875.37 | 27-AUG-22:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.380148E+09 | 224257.54 | 04-SEP-17:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.908977E+09 | 224255.72 | 09-OCT-00:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.459536E+09 | 224254.85 | 12-NOV-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.423229E+09 | 223414.90 | 25-DEC-21:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.594678E+10 | |||||||
Minimum of Months | 44649758.75 | 223246.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107598E+10 | 224257.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_HEATC
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 80225748.31 | 7788.69 | 28-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18383255.89 | 3625.48 | 30-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1170896.77 | 1220.66 | 12-DEC-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 99779900.98 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80225748.31 | 7788.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_HEATC
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.240080E+10 | 108683.08 | 09-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147152E+09 | 33429.29 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124422E+10 | 68716.47 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23966238.24 | 25689.08 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2536674.40 | 2967.10 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100124E+10 | 60388.38 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.481992E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.240080E+10 | 108683.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_HEATC
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.641777E+09 | 16024.37 | 09-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136322E+09 | 7480.84 | 09-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.428777E+09 | 11494.62 | 30-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11907517.97 | 6517.84 | 01-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2035.95 | 0.64 | 04-MAY-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4723.87 | 0.81 | 06-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2850.41 | 0.90 | 03-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7888.21 | 0.71 | 07-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6699.46 | 0.77 | 29-SEP-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1272404.46 | 1535.26 | 12-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23337775.35 | 5295.99 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.374253E+09 | 10224.33 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161767E+10 | |||||||
Minimum of Months | 2035.95 | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.641777E+09 | 16024.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAELECHEATC
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.121068E+11 | 0.119468E+11 | 85421.96 | 16-JAN-14:51 | 58579.52 | 0.13 |
February | 0.00 | 0.00 | 0.545688E+10 | 0.536838E+10 | 74937.05 | 13-FEB-05:51 | 34103.97 | 0.08 |
March | 0.00 | 0.00 | 0.604915E+10 | 0.595727E+10 | 55700.47 | 24-MAR-03:01 | 23580.30 | 0.10 |
April | 0.00 | 0.00 | 0.158068E+11 | 0.155584E+11 | 82966.32 | 30-APR-23:10 | 36849.59 | 0.26 |
May | 0.00 | 0.00 | 0.151443E+11 | 0.149517E+11 | 82478.99 | 29-MAY-14:30 | 63108.86 | 0.27 |
June | 0.00 | 0.00 | 0.268395E+11 | 0.260177E+11 | 95330.86 | 28-JUN-03:01 | 40604.62 | 0.38 |
July | 0.00 | 0.00 | 0.454068E+11 | 0.400346E+11 | 105748.74 | 28-JUL-03:01 | 43614.36 | 0.44 |
August | 0.00 | 0.00 | 0.518765E+11 | 0.442754E+11 | 120428.16 | 06-AUG-18:30 | 51897.34 | 0.49 |
September | 0.00 | 0.00 | 0.315283E+11 | 0.289108E+11 | 105745.06 | 22-SEP-04:51 | 43582.10 | 0.37 |
October | 0.00 | 0.00 | 0.419918E+11 | 0.374177E+11 | 124194.05 | 05-OCT-03:01 | 57506.55 | 0.29 |
November | 0.00 | 0.00 | 0.133721E+11 | 0.131940E+11 | 83975.06 | 12-NOV-00:01 | 37893.69 | 0.15 |
December | 0.00 | 0.00 | 0.163690E+11 | 0.163397E+11 | 93595.60 | 25-DEC-11:51 | 93595.60 | 0.04 |
Annual Sum or Average | 0.281948E+12 | 0.259972E+12 | 0.25 | |||||
Minimum of Months | 0.00 | 0.00 | 0.545688E+10 | 0.536838E+10 | 55700.47 | 23580.30 | 0.04 | |
Maximum of Months | 0.00 | 0.00 | 0.518765E+11 | 0.442754E+11 | 124194.05 | 93595.60 | 0.49 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.233312E+11 | 0.231267E+11 | 83762.90 | 18-JAN-13:50 | 83762.90 | 0.22 |
February | 0.00 | 0.00 | 0.156099E+11 | 0.150503E+11 | 80554.46 | 01-FEB-12:00 | 80554.46 | 0.21 |
March | 0.00 | 0.00 | 0.186911E+11 | 0.173055E+11 | 103896.26 | 23-MAR-15:00 | 70660.09 | 0.24 |
April | 0.00 | 0.00 | 0.384943E+11 | 0.360596E+11 | 103840.41 | 26-APR-11:00 | 89154.06 | 0.41 |
May | 0.00 | 0.00 | 0.342926E+11 | 0.335002E+11 | 76516.27 | 04-MAY-13:50 | 68192.40 | 0.46 |
June | 0.00 | 0.00 | 0.648715E+11 | 0.517851E+11 | 125329.81 | 29-JUN-13:00 | 73357.45 | 0.60 |
July | 0.00 | 0.00 | 0.115272E+12 | 0.735293E+11 | 169012.37 | 31-JUL-15:40 | 92210.39 | 0.68 |
August | 0.00 | 0.00 | 0.141050E+12 | 0.844230E+11 | 173657.76 | 18-AUG-15:50 | 93852.27 | 0.75 |
September | 0.00 | 0.00 | 0.732311E+11 | 0.530012E+11 | 142178.71 | 22-SEP-11:40 | 66649.70 | 0.57 |
October | 0.00 | 0.00 | 0.810878E+11 | 0.649061E+11 | 188362.51 | 05-OCT-04:11 | 85583.97 | 0.41 |
November | 0.00 | 0.00 | 0.290306E+11 | 0.282493E+11 | 90795.89 | 28-NOV-14:00 | 90795.89 | 0.25 |
December | 0.00 | 0.00 | 0.312344E+11 | 0.311690E+11 | 97195.85 | 05-DEC-15:00 | 97195.85 | 0.12 |
Annual Sum or Average | 0.666196E+12 | 0.512105E+12 | 0.41 | |||||
Minimum of Months | 0.00 | 0.00 | 0.156099E+11 | 0.150503E+11 | 76516.27 | 66649.70 | 0.12 | |
Maximum of Months | 0.00 | 0.00 | 0.141050E+12 | 0.844230E+11 | 188362.51 | 97195.85 | 0.75 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.189321E+12 | 0.187976E+12 | 675302.12 | 18-JAN-14:00 | 675302.12 | 0.23 |
February | 0.00 | 0.00 | 0.120341E+12 | 0.116266E+12 | 646570.18 | 01-FEB-12:00 | 646570.18 | 0.22 |
March | 0.00 | 0.00 | 0.138602E+12 | 0.128359E+12 | 849977.00 | 23-MAR-15:00 | 582513.88 | 0.24 |
April | 0.00 | 0.00 | 0.271207E+12 | 0.255940E+12 | 807866.36 | 26-APR-11:00 | 674194.65 | 0.40 |
May | 0.00 | 0.00 | 0.278519E+12 | 0.272091E+12 | 664799.02 | 04-MAY-14:00 | 595464.45 | 0.46 |
June | 0.00 | 0.00 | 0.517198E+12 | 0.414943E+12 | 1051566.23 | 29-JUN-13:00 | 617089.02 | 0.57 |
July | 0.00 | 0.00 | 0.872444E+12 | 0.560464E+12 | 1344285.93 | 31-JUL-15:50 | 727264.10 | 0.59 |
August | 0.00 | 0.00 | 0.100669E+13 | 0.615006E+12 | 1418285.81 | 18-AUG-15:50 | 769138.83 | 0.61 |
September | 0.00 | 0.00 | 0.618168E+12 | 0.449651E+12 | 1194556.83 | 22-SEP-12:30 | 595062.19 | 0.55 |
October | 0.00 | 0.00 | 0.652647E+12 | 0.525284E+12 | 1392966.25 | 05-OCT-04:11 | 632908.57 | 0.39 |
November | 0.00 | 0.00 | 0.212543E+12 | 0.207336E+12 | 657756.77 | 28-NOV-14:10 | 657756.77 | 0.25 |
December | 0.00 | 0.00 | 0.221693E+12 | 0.221411E+12 | 707162.92 | 05-DEC-15:00 | 707162.92 | 0.12 |
Annual Sum or Average | 0.509937E+13 | 0.395473E+13 | 0.39 | |||||
Minimum of Months | 0.00 | 0.00 | 0.120341E+12 | 0.116266E+12 | 646570.18 | 582513.88 | 0.12 | |
Maximum of Months | 0.00 | 0.00 | 0.100669E+13 | 0.615006E+12 | 1418285.81 | 769138.83 | 0.61 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.164824E+11 | 0.163800E+11 | 62113.72 | 18-JAN-13:20 | 62113.72 | 0.21 |
February | 0.00 | 0.00 | 0.106349E+11 | 0.102462E+11 | 60191.22 | 03-FEB-15:00 | 60191.22 | 0.19 |
March | 0.00 | 0.00 | 0.126544E+11 | 0.116293E+11 | 89953.38 | 23-MAR-15:00 | 61520.55 | 0.20 |
April | 0.00 | 0.00 | 0.270165E+11 | 0.254276E+11 | 96513.94 | 26-APR-14:00 | 90491.95 | 0.37 |
May | 0.00 | 0.00 | 0.277870E+11 | 0.271186E+11 | 77388.95 | 03-MAY-14:00 | 68575.46 | 0.43 |
June | 0.00 | 0.00 | 0.540263E+11 | 0.430272E+11 | 120377.58 | 29-JUN-13:00 | 70426.32 | 0.56 |
July | 0.00 | 0.00 | 0.930951E+11 | 0.596283E+11 | 166146.30 | 19-JUL-15:40 | 96084.65 | 0.58 |
August | 0.00 | 0.00 | 0.107182E+12 | 0.647752E+11 | 169655.76 | 17-AUG-15:40 | 95157.94 | 0.60 |
September | 0.00 | 0.00 | 0.616377E+11 | 0.448197E+11 | 127854.84 | 22-SEP-12:20 | 62959.98 | 0.53 |
October | 0.00 | 0.00 | 0.637254E+11 | 0.509907E+11 | 154690.91 | 05-OCT-05:02 | 68251.62 | 0.38 |
November | 0.00 | 0.00 | 0.184394E+11 | 0.179780E+11 | 60774.74 | 28-NOV-14:00 | 60774.74 | 0.23 |
December | 0.00 | 0.00 | 0.195179E+11 | 0.194942E+11 | 69591.61 | 05-DEC-15:00 | 69591.61 | 0.10 |
Annual Sum or Average | 0.512199E+12 | 0.391515E+12 | 0.37 | |||||
Minimum of Months | 0.00 | 0.00 | 0.106349E+11 | 0.102462E+11 | 60191.22 | 60191.22 | 0.10 | |
Maximum of Months | 0.00 | 0.00 | 0.107182E+12 | 0.647752E+11 | 169655.76 | 96084.65 | 0.60 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.821528E+11 | 0.820024E+11 | 135050.40 | 17-JAN-02:70 | 119551.31 | 0.00 |
February | 0.00 | 0.00 | 0.135071E+12 | 0.134386E+12 | 271307.29 | 12-FEB-14:10 | 205193.28 | 0.00 |
March | 0.00 | 0.00 | 0.228778E+12 | 0.214901E+12 | 331738.55 | 19-MAR-08:27 | 293507.67 | 0.00 |
April | 0.00 | 0.00 | 0.565517E+12 | 0.476919E+12 | 417003.10 | 11-APR-21:40 | 382652.22 | 0.00 |
May | 0.00 | 0.00 | 0.168852E+11 | 0.164257E+11 | 147365.17 | 01-MAY-00:20 | 131940.35 | 0.00 |
June | 0.00 | 0.00 | 0.910115E+11 | 0.671037E+11 | 245784.94 | 14-JUN-24:00 | 206436.33 | 0.00 |
July | 0.00 | 0.00 | 0.482460E+12 | 0.289545E+12 | 422584.12 | 31-JUL-13:55 | 284848.73 | 0.00 |
August | 0.00 | 0.00 | 0.932016E+12 | 0.512373E+12 | 422438.88 | 07-AUG-07:15 | 188179.82 | 0.00 |
September | 0.00 | 0.00 | 0.304107E+11 | 0.270109E+11 | 190926.93 | 22-SEP-01:10 | 118944.93 | 0.00 |
October | 0.00 | 0.00 | 0.222204E+12 | 0.193288E+12 | 313018.31 | 01-OCT-03:40 | 202650.45 | 0.00 |
November | 0.00 | 0.00 | 0.234070E+12 | 0.220517E+12 | 369794.58 | 12-NOV-05:10 | 294997.37 | 0.00 |
December | 0.00 | 0.00 | 0.461455E+12 | 0.438880E+12 | 395567.33 | 26-DEC-04:50 | 395567.33 | 0.00 |
Annual Sum or Average | 0.348203E+13 | 0.267335E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.168852E+11 | 0.164257E+11 | 135050.40 | 118944.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.932016E+12 | 0.512373E+12 | 422584.12 | 395567.33 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.510533E+10 | 0.510533E+10 | 2407.74 | 30-JAN-16:50 | 2407.74 | 0.00 |
February | 0.00 | 0.00 | 0.914152E+10 | 0.914152E+10 | 4388.28 | 20-FEB-17:00 | 4388.28 | 0.00 |
March | 0.00 | 0.00 | 0.150901E+11 | 0.150901E+11 | 6280.86 | 19-MAR-17:20 | 6280.86 | 0.00 |
April | 0.00 | 0.00 | 0.194730E+11 | 0.194730E+11 | 8071.73 | 16-APR-17:37 | 8071.73 | 0.00 |
May | 0.00 | 0.00 | 0.537269E+10 | 0.537269E+10 | 2473.30 | 29-MAY-17:43 | 2473.30 | 0.00 |
June | 0.00 | 0.00 | 0.100968E+11 | 0.100968E+11 | 4265.45 | 25-JUN-17:50 | 4265.45 | 0.00 |
July | 0.00 | 0.00 | 0.153739E+11 | 0.153739E+11 | 6190.94 | 04-JUL-18:20 | 6190.94 | 0.00 |
August | 0.00 | 0.00 | 0.202270E+11 | 0.202270E+11 | 8199.36 | 06-AUG-18:03 | 8199.36 | 0.00 |
September | 0.00 | 0.00 | 0.532488E+10 | 0.532488E+10 | 2514.39 | 04-SEP-16:57 | 2514.39 | 0.00 |
October | 0.00 | 0.00 | 0.104080E+11 | 0.104080E+11 | 4515.94 | 15-OCT-16:55 | 4515.94 | 0.00 |
November | 0.00 | 0.00 | 0.147128E+11 | 0.147128E+11 | 6219.75 | 12-NOV-16:30 | 6219.75 | 0.00 |
December | 0.00 | 0.00 | 0.200263E+11 | 0.200263E+11 | 8118.57 | 25-DEC-16:17 | 8118.57 | 0.00 |
Annual Sum or Average | 0.150353E+12 | 0.150353E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.510533E+10 | 0.510533E+10 | 2407.74 | 2407.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202270E+11 | 0.202270E+11 | 8199.36 | 8199.36 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.383603E+11 | 0.383603E+11 | 21965.91 | 30-JAN-16:50 | 21965.91 | 0.00 |
February | 0.00 | 0.00 | 0.781194E+11 | 0.781194E+11 | 40484.32 | 22-FEB-17:00 | 40484.32 | 0.00 |
March | 0.00 | 0.00 | 0.134869E+12 | 0.134869E+12 | 57609.05 | 10-MAR-17:20 | 57609.05 | 0.00 |
April | 0.00 | 0.00 | 0.180326E+12 | 0.180326E+12 | 75109.01 | 27-APR-17:40 | 75109.01 | 0.00 |
May | 0.00 | 0.00 | 0.452269E+11 | 0.452269E+11 | 22074.68 | 28-MAY-17:45 | 22074.68 | 0.00 |
June | 0.00 | 0.00 | 0.917547E+11 | 0.917547E+11 | 39504.86 | 25-JUN-17:55 | 39504.86 | 0.00 |
July | 0.00 | 0.00 | 0.143297E+12 | 0.143297E+12 | 57747.65 | 04-JUL-18:17 | 57747.65 | 0.00 |
August | 0.00 | 0.00 | 0.190066E+12 | 0.190066E+12 | 75521.51 | 06-AUG-17:54 | 75521.51 | 0.00 |
September | 0.00 | 0.00 | 0.456252E+11 | 0.456252E+11 | 23339.11 | 29-SEP-16:40 | 23339.11 | 0.00 |
October | 0.00 | 0.00 | 0.931279E+11 | 0.931279E+11 | 41854.01 | 15-OCT-16:46 | 41854.01 | 0.00 |
November | 0.00 | 0.00 | 0.131882E+12 | 0.131882E+12 | 57376.77 | 07-NOV-16:30 | 57376.77 | 0.00 |
December | 0.00 | 0.00 | 0.181161E+12 | 0.181161E+12 | 74640.73 | 19-DEC-16:20 | 74640.73 | 0.00 |
Annual Sum or Average | 0.135381E+13 | 0.135381E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.383603E+11 | 0.383603E+11 | 21965.91 | 21965.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.190066E+12 | 0.190066E+12 | 75521.51 | 75521.51 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.260937E+10 | 0.260937E+10 | 2144.46 | 26-JAN-16:20 | 2144.46 | 0.00 |
February | 0.00 | 0.00 | 0.688156E+10 | 0.688156E+10 | 4050.85 | 22-FEB-17:00 | 4050.85 | 0.00 |
March | 0.00 | 0.00 | 0.126477E+11 | 0.126477E+11 | 5797.27 | 22-MAR-17:20 | 5797.27 | 0.00 |
April | 0.00 | 0.00 | 0.175735E+11 | 0.175735E+11 | 7566.57 | 27-APR-17:30 | 7566.57 | 0.00 |
May | 0.00 | 0.00 | 0.407187E+10 | 0.407187E+10 | 2284.27 | 29-MAY-17:43 | 2284.27 | 0.00 |
June | 0.00 | 0.00 | 0.896517E+10 | 0.896517E+10 | 4064.02 | 25-JUN-18:00 | 4064.02 | 0.00 |
July | 0.00 | 0.00 | 0.142298E+11 | 0.142298E+11 | 5884.32 | 09-JUL-18:00 | 5884.32 | 0.00 |
August | 0.00 | 0.00 | 0.188844E+11 | 0.188844E+11 | 7646.91 | 20-AUG-17:32 | 7646.91 | 0.00 |
September | 0.00 | 0.00 | 0.425549E+10 | 0.425549E+10 | 2409.26 | 29-SEP-16:40 | 2409.26 | 0.00 |
October | 0.00 | 0.00 | 0.881659E+10 | 0.881659E+10 | 4293.39 | 15-OCT-16:42 | 4293.39 | 0.00 |
November | 0.00 | 0.00 | 0.122900E+11 | 0.122900E+11 | 5723.72 | 07-NOV-16:30 | 5723.72 | 0.00 |
December | 0.00 | 0.00 | 0.169564E+11 | 0.169564E+11 | 7462.96 | 19-DEC-16:20 | 7462.96 | 0.00 |
Annual Sum or Average | 0.128182E+12 | 0.128182E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.260937E+10 | 0.260937E+10 | 2144.46 | 2144.46 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.188844E+11 | 0.188844E+11 | 7646.91 | 7646.91 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7194.05 | 37949.41 | 01-JAN-08:10 | 11481.65 | 45618.11 | 30-JAN-12:20 |
