Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:58
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2020-06-03 19:58:48
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 26722.50 | 576.91 | 576.91 |
Net Site Energy | 26722.50 | 576.91 | 576.91 |
Total Source Energy | 81376.73 | 1756.82 | 1756.82 |
Net Source Energy | 81376.73 | 1756.82 | 1756.82 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 969.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1353.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3187.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 348.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1955.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2076.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 461.68 | 0.00 | 0.00 | 0.00 | 0.00 | 2035.84 |
Humidification | 880.75 | 0.00 | 0.00 | 0.00 | 0.00 | 327.64 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 592.25 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 25160.60 | 1561.90 | 0.00 | 0.00 | 0.00 | 4643.64 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 969.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 412.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 941.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Lighting | LightsWired | 3187.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 348.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 55.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1895.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2076.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 31.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 429.83 | 0.00 | 0.00 | 0.00 | 0.00 | 2035.84 | |
Humidification | General | 880.75 | 0.00 | 0.00 | 0.00 | 0.00 | 327.64 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 592.25 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 76.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 107.77 | 33.72 | 0.00 | 0.00 | 0.00 | 0.10 |
Other | 359.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 543.19 | 33.72 | 0.00 | 0.00 | 0.00 | 0.10 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 76.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 107.77 | 33.72 | 0.00 | 0.00 | 0.00 | 0.10 |
Other | 359.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 543.19 | 33.72 | 0.00 | 0.00 | 0.00 | 0.10 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 25160.604 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 25160.604 | 100.00 |
Total On-Site and Utility Electric Sources | 25160.604 | 100.00 |
Total Electricity End Uses | 25160.604 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 4643.64 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 4643.64 | 100.00 |
Total Water End Uses | 4643.64 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 20.50 |
Time Setpoint Not Met During Occupied Cooling | 79.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1664.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | DUMMY BOILER |DXReportMonthly
| CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SHWSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| DATACENTER_EXTRAWATERHEATC | CORE_BOTTOM VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS_HEATC | VAV_BOT WITH REHEAT_HEATC | VAV_MID WITH REHEAT_HEATC | VAV_TOP WITH REHEAT_HEATC | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | DATACENTER_EXTRAELECHEATC | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |PlantLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | DATACENTER BASEMENT SUPPLY FAN | DATACENTER BOT SUPPLY FAN | DATACENTER MID SUPPLY FAN | DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SHWSYS1 PUMP | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:58 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 8.5035 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.5035 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.5035 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.5035 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.5035 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.5035 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.5035 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.5035 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.5035 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.5035 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.5035 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.5035 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.5035 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.5035 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.5035 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.5035 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.5035 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.5035 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.5035 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 8.5035 | 484.4232 | |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.5035 | 19.08 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.5035 | 19.08 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-AUG-15:09 | 02-JAN-05:19 | - | - | - | 10-AUG-15:00 |
Heating | 0.00 | 1406716.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 407473.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 276093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 89246.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 140767.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 32158.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 79389.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7280.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1803500.90 | 1413997.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 1406716.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 238025.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 276093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3428.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 85555.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 140767.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 32158.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 30141.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 7280.88 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1051.10 | 0.00 | 0.00 | 0.00 |