February | 6830.24 | 37939.40 | 26-FEB-08:35 | 11592.87 | 45616.82 | 06-FEB-12:20 |
March | 5570.30 | 37982.61 | 26-MAR-07:40 | 12401.76 | 45400.67 | 01-MAR-12:20 |
April | 6644.09 | 38065.03 | 30-APR-07:13 | 11118.51 | 44594.98 | 03-APR-11:40 |
May | 6512.06 | 38137.77 | 29-MAY-07:20 | 11218.26 | 43634.71 | 01-MAY-12:00 |
June | 5870.79 | 38192.40 | 25-JUN-07:07 | 11284.00 | 42534.99 | 01-JUN-11:50 |
July | 7500.70 | 38225.54 | 30-JUL-07:10 | 10019.19 | 41702.68 | 03-JUL-11:40 |
August | 5795.83 | 38225.93 | 06-AUG-07:05 | 11234.00 | 41604.60 | 31-AUG-11:40 |
September | 6791.97 | 38206.25 | 03-SEP-07:03 | 10406.38 | 42303.76 | 29-SEP-11:20 |
October | 7350.32 | 38157.02 | 01-OCT-07:30 | 10692.29 | 43394.19 | 31-OCT-11:30 |
November | 7415.59 | 38071.48 | 05-NOV-07:20 | 11200.10 | 44453.49 | 30-NOV-12:40 |
December | 7272.26 | 38002.81 | 03-DEC-08:25 | 11011.31 | 45223.95 | 29-DEC-12:20 |
Annual Sum or Average | 6728.72 | 11136.12 | ||||
Minimum of Months | 5570.30 | 37939.40 | 10019.19 | 41604.60 | ||
Maximum of Months | 7500.70 | 38225.93 | 12401.76 | 45618.11 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 3685.48 | 1319183.92 | 12-JAN-06:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1397.90 | 2604482.01 | 10-FEB-05:15 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1914.27 | 1023997.74 | 30-MAR-05:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 466.45 | 742208.66 | 03-APR-03:37 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 255.31 | 935082.45 | 15-MAY-04:12 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 47.69 | 225078.24 | 08-JUN-03:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 260.30 | 224122.42 | 03-JUL-03:47 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 181.00 | 221533.52 | 06-AUG-18:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 146.28 | 225854.94 | 30-SEP-03:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 417.24 | 756671.92 | 18-OCT-03:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 522.94 | 1452333.07 | 22-NOV-04:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1861.08 | 2730770.45 | 22-DEC-04:02 |
Annual Sum or Average | 0.00 | 932.76 | ||||
Minimum of Months | 0.00 | 0.00 | 47.69 | 221533.52 | ||
Maximum of Months | 0.00 | 0.00 | 3685.48 | 2730770.45 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 92005.45 | 933617.44 | 17-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 64329.71 | 998299.30 | 01-FEB-12:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 68943.29 | 1251462.76 | 23-MAR-14:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 142806.35 | 1231614.32 | 26-APR-15:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 136166.25 | 1292804.73 | 04-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 270612.21 | 1354449.58 | 29-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 446566.99 | 1713371.80 | 31-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 513852.97 | 1774561.16 | 18-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 319834.47 | 1480641.98 | 22-SEP-12:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 331382.70 | 1621929.49 | 03-OCT-13:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 108473.16 | 1180619.02 | 28-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 113032.20 | 1263994.23 | 19-DEC-13:15 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 218667.02 | 0.00 | ||||
Minimum of Months | 64329.71 | 933617.44 | 0.00 | 0.00 | ||
Maximum of Months | 513852.97 | 1774561.16 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 91607.78 | 1078535.60 | 18-JAN-14:20 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 63825.44 | 980246.01 | 01-FEB-12:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 68583.76 | 1447076.46 | 22-MAR-13:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 142370.52 | 1359801.53 | 11-APR-15:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 135330.62 | 1161392.45 | 04-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 269857.52 | 1416725.22 | 14-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 445258.72 | 1727526.38 | 31-JUL-15:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 512539.46 | 1912771.99 | 07-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 319665.18 | 1538372.10 | 30-SEP-05:01 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 331011.46 | 2437390.65 | 05-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 107848.19 | 1138697.08 | 28-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 112502.51 | 1243148.27 | 05-DEC-15:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 218030.73 | 0.00 | ||||
Minimum of Months | 63825.44 | 980246.01 | 0.00 | 0.00 | ||
Maximum of Months | 512539.46 | 2437390.65 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 82373.02 | 616532.18 | 14-JAN-12:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 127633.79 | 784368.51 | 01-FEB-12:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 202340.80 | 827317.44 | 23-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 462928.49 | 1307099.52 | 26-APR-13:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 58921.92 | 404481.27 | 04-MAY-12:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 171483.29 | 833982.61 | 29-JUN-11:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 500255.18 | 1353306.69 | 31-JUL-11:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 843231.51 | 1422162.72 | 18-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 121769.95 | 1158731.41 | 29-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 298890.57 | 1433266.45 | 16-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 226603.23 | 1095454.59 | 19-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 382754.69 | 1185692.75 | 05-DEC-10:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 291750.94 | 0.00 | ||||
Minimum of Months | 58921.92 | 404481.27 | 0.00 | 0.00 | ||
Maximum of Months | 843231.51 | 1433266.45 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 133807.55 | 1489457.14 | 17-JAN-13:50 | 955.32 | 85251.78 | 07-JAN-06:50 |
February | 94028.78 | 1286384.10 | 01-FEB-11:40 | 778.29 | 79325.51 | 04-FEB-06:50 |
March | 102395.32 | 2227792.95 | 23-MAR-14:10 | 779.04 | 55621.70 | 23-MAR-06:00 |
April | 210091.41 | 2428472.79 | 26-APR-10:50 | 477.39 | 49695.55 | 21-APR-16:10 |
May | 198937.30 | 1976519.87 | 04-MAY-13:40 | 474.58 | 44636.56 | 31-MAY-03:01 |
June | 445121.02 | 3553726.09 | 29-JUN-13:00 | 131.78 | 42704.24 | 08-JUN-19:00 |
July | 872785.12 | 4777586.23 | 31-JUL-16:00 | 61.59 | 36590.07 | 17-JUL-03:41 |
August | 1048429.54 | 4961357.96 | 18-AUG-16:00 | 36.14 | 16699.47 | 23-AUG-03:25 |
September | 552209.97 | 4266003.20 | 22-SEP-12:40 | 196.92 | 40151.58 | 19-SEP-19:00 |
October | 559431.48 | 4447179.34 | 04-OCT-11:00 | 258.71 | 63749.59 | 25-OCT-05:30 |
November | 156955.76 | 1547674.76 | 28-NOV-14:10 | 620.90 | 75661.82 | 24-NOV-09:00 |
December | 160231.84 | 1759364.70 | 19-DEC-13:15 | 906.85 | 83746.78 | 26-DEC-07:00 |
Annual Sum or Average | 380604.69 | 471.89 | ||||
Minimum of Months | 94028.78 | 1286384.10 | 36.14 | 16699.47 | ||
Maximum of Months | 1048429.54 | 4961357.96 | 955.32 | 85251.78 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150921E+11 | 0.86 | 9230.66 | 01-JAN-00:20 | 1.41 |
February | 0.130126E+11 | 0.82 | 9230.66 | 01-FEB-04:01 | 1.42 |
March | 0.150072E+11 | 0.85 | 9230.66 | 01-MAR-05:11 | 1.41 |
April | 0.139231E+11 | 0.82 | 9230.66 | 01-APR-04:11 | 1.42 |
May | 0.143901E+11 | 0.82 | 9230.66 | 01-MAY-00:10 | 1.40 |
June | 0.144243E+11 | 0.85 | 9230.66 | 01-JUN-03:01 | 1.41 |
July | 0.142255E+11 | 0.81 | 9230.66 | 01-JUL-03:01 | 1.41 |
August | 0.153801E+11 | 0.87 | 9230.66 | 01-AUG-03:01 | 1.41 |
September | 0.144432E+11 | 0.85 | 9230.66 | 01-SEP-03:01 | 1.41 |
October | 0.151265E+11 | 0.86 | 9230.66 | 01-OCT-16:20 | 1.40 |
November | 0.147843E+11 | 0.87 | 9230.66 | 01-NOV-03:01 | 1.41 |
December | 0.148927E+11 | 0.85 | 9230.66 | 01-DEC-04:01 | 1.41 |
Annual Sum or Average | 0.174702E+12 | 0.84 | |||
Minimum of Months | 0.130126E+11 | 0.81 | 9230.66 | 1.40 | |
Maximum of Months | 0.153801E+11 | 0.87 | 9230.66 | 1.42 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.495866E+10 | 0.36 | 9364.19 | 25-JAN-05:11 | 1.14 |
February | 0.477600E+10 | 0.38 | 12311.83 | 15-FEB-05:11 | 1.35 |
March | 0.602833E+10 | 0.41 | 12723.29 | 03-MAR-05:11 | 1.38 |
April | 0.621313E+10 | 0.44 | 12723.29 | 03-APR-04:11 | 1.38 |
May | 0.475200E+10 | 0.37 | 12723.29 | 01-MAY-04:12 | 1.37 |
June | 0.527345E+10 | 0.40 | 15071.42 | 05-JUN-05:01 | 1.53 |
July | 0.596468E+10 | 0.43 | 15488.76 | 03-JUL-05:01 | 1.55 |
August | 0.706800E+10 | 0.50 | 13109.92 | 28-AUG-05:01 | 1.40 |
September | 0.489830E+10 | 0.38 | 15306.69 | 30-SEP-03:01 | 1.55 |
October | 0.565662E+10 | 0.40 | 18216.73 | 16-OCT-05:01 | 1.74 |
November | 0.608243E+10 | 0.42 | 12723.29 | 02-NOV-04:11 | 1.38 |
December | 0.643650E+10 | 0.42 | 12723.29 | 01-DEC-05:11 | 1.38 |
Annual Sum or Average | 0.681081E+11 | 0.41 | |||
Minimum of Months | 0.475200E+10 | 0.36 | 9364.19 | 1.14 | |
Maximum of Months | 0.706800E+10 | 0.50 | 18216.73 | 1.74 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.356253E+11 | 0.32 | 93341.08 | 10-JAN-06:03 | 1.20 |
February | 0.318919E+11 | 0.32 | 85539.90 | 01-FEB-06:03 | 1.14 |
March | 0.362575E+11 | 0.33 | 113152.51 | 30-MAR-05:02 | 1.35 |
April | 0.356185E+11 | 0.33 | 108959.59 | 24-APR-05:01 | 1.31 |
May | 0.356315E+11 | 0.33 | 90410.43 | 01-MAY-05:03 | 1.17 |
June | 0.376895E+11 | 0.35 | 119806.98 | 19-JUN-05:01 | 1.39 |
July | 0.392173E+11 | 0.35 | 139509.26 | 03-JUL-05:01 | 1.53 |
August | 0.432892E+11 | 0.37 | 119806.98 | 28-AUG-05:01 | 1.39 |
September | 0.381998E+11 | 0.34 | 178780.33 | 30-SEP-05:01 | 1.80 |
October | 0.402425E+11 | 0.34 | 148922.29 | 16-OCT-05:01 | 1.61 |
November | 0.370306E+11 | 0.33 | 85539.90 | 01-NOV-05:02 | 1.13 |
December | 0.366684E+11 | 0.32 | 92908.89 | 13-DEC-06:03 | 1.19 |
Annual Sum or Average | 0.447362E+12 | 0.34 | |||
Minimum of Months | 0.318919E+11 | 0.32 | 85539.90 | 1.13 | |
Maximum of Months | 0.432892E+11 | 0.37 | 178780.33 | 1.80 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.300538E+10 | 0.30 | 4771.18 | 26-JAN-15:30 | 0.80 |
February | 0.272339E+10 | 0.30 | 4694.69 | 16-FEB-14:50 | 0.79 |
March | 0.314912E+10 | 0.31 | 5536.93 | 24-MAR-05:02 | 0.86 |
April | 0.342057E+10 | 0.32 | 7948.90 | 13-APR-05:02 | 1.07 |
May | 0.343516E+10 | 0.32 | 7948.90 | 03-MAY-05:03 | 1.07 |
June | 0.387017E+10 | 0.35 | 9200.16 | 26-JUN-05:03 | 1.16 |
July | 0.421784E+10 | 0.35 | 11351.97 | 05-JUL-05:01 | 1.33 |
August | 0.460880E+10 | 0.37 | 9310.07 | 07-AUG-05:03 | 1.17 |
September | 0.374378E+10 | 0.33 | 18199.18 | 30-SEP-05:01 | 1.80 |
October | 0.374296E+10 | 0.33 | 17297.18 | 05-OCT-05:02 | 1.73 |
November | 0.303143E+10 | 0.30 | 4531.10 | 22-NOV-15:00 | 0.78 |
December | 0.302156E+10 | 0.30 | 4392.61 | 07-DEC-15:40 | 0.76 |
Annual Sum or Average | 0.419702E+11 | 0.32 | |||
Minimum of Months | 0.272339E+10 | 0.30 | 4392.61 | 0.76 | |
Maximum of Months | 0.460880E+10 | 0.37 | 18199.18 | 1.80 |
Report: FanReportMonthly
For: DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.956558E+11 | 1.38 | 35713.80 | 01-JAN-00:05 | 1.38 |
February | 0.863988E+11 | 1.38 | 35713.80 | 01-FEB-00:10 | 1.38 |
March | 0.956558E+11 | 1.38 | 35713.80 | 01-MAR-00:10 | 1.38 |
April | 0.925702E+11 | 1.38 | 35713.80 | 01-APR-00:10 | 1.38 |
May | 0.956558E+11 | 1.38 | 35713.80 | 01-MAY-00:10 | 1.37 |
June | 0.925702E+11 | 1.37 | 35713.80 | 01-JUN-00:10 | 1.37 |
July | 0.956558E+11 | 1.37 | 35713.80 | 01-JUL-00:10 | 1.37 |
August | 0.956558E+11 | 1.37 | 35713.80 | 01-AUG-00:10 | 1.37 |
September | 0.925702E+11 | 1.37 | 35713.80 | 01-SEP-00:10 | 1.37 |
October | 0.956558E+11 | 1.38 | 35713.80 | 01-OCT-00:10 | 1.37 |
November | 0.925702E+11 | 1.38 | 35713.80 | 01-NOV-00:10 | 1.38 |
December | 0.956558E+11 | 1.38 | 35713.80 | 01-DEC-00:10 | 1.39 |
Annual Sum or Average | 0.112627E+13 | 1.37 | |||
Minimum of Months | 0.863988E+11 | 1.37 | 35713.80 | 1.37 | |
Maximum of Months | 0.956558E+11 | 1.38 | 35713.80 | 1.39 |
Report: FanReportMonthly
For: DATACENTER BOT SUPPLY FAN
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140997E+10 | 0.93 | 526.42 | 01-JAN-00:05 | 0.93 |
February | 0.127352E+10 | 0.93 | 526.42 | 01-FEB-00:10 | 0.93 |
March | 0.140997E+10 | 0.93 | 526.42 | 01-MAR-00:10 | 0.93 |
April | 0.136449E+10 | 0.93 | 526.42 | 01-APR-00:10 | 0.93 |
May | 0.140997E+10 | 0.93 | 526.42 | 01-MAY-00:10 | 0.93 |
June | 0.136449E+10 | 0.93 | 526.42 | 01-JUN-00:10 | 0.93 |
July | 0.140997E+10 | 0.93 | 526.42 | 01-JUL-00:10 | 0.93 |
August | 0.140997E+10 | 0.93 | 526.42 | 01-AUG-00:10 | 0.93 |
September | 0.136449E+10 | 0.93 | 526.42 | 01-SEP-00:10 | 0.93 |
October | 0.140997E+10 | 0.93 | 526.42 | 01-OCT-00:10 | 0.93 |
November | 0.136449E+10 | 0.93 | 526.42 | 01-NOV-00:10 | 0.93 |
December | 0.140997E+10 | 0.93 | 526.42 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.166013E+11 | 0.93 | |||
Minimum of Months | 0.127352E+10 | 0.93 | 526.42 | 0.93 | |
Maximum of Months | 0.140997E+10 | 0.93 | 526.42 | 0.93 |
Report: FanReportMonthly
For: DATACENTER MID SUPPLY FAN
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134395E+11 | 0.93 | 5017.73 | 01-JAN-00:05 | 0.93 |
February | 0.121389E+11 | 0.93 | 5017.73 | 01-FEB-00:10 | 0.93 |
March | 0.134395E+11 | 0.93 | 5017.73 | 01-MAR-00:10 | 0.93 |
April | 0.130060E+11 | 0.93 | 5017.73 | 01-APR-00:10 | 0.93 |
May | 0.134395E+11 | 0.93 | 5017.73 | 01-MAY-00:10 | 0.93 |
June | 0.130060E+11 | 0.93 | 5017.73 | 01-JUN-00:10 | 0.93 |
July | 0.134395E+11 | 0.93 | 5017.73 | 01-JUL-00:10 | 0.93 |
August | 0.134395E+11 | 0.93 | 5017.73 | 01-AUG-00:10 | 0.93 |
September | 0.130060E+11 | 0.93 | 5017.73 | 01-SEP-00:10 | 0.93 |
October | 0.134395E+11 | 0.93 | 5017.73 | 01-OCT-00:10 | 0.93 |
November | 0.130060E+11 | 0.93 | 5017.73 | 01-NOV-00:10 | 0.93 |
December | 0.134395E+11 | 0.93 | 5017.73 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.158239E+12 | 0.93 | |||
Minimum of Months | 0.121389E+11 | 0.93 | 5017.73 | 0.93 | |
Maximum of Months | 0.134395E+11 | 0.93 | 5017.73 | 0.93 |
Report: FanReportMonthly
For: DATACENTER TOP SUPPLY FAN
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136481E+10 | 0.93 | 509.56 | 01-JAN-00:05 | 0.93 |
February | 0.123273E+10 | 0.93 | 509.56 | 01-FEB-00:10 | 0.93 |
March | 0.136481E+10 | 0.93 | 509.56 | 01-MAR-00:10 | 0.93 |
April | 0.132078E+10 | 0.93 | 509.56 | 01-APR-00:10 | 0.93 |
May | 0.136481E+10 | 0.93 | 509.56 | 01-MAY-00:10 | 0.93 |
June | 0.132078E+10 | 0.93 | 509.56 | 01-JUN-00:10 | 0.93 |
July | 0.136481E+10 | 0.93 | 509.56 | 01-JUL-00:10 | 0.93 |
August | 0.136481E+10 | 0.93 | 509.56 | 01-AUG-00:10 | 0.93 |
September | 0.132078E+10 | 0.93 | 509.56 | 01-SEP-00:10 | 0.93 |
October | 0.136481E+10 | 0.93 | 509.56 | 01-OCT-00:10 | 0.93 |
November | 0.132078E+10 | 0.93 | 509.56 | 01-NOV-00:10 | 0.93 |
December | 0.136481E+10 | 0.93 | 509.56 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.160695E+11 | 0.93 | |||
Minimum of Months | 0.123273E+10 | 0.93 | 509.56 | 0.93 | |
Maximum of Months | 0.136481E+10 | 0.93 | 509.56 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 2347649.02 | 2112884.12 | 1915.23 | 02-JAN-05:12 | 1723.71 | 1723.71 | 74.59 | 23.56 |
February | 1230247.36 | 1107222.62 | 1735.89 | 23-FEB-06:20 | 1562.30 | 1562.30 | 72.87 | 22.59 |
March | 312691.73 | 281422.55 | 226.53 | 30-MAR-05:02 | 203.88 | 203.88 | 53.82 | 8.69 |
April | 200083.53 | 180075.17 | 101.11 | 30-APR-23:10 | 91.00 | 91.00 | 69.86 | 5.59 |
May | 372616.14 | 335354.52 | 1731.37 | 15-MAY-04:12 | 1558.24 | 1558.24 | 72.12 | 22.57 |
June | 55761.49 | 50185.34 | 101.38 | 26-JUN-03:40 | 91.24 | 91.24 | 72.43 | 5.59 |
July | 316327.28 | 284694.55 | 101.39 | 31-JUL-03:40 | 91.25 | 91.25 | 72.53 | 5.59 |
August | 223082.84 | 200774.56 | 101.40 | 14-AUG-00:07 | 91.26 | 91.26 | 72.63 | 5.59 |
September | 172419.00 | 155177.10 | 101.39 | 04-SEP-05:20 | 91.25 | 91.25 | 72.54 | 5.59 |
October | 836162.59 | 752546.34 | 1740.50 | 25-OCT-04:52 | 1566.45 | 1566.45 | 75.97 | 22.57 |
November | 673975.84 | 606578.26 | 1741.05 | 01-NOV-03:03 | 1566.94 | 1566.94 | 76.20 | 22.57 |
December | 604078.44 | 543670.59 | 1696.94 | 11-DEC-02:12 | 1527.24 | 1527.24 | 56.12 | 22.57 |
Annual Sum or Average | 7345095.26 | 6610585.73 | ||||||
Minimum of Months | 55761.49 | 50185.34 | 101.11 | 91.00 | 91.00 | 53.82 | 5.59 | |
Maximum of Months | 2347649.02 | 2112884.12 | 1915.23 | 1723.71 | 1723.71 | 76.20 | 23.56 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.196509E+09 | 0.176858E+09 | 3466.96 | 18-JAN-14:20 | 3120.26 | 3120.26 | 7.91 | 36.08 |
February | 86792978.12 | 78113680.30 | 1361.36 | 01-FEB-12:30 | 1225.23 | 1225.23 | 6.72 | 24.20 |
March | 0.138305E+09 | 0.124474E+09 | 3676.10 | 22-MAR-13:00 | 3308.49 | 3308.49 | 9.24 | 36.96 |
April | 0.333869E+09 | 0.300482E+09 | 3419.10 | 11-APR-15:40 | 3077.19 | 3077.19 | 10.82 | 35.86 |
May | 0.287934E+09 | 0.259141E+09 | 2208.50 | 04-MAY-14:00 | 1987.65 | 1987.65 | 9.29 | 29.84 |
June | 0.701671E+09 | 0.631504E+09 | 3446.82 | 14-JUN-14:00 | 3102.14 | 3102.14 | 9.08 | 35.99 |
July | 0.136501E+10 | 0.122851E+10 | 3592.33 | 31-JUL-15:50 | 3233.09 | 3233.09 | 6.72 | 36.61 |
August | 0.165988E+10 | 0.149389E+10 | 5821.68 | 07-AUG-05:03 | 5239.52 | 5239.52 | 8.73 | 44.61 |
September | 0.940351E+09 | 0.846316E+09 | 4167.23 | 29-SEP-10:40 | 3750.51 | 3750.51 | 6.72 | 38.93 |
October | 0.934689E+09 | 0.841220E+09 | 10309.45 | 05-OCT-05:02 | 9278.51 | 9278.51 | 9.54 | 56.02 |
November | 0.191810E+09 | 0.172629E+09 | 1487.05 | 30-NOV-15:00 | 1338.35 | 1338.35 | 6.71 | 25.16 |
December | 0.152687E+09 | 0.137418E+09 | 1264.45 | 05-DEC-14:30 | 1138.00 | 1138.00 | 7.86 | 23.43 |
Annual Sum or Average | 0.698951E+10 | 0.629056E+10 | ||||||
Minimum of Months | 86792978.12 | 78113680.30 | 1264.45 | 1138.00 | 1138.00 | 6.71 | 23.43 | |
Maximum of Months | 0.165988E+10 | 0.149389E+10 | 10309.45 | 9278.51 | 9278.51 | 10.82 | 56.02 |
Report: PumpReportMonthly
For: SHWSYS1 PUMP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871592.27 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 74.93 | 0.44 |
February | 0.101979E+09 | 30593696.24 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 66.94 | 0.44 |
March | 0.112905E+09 | 33871592.27 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 66.30 | 0.44 |
April | 0.109263E+09 | 32778960.26 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 64.86 | 0.44 |
May | 0.112905E+09 | 33871592.27 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 78.23 | 0.44 |
June | 0.109263E+09 | 32778960.26 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 66.85 | 0.44 |
July | 0.112905E+09 | 33871592.27 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 67.34 | 0.44 |
August | 0.112905E+09 | 33871592.27 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 67.22 | 0.44 |
September | 0.109263E+09 | 32778960.26 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 69.70 | 0.44 |
October | 0.112905E+09 | 33871592.27 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 75.27 | 0.44 |
November | 0.109263E+09 | 32778960.26 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 64.98 | 0.44 |
December | 0.112905E+09 | 33871592.27 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 66.93 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398811E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593696.24 | 56.21 | 16.86 | 16.86 | 64.86 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871592.27 | 56.21 | 16.86 | 16.86 | 78.23 | 0.44 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.186504E+10 | 0.167854E+10 | 1838.79 | 01-JAN-03:02 | 1654.91 | 1654.91 | 6.82 | 28.84 |
February | 0.150337E+10 | 0.135303E+10 | 1838.79 | 01-FEB-04:01 | 1654.91 | 1654.91 | 6.85 | 28.84 |
March | 0.154999E+10 | 0.139499E+10 | 1838.79 | 01-MAR-06:03 | 1654.91 | 1654.91 | 6.72 | 28.84 |
April | 0.224829E+10 | 0.202346E+10 | 1838.79 | 01-APR-05:02 | 1654.91 | 1654.91 | 6.74 | 28.84 |
May | 0.251101E+10 | 0.225991E+10 | 1838.79 | 01-MAY-00:31 | 1654.91 | 1654.91 | 7.07 | 28.84 |
June | 0.295369E+10 | 0.265832E+10 | 1838.79 | 01-JUN-03:01 | 1654.91 | 1654.91 | 6.96 | 28.84 |
July | 0.346803E+10 | 0.312122E+10 | 1838.79 | 01-JUL-03:01 | 1654.91 | 1654.91 | 7.83 | 28.84 |
August | 0.377836E+10 | 0.340052E+10 | 1838.79 | 01-AUG-01:12 | 1654.91 | 1654.91 | 7.00 | 28.84 |
September | 0.290257E+10 | 0.261231E+10 | 1838.79 | 01-SEP-00:42 | 1654.91 | 1654.91 | 6.83 | 28.84 |
October | 0.292522E+10 | 0.263270E+10 | 1838.79 | 01-OCT-08:42 | 1654.91 | 1654.91 | 9.64 | 28.84 |
November | 0.200444E+10 | 0.180399E+10 | 1838.79 | 01-NOV-03:01 | 1654.91 | 1654.91 | 8.04 | 28.84 |
December | 0.188756E+10 | 0.169880E+10 | 1838.79 | 01-DEC-04:01 | 1654.91 | 1654.91 | 6.75 | 28.84 |
Annual Sum or Average | 0.295976E+11 | 0.266378E+11 | ||||||
Minimum of Months | 0.150337E+10 | 0.135303E+10 | 1838.79 | 1654.91 | 1654.91 | 6.72 | 28.84 | |
Maximum of Months | 0.377836E+10 | 0.340052E+10 | 1838.79 | 1654.91 | 1654.91 | 9.64 | 28.84 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.86 | 0.00 |
February | 1103272.35 | 992945.11 | 1838.79 | 01-FEB-12:00 | 1654.91 | 1654.91 | 14.58 | 14.42 |
March | 34201442.78 | 30781298.50 | 1838.79 | 22-MAR-12:20 | 1654.91 | 1654.91 | 15.73 | 14.42 |
April | 63989796.17 | 57590816.55 | 1838.79 | 04-APR-12:50 | 1654.91 | 1654.91 | 15.41 | 14.42 |
May | 13239268.17 | 11915341.36 | 1838.79 | 03-MAY-14:00 | 1654.91 | 1654.91 | 15.45 | 14.42 |
June | 0.329878E+09 | 0.296891E+09 | 1838.79 | 14-JUN-10:00 | 1654.91 | 1654.91 | 15.47 | 14.42 |
July | 0.883537E+09 | 0.795184E+09 | 1838.79 | 03-JUL-10:40 | 1654.91 | 1654.91 | 15.34 | 14.42 |
August | 0.118878E+10 | 0.106990E+10 | 1838.79 | 01-AUG-10:50 | 1654.91 | 1654.91 | 15.45 | 14.42 |
September | 0.500886E+09 | 0.450797E+09 | 1838.79 | 05-SEP-12:20 | 1654.91 | 1654.91 | 16.03 | 14.42 |
October | 0.585838E+09 | 0.527254E+09 | 1838.79 | 01-OCT-11:35 | 1654.91 | 1654.91 | 15.35 | 14.42 |
November | 6619634.09 | 5957670.68 | 1838.79 | 28-NOV-13:50 | 1654.91 | 1654.91 | 14.75 | 14.42 |
December | 12687632.00 | 11418868.80 | 1838.79 | 05-DEC-14:10 | 1654.91 | 1654.91 | 14.86 | 14.42 |
Annual Sum or Average | 0.362076E+10 | 0.325868E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.86 | 0.00 | |
Maximum of Months | 0.118878E+10 | 0.106990E+10 | 1838.79 | 1654.91 | 1654.91 | 16.03 | 14.42 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.881469E+10 | 0.793322E+10 | 3291.03 | 01-JAN-00:05 | 2961.92 | 2961.92 | 18.70 | 13.74 |
February | 0.796165E+10 | 0.716549E+10 | 3291.03 | 01-FEB-00:10 | 2961.92 | 2961.92 | 19.31 | 13.74 |
March | 0.881469E+10 | 0.793322E+10 | 3291.03 | 01-MAR-00:10 | 2961.92 | 2961.92 | 19.87 | 13.74 |
April | 0.853034E+10 | 0.767731E+10 | 3291.03 | 01-APR-00:10 | 2961.92 | 2961.92 | 29.76 | 13.74 |
May | 0.881469E+10 | 0.793322E+10 | 3291.03 | 01-MAY-00:10 | 2961.92 | 2961.92 | 19.62 | 13.74 |
June | 0.853034E+10 | 0.767731E+10 | 3291.03 | 01-JUN-00:10 | 2961.92 | 2961.92 | 19.33 | 13.74 |
July | 0.881469E+10 | 0.793322E+10 | 3291.03 | 01-JUL-00:10 | 2961.92 | 2961.92 | 21.23 | 13.74 |
August | 0.881469E+10 | 0.793322E+10 | 3291.03 | 01-AUG-00:10 | 2961.92 | 2961.92 | 32.88 | 13.74 |
September | 0.853034E+10 | 0.767731E+10 | 3291.03 | 01-SEP-00:10 | 2961.92 | 2961.92 | 19.87 | 13.74 |
October | 0.881469E+10 | 0.793322E+10 | 3291.03 | 01-OCT-00:10 | 2961.92 | 2961.92 | 19.97 | 13.74 |
November | 0.853034E+10 | 0.767731E+10 | 3291.03 | 01-NOV-00:10 | 2961.92 | 2961.92 | 27.12 | 13.74 |
December | 0.881469E+10 | 0.793322E+10 | 3291.03 | 01-DEC-00:10 | 2961.92 | 2961.92 | 20.56 | 13.74 |
Annual Sum or Average | 0.103786E+12 | 0.934072E+11 | ||||||
Minimum of Months | 0.796165E+10 | 0.716549E+10 | 3291.03 | 2961.92 | 2961.92 | 18.70 | 13.74 | |
Maximum of Months | 0.881469E+10 | 0.793322E+10 | 3291.03 | 2961.92 | 2961.92 | 32.88 | 13.74 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.111171E+11 | 0.100054E+11 | 11005.89 | 17-JAN-13:50 | 9905.30 | 9905.30 | 27.97 | 51.91 |
February | 0.895899E+10 | 0.806309E+10 | 10997.24 | 01-FEB-11:40 | 9897.52 | 9897.52 | 27.03 | 51.91 |
March | 0.942880E+10 | 0.848592E+10 | 21979.84 | 23-MAR-14:10 | 19781.86 | 19781.86 | 26.23 | 103.81 |
April | 0.137474E+11 | 0.123727E+11 | 21988.37 | 26-APR-10:50 | 19789.53 | 19789.53 | 26.70 | 103.81 |
May | 0.150220E+11 | 0.135198E+11 | 21969.17 | 04-MAY-13:40 | 19772.26 | 19772.26 | 25.66 | 103.81 |
June | 0.195403E+11 | 0.175863E+11 | 22027.36 | 28-JUN-11:00 | 19824.63 | 19824.63 | 28.83 | 103.81 |
July | 0.258906E+11 | 0.233015E+11 | 22027.36 | 13-JUL-15:00 | 19824.63 | 19824.63 | 29.05 | 103.81 |
August | 0.295136E+11 | 0.265623E+11 | 22027.36 | 07-AUG-08:40 | 19824.63 | 19824.63 | 28.96 | 103.81 |
September | 0.202646E+11 | 0.182381E+11 | 22027.36 | 21-SEP-12:20 | 19824.63 | 19824.63 | 28.87 | 103.81 |
October | 0.206900E+11 | 0.186210E+11 | 22027.36 | 02-OCT-12:20 | 19824.63 | 19824.63 | 29.07 | 103.81 |
November | 0.119686E+11 | 0.107717E+11 | 21951.86 | 28-NOV-14:10 | 19756.67 | 19756.67 | 24.67 | 103.81 |
December | 0.112966E+11 | 0.101669E+11 | 21959.96 | 19-DEC-13:15 | 19763.97 | 19763.97 | 25.16 | 103.81 |
Annual Sum or Average | 0.197439E+12 | 0.177695E+12 | ||||||
Minimum of Months | 0.895899E+10 | 0.806309E+10 | 10997.24 | 9897.52 | 9897.52 | 24.67 | 51.91 | |
Maximum of Months | 0.295136E+11 | 0.265623E+11 | 22027.36 | 19824.63 | 19824.63 | 29.07 | 103.81 |
Report: CondLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7194.05 | 37949.41 | 01-JAN-08:10 | 80.54 | 82.22 | 11481.65 | 45618.11 | 30-JAN-12:20 |
February | 6830.24 | 37939.40 | 26-FEB-08:35 | 80.53 | 82.22 | 11592.87 | 45616.82 | 06-FEB-12:20 |
March | 5570.30 | 37982.61 | 26-MAR-07:40 | 80.55 | 82.22 | 12401.76 | 45400.67 | 01-MAR-12:20 |
April | 6644.09 | 38065.03 | 30-APR-07:13 | 80.60 | 82.22 | 11118.51 | 44594.98 | 03-APR-11:40 |
May | 6512.06 | 38137.77 | 29-MAY-07:20 | 80.64 | 82.22 | 11218.26 | 43634.71 | 01-MAY-12:00 |
June | 5870.79 | 38192.40 | 25-JUN-07:07 | 80.67 | 82.22 | 11284.00 | 42534.99 | 01-JUN-11:50 |
July | 7500.70 | 38225.54 | 30-JUL-07:10 | 80.68 | 82.22 | 10019.19 | 41702.68 | 03-JUL-11:40 |
August | 5795.83 | 38225.93 | 06-AUG-07:05 | 80.69 | 82.22 | 11234.00 | 41604.60 | 31-AUG-11:40 |
September | 6791.97 | 38206.25 | 03-SEP-07:03 | 80.67 | 82.22 | 10406.38 | 42303.76 | 29-SEP-11:20 |
October | 7350.32 | 38157.02 | 01-OCT-07:30 | 80.65 | 82.22 | 10692.29 | 43394.19 | 31-OCT-11:30 |
November | 7415.59 | 38071.48 | 05-NOV-07:20 | 80.60 | 82.22 | 11200.10 | 44453.49 | 30-NOV-12:40 |
December | 7272.26 | 38002.81 | 03-DEC-08:25 | 80.56 | 82.22 | 11011.31 | 45223.95 | 29-DEC-12:20 |
Annual Sum or Average | 6728.72 | 11136.12 | ||||||
Minimum of Months | 5570.30 | 37939.40 | 80.53 | 82.22 | 10019.19 | 41604.60 | ||
Maximum of Months | 7500.70 | 38225.93 | 80.69 | 82.22 | 12401.76 | 45618.11 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 72.90 | 72.90 | 3685.48 | 1319183.92 | 12-JAN-06:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 52.02 | 52.02 | 1397.90 | 2604482.01 | 10-FEB-05:15 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 59.51 | 59.51 | 1914.27 | 1023997.74 | 30-MAR-05:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 48.04 | 48.04 | 466.45 | 742208.66 | 03-APR-03:37 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 70.28 | 70.28 | 255.31 | 935082.45 | 15-MAY-04:12 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 72.40 | 72.40 | 47.69 | 225078.24 | 08-JUN-03:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 72.44 | 72.44 | 260.30 | 224122.42 | 03-JUL-03:47 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 72.54 | 72.54 | 181.00 | 221533.52 | 06-AUG-18:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 72.56 | 72.56 | 146.28 | 225854.94 | 30-SEP-03:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 72.39 | 72.39 | 417.24 | 756671.92 | 18-OCT-03:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 74.93 | 74.93 | 522.94 | 1452333.07 | 22-NOV-04:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 54.48 | 54.48 | 1861.08 | 2730770.45 | 22-DEC-04:02 |
Annual Sum or Average | 0.00 | 932.76 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.04 | 48.04 | 47.69 | 221533.52 | ||