Cooling | 4287.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10095.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1104.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46479.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6194.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6576.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 694.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1462.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 2789.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 642.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 79683.63 | 1693.10 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 22.69 | 0.00 | 0.00 | 0.00 |
Cooling | 92.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 217.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 133.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 141.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 14.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 31.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 60.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.86 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1720.27 | 36.55 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 22.69 | 0.00 | 0.00 | 0.00 |
Cooling | 92.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 217.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 133.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 141.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 14.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 31.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 60.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.86 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1720.27 | 36.55 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.56 |
DATACENTER BOT DIRECT AIR | 0.497179 |
DATACENTER MID DIRECT AIR | 4.76 |
DATACENTER TOP DIRECT AIR | 0.483298 |
DATACENTER BASEMENT DIRECT AIR | 21.52 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.77 | 0.329443 | 0.329000 | 1.90 | 0.878514 | 0.500000 | 0.001156 | 0.000417 | 1.90 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 54.06 | 0.351861 | 0.343000 | 18.54 | 0.938295 | 0.500000 | 0.001083 | 0.008218 | 18.54 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.24 | 0.363309 | 0.359000 | 1.88 | 0.968824 | 0.500000 | 0.001049 | 0.001480 | 2.02 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.768890 | 0.310604 | 0.311000 | 0.239125 | 0.828278 | 0.500000 | 0.001227 | 0.000145 | 0.239125 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.23 | 0.125394 | 0.200000 | 0.245474 | 0.334385 | 0.500000 | 0.003038 | 0.000125 | 0.245474 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.47 | 0.162863 | 0.200000 | 0.293285 | 0.434301 | 0.500000 | 0.002339 | 0.000201 | 0.293285 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.47 | 0.104907 | 0.200000 | 0.293411 | 0.300000 | 0.500000 | 0.003632 | 0.000102 | 0.293411 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 6.81 | 0.350760 | 0.342000 | 2.33 | 0.935360 | 0.500000 | 0.001086 | 0.003590 | 4.91 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 12.67 | 0.121430 | 0.200000 | 2.53 | 0.323814 | 0.500000 | 0.003138 | 0.002401 | 3.29 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 14.90 | 0.160266 | 0.200000 | 2.98 | 0.427376 | 0.500000 | 0.002377 | 0.003583 | 4.90 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 13.27 | 0.115998 | 0.200000 | 2.65 | 0.309329 | 0.500000 | 0.003285 | 0.002201 | 3.01 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.773950 | 0.308574 | 0.305000 | 0.236055 | 0.822863 | 0.500000 | 0.001235 | 0.000459 | 0.628680 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.25 | 0.122704 | 0.200000 | 0.250857 | 0.327210 | 0.500000 | 0.003105 | 0.000304 | 0.416683 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.58 | 0.151512 | 0.200000 | 0.315256 | 0.404033 | 0.500000 | 0.002515 | 0.000458 | 0.626865 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.39 | 0.111027 | 0.200000 | 0.277239 | 0.300000 | 0.500000 | 0.003432 | 0.000287 | 0.392789 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18852.77 | 0.000417 | 328.14 |
CORE_MID VAV BOX REHEAT COIL | 371948.94 | 0.008218 | 6999.43 |
CORE_TOP VAV BOX REHEAT COIL | 66990.26 | 0.001480 | 1399.05 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6543.71 | 0.000145 | 130.01 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5656.28 | 0.000125 | 108.71 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9086.02 | 0.000201 | 186.07 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4622.63 | 0.000102 | 84.65 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 162491.59 | 0.003590 | 3390.43 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 108684.14 | 0.002401 | 2267.66 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 162180.63 | 0.003583 | 3383.95 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 99633.96 | 0.002201 | 2078.95 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 20781.47 | 0.000459 | 433.54 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13772.92 | 0.000304 | 287.32 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 20721.62 | 0.000458 | 432.29 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12984.57 | 0.000287 | 270.89 |
CAV_BAS_HEATC | 271361.41 | 0.005995 | 5012.66 |
VAV_BOT WITH REHEAT_HEATC | 52612.27 | 0.001162 | 760.54 |
VAV_MID WITH REHEAT_HEATC | 512064.09 | 0.011313 | 7348.48 |
VAV_TOP WITH REHEAT_HEATC | 50825.36 | 0.001123 | 733.99 |
DATACENTER_EXTRAWATERHEATC | 1028640.65 | 0.022727 | 19136.89 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
CAV_BAS | 5.56 | 5.56 | 5.56 | 5.56 | 5.56 | 5.56 | 1.00 | 1.00 | 5.56 |
VAV_BOT WITH REHEAT | 5.35 | 2.97 | 10.70 | 2.97 | 9.13 | 9.13 | 0.300000 | 0.325364 | 9.13 |
VAV_MID WITH REHEAT | 50.85 | 29.04 | 101.71 | 29.04 | 84.18 | 84.18 | 0.300000 | 0.344967 | 84.18 |
VAV_TOP WITH REHEAT | 5.11 | 2.96 | 10.23 | 4.08 | 8.76 | 8.76 | 0.300000 | 0.466365 | 8.76 |
AIRLOOP DATACENTER BASEMENT | 21.52 | 21.52 | 21.52 | 21.52 | 21.52 | 21.52 | 1.00 | 1.00 | 21.52 |
AIRLOOP DATACENTER BOT | 0.497179 | 0.497179 | 0.497179 | 0.497179 | 0.497179 | 0.497179 | 1.00 | 1.00 | 0.497179 |
AIRLOOP DATACENTER MID | 4.76 | 4.76 | 4.76 | 4.76 | 4.76 | 4.76 | 1.00 | 1.00 | 4.76 |
AIRLOOP DATACENTER TOP | 0.483298 | 0.483298 | 0.483298 | 0.483298 | 0.483298 | 0.483298 | 1.00 | 1.00 | 0.483298 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
CAV_BAS_OA_CONTROLLER | 5.56 | 1.20 |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.13 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 84.18 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 8.76 | |
AIRLOOP DATACENTER BASEMENT OA CONTROLLER | 21.52 | 0.338372 |
AIRLOOP DATACENTER BOT OA CONTROLLER | 0.497179 | |
AIRLOOP DATACENTER MID OA CONTROLLER | 4.76 | |