Maximum of Months | 0.00 | 0.00 | 74.93 | 74.93 | 3685.48 | 2730770.45 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 92005.45 | 933617.44 | 17-JAN-14:00 | 14.44 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 64329.71 | 998299.30 | 01-FEB-12:10 | 14.97 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 68943.29 | 1251462.76 | 23-MAR-14:10 | 11.88 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 142806.35 | 1231614.32 | 26-APR-15:20 | 11.80 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 136166.25 | 1292804.73 | 04-MAY-13:00 | 12.05 | 8.83 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 270612.21 | 1354449.58 | 29-JUN-13:00 | 12.31 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 446566.99 | 1713371.80 | 31-JUL-16:00 | 13.80 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 513852.97 | 1774561.16 | 18-AUG-16:00 | 14.05 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 319834.47 | 1480641.98 | 22-SEP-12:30 | 12.83 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 331382.70 | 1621929.49 | 03-OCT-13:30 | 13.42 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 108473.16 | 1180619.02 | 28-NOV-14:00 | 16.49 | 9.48 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 113032.20 | 1263994.23 | 19-DEC-13:15 | 11.93 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 218667.02 | 0.00 | ||||||
Minimum of Months | 64329.71 | 933617.44 | 11.80 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 513852.97 | 1774561.16 | 16.49 | 9.48 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 91607.78 | 1078535.60 | 18-JAN-14:20 | 13.84 | 8.12 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 63825.44 | 980246.01 | 01-FEB-12:10 | 20.03 | 7.31 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 68583.76 | 1447076.46 | 22-MAR-13:00 | 16.06 | 9.25 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 142370.52 | 1359801.53 | 11-APR-15:40 | 15.76 | 11.14 | 0.00 | 0.00 | 01-APR-00:10 |
May | 135330.62 | 1161392.45 | 04-MAY-14:00 | 16.00 | 9.50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 269857.52 | 1416725.22 | 14-JUN-14:00 | 16.11 | 9.07 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 445258.72 | 1727526.38 | 31-JUL-15:50 | 17.98 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 512539.46 | 1912771.99 | 07-AUG-05:03 | 16.95 | 10.30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 319665.18 | 1538372.10 | 30-SEP-05:01 | 20.93 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 331011.46 | 2437390.65 | 05-OCT-05:02 | 17.10 | 11.73 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 107848.19 | 1138697.08 | 28-NOV-14:00 | 19.59 | 9.90 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 112502.51 | 1243148.27 | 05-DEC-15:10 | 19.52 | 7.32 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 218030.73 | 0.00 | ||||||
Minimum of Months | 63825.44 | 980246.01 | 13.84 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 512539.46 | 2437390.65 | 20.93 | 11.73 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 82373.02 | 616532.18 | 14-JAN-12:00 | 31.13 | 27.45 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 127633.79 | 784368.51 | 01-FEB-12:00 | 34.56 | 28.43 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 202340.80 | 827317.44 | 23-MAR-14:00 | 35.43 | 26.53 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 462928.49 | 1307099.52 | 26-APR-13:00 | 45.10 | 32.20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 58921.92 | 404481.27 | 04-MAY-12:00 | 26.76 | 24.77 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 171483.29 | 833982.61 | 29-JUN-11:00 | 35.57 | 28.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 500255.18 | 1353306.69 | 31-JUL-11:30 | 46.02 | 32.82 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 843231.51 | 1422162.72 | 18-AUG-12:00 | 47.39 | 33.58 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 121769.95 | 1158731.41 | 29-SEP-13:00 | 42.13 | 37.75 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 298890.57 | 1433266.45 | 16-OCT-11:00 | 47.61 | 40.06 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 226603.23 | 1095454.59 | 19-NOV-13:00 | 40.86 | 30.96 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 382754.69 | 1185692.75 | 05-DEC-10:00 | 42.67 | 30.77 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 291750.94 | 0.00 | ||||||
Minimum of Months | 58921.92 | 404481.27 | 26.76 | 24.77 | 0.00 | 0.00 | ||
Maximum of Months | 843231.51 | 1433266.45 | 47.61 | 40.06 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 133807.55 | 1489457.14 | 17-JAN-13:50 | 27.97 | 21.76 | 955.32 | 85251.78 | 07-JAN-06:50 |
February | 94028.78 | 1286384.10 | 01-FEB-11:40 | 27.03 | 21.10 | 778.29 | 79325.51 | 04-FEB-06:50 |
March | 102395.32 | 2227792.95 | 23-MAR-14:10 | 26.23 | 23.11 | 779.04 | 55621.70 | 23-MAR-06:00 |
April | 210091.41 | 2428472.79 | 26-APR-10:50 | 26.70 | 23.64 | 477.39 | 49695.55 | 21-APR-16:10 |
May | 198937.30 | 1976519.87 | 04-MAY-13:40 | 25.66 | 22.57 | 474.58 | 44636.56 | 31-MAY-03:01 |
June | 445121.02 | 3553726.09 | 29-JUN-13:00 | 29.29 | 25.55 | 131.78 | 42704.24 | 08-JUN-19:00 |
July | 872785.12 | 4777586.23 | 31-JUL-16:00 | 32.11 | 27.35 | 61.59 | 36590.07 | 17-JUL-03:41 |
August | 1048429.54 | 4961357.96 | 18-AUG-16:00 | 32.53 | 27.59 | 36.14 | 16699.47 | 23-AUG-03:25 |
September | 552209.97 | 4266003.20 | 22-SEP-12:40 | 30.93 | 26.82 | 196.92 | 40151.58 | 19-SEP-19:00 |
October | 559431.48 | 4447179.34 | 04-OCT-11:00 | 31.35 | 26.92 | 258.71 | 63749.59 | 25-OCT-05:30 |
November | 156955.76 | 1547674.76 | 28-NOV-14:10 | 24.67 | 21.76 | 620.90 | 75661.82 | 24-NOV-09:00 |
December | 160231.84 | 1759364.70 | 19-DEC-13:15 | 25.16 | 21.85 | 906.85 | 83746.78 | 26-DEC-07:00 |
Annual Sum or Average | 380604.69 | 471.89 | ||||||
Minimum of Months | 94028.78 | 1286384.10 | 24.67 | 21.10 | 36.14 | 16699.47 | ||
Maximum of Months | 1048429.54 | 4961357.96 | 32.53 | 27.59 | 955.32 | 85251.78 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.22 | 5.61 |
February | 0.08 | 7.48 |
March | 0.06 | 7.48 |
April | 0.22 | 7.48 |
May | 0.14 | 2.99 |
June | 0.69 | 7.48 |
July | 0.37 | 7.48 |
August | 1.21 | 7.48 |
September | 0.17 | 7.48 |
October | 0.94 | 5.94 |
November | 0.94 | 6.82 |
December | 0.50 | 7.48 |
Annual Sum or Average | 5.56 | 6.92 |
Minimum of Months | 0.06 | 2.99 |
Maximum of Months | 1.21 | 7.48 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.56 | 5.67 |
February | 0.78 | 4.44 |
March | 2.99 | 2.97 |
April | 8.86 | 2.10 |
May | 2.31 | 5.42 |
June | 5.27 | 3.18 |
July | 14.03 | 1.75 |
August | 23.41 | 1.77 |
September | 3.71 | 3.39 |
October | 6.84 | 2.59 |
November | 4.04 | 2.92 |
December | 3.99 | 2.62 |
Annual Sum or Average | 77.78 | 2.41 |
Minimum of Months | 0.78 | 1.75 |
Maximum of Months | 23.41 | 5.67 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.08 | 11.20 |
February | 0.71 | 9.09 |
March | 0.97 | 10.17 |
April | 2.62 | 10.56 |
May | 1.74 | 9.29 |
June | 1.46 | 7.74 |
July | 2.14 | 5.41 |
August | 1.09 | 6.55 |
September | 1.81 | 7.75 |
October | 2.78 | 8.50 |
November | 1.96 | 10.71 |
December | 1.07 | 10.21 |
Annual Sum or Average | 19.44 | 8.84 |
Minimum of Months | 0.71 | 5.41 |
Maximum of Months | 2.78 | 11.20 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.81 | 13.44 |
February | 1.17 | 12.48 |
March | 1.40 | 12.57 |
April | 2.34 | 10.39 |
May | 2.26 | 11.09 |
June | 1.79 | 8.28 |
July | 2.16 | 8.28 |
August | 2.33 | 8.28 |
September | 2.02 | 10.09 |
October | 2.25 | 9.87 |
November | 1.42 | 13.04 |
December | 0.94 | 12.05 |
Annual Sum or Average | 20.88 | 10.38 |
Minimum of Months | 0.81 | 8.28 |
Maximum of Months | 2.34 | 13.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.60 | 0.69 |
February | 0.26 | 0.71 |
March | 0.57 | 0.60 |
April | 2.67 | 0.39 |
May | 1.35 | 0.76 |
June | 1.86 | 0.64 |
July | 4.26 | 0.30 |
August | 7.94 | 0.20 |
September | 1.72 | 0.56 |
October | 2.22 | 0.50 |
November | 0.79 | 0.78 |
December | 0.85 | 0.79 |
Annual Sum or Average | 25.10 | 0.42 |
Minimum of Months | 0.26 | 0.20 |
Maximum of Months | 7.94 | 0.79 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.69 | 0.55 |
February | 1.18 | 0.56 |
March | 0.92 | 0.42 |
April | 3.78 | 0.26 |
May | 3.22 | 0.44 |
June | 3.00 | 0.42 |
July | 5.94 | 0.23 |
August | 8.79 | 0.13 |
September | 3.21 | 0.48 |
October | 4.04 | 0.29 |
November | 1.54 | 0.50 |
December | 1.79 | 0.49 |
Annual Sum or Average | 39.10 | 0.32 |
Minimum of Months | 0.92 | 0.13 |
Maximum of Months | 8.79 | 0.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.61 | 0.69 |
February | 0.25 | 0.56 |
March | 0.76 | 0.66 |
April | 2.72 | 0.40 |
May | 1.43 | 0.73 |
June | 2.00 | 0.59 |
July | 4.71 | 0.34 |
August | 8.08 | 0.21 |
September | 1.72 | 0.52 |
October | 2.26 | 0.37 |
November | 0.60 | 0.77 |
December | 0.49 | 0.75 |
Annual Sum or Average | 25.64 | 0.40 |
Minimum of Months | 0.25 | 0.21 |
Maximum of Months | 8.08 | 0.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.53 | 0.66 |
February | 1.62 | 0.53 |
March | 2.65 | 0.39 |
April | 10.16 | 0.20 |
May | 4.49 | 0.52 |
June | 4.83 | 0.39 |
July | 12.74 | 0.17 |
August | 23.79 | 0.14 |
September | 3.37 | 0.32 |
October | 4.85 | 0.24 |
November | 3.17 | 0.41 |
December | 3.44 | 0.37 |
Annual Sum or Average | 77.64 | 0.26 |
Minimum of Months | 1.62 | 0.14 |
Maximum of Months | 23.79 | 0.66 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.25 | 1.31 |
February | 0.04 | 0.84 |
March | 0.21 | 1.52 |
April | 0.65 | 1.06 |
May | 0.48 | 0.70 |
June | 0.67 | 0.91 |
July | 1.51 | 0.61 |
August | 0.89 | 0.87 |
September | 1.15 | 0.92 |
October | 0.72 | 0.96 |
November | 0.06 | 0.84 |
December | 0.22 | 1.16 |
Annual Sum or Average | 6.85 | 0.89 |
Minimum of Months | 0.04 | 0.61 |
Maximum of Months | 1.51 | 1.52 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.14 | 0.77 |
February | 1.46 | 0.73 |
March | 0.97 | 0.85 |
April | 2.53 | 0.85 |
May | 2.34 | 0.54 |
June | 3.03 | 0.55 |
July | 3.49 | 0.45 |
August | 2.71 | 0.56 |
September | 3.32 | 0.65 |
October | 3.49 | 0.56 |
November | 1.78 | 0.77 |
December | 1.46 | 0.73 |
Annual Sum or Average | 27.71 | 0.63 |
Minimum of Months | 0.97 | 0.45 |
Maximum of Months | 3.49 | 0.85 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.28 | 1.43 |
February | 0.08 | 1.69 |
March | 0.63 | 1.24 |
April | 0.82 | 0.96 |
May | 0.57 | 0.80 |
June | 0.83 | 0.98 |
July | 1.81 | 0.68 |
August | 1.65 | 0.69 |
September | 1.51 | 0.89 |
October | 0.74 | 0.91 |
November | 0.43 | 0.95 |
December | 0.17 | 1.27 |
Annual Sum or Average | 9.51 | 0.88 |
Minimum of Months | 0.08 | 0.68 |
Maximum of Months | 1.81 | 1.69 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.04 | 0.88 |
February | 1.21 | 0.92 |
March | 1.10 | 0.94 |
April | 2.61 | 0.77 |
May | 2.58 | 0.72 |
June | 2.96 | 0.62 |
July | 3.25 | 0.56 |
August | 2.53 | 0.62 |
September | 3.14 | 0.69 |
October | 2.49 | 0.63 |
November | 1.20 | 0.85 |
December | 1.07 | 0.88 |
Annual Sum or Average | 25.18 | 0.71 |
Minimum of Months | 1.04 | 0.56 |
Maximum of Months | 3.25 | 0.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.12 | 1.12 |
February | 0.00 | 0.00 |
March | 0.04 | 0.84 |
April | 0.49 | 0.99 |
May | 0.53 | 0.67 |
June | 1.04 | 0.84 |
July | 1.75 | 1.00 |
August | 2.01 | 1.08 |
September | 1.50 | 1.31 |
October | 0.85 | 1.05 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 8.32 | 1.04 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.01 | 1.31 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.21 | 0.90 |
February | 0.25 | 0.72 |
March | 0.36 | 0.67 |
April | 1.65 | 0.74 |
May | 1.93 | 0.51 |
June | 2.85 | 0.56 |
July | 4.29 | 0.48 |
August | 3.62 | 0.56 |
September | 2.58 | 0.77 |
October | 2.64 | 0.66 |
November | 0.21 | 0.69 |
December | 0.25 | 0.54 |
Annual Sum or Average | 20.85 | 0.60 |
Minimum of Months | 0.21 | 0.48 |
Maximum of Months | 4.29 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.12 | 1.45 |
February | 0.00 | 0.00 |
March | 0.15 | 0.54 |
April | 0.69 | 0.94 |
May | 0.53 | 0.67 |
June | 1.00 | 0.98 |
July | 2.52 | 1.02 |
August | 2.34 | 1.02 |
September | 1.58 | 1.29 |
October | 0.67 | 1.12 |
November | 0.16 | 0.84 |
December | 0.04 | 0.84 |
Annual Sum or Average | 9.79 | 1.04 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.52 | 1.45 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.55 | 0.68 |
February | 0.64 | 0.82 |
March | 1.03 | 0.81 |
April | 1.94 | 0.82 |
May | 2.07 | 0.71 |
June | 3.12 | 0.65 |
July | 3.20 | 0.55 |
August | 3.02 | 0.64 |
September | 2.36 | 0.83 |
October | 2.10 | 0.71 |
November | 0.61 | 0.79 |
December | 0.71 | 0.71 |
Annual Sum or Average | 21.37 | 0.70 |
Minimum of Months | 0.55 | 0.55 |
Maximum of Months | 3.20 | 0.83 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 21.63 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 21.63 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 21.63 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.107598E+10 | 0.00 | 0.121068E+11 | 0.150921E+11 | 0.00 | 0.00 |
February | 0.384062E+09 | 0.00 | 0.545688E+10 | 0.130126E+11 | 0.00 | 0.00 |
March | 44649758.75 | 0.00 | 0.604915E+10 | 0.150072E+11 | 0.00 | 0.00 |
April | 0.403523E+09 | 0.00 | 0.158068E+11 | 0.139231E+11 | 0.00 | 0.00 |
May | 0.560618E+09 | 0.00 | 0.151443E+11 | 0.143901E+11 | 0.00 | 0.00 |
June | 0.123237E+09 | 0.00 | 0.268395E+11 | 0.144243E+11 | 0.00 | 0.00 |
July | 0.697344E+09 | 0.00 | 0.454068E+11 | 0.142255E+11 | 0.00 | 0.00 |
August | 0.485481E+09 | 0.00 | 0.518765E+11 | 0.153801E+11 | 0.00 | 0.00 |
September | 0.380148E+09 | 0.00 | 0.315283E+11 | 0.144432E+11 | 0.00 | 0.00 |
October | 0.908977E+09 | 0.00 | 0.419918E+11 | 0.151265E+11 | 0.00 | 0.00 |
November | 0.459536E+09 | 0.00 | 0.133721E+11 | 0.147843E+11 | 0.00 | 0.00 |
December | 0.423229E+09 | 0.00 | 0.163690E+11 | 0.148927E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.594678E+10 | 0.00 | 0.281948E+12 | 0.174702E+12 | 0.00 | 0.00 |
Minimum of Months | 44649758.75 | 0.00 | 0.545688E+10 | 0.130126E+11 | 0.00 | 0.00 |
Maximum of Months | 0.107598E+10 | 0.00 | 0.518765E+11 | 0.153801E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 80225748.31 | 0.00 | 0.233312E+11 | 0.495866E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.156099E+11 | 0.477600E+10 | 0.00 | 0.00 |
March | 18383255.89 | 0.00 | 0.186911E+11 | 0.602833E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.384943E+11 | 0.621313E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.342926E+11 | 0.475200E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.648715E+11 | 0.527345E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.115272E+12 | 0.596468E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.141050E+12 | 0.706800E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.732311E+11 | 0.489830E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.810878E+11 | 0.565662E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.290306E+11 | 0.608243E+10 | 0.00 | 0.00 |
December | 1170896.77 | 0.00 | 0.312344E+11 | 0.643650E+10 | 0.00 | 0.00 |
Annual Sum or Average | 99779900.98 | 0.00 | 0.666196E+12 | 0.681081E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.156099E+11 | 0.475200E+10 | 0.00 | 0.00 |
Maximum of Months | 80225748.31 | 0.00 | 0.141050E+12 | 0.706800E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.566886E+10 | 0.00 | 0.189321E+12 | 0.356253E+11 | 0.00 | 0.00 |
February | 0.108144E+10 | 0.00 | 0.120341E+12 | 0.318919E+11 | 0.00 | 0.00 |
March | 0.320376E+10 | 0.00 | 0.138602E+12 | 0.362575E+11 | 0.00 | 0.00 |
April | 0.232643E+09 | 0.00 | 0.271207E+12 | 0.356185E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.278519E+12 | 0.356315E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.517198E+12 | 0.376895E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.872444E+12 | 0.392173E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.100669E+13 | 0.432892E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.618168E+12 | 0.381998E+11 | 0.00 | 0.00 |
October | 1456792.95 | 0.00 | 0.652647E+12 | 0.402425E+11 | 0.00 | 0.00 |
November | 0.260789E+09 | 0.00 | 0.212543E+12 | 0.370306E+11 | 0.00 | 0.00 |
December | 0.235844E+10 | 0.00 | 0.221693E+12 | 0.366684E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.128074E+11 | 0.00 | 0.509937E+13 | 0.447362E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.120341E+12 | 0.318919E+11 | 0.00 | 0.00 |
Maximum of Months | 0.566886E+10 | 0.00 | 0.100669E+13 | 0.432892E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.337735E+10 | 0.00 | 0.164824E+11 | 0.300538E+10 | 0.00 | 0.00 |
February | 0.172905E+10 | 0.00 | 0.106349E+11 | 0.272339E+10 | 0.00 | 0.00 |
March | 0.203275E+10 | 0.00 | 0.126544E+11 | 0.314912E+10 | 0.00 | 0.00 |
April | 0.268424E+09 | 0.00 | 0.270165E+11 | 0.342057E+10 | 0.00 | 0.00 |
May | 95314102.35 | 0.00 | 0.277870E+11 | 0.343516E+10 | 0.00 | 0.00 |
June | 84336.98 | 0.00 | 0.540263E+11 | 0.387017E+10 | 0.00 | 0.00 |
July | 2850.41 | 0.00 | 0.930951E+11 | 0.421784E+10 | 0.00 | 0.00 |
August | 7888.21 | 0.00 | 0.107182E+12 | 0.460880E+10 | 0.00 | 0.00 |
September | 2243715.37 | 0.00 | 0.616377E+11 | 0.374378E+10 | 0.00 | 0.00 |
October | 0.174401E+09 | 0.00 | 0.637254E+11 | 0.374296E+10 | 0.00 | 0.00 |
November | 0.923609E+09 | 0.00 | 0.184394E+11 | 0.303143E+10 | 0.00 | 0.00 |
December | 0.215343E+10 | 0.00 | 0.195179E+11 | 0.302156E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.107567E+11 | 0.00 | 0.512199E+12 | 0.419702E+11 | 0.00 | 0.00 |
Minimum of Months | 2850.41 | 0.00 | 0.106349E+11 | 0.272339E+10 | 0.00 | 0.00 |
Maximum of Months | 0.337735E+10 | 0.00 | 0.107182E+12 | 0.460880E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.100471E+12 | 0.159221E+12 | 0.00 | 13.61 |
February | 0.00 | 0.00 | 0.164870E+12 | 0.164848E+12 | 0.00 | 13.09 |
March | 0.00 | 0.00 | 0.280521E+12 | 0.197765E+12 | 0.00 | 10.84 |
April | 0.00 | 0.00 | 0.701830E+12 | 0.250952E+12 | 0.00 | 4.03 |
May | 0.00 | 0.00 | 0.205310E+11 | 0.112273E+12 | 0.00 | 1.81 |
June | 0.00 | 0.00 | 0.113866E+12 | 0.137316E+12 | 0.00 | 0.12 |
July | 0.00 | 0.00 | 0.606193E+12 | 0.228841E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.117456E+13 | 0.342664E+12 | 0.00 | 0.01 |
September | 0.00 | 0.00 | 0.387365E+11 | 0.118856E+12 | 0.00 | 0.66 |
October | 0.00 | 0.00 | 0.280269E+12 | 0.224093E+12 | 0.00 | 18.25 |
November | 0.00 | 0.00 | 0.289886E+12 | 0.237199E+12 | 0.00 | 26.05 |
December | 0.00 | 0.00 | 0.578216E+12 | 0.330056E+12 | 0.00 | 41.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.434995E+13 | 0.250409E+13 | 0.00 | 129.60 |
Minimum of Months | 0.00 | 0.00 | 0.205310E+11 | 0.112273E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.117456E+13 | 0.342664E+12 | 0.00 | 41.12 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.619833E+10 | 0.269639E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.110842E+11 | 0.342656E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.183244E+11 | 0.484108E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.238467E+11 | 0.582631E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.652735E+10 | 0.276321E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.123479E+11 | 0.384857E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.190998E+11 | 0.533741E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.254596E+11 | 0.671518E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.651950E+10 | 0.276025E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.128489E+11 | 0.409950E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.179028E+11 | 0.474447E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.244529E+11 | 0.593182E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.184612E+12 | 0.529907E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.619833E+10 | 0.269639E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.254596E+11 | 0.671518E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.465890E+11 | 0.233062E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.947255E+11 | 0.307320E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.163784E+12 | 0.443440E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.220849E+12 | 0.545078E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.549556E+11 | 0.249532E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.112229E+12 | 0.357028E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.178051E+12 | 0.501701E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.239249E+12 | 0.634056E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.558838E+11 | 0.250921E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.115018E+12 | 0.377016E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.160486E+12 | 0.435317E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.221230E+12 | 0.546607E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.166305E+13 | 0.488108E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.465890E+11 | 0.233062E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.239249E+12 | 0.634056E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.317242E+10 | 0.205512E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.834507E+10 | 0.289103E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.153613E+11 | 0.428990E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.215279E+11 | 0.539205E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.494987E+10 | 0.241247E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.109695E+11 | 0.354995E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.176872E+11 | 0.502751E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.237768E+11 | 0.634934E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.521658E+10 | 0.245963E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.108978E+11 | 0.368481E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.149577E+11 | 0.419433E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.207110E+11 | 0.526769E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.157573E+12 | 0.475738E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.317242E+10 | 0.205512E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.237768E+11 | 0.634934E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.150921E+11 | 0.121068E+11 | 0.107598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130126E+11 | 0.545688E+10 | 0.384062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150072E+11 | 0.604915E+10 | 44649758.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139231E+11 | 0.158068E+11 | 0.403523E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143901E+11 | 0.151443E+11 | 0.560618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144243E+11 | 0.268395E+11 | 0.123237E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142255E+11 | 0.454068E+11 | 0.697344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153801E+11 | 0.518765E+11 | 0.485481E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144432E+11 | 0.315283E+11 | 0.380148E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151265E+11 | 0.419918E+11 | 0.908977E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147843E+11 | 0.133721E+11 | 0.459536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148927E+11 | 0.163690E+11 | 0.423229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174702E+12 | 0.281948E+12 | 0.594678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130126E+11 | 0.545688E+10 | 44649758.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153801E+11 | 0.518765E+11 | 0.107598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.495866E+10 | 0.233312E+11 | 80225748.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.477600E+10 | 0.156099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.602833E+10 | 0.186911E+11 | 18383255.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.621313E+10 | 0.384943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.475200E+10 | 0.342926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.527345E+10 | 0.648715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.596468E+10 | 0.115272E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.706800E+10 | 0.141050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.489830E+10 | 0.732311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.565662E+10 | 0.810878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.608243E+10 | 0.290306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.643650E+10 | 0.312344E+11 | 1170896.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.681081E+11 | 0.666196E+12 | 99779900.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.475200E+10 | 0.156099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.706800E+10 | 0.141050E+12 | 80225748.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.356253E+11 | 0.189321E+12 | 0.566886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.318919E+11 | 0.120341E+12 | 0.108144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.362575E+11 | 0.138602E+12 | 0.320376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.356185E+11 | 0.271207E+12 | 0.232643E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.356315E+11 | 0.278519E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.376895E+11 | 0.517198E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.392173E+11 | 0.872444E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.432892E+11 | 0.100669E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.381998E+11 | 0.618168E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.402425E+11 | 0.652647E+12 | 1456792.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.370306E+11 | 0.212543E+12 | 0.260789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.366684E+11 | 0.221693E+12 | 0.235844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.447362E+12 | 0.509937E+13 | 0.128074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.318919E+11 | 0.120341E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.432892E+11 | 0.100669E+13 | 0.566886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.300538E+10 | 0.164824E+11 | 0.337735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272339E+10 | 0.106349E+11 | 0.172905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.314912E+10 | 0.126544E+11 | 0.203275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.342057E+10 | 0.270165E+11 | 0.268424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.343516E+10 | 0.277870E+11 | 95314102.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.387017E+10 | 0.540263E+11 | 84336.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.421784E+10 | 0.930951E+11 | 2850.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.460880E+10 | 0.107182E+12 | 7888.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.374378E+10 | 0.616377E+11 | 2243715.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.374296E+10 | 0.637254E+11 | 0.174401E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.303143E+10 | 0.184394E+11 | 0.923609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.302156E+10 | 0.195179E+11 | 0.215343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.419702E+11 | 0.512199E+12 | 0.107567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.272339E+10 | 0.106349E+11 | 2850.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.460880E+10 | 0.107182E+12 | 0.337735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.956558E+11 | 0.853521E+11 | 0.00 | 0.00 | 0.00 | 0.364221E+11 | 0.00 | 0.00 |
February | 0.863988E+11 | 0.140372E+12 | 0.00 | 0.00 | 0.00 | 0.350224E+11 | 0.00 | 0.00 |
March | 0.956558E+11 | 0.236673E+12 | 0.00 | 0.00 | 0.00 | 0.290013E+11 | 0.00 | 0.00 |
April | 0.925702E+11 | 0.579716E+12 | 0.00 | 0.00 | 0.00 | 0.107797E+11 | 0.00 | 0.00 |
May | 0.956558E+11 | 0.175754E+11 | 0.00 | 0.00 | 0.00 | 0.485665E+10 | 0.00 | 0.00 |
June | 0.925702E+11 | 0.937954E+11 | 0.00 | 0.00 | 0.00 | 0.324088E+09 | 0.00 | 0.00 |
July | 0.956558E+11 | 0.495626E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.956558E+11 | 0.954576E+12 | 0.00 | 0.00 | 0.00 | 33890520.47 | 0.00 | 0.00 |
September | 0.925702E+11 | 0.316618E+11 | 0.00 | 0.00 | 0.00 | 0.176715E+10 | 0.00 | 0.00 |
October | 0.956558E+11 | 0.230094E+12 | 0.00 | 0.00 | 0.00 | 0.488506E+11 | 0.00 | 0.00 |
November | 0.925702E+11 | 0.241245E+12 | 0.00 | 0.00 | 0.00 | 0.697070E+11 | 0.00 | 0.00 |
December | 0.956558E+11 | 0.472299E+12 | 0.00 | 0.00 | 0.00 | 0.110054E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.112627E+13 | 0.357899E+13 | 0.00 | 0.00 | 0.00 | 0.346819E+12 | 0.00 | 0.00 |