AIRLOOP DATACENTER TOP OA CONTROLLER | 0.483298 |
Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | |
CAV_BAS_COOLC | 98927.73 | 0.002829 | 5.56 | 0.008948 | 24.97 | 6.67 | 11.40 | 0.008398 |
VAV_BOT WITH REHEAT_COOLC | 170926.32 | 0.004888 | 9.13 | 0.008847 | 25.60 | 6.67 | 11.40 | 0.008398 |
VAV_MID WITH REHEAT_COOLC | 1611057.81 | 0.046076 | 84.18 | 0.008873 | 25.78 | 6.67 | 11.40 | 0.008398 |
VAV_TOP WITH REHEAT_COOLC | 163458.78 | 0.004675 | 8.76 | 0.008843 | 25.57 | 6.67 | 11.40 | 0.008398 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.56 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
CAV_BAS_COOLC_CONTROLLER | 0.002829 | 0.000168 |
CAV_BAS_HEATC_CONTROLLER | 0.005995 | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.004888 | 0.000097 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.001162 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.046076 | 0.000010 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.011313 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.004675 | 0.000102 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.001123 | |
DATACENTER_BAS_HEATC_CONTROLLER | 0.022727 | 0.000021 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.13 |
VAV_MID WITH REHEAT FAN | 84.18 |
VAV_TOP WITH REHEAT FAN | 8.76 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | 21.52 | 423781.17 | 303777.32 | 0.010378 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | 0.497179 | 9505.35 | 6917.29 | 0.000233 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | 4.76 | 91085.73 | 66286.98 | 0.002231 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | 0.483298 | 9243.86 | 6725.48 | 0.000226 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.52 | 21.52 | 21.52 | 21.52 | 423781.17 | 423781.17 | 17838.92 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.497179 | 0.497179 | 0.497179 | 0.497179 | 9505.35 | 9505.35 | 824.08 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.76 | 4.76 | 4.76 | 4.76 | 91085.73 | 91085.73 | 8240.84 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.483298 | 0.483298 | 0.483298 | 0.483298 | 9243.86 | 9243.86 | 824.08 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
DATACENTER BASEMENT SUPPLY FAN | 21.52 |
DATACENTER BOT SUPPLY FAN | 0.497179 |
DATACENTER MID SUPPLY FAN | 4.76 |
DATACENTER TOP SUPPLY FAN | 0.483298 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | 21.52 | 423781.17 | 0.010378 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | 0.497179 | 9505.35 | 0.000233 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | 4.76 | 91085.73 | 0.002231 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | 0.483298 | 9243.86 | 0.000226 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | 17838.92 | |
DATACENTER_EXTRAELECHEATC | 423781.17 | 10000000.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | 824.08 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | 8240.84 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | 824.08 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER BASEMENT HUMIDIFIER | 0.000143 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.058469 | 11184.34 |
HEATSYS1 PUMP | 0.066291 | 16936.60 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.058469 | 7.02 |
SHWSYS1 | 0.000440 | 0.052800 |
HEATSYS1 | 0.066291 | 7.95 |
COOLSYS1_SUPPLY | 0.058469 | 7.02 |
SINGLE WATER PLANT LOOP | 0.013068 | 1.57 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.058469 | 0.058469 | 245422.65 | 8.33 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SHWSYS1 PUMP | 0.000440 | 56.21 |
COOLSYS1 CHILLER1 PUMP | 0.029234 | 1864.06 |
COOLSYS1 CHILLER2 PUMP | 0.029234 | 1864.06 |
PLANT CIRC PUMP | 0.013068 | 3333.05 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000440 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3000455.28 | 1500227.64 | 0.066291 |
DUMMY BOILER | 538298.80 | 93894.07 | 0.013068 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.058469 | 0.029446 | 1030729.23 | 1037003.00 | 0.052574 |
COOLSYS1 CHILLER2 | 0.058469 | 0.029446 | 1030729.23 | 1037003.00 | 0.052574 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013068 | 139666.47 | 60218.25 | 69833.23 | 7879.72 | 21506.24 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.105148 | 12.62 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.105148 | 22251.26 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 40.24 | 985532.85 | 8.05 | 123191.61 |
TOWERWATERSYS COOLTOWER 2 | 40.24 | 985532.85 | 8.05 | 123191.61 |
Design Water Flow Rate [m3/s] Equipment # 48 | |
WSHPPLANT OPERATION SCHEME | 0.042642 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 8.503 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.345 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.503 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.573 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 8.503 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 223.803 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 8.503 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 223.803 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 8.503 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 223.803 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | N/A | 0.000 | 8.503 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 492.927 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_SCH | BASEMENT | 2779.43 | 149.6 | 23634.824 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23634.824 |
2 | CORE_BOTTOM_LIGHTS | BLDG_LIGHT_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 21225.733 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21225.733 |
3 | CORE_MID_LIGHTS | BLDG_LIGHT_SCH | CORE_MID | 2496.12 | 134.4 | 21225.733 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21225.733 |
4 | CORE_TOP_LIGHTS | BLDG_LIGHT_SCH | CORE_TOP | 2496.12 | 134.4 | 21225.733 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21225.733 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2665.103 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2665.103 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1717.494 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1717.494 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2665.161 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2665.161 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1717.494 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1717.494 |
9 | PERIMETER_MID_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2665.103 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2665.103 |