Minimum of Months | 0.863988E+11 | 0.175754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.956558E+11 | 0.954576E+12 | 0.00 | 0.00 | 0.00 | 0.110054E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140997E+10 | 0.530005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127352E+10 | 0.949020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140997E+10 | 0.156657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136449E+10 | 0.202158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140997E+10 | 0.557761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136449E+10 | 0.104820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140997E+10 | 0.159603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140997E+10 | 0.209985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136449E+10 | 0.552798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140997E+10 | 0.108049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136449E+10 | 0.152740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140997E+10 | 0.207902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166013E+11 | 0.156087E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127352E+10 | 0.530005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140997E+10 | 0.209985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.134395E+11 | 0.398235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121389E+11 | 0.810990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134395E+11 | 0.140013E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130060E+11 | 0.187204E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134395E+11 | 0.469520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130060E+11 | 0.952544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134395E+11 | 0.148762E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134395E+11 | 0.197316E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130060E+11 | 0.473654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134395E+11 | 0.966799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130060E+11 | 0.136912E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134395E+11 | 0.188070E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158239E+12 | 0.140545E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121389E+11 | 0.398235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134395E+11 | 0.197316E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136481E+10 | 0.270894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123273E+10 | 0.714403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136481E+10 | 0.131301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132078E+10 | 0.182438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136481E+10 | 0.422718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132078E+10 | 0.930712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136481E+10 | 0.147725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136481E+10 | 0.196047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132078E+10 | 0.441781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136481E+10 | 0.915287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132078E+10 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136481E+10 | 0.176031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160695E+11 | 0.133071E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123273E+10 | 0.270894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136481E+10 | 0.196047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.150921E+11 | 0.107598E+10 | 0.121068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130126E+11 | 0.384062E+09 | 0.545688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150072E+11 | 44649758.75 | 0.604915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139231E+11 | 0.403523E+09 | 0.158068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143901E+11 | 0.560618E+09 | 0.151443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144243E+11 | 0.123237E+09 | 0.268395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142255E+11 | 0.697344E+09 | 0.454068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153801E+11 | 0.485481E+09 | 0.518765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144432E+11 | 0.380148E+09 | 0.315283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151265E+11 | 0.908977E+09 | 0.419918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147843E+11 | 0.459536E+09 | 0.133721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148927E+11 | 0.423229E+09 | 0.163690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174702E+12 | 0.594678E+10 | 0.281948E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.130126E+11 | 44649758.75 | 0.545688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153801E+11 | 0.107598E+10 | 0.518765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.495866E+10 | 80225748.31 | 0.233312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.477600E+10 | 0.00 | 0.156099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.602833E+10 | 18383255.89 | 0.186911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.621313E+10 | 0.00 | 0.384943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.475200E+10 | 0.00 | 0.342926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.527345E+10 | 0.00 | 0.648715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.596468E+10 | 0.00 | 0.115272E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.706800E+10 | 0.00 | 0.141050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.489830E+10 | 0.00 | 0.732311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.565662E+10 | 0.00 | 0.810878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.608243E+10 | 0.00 | 0.290306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.643650E+10 | 1170896.77 | 0.312344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.681081E+11 | 99779900.98 | 0.666196E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.475200E+10 | 0.00 | 0.156099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.706800E+10 | 80225748.31 | 0.141050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.356253E+11 | 0.566886E+10 | 0.189321E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.318919E+11 | 0.108144E+10 | 0.120341E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.362575E+11 | 0.320376E+10 | 0.138602E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.356185E+11 | 0.232643E+09 | 0.271207E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.356315E+11 | 0.00 | 0.278519E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.376895E+11 | 0.00 | 0.517198E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.392173E+11 | 0.00 | 0.872444E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.432892E+11 | 0.00 | 0.100669E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.381998E+11 | 0.00 | 0.618168E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.402425E+11 | 1456792.95 | 0.652647E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.370306E+11 | 0.260789E+09 | 0.212543E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.366684E+11 | 0.235844E+10 | 0.221693E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.447362E+12 | 0.128074E+11 | 0.509937E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.318919E+11 | 0.00 | 0.120341E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.432892E+11 | 0.566886E+10 | 0.100669E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.300538E+10 | 0.337735E+10 | 0.164824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272339E+10 | 0.172905E+10 | 0.106349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.314912E+10 | 0.203275E+10 | 0.126544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.342057E+10 | 0.268424E+09 | 0.270165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.343516E+10 | 95314102.35 | 0.277870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.387017E+10 | 84336.98 | 0.540263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.421784E+10 | 2850.41 | 0.930951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.460880E+10 | 7888.21 | 0.107182E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.374378E+10 | 2243715.37 | 0.616377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.374296E+10 | 0.174401E+09 | 0.637254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.303143E+10 | 0.923609E+09 | 0.184394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.302156E+10 | 0.215343E+10 | 0.195179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.419702E+11 | 0.107567E+11 | 0.512199E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.272339E+10 | 2850.41 | 0.106349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.460880E+10 | 0.337735E+10 | 0.107182E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.956558E+11 | 0.00 | 0.100471E+12 | 0.00 | 0.269793E+11 | 0.00 | 0.00 | 0.00 | 0.365860E+11 | 0.00 | 0.00 | 0.00 |
February | 0.863988E+11 | 0.00 | 0.164870E+12 | 0.00 | 0.432693E+11 | 0.00 | 0.00 | 0.00 | 0.351800E+11 | 0.00 | 0.00 | 0.00 |
March | 0.956558E+11 | 0.00 | 0.280521E+12 | 0.00 | 0.729771E+11 | 0.00 | 0.00 | 0.00 | 0.291319E+11 | 0.00 | 0.00 | 0.00 |
April | 0.925702E+11 | 0.00 | 0.701830E+12 | 0.00 | 0.147554E+12 | 0.00 | 0.00 | 0.00 | 0.108282E+11 | 0.00 | 0.00 | 0.00 |
May | 0.956558E+11 | 0.00 | 0.205310E+11 | 0.00 | 0.117390E+11 | 0.00 | 0.00 | 0.00 | 0.487851E+10 | 0.00 | 0.00 | 0.00 |
June | 0.925702E+11 | 0.00 | 0.113866E+12 | 0.00 | 0.444198E+11 | 0.00 | 0.00 | 0.00 | 0.325547E+09 | 0.00 | 0.00 | 0.00 |
July | 0.956558E+11 | 0.00 | 0.606193E+12 | 0.00 | 0.133185E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.956558E+11 | 0.00 | 0.117456E+13 | 0.00 | 0.246975E+12 | 0.00 | 0.00 | 0.00 | 34043422.82 | 0.00 | 0.00 | 0.00 |
September | 0.925702E+11 | 0.00 | 0.387365E+11 | 0.00 | 0.245110E+11 | 0.00 | 0.00 | 0.00 | 0.177511E+10 | 0.00 | 0.00 | 0.00 |
October | 0.956558E+11 | 0.00 | 0.280269E+12 | 0.00 | 0.793668E+11 | 0.00 | 0.00 | 0.00 | 0.490705E+11 | 0.00 | 0.00 | 0.00 |
November | 0.925702E+11 | 0.00 | 0.289886E+12 | 0.00 | 0.746076E+11 | 0.00 | 0.00 | 0.00 | 0.700208E+11 | 0.00 | 0.00 | 0.00 |
December | 0.956558E+11 | 0.00 | 0.578216E+12 | 0.00 | 0.123850E+12 | 0.00 | 0.00 | 0.00 | 0.110550E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112627E+13 | 0.00 | 0.434995E+13 | 0.00 | 0.102943E+13 | 0.00 | 0.00 | 0.00 | 0.348380E+12 | 0.00 | 0.00 | |
Minimum of Months | 0.863988E+11 | 0.00 | 0.205310E+11 | 0.00 | 0.117390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.956558E+11 | 0.00 | 0.117456E+13 | 0.00 | 0.246975E+12 | 0.00 | 0.00 | 0.00 | 0.110550E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.140997E+10 | 0.00 | 0.619833E+10 | 0.00 | 0.128642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127352E+10 | 0.00 | 0.110842E+11 | 0.00 | 0.215304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140997E+10 | 0.00 | 0.183244E+11 | 0.00 | 0.343111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136449E+10 | 0.00 | 0.238467E+11 | 0.00 | 0.446182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140997E+10 | 0.00 | 0.652735E+10 | 0.00 | 0.135324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136449E+10 | 0.00 | 0.123479E+11 | 0.00 | 0.248408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140997E+10 | 0.00 | 0.190998E+11 | 0.00 | 0.392744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140997E+10 | 0.00 | 0.254596E+11 | 0.00 | 0.530521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136449E+10 | 0.00 | 0.651950E+10 | 0.00 | 0.139576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140997E+10 | 0.00 | 0.128489E+11 | 0.00 | 0.268953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136449E+10 | 0.00 | 0.179028E+11 | 0.00 | 0.337998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140997E+10 | 0.00 | 0.244529E+11 | 0.00 | 0.452185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166013E+11 | 0.00 | 0.184612E+12 | 0.00 | 0.363895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.127352E+10 | 0.00 | 0.619833E+10 | 0.00 | 0.128642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140997E+10 | 0.00 | 0.254596E+11 | 0.00 | 0.530521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.134395E+11 | 0.00 | 0.465890E+11 | 0.00 | 0.986668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121389E+11 | 0.00 | 0.947255E+11 | 0.00 | 0.185931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134395E+11 | 0.00 | 0.163784E+12 | 0.00 | 0.309045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130060E+11 | 0.00 | 0.220849E+12 | 0.00 | 0.415018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134395E+11 | 0.00 | 0.549556E+11 | 0.00 | 0.115137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130060E+11 | 0.00 | 0.112229E+12 | 0.00 | 0.226968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134395E+11 | 0.00 | 0.178051E+12 | 0.00 | 0.367306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134395E+11 | 0.00 | 0.239249E+12 | 0.00 | 0.499661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130060E+11 | 0.00 | 0.558838E+11 | 0.00 | 0.120861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134395E+11 | 0.00 | 0.115018E+12 | 0.00 | 0.242621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130060E+11 | 0.00 | 0.160486E+12 | 0.00 | 0.305258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134395E+11 | 0.00 | 0.221230E+12 | 0.00 | 0.412212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158239E+12 | 0.00 | 0.166305E+13 | 0.00 | 0.329869E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.121389E+11 | 0.00 | 0.465890E+11 | 0.00 | 0.986668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134395E+11 | 0.00 | 0.239249E+12 | 0.00 | 0.499661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.136481E+10 | 0.00 | 0.317242E+10 | 0.00 | 0.690310E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123273E+10 | 0.00 | 0.834507E+10 | 0.00 | 0.165830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136481E+10 | 0.00 | 0.153613E+11 | 0.00 | 0.292509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132078E+10 | 0.00 | 0.215279E+11 | 0.00 | 0.407126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136481E+10 | 0.00 | 0.494987E+10 | 0.00 | 0.104766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132078E+10 | 0.00 | 0.109695E+11 | 0.00 | 0.222917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136481E+10 | 0.00 | 0.176872E+11 | 0.00 | 0.366270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136481E+10 | 0.00 | 0.237768E+11 | 0.00 | 0.498453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132078E+10 | 0.00 | 0.521658E+10 | 0.00 | 0.113885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136481E+10 | 0.00 | 0.108978E+11 | 0.00 | 0.232000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132078E+10 | 0.00 | 0.149577E+11 | 0.00 | 0.287354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136481E+10 | 0.00 | 0.207110E+11 | 0.00 | 0.390288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160695E+11 | 0.00 | 0.157573E+12 | 0.00 | 0.315043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.123273E+10 | 0.00 | 0.317242E+10 | 0.00 | 0.690310E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136481E+10 | 0.00 | 0.237768E+11 | 0.00 | 0.498453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.267262E+09 | 92571497.69 | 0.00 | 0.163177E+09 | 0.00 | 0.00 | 0.667094E+11 | 0.00 | 1.21 |
February | 0.289501E+09 | 5118263.98 | 0.00 | 0.127797E+09 | 0.00 | 0.00 | 0.624127E+11 | 0.00 | 1.19 |
March | 0.307706E+09 | 0.00 | 0.00 | 0.141976E+09 | 0.00 | 0.00 | 0.731708E+11 | 0.00 | 1.22 |
April | 0.210783E+09 | 9312891.45 | 0.00 | 0.143314E+09 | 0.00 | 0.00 | 0.585342E+11 | 0.00 | 1.33 |
May | 0.194246E+09 | 4313973.38 | 0.00 | 0.138091E+09 | 0.00 | 0.00 | 0.606727E+11 | 0.00 | 1.40 |
June | 0.153686E+09 | 24759258.99 | 0.00 | 0.139075E+09 | 0.00 | 0.00 | 0.493673E+11 | 0.00 | 1.55 |
July | 0.125415E+09 | 0.157675E+10 | 0.00 | 0.141626E+09 | 0.00 | 0.00 | 0.335848E+11 | 0.00 | 1.37 |
August | 0.106741E+09 | 0.207232E+10 | 0.00 | 0.143200E+09 | 0.00 | 0.00 | 0.347078E+11 | 0.00 | 1.49 |
September | 0.173071E+09 | 0.973511E+09 | 0.00 | 0.144635E+09 | 31716464.82 | 0.00 | 0.451827E+11 | 0.00 | 1.47 |
October | 0.182273E+09 | 0.228468E+10 | 0.00 | 0.151578E+09 | 21436841.61 | 0.00 | 0.421467E+11 | 0.00 | 1.37 |
November | 0.268387E+09 | 10863840.13 | 0.00 | 0.169190E+09 | 0.00 | 0.00 | 0.672152E+11 | 0.00 | 1.33 |
December | 0.464886E+09 | 397414.65 | 0.00 | 0.169322E+09 | 0.00 | 0.00 | 0.633739E+11 | 0.00 | 1.21 |
Annual Sum or Average | 0.274396E+10 | 0.705460E+10 | 0.00 | 0.177298E+10 | 53153306.42 | 0.00 | 0.657078E+12 | 0.00 | 1.35 |
Minimum of Months | 0.106741E+09 | 0.00 | 0.00 | 0.127797E+09 | 0.00 | 0.00 | 0.335848E+11 | 0.00 | 1.19 |
Maximum of Months | 0.464886E+09 | 0.228468E+10 | 0.00 | 0.169322E+09 | 31716464.82 | 0.00 | 0.731708E+11 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.293341E+10 | 56958325.09 | 0.00 | 91597245.93 | 36470877.32 | 0.00 | 0.415709E+11 | 0.00 | 0.73 |
February | 0.320421E+10 | 14175117.51 | 0.00 | 86584739.07 | 0.00 | 0.00 | 0.427735E+11 | 0.00 | 0.79 |
March | 0.318322E+10 | 9556123.26 | 0.00 | 0.108554E+09 | 13528546.28 | 0.00 | 0.539218E+11 | 0.00 | 0.86 |
April | 0.588481E+10 | 16213006.61 | 0.00 | 0.109377E+09 | 53823807.17 | 0.00 | 0.408032E+11 | 0.00 | 0.93 |
May | 0.339761E+10 | 24994097.14 | 0.00 | 93030606.28 | 0.00 | 0.00 | 0.377606E+11 | 0.00 | 0.82 |
June | 0.296655E+10 | 0.170013E+10 | 0.00 | 90652957.68 | 35552813.80 | 0.00 | 0.257596E+11 | 0.00 | 0.89 |
July | 0.365116E+10 | 0.877974E+10 | 0.00 | 59564952.18 | 0.104223E+10 | 0.00 | 0.903208E+10 | 0.00 | 0.89 |
August | 0.282836E+10 | 0.117620E+11 | 0.00 | 50076152.12 | 0.142540E+10 | 0.00 | 0.771788E+10 | 0.00 | 1.00 |
September | 0.197209E+10 | 0.296416E+10 | 0.00 | 72135600.25 | 0.145619E+09 | 0.00 | 0.183575E+11 | 0.00 | 0.79 |
October | 0.269768E+10 | 0.450326E+10 | 0.00 | 75444401.65 | 0.537923E+09 | 0.00 | 0.212283E+11 | 0.00 | 0.77 |
November | 0.391624E+10 | 3166269.57 | 0.00 | 0.112101E+09 | 24906947.47 | 0.00 | 0.455661E+11 | 0.00 | 0.88 |
December | 0.501768E+10 | 976326.96 | 0.00 | 0.118019E+09 | 0.00 | 0.00 | 0.449595E+11 | 0.00 | 0.85 |
Annual Sum or Average | 0.416530E+11 | 0.298353E+11 | 0.00 | 0.106714E+10 | 0.331545E+10 | 0.00 | 0.389451E+12 | 0.00 | 0.85 |
Minimum of Months | 0.197209E+10 | 976326.96 | 0.00 | 50076152.12 | 0.00 | 0.00 | 0.771788E+10 | 0.00 | 0.73 |
Maximum of Months | 0.588481E+10 | 0.117620E+11 | 0.00 | 0.118019E+09 | 0.142540E+10 | 0.00 | 0.539218E+11 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.759328E+11 | 98413148.64 | 0.00 | 0.474660E+09 | 0.578521E+09 | 0.00 | 0.255040E+12 | 0.00 | 0.56 |
February | 0.673104E+11 | 0.148400E+09 | 0.00 | 0.423056E+09 | 0.00 | 0.00 | 0.263555E+12 | 0.00 | 0.59 |
March | 0.684249E+11 | 26095293.38 | 0.00 | 0.502209E+09 | 0.398025E+09 | 0.00 | 0.321652E+12 | 0.00 | 0.61 |
April | 0.449488E+11 | 92099897.25 | 0.00 | 0.524907E+09 | 0.654083E+09 | 0.00 | 0.262483E+12 | 0.00 | 0.64 |
May | 0.471065E+11 | 0.261086E+09 | 0.00 | 0.556415E+09 | 0.00 | 0.00 | 0.280816E+12 | 0.00 | 0.67 |
June | 0.237962E+11 | 0.124937E+11 | 0.00 | 0.522852E+09 | 0.314649E+09 | 0.00 | 0.196475E+12 | 0.00 | 0.72 |
July | 0.192711E+11 | 0.615948E+11 | 0.00 | 0.295368E+09 | 0.153422E+11 | 0.00 | 0.619774E+11 | 0.00 | 0.66 |
August | 0.782471E+10 | 0.787779E+11 | 0.00 | 0.256598E+09 | 0.177488E+11 | 0.00 | 0.556162E+11 | 0.00 | 0.69 |
September | 0.213544E+11 | 0.215892E+11 | 0.00 | 0.414442E+09 | 0.559452E+10 | 0.00 | 0.139234E+12 | 0.00 | 0.66 |
October | 0.289965E+11 | 0.358289E+11 | 0.00 | 0.385464E+09 | 0.594505E+10 | 0.00 | 0.144276E+12 | 0.00 | 0.61 |
November | 0.491524E+11 | 15626357.64 | 0.00 | 0.532282E+09 | 0.270933E+09 | 0.00 | 0.289786E+12 | 0.00 | 0.63 |
December | 0.671823E+11 | 19854359.95 | 0.00 | 0.484993E+09 | 16088003.88 | 0.00 | 0.255560E+12 | 0.00 | 0.58 |
Annual Sum or Average | 0.521301E+12 | 0.210946E+12 | 0.00 | 0.537324E+10 | 0.468628E+11 | 0.00 | 0.252647E+13 | 0.00 | 0.64 |
Minimum of Months | 0.782471E+10 | 15626357.64 | 0.00 | 0.256598E+09 | 0.00 | 0.00 | 0.556162E+11 | 0.00 | 0.56 |
Maximum of Months | 0.759328E+11 | 0.787779E+11 | 0.00 | 0.556415E+09 | 0.177488E+11 | 0.00 | 0.321652E+12 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.165787E+11 | 3610624.79 | 0.00 | 15754606.61 | 60200732.19 | 0.221692E+09 | 0.979736E+10 | 0.00 | 0.48 |
February | 0.138120E+11 | 4506533.72 | 0.00 | 18746631.01 | 9784851.77 | 4637639.32 | 0.135265E+11 | 0.00 | 0.52 |
March | 0.147126E+11 | 0.00 | 0.00 | 24766762.04 | 26344580.25 | 0.00 | 0.183457E+11 | 0.00 | 0.53 |
April | 0.953815E+10 | 1266434.37 | 0.00 | 38685571.08 | 30211812.62 | 0.00 | 0.197773E+11 | 0.00 | 0.61 |
May | 0.935001E+10 | 9674320.85 | 0.00 | 43035858.99 | 0.00 | 0.00 | 0.221037E+11 | 0.00 | 0.64 |
June | 0.583553E+10 | 0.907606E+09 | 0.00 | 44594121.01 | 264516.89 | 0.00 | 0.161332E+11 | 0.00 | 0.71 |
July | 0.292331E+10 | 0.550913E+10 | 0.00 | 23633082.91 | 0.169959E+10 | 0.00 | 0.513882E+10 | 0.00 | 0.68 |
August | 0.164830E+10 | 0.727509E+10 | 0.00 | 20960801.76 | 0.229000E+10 | 0.00 | 0.402909E+10 | 0.00 | 0.73 |
September | 0.506049E+10 | 0.160983E+10 | 0.00 | 31890280.57 | 0.464308E+09 | 0.00 | 0.977467E+10 | 0.00 | 0.63 |
October | 0.738794E+10 | 0.306221E+10 | 0.00 | 23959225.29 | 0.951193E+09 | 0.00 | 0.750600E+10 | 0.00 | 0.57 |
November | 0.127115E+11 | 45313.03 | 0.00 | 24246329.09 | 20846999.92 | 0.00 | 0.147144E+11 | 0.00 | 0.53 |
December | 0.147573E+11 | 523778.67 | 0.00 | 17129643.10 | 7675896.32 | 17020543.06 | 0.103248E+11 | 0.00 | 0.49 |
Annual Sum or Average | 0.114316E+12 | 0.183835E+11 | 0.00 | 0.327403E+09 | 0.556041E+10 | 0.243350E+09 | 0.151171E+12 | 0.00 | 0.59 |
Minimum of Months | 0.164830E+10 | 0.00 | 0.00 | 15754606.61 | 0.00 | 0.00 | 0.402909E+10 | 0.00 | 0.48 |
Maximum of Months | 0.165787E+11 | 0.727509E+10 | 0.00 | 44594121.01 | 0.229000E+10 | 0.221692E+09 | 0.221037E+11 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.234954E+10 | 5000344.98 | 0.00 | 3645906.05 | 6520390.79 | 0.00 | 0.184653E+10 | 0.00 | 0.55 |
February | 0.213235E+10 | 1610480.43 | 0.00 | 3944914.78 | 0.00 | 0.00 | 0.232912E+10 | 0.00 | 0.62 |
March | 0.205096E+10 | 1167598.46 | 0.00 | 5466450.16 | 1696078.75 | 0.00 | 0.340301E+10 | 0.00 | 0.67 |
April | 0.172438E+10 | 2195972.23 | 0.00 | 7188902.92 | 6747910.22 | 0.00 | 0.322247E+10 | 0.00 | 0.82 |
May | 0.150379E+10 | 3362936.92 | 0.00 | 6980644.95 | 0.00 | 0.00 | 0.321203E+10 | 0.00 | 0.76 |
June | 0.636493E+09 | 0.243359E+09 | 0.00 | 8112517.21 | 4457269.16 | 0.00 | 0.280204E+10 | 0.00 | 0.90 |
July | 0.514036E+09 | 0.128947E+10 | 0.00 | 4666738.31 | 0.130665E+09 | 0.00 | 0.988349E+09 | 0.00 | 0.92 |
August | 0.424998E+09 | 0.165143E+10 | 0.00 | 3295049.97 | 0.179195E+09 | 0.00 | 0.757457E+09 | 0.00 | 1.00 |
September | 0.928180E+09 | 0.405794E+09 | 0.00 | 4476985.99 | 18266218.22 | 0.00 | 0.133313E+10 | 0.00 | 0.75 |
October | 0.114930E+10 | 0.609056E+09 | 0.00 | 4233238.18 | 68360621.72 | 0.00 | 0.137121E+10 | 0.00 | 0.70 |
November | 0.205905E+10 | 345870.00 | 0.00 | 5427776.46 | 3122593.04 | 0.00 | 0.267058E+10 | 0.00 | 0.68 |
December | 0.223515E+10 | 105361.93 | 0.00 | 4989158.53 | 0.00 | 0.00 | 0.230430E+10 | 0.00 | 0.64 |
Annual Sum or Average | 0.177082E+11 | 0.421290E+10 | 0.00 | 62428283.51 | 0.419031E+09 | 0.00 | 0.262402E+11 | 0.00 | 0.75 |
Minimum of Months | 0.424998E+09 | 105361.93 | 0.00 | 3295049.97 | 0.00 | 0.00 | 0.757457E+09 | 0.00 | 0.55 |
Maximum of Months | 0.234954E+10 | 0.165143E+10 | 0.00 | 8112517.21 | 0.179195E+09 | 0.00 | 0.340301E+10 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.175180E+10 | 2389068.78 | 0.00 | 4431974.65 | 7335664.46 | 0.00 | 0.215477E+10 | 0.00 | 0.77 |
February | 0.177200E+10 | 1142767.59 | 0.00 | 3961534.59 | 0.00 | 0.00 | 0.218931E+10 | 0.00 | 0.84 |
March | 0.193433E+10 | 853532.08 | 0.00 | 5223878.82 | 1431811.05 | 0.00 | 0.286431E+10 | 0.00 | 0.92 |
April | 0.172136E+10 | 2081989.15 | 0.00 | 7404476.04 | 5702276.63 | 0.00 | 0.300685E+10 | 0.00 | 1.19 |
May | 0.128840E+10 | 3018032.62 | 0.00 | 7022665.06 | 0.00 | 0.00 | 0.310680E+10 | 0.00 | 1.09 |
June | 0.980696E+09 | 0.190320E+09 | 0.00 | 6984617.11 | 3749169.26 | 0.00 | 0.206564E+10 | 0.00 | 1.23 |
July | 0.627185E+09 | 0.108024E+10 | 0.00 | 4546752.56 | 94050965.71 | 0.00 | 0.826521E+09 | 0.00 | 1.32 |
August | 0.603885E+09 | 0.148221E+10 | 0.00 | 2883663.09 | 0.132852E+09 | 0.00 | 0.543638E+09 | 0.00 | 1.43 |
September | 0.914859E+09 | 0.305302E+09 | 0.00 | 4692475.57 | 21837993.07 | 0.00 | 0.121451E+10 | 0.00 | 1.06 |
October | 0.108671E+10 | 0.395420E+09 | 0.00 | 4223675.08 | 98980944.92 | 0.00 | 0.127320E+10 | 0.00 | 0.94 |
November | 0.175658E+10 | 247472.17 | 0.00 | 4947888.00 | 2660194.77 | 0.00 | 0.232520E+10 | 0.00 | 0.89 |
December | 0.199316E+10 | 92076.01 | 0.00 | 4421065.25 | 0.00 | 0.00 | 0.189426E+10 | 0.00 | 0.82 |
Annual Sum or Average | 0.164310E+11 | 0.346332E+10 | 0.00 | 60744665.83 | 0.368601E+09 | 0.00 | 0.234650E+11 | 0.00 | 1.04 |
Minimum of Months | 0.603885E+09 | 92076.01 | 0.00 | 2883663.09 | 0.00 | 0.00 | 0.543638E+09 | 0.00 | 0.77 |
Maximum of Months | 0.199316E+10 | 0.148221E+10 | 0.00 | 7404476.04 | 0.132852E+09 | 0.00 | 0.310680E+10 | 0.00 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126271E+10 | 27924992.29 | 0.00 | 17580624.34 | 4280928.01 | 0.00 | 0.688848E+10 | 0.00 | 1.18 |
February | 0.149054E+10 | 4408939.79 | 0.00 | 11873119.31 | 0.00 | 0.00 | 0.546177E+10 | 0.00 | 1.06 |
March | 0.185073E+10 | 4070253.54 | 0.00 | 9845059.87 | 297757.15 | 0.00 | 0.520165E+10 | 0.00 | 0.96 |
April | 0.170918E+10 | 3634031.00 | 0.00 | 9256126.22 | 6431811.57 | 0.00 | 0.383438E+10 | 0.00 | 0.97 |
May | 0.175476E+10 | 3672785.34 | 0.00 | 6613852.46 | 0.00 | 0.00 | 0.291301E+10 | 0.00 | 0.76 |
June | 0.109418E+10 | 0.244936E+09 | 0.00 | 6738338.23 | 4461374.43 | 0.00 | 0.217432E+10 | 0.00 | 0.86 |
July | 0.620867E+09 | 0.131950E+10 | 0.00 | 3641218.45 | 0.130122E+09 | 0.00 | 0.827228E+09 | 0.00 | 0.91 |
August | 0.486384E+09 | 0.196328E+10 | 0.00 | 3430443.28 | 0.180832E+09 | 0.00 | 0.720127E+09 | 0.00 | 1.12 |
September | 0.733176E+09 | 0.637950E+09 | 0.00 | 7537352.42 | 17112754.17 | 0.00 | 0.197928E+10 | 0.00 | 1.03 |
October | 0.827027E+09 | 0.966491E+09 | 0.00 | 10908473.14 | 39388432.00 | 0.00 | 0.251578E+10 | 0.00 | 1.07 |
November | 0.108309E+10 | 4844703.96 | 0.00 | 19079190.35 | 410853.13 | 0.00 | 0.700560E+10 | 0.00 | 1.29 |
December | 0.113081E+10 | 266452.21 | 0.00 | 23660021.06 | 0.00 | 0.00 | 0.715034E+10 | 0.00 | 1.31 |
Annual Sum or Average | 0.140435E+11 | 0.518097E+10 | 0.00 | 0.130164E+09 | 0.383337E+09 | 0.00 | 0.466719E+11 | 0.00 | 1.04 |
Minimum of Months | 0.486384E+09 | 266452.21 | 0.00 | 3430443.28 | 0.00 | 0.00 | 0.720127E+09 | 0.00 | 0.76 |
Maximum of Months | 0.185073E+10 | 0.196328E+10 | 0.00 | 23660021.06 | 0.180832E+09 | 0.00 | 0.715034E+10 | 0.00 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.170344E+10 | 11325040.43 | 0.00 | 5760190.49 | 4496183.12 | 0.00 | 0.333493E+10 | 0.00 | 1.04 |
February | 0.767507E+09 | 2193818.18 | 0.00 | 8426415.97 | 0.00 | 0.00 | 0.495111E+10 | 0.00 | 1.26 |
March | 0.541231E+09 | 2426875.10 | 0.00 | 13190893.95 | 1802621.21 | 0.00 | 0.725823E+10 | 0.00 | 1.53 |
April | 0.594535E+09 | 7586879.03 | 0.00 | 20974492.95 | 4065829.49 | 0.00 | 0.729046E+10 | 0.00 | 2.05 |
May | 0.633615E+09 | 3271269.75 | 0.00 | 11951993.77 | 0.00 | 0.00 | 0.514281E+10 | 0.00 | 1.47 |
June | 0.353996E+09 | 0.314220E+09 | 0.00 | 15017501.50 | 1911265.33 | 0.00 | 0.413176E+10 | 0.00 | 1.87 |
July | 0.371329E+09 | 0.197633E+10 | 0.00 | 13182023.96 | 68305094.69 | 0.00 | 0.171094E+10 | 0.00 | 2.04 |
August | 0.317188E+09 | 0.270302E+10 | 0.00 | 10885006.05 | 98928668.73 | 0.00 | 0.138213E+10 | 0.00 | 2.38 |
September | 0.299403E+09 | 0.469640E+09 | 0.00 | 9471582.41 | 18074258.72 | 0.00 | 0.249978E+10 | 0.00 | 1.46 |
October | 0.459004E+09 | 0.702282E+09 | 0.00 | 9051491.87 | 49492511.55 | 0.00 | 0.257784E+10 | 0.00 | 1.34 |
November | 0.569783E+09 | 3673990.89 | 0.00 | 13057289.18 | 652795.98 | 0.00 | 0.591719E+10 | 0.00 | 1.50 |
December | 0.641754E+09 | 165644.76 | 0.00 | 14725863.13 | 0.00 | 0.00 | 0.607566E+10 | 0.00 | 1.50 |
Annual Sum or Average | 0.725278E+10 | 0.619614E+10 | 0.00 | 0.145695E+09 | 0.247729E+09 | 0.00 | 0.522728E+11 | 0.00 | 1.62 |
Minimum of Months | 0.299403E+09 | 165644.76 | 0.00 | 5760190.49 | 0.00 | 0.00 | 0.138213E+10 | 0.00 | 1.04 |
Maximum of Months | 0.170344E+10 | 0.270302E+10 | 0.00 | 20974492.95 | 98928668.73 | 0.00 | 0.729046E+10 | 0.00 | 2.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.312913E+11 | 6009887.10 | 0.00 | 6178941.33 | 75769923.49 | 0.109005E+10 | 0.298155E+10 | 0.00 | 0.47 |
February | 0.287894E+11 | 13093052.17 | 0.00 | 5516634.42 | 0.00 | 0.134269E+09 | 0.574175E+10 | 0.00 | 0.49 |
March | 0.335728E+11 | 2624743.29 | 0.00 | 9002566.25 | 49954966.93 | 0.436518E+09 | 0.643609E+10 | 0.00 | 0.50 |
April | 0.216493E+11 | 10844594.35 | 0.00 | 26144292.67 | 82092186.92 | 3759846.44 | 0.117177E+11 | 0.00 | 0.56 |
May | 0.200350E+11 | 31416776.44 | 0.00 | 36536343.30 | 0.00 | 0.00 | 0.166401E+11 | 0.00 | 0.60 |
June | 0.113800E+11 | 0.171311E+10 | 0.00 | 43348828.26 | 39490759.13 | 0.00 | 0.141736E+11 | 0.00 | 0.69 |
July | 0.572418E+10 | 0.929679E+10 | 0.00 | 19365085.99 | 0.114027E+10 | 0.00 | 0.391866E+10 | 0.00 | 0.66 |
August | 0.488632E+10 | 0.106922E+11 | 0.00 | 11423504.52 | 0.180611E+10 | 0.00 | 0.236070E+10 | 0.00 | 0.67 |
September | 0.119284E+11 | 0.301739E+10 | 0.00 | 21389044.07 | 0.450080E+09 | 0.00 | 0.600019E+10 | 0.00 | 0.60 |
October | 0.146917E+11 | 0.430703E+10 | 0.00 | 16083784.29 | 0.102977E+10 | 0.00 | 0.459729E+10 | 0.00 | 0.55 |
November | 0.274066E+11 | 969804.12 | 0.00 | 9266288.18 | 34367383.52 | 39766129.29 | 0.730316E+10 | 0.00 | 0.50 |
December | 0.307418E+11 | 1663241.15 | 0.00 | 4637984.70 | 2019161.14 | 0.257706E+09 | 0.278255E+10 | 0.00 | 0.48 |
Annual Sum or Average | 0.242097E+12 | 0.290931E+11 | 0.00 | 0.208893E+09 | 0.470992E+10 | 0.196207E+10 | 0.846533E+11 | 0.00 | 0.56 |
Minimum of Months | 0.488632E+10 | 969804.12 | 0.00 | 4637984.70 | 0.00 | 0.00 | 0.236070E+10 | 0.00 | 0.47 |
Maximum of Months | 0.335728E+11 | 0.106922E+11 | 0.00 | 43348828.26 | 0.180611E+10 | 0.109005E+10 | 0.166401E+11 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.224500E+11 | 9068917.00 | 0.00 | 16884447.82 | 64446469.95 | 0.476012E+09 | 0.100655E+11 | 0.00 | 0.67 |
February | 0.213541E+11 | 12694644.28 | 0.00 | 19369958.68 | 0.00 | 9922736.24 | 0.117974E+11 | 0.00 | 0.73 |
March | 0.231157E+11 | 3655106.71 | 0.00 | 27697072.95 | 43983372.75 | 0.208070E+09 | 0.160944E+11 | 0.00 | 0.77 |
April | 0.147316E+11 | 24671034.27 | 0.00 | 56533229.34 | 64247042.27 | 15385752.79 | 0.225594E+11 | 0.00 | 0.98 |
May | 0.161431E+11 | 36864281.26 | 0.00 | 51932533.04 | 0.00 | 0.00 | 0.217524E+11 | 0.00 | 0.97 |
June | 0.104105E+11 | 0.157321E+10 | 0.00 | 55781502.64 | 35050847.70 | 0.00 | 0.156324E+11 | 0.00 | 1.10 |
July | 0.433864E+10 | 0.978867E+10 | 0.00 | 38484582.94 | 0.888436E+09 | 0.00 | 0.670006E+10 | 0.00 | 1.14 |
August | 0.391755E+10 | 0.135385E+11 | 0.00 | 23497212.55 | 0.871299E+09 | 0.00 | 0.446826E+10 | 0.00 | 1.19 |
September | 0.999807E+10 | 0.273807E+10 | 0.00 | 35349856.51 | 0.332355E+09 | 0.00 | 0.858989E+10 | 0.00 | 0.96 |
October | 0.112349E+11 | 0.344842E+10 | 0.00 | 26856986.07 | 0.105449E+10 | 0.00 | 0.816522E+10 | 0.00 | 0.82 |
November | 0.196143E+11 | 1198441.57 | 0.00 | 21321410.63 | 30567675.33 | 3438396.48 | 0.132036E+11 | 0.00 | 0.73 |
December | 0.230581E+11 | 1602015.75 | 0.00 | 15649324.23 | 1815110.74 | 0.134376E+09 | 0.783347E+10 | 0.00 | 0.68 |
Annual Sum or Average | 0.180366E+12 | 0.311767E+11 | 0.00 | 0.389358E+09 | 0.338669E+10 | 0.847204E+09 | 0.146862E+12 | 0.00 | 0.90 |
Minimum of Months | 0.391755E+10 | 1198441.57 | 0.00 | 15649324.23 | 0.00 | 0.00 | 0.446826E+10 | 0.00 | 0.67 |
Maximum of Months | 0.231157E+11 | 0.135385E+11 | 0.00 | 56533229.34 | 0.105449E+10 | 0.476012E+09 | 0.225594E+11 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.123201E+11 | 0.322549E+09 | 0.00 | 0.182328E+09 | 885272.07 | 47736115.44 | 0.612136E+11 | 0.00 | 1.10 |
February | 0.155968E+11 | 52328081.29 | 0.00 | 0.107310E+09 | 0.00 | 0.00 | 0.436415E+11 | 0.00 | 0.94 |
March | 0.208762E+11 | 41269075.25 | 0.00 | 72602659.59 | 22978381.65 | 0.267089E+09 | 0.348288E+11 | 0.00 | 0.79 |
April | 0.179908E+11 | 34237331.91 | 0.00 | 60818958.68 | 71913484.84 | 0.00 | 0.229128E+11 | 0.00 | 0.73 |
May | 0.198458E+11 | 36646297.17 | 0.00 | 42931383.17 | 0.00 | 0.00 | 0.184127E+11 | 0.00 | 0.64 |
June | 0.126340E+11 | 0.178476E+10 | 0.00 | 40366994.57 | 39495586.23 | 0.00 | 0.130340E+11 | 0.00 | 0.69 |
July | 0.587817E+10 | 0.996540E+10 | 0.00 | 19061264.01 | 0.116413E+10 | 0.00 | 0.385408E+10 | 0.00 | 0.68 |
August | 0.432387E+10 | 0.145660E+11 | 0.00 | 18083494.67 | 0.147192E+10 | 0.00 | 0.346335E+10 | 0.00 | 0.81 |
September | 0.817674E+10 | 0.584307E+10 | 0.00 | 60943374.51 | 0.300115E+09 | 0.00 | 0.149775E+11 | 0.00 | 0.93 |
October | 0.826000E+10 | 0.905019E+10 | 0.00 | 0.101301E+09 | 0.385606E+09 | 0.00 | 0.192484E+11 | 0.00 | 0.96 |
November | 0.116457E+11 | 62988069.21 | 0.00 | 0.175215E+09 | 3549778.23 | 0.00 | 0.569287E+11 | 0.00 | 1.14 |
December | 0.114012E+11 | 14639112.55 | 0.00 | 0.215896E+09 | 0.00 | 32305612.76 | 0.562224E+11 | 0.00 | 1.14 |
Annual Sum or Average | 0.148949E+12 | 0.417740E+11 | 0.00 | 0.109686E+10 | 0.346059E+10 | 0.347131E+09 | 0.348738E+12 | 0.00 | 0.88 |
Minimum of Months | 0.432387E+10 | 14639112.55 | 0.00 | 18083494.67 | 0.00 | 0.00 | 0.346335E+10 | 0.00 | 0.64 |
Maximum of Months | 0.208762E+11 | 0.145660E+11 | 0.00 | 0.215896E+09 | 0.147192E+10 | 0.267089E+09 | 0.612136E+11 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.252643E+11 | 60283909.45 | 0.00 | 20391858.14 | 30616749.45 | 0.368492E+09 | 0.109406E+11 | 0.00 | 0.76 |
February | 0.232261E+11 | 16653101.32 | 0.00 | 22328777.43 | 0.00 | 0.00 | 0.139365E+11 | 0.00 | 0.83 |
March | 0.253062E+11 | 5361139.23 | 0.00 | 31853223.08 | 46595979.35 | 95984995.93 | 0.192399E+11 | 0.00 | 0.89 |
April | 0.134764E+11 | 62372332.64 | 0.00 | 69533692.17 | 32923035.99 | 0.00 | 0.274021E+11 | 0.00 | 1.11 |
May | 0.137120E+11 | 26519138.31 | 0.00 | 66513458.58 | 0.00 | 0.00 | 0.284215E+11 | 0.00 | 1.10 |
June | 0.734780E+10 | 0.205179E+10 | 0.00 | 73018898.16 | 14657435.93 | 0.00 | 0.218576E+11 | 0.00 | 1.28 |
July | 0.324001E+10 | 0.128903E+11 | 0.00 | 48921594.43 | 0.519279E+09 | 0.00 | 0.786382E+10 | 0.00 | 1.25 |
August | 0.275806E+10 | 0.150793E+11 | 0.00 | 25638006.36 | 0.844248E+09 | 0.00 | 0.490245E+10 | 0.00 | 1.30 |
September | 0.715912E+10 | 0.335759E+10 | 0.00 | 48506484.16 | 0.358887E+09 | 0.00 | 0.132309E+11 | 0.00 | 1.11 |
October | 0.116079E+11 | 0.424542E+10 | 0.00 | 28259452.41 | 0.830383E+09 | 0.00 | 0.788042E+10 | 0.00 | 0.91 |
November | 0.220180E+11 | 5902607.09 | 0.00 | 29747110.46 | 28780095.80 | 0.00 | 0.155429E+11 | 0.00 | 0.87 |
December | 0.242055E+11 | 2986838.14 | 0.00 | 22366472.74 | 1883392.12 | 7623708.78 | 0.102758E+11 | 0.00 | 0.78 |
Annual Sum or Average | 0.179321E+12 | 0.378046E+11 | 0.00 | 0.487079E+09 | 0.270825E+10 | 0.472100E+09 | 0.181494E+12 | 0.00 | 1.02 |
Minimum of Months | 0.275806E+10 | 2986838.14 | 0.00 | 20391858.14 | 0.00 | 0.00 | 0.490245E+10 | 0.00 | 0.76 |
Maximum of Months | 0.253062E+11 | 0.150793E+11 | 0.00 | 73018898.16 | 0.844248E+09 | 0.368492E+09 | 0.284215E+11 | 0.00 | 1.30 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.262067E+10 | 0.00 | 49691.52 | 201130.47 | 7949314.54 | 0.459689E+09 | 0.126646E+09 | 1790.52 | 0.46 |
February | 0.270523E+10 | 435120.74 | 0.00 | 234763.55 | 1227904.68 | 0.268657E+09 | 0.218395E+09 | 0.00 | 0.48 |
March | 0.323779E+10 | 0.00 | 0.00 | 567920.23 | 3305991.15 | 0.278202E+09 | 0.359139E+09 | 0.00 | 0.49 |
April | 0.213554E+10 | 147172.78 | 0.00 | 2345587.53 | 3791291.58 | 45965036.27 | 0.115061E+10 | 0.00 | 0.55 |
May | 0.203157E+10 | 1100417.98 | 0.00 | 3263621.26 | 0.00 | 11196158.82 | 0.163402E+10 | 0.00 | 0.60 |
June | 0.116826E+10 | 0.123008E+09 | 0.00 | 4250391.95 | 33194.32 | 0.00 | 0.148001E+10 | 0.00 | 0.70 |
July | 0.518981E+09 | 0.847965E+09 | 0.00 | 1995903.68 | 0.132191E+09 | 0.00 | 0.468435E+09 | 0.00 | 0.69 |
August | 0.410766E+09 | 0.102675E+10 | 0.00 | 1337632.76 | 0.220414E+09 | 0.00 | 0.259227E+09 | 0.00 | 0.72 |
September | 0.114407E+10 | 0.216718E+09 | 0.00 | 2070443.09 | 54049686.45 | 0.00 | 0.586018E+09 | 0.00 | 0.59 |
October | 0.132217E+10 | 0.378526E+09 | 0.00 | 1399087.98 | 0.132988E+09 | 36099760.33 | 0.397252E+09 | 0.00 | 0.54 |
November | 0.271215E+10 | 0.00 | 0.00 | 231279.18 | 2621784.11 | 0.200053E+09 | 0.260394E+09 | 0.00 | 0.49 |
December | 0.256283E+10 | 0.00 | 0.00 | 133534.99 | 1022472.76 | 0.361777E+09 | 81365140.12 | 0.00 | 0.46 |
Annual Sum or Average | 0.225700E+11 | 0.259465E+10 | 49691.52 | 18031296.67 | 0.559594E+09 | 0.166164E+10 | 0.702151E+10 | 1790.52 | 0.56 |
Minimum of Months | 0.410766E+09 | 0.00 | 0.00 | 133534.99 | 0.00 | 0.00 | 81365140.12 | 0.00 | 0.46 |
Maximum of Months | 0.323779E+10 | 0.102675E+10 | 49691.52 | 4250391.95 | 0.220414E+09 | 0.459689E+09 | 0.163402E+10 | 1790.52 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.219714E+10 | 380970.31 | 30247.18 | 706405.21 | 6666196.24 | 0.234191E+09 | 0.417525E+09 | 730.19 | 0.63 |
February | 0.188981E+10 | 404437.89 | 0.00 | 1281875.67 | 1086302.59 | 0.154637E+09 | 0.844587E+09 | 0.00 | 0.67 |
March | 0.221838E+10 | 27656.35 | 0.00 | 2055346.03 | 2906176.20 | 0.141800E+09 | 0.121210E+10 | 0.00 | 0.72 |
April | 0.133880E+10 | 618931.38 | 0.00 | 5201228.56 | 2946638.63 | 14566280.60 | 0.221733E+10 | 0.00 | 0.95 |
May | 0.154303E+10 | 1451526.38 | 0.00 | 4876769.21 | 0.00 | 783826.69 | 0.214458E+10 | 0.00 | 0.95 |
June | 0.964961E+09 | 0.112248E+09 | 0.00 | 5633258.14 | 29366.35 | 0.00 | 0.167071E+10 | 0.00 | 1.11 |
July | 0.368313E+09 | 0.918711E+09 | 0.00 | 3815226.64 | 83977841.60 | 0.00 | 0.725024E+09 | 0.00 | 1.17 |
August | 0.303176E+09 | 0.134048E+10 | 0.00 | 2450174.10 | 97010957.57 | 0.00 | 0.460077E+09 | 0.00 | 1.25 |
September | 0.883058E+09 | 0.209161E+09 | 0.00 | 3419127.68 | 35844392.39 | 0.00 | 0.874239E+09 | 0.00 | 0.94 |
October | 0.995465E+09 | 0.320579E+09 | 0.00 | 2411777.55 | 0.122630E+09 | 16614549.56 | 0.657629E+09 | 0.00 | 0.79 |
November | 0.191490E+10 | 5030.60 | 0.00 | 1000505.51 | 2314409.10 | 63069327.26 | 0.849820E+09 | 0.00 | 0.68 |
December | 0.227248E+10 | 164157.94 | 0.00 | 481433.93 | 780178.97 | 0.166331E+09 | 0.225489E+09 | 0.00 | 0.64 |
Annual Sum or Average | 0.168895E+11 | 0.290423E+10 | 30247.18 | 33333128.22 | 0.356192E+09 | 0.791992E+09 | 0.122991E+11 | 730.19 | 0.88 |
Minimum of Months | 0.303176E+09 | 5030.60 | 0.00 | 481433.93 | 0.00 | 0.00 | 0.225489E+09 | 0.00 | 0.63 |
Maximum of Months | 0.227248E+10 | 0.134048E+10 | 30247.18 | 5633258.14 | 0.122630E+09 | 0.234191E+09 | 0.221733E+10 | 730.19 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120962E+10 | 31827650.40 | 0.00 | 12888762.99 | 91513.78 | 0.180429E+09 | 0.497242E+10 | 0.00 | 1.01 |
February | 0.146897E+10 | 1900063.86 | 0.00 | 7907071.46 | 1227887.43 | 0.143529E+09 | 0.367481E+10 | 0.00 | 0.86 |
March | 0.211998E+10 | 1464262.51 | 0.00 | 5842341.32 | 2128732.23 | 0.201817E+09 | 0.297504E+10 | 0.00 | 0.74 |
April | 0.171774E+10 | 306997.21 | 0.00 | 5715607.97 | 3771697.59 | 33860571.35 | 0.241514E+10 | 0.00 | 0.72 |
May | 0.200466E+10 | 1272027.05 | 0.00 | 3928327.97 | 0.00 | 14464859.30 | 0.183190E+10 | 0.00 | 0.63 |
June | 0.125520E+10 | 0.127127E+09 | 0.00 | 4015756.69 | 33193.86 | 0.00 | 0.140399E+10 | 0.00 | 0.71 |
July | 0.527255E+09 | 0.906701E+09 | 0.00 | 1995841.54 | 0.132499E+09 | 0.00 | 0.471745E+09 | 0.00 | 0.71 |
August | 0.357715E+09 | 0.137255E+10 | 0.00 | 2176702.65 | 0.188235E+09 | 0.00 | 0.388924E+09 | 0.00 | 0.87 |
September | 0.830199E+09 | 0.415526E+09 | 0.00 | 5956399.78 | 30793025.38 | 0.00 | 0.151322E+10 | 0.00 | 0.91 |
October | 0.866528E+09 | 0.835212E+09 | 0.00 | 8857249.78 | 60796061.12 | 319486.63 | 0.168773E+10 | 0.00 | 0.94 |
November | 0.123486E+10 | 3465959.08 | 0.00 | 12935749.61 | 662454.57 | 40607900.54 | 0.478055E+10 | 0.00 | 1.04 |
December | 0.120353E+10 | 4243158.68 | 0.00 | 14491931.61 | 0.00 | 0.119475E+09 | 0.434004E+10 | 0.00 | 1.02 |
Annual Sum or Average | 0.147962E+11 | 0.370159E+10 | 0.00 | 86711743.38 | 0.420238E+09 | 0.734503E+09 | 0.304555E+11 | 0.00 | 0.85 |
Minimum of Months | 0.357715E+09 | 306997.21 | 0.00 | 1995841.54 | 0.00 | 0.00 | 0.388924E+09 | 0.00 | 0.63 |
Maximum of Months | 0.211998E+10 | 0.137255E+10 | 0.00 | 14491931.61 | 0.188235E+09 | 0.201817E+09 | 0.497242E+10 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.222111E+10 | 4187734.68 | 0.00 | 1518236.54 | 4267711.23 | 0.291144E+09 | 0.882376E+09 | 0.00 | 0.76 |
February | 0.223312E+10 | 524760.98 | 0.00 | 1805132.44 | 1202850.73 | 0.133404E+09 | 0.116870E+10 | 0.00 | 0.83 |
March | 0.262422E+10 | 0.00 | 0.00 | 2777977.92 | 3238536.30 | 0.142669E+09 | 0.168486E+10 | 0.00 | 0.89 |
April | 0.154097E+10 | 2736132.99 | 0.00 | 6378298.39 | 1405918.81 | 18999559.28 | 0.273206E+10 | 0.00 | 1.12 |
May | 0.165233E+10 | 835464.92 | 0.00 | 6065431.94 | 0.00 | 1176120.02 | 0.277902E+10 | 0.00 | 1.12 |
June | 0.863563E+09 | 0.139986E+09 | 0.00 | 7337218.72 | 0.00 | 0.00 | 0.229969E+10 | 0.00 | 1.32 |
July | 0.327508E+09 | 0.115807E+10 | 0.00 | 4818557.12 | 85594126.96 | 0.00 | 0.869040E+09 | 0.00 | 1.32 |
August | 0.264913E+09 | 0.139556E+10 | 0.00 | 3117407.63 | 0.147367E+09 | 0.00 | 0.491613E+09 | 0.00 | 1.40 |
September | 0.837161E+09 | 0.229440E+09 | 0.00 | 4635812.87 | 56146503.73 | 0.00 | 0.126122E+10 | 0.00 | 1.12 |
October | 0.118719E+10 | 0.361713E+09 | 0.00 | 2698257.03 | 0.125909E+09 | 321248.51 | 0.703851E+09 | 0.00 | 0.92 |
November | 0.223537E+10 | 164576.48 | 0.00 | 2355418.31 | 2409490.72 | 64999916.90 | 0.122813E+10 | 0.00 | 0.85 |
December | 0.218603E+10 | 56252.74 | 0.00 | 1615629.67 | 967670.43 | 0.204729E+09 | 0.766834E+09 | 0.00 | 0.77 |
Annual Sum or Average | 0.181735E+11 | 0.329327E+10 | 0.00 | 45123378.60 | 0.428509E+09 | 0.857442E+09 | 0.168674E+11 | 0.00 | 1.04 |
Minimum of Months | 0.264913E+09 | 0.00 | 0.00 | 1518236.54 | 0.00 | 0.00 | 0.491613E+09 | 0.00 | 0.76 |
Maximum of Months | 0.262422E+10 | 0.139556E+10 | 0.00 | 7337218.72 | 0.147367E+09 | 0.291144E+09 | 0.277902E+10 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.501894E+09 | 0.00 | 0.00 | 0.284284E+12 | 0.00 | 13.49 |
February | 0.00 | 0.00 | 0.00 | 0.810506E+09 | 0.00 | 0.00 | 0.414106E+12 | 0.00 | 20.90 |
March | 0.00 | 0.00 | 0.00 | 0.138753E+10 | 0.00 | 0.00 | 0.613096E+12 | 0.00 | 27.95 |
April | 0.00 | 99974540.99 | 0.00 | 0.215107E+10 | 0.00 | 0.00 | 0.463227E+12 | 0.00 | 31.69 |
May | 0.00 | 0.00 | 0.00 | 0.539499E+09 | 0.00 | 0.00 | 0.320164E+12 | 0.00 | 18.83 |
June | 0.00 | 0.178110E+09 | 0.00 | 0.113341E+10 | 0.00 | 0.00 | 0.464617E+12 | 0.00 | 34.67 |
July | 0.00 | 0.273430E+11 | 0.00 | 0.189914E+10 | 0.00 | 0.00 | 0.353549E+12 | 0.00 | 41.66 |
August | 0.00 | 0.322641E+11 | 0.00 | 0.203867E+10 | 0.00 | 0.00 | 0.143309E+12 | 0.00 | 42.12 |
September | 0.00 | 0.426861E+09 | 0.00 | 0.569090E+09 | 0.00 | 0.00 | 0.294419E+12 | 0.00 | 22.98 |
October | 0.00 | 0.175538E+10 | 0.00 | 0.111077E+10 | 0.00 | 0.00 | 0.400702E+12 | 0.00 | 29.17 |
November | 0.00 | 0.00 | 0.00 | 0.168366E+10 | 0.00 | 0.00 | 0.625589E+12 | 0.00 | 30.54 |
December | 0.00 | 0.00 | 0.00 | 0.219868E+10 | 0.00 | 0.00 | 0.703447E+12 | 0.00 | 31.62 |
Annual Sum or Average | 0.00 | 0.620674E+11 | 0.00 | 0.160239E+11 | 0.00 | 0.00 | 0.508051E+13 | 0.00 | 28.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.501894E+09 | 0.00 | 0.00 | 0.143309E+12 | 0.00 | 13.49 |
Maximum of Months | 0.00 | 0.322641E+11 | 0.00 | 0.219868E+10 | 0.00 | 0.00 | 0.703447E+12 | 0.00 | 42.12 |