10 | PERIMETER_MID_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1717.494 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1717.494 |
11 | PERIMETER_MID_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2665.161 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2665.161 |
12 | PERIMETER_MID_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1717.494 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1717.494 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2665.103 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2665.103 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1717.494 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1717.494 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2665.161 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2665.161 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1717.494 | 8.503 | 157.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1717.494 |
17 | DATACENTER_BASEMENT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 6664.009 | 8.503 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6664.009 |
18 | DATACENTER_BOT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 307.850 | 8.503 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 307.850 |
19 | DATACENTER_MID_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 307.850 | 8.503 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 307.850 |
20 | DATACENTER_TOP_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 307.850 | 8.503 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 307.850 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 379632.522 | 484.423 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL | 20 | 3 | 9 | 0.167 | 0.6478 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_EAST_CFACTOR | 30 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_SOUTH_CFACTOR | 31 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_NORTH_CFACTOR | 32 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 34 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 35 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.376 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1010000 | 2.1010000 | 2.1010000 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | 0.49119318E-15 | -0.33550344E-15 | -0.16284357E-09 | -0.12303907E-16 |
51 | 8 | 0.23714982E-07 | 0.88106564E-13 | 0.39686193E-03 | -0.26964751E-09 |
52 | 7 | -0.12809687E-01 | 0.44996568E-08 | -0.23903550E-01 | 0.14565082E-03 |
53 | 6 | 0.42078637 | 0.15559313E-05 | 0.48521577 | -0.49297162E-02 |
54 | 5 | -5.3411857 | 0.57794581E-04 | -4.5419698 | 0.65051509E-01 |
55 | 4 | 33.669005 | 0.47055528E-03 | 21.833772 | -0.43096765 |
56 | 3 | -112.64328 | 0.10212385E-02 | -56.401742 | 1.5356680 |
57 | 2 | 198.53538 | 0.57229644E-03 | 78.588493 | -2.9230166 |
58 | 1 | -171.68312 | 0.60883279E-04 | -55.462911 | 2.7546764 |
59 | 0 | 57.057407 | 0.34515708E-06 | 15.524833 | |
60 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
61 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
62 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
63 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
64 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
65 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
66 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
67 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
68 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
69 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
70 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
71 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
72 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
73 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
74 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
75 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
76 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
77 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
78 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
79 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
80 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
81 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
82 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
83 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
84 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
85 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
86 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
87 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
88 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
89 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
90 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
91 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
92 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
93 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
94 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
95 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
96 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
97 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
98 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
99 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
100 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
101 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
102 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
103 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
104 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
105 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
106 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
107 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.38_SHGC_0.36 | 29 | 1 | VerySmooth | 2.159 | 0.355 | 0.274 | 0.397 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.741E-005 | 4.376E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 76148.77613 | 76148.77613 | 5.56168 | 5.56168 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20008 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20000 | 2.69032E-003 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 79057.24189 | 79057.24189 | 5.77352 | 5.77352 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07776 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 | |
5 | CORE_MID | Cooling | 740411.98314 | 740411.98314 | 54.05674 | 54.05674 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
6 | CORE_MID | Heating | 187921.53765 | 187921.53765 | 7.99023 | 10.77757 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
7 | CORE_TOP | Cooling | 71713.86227 | 71713.86227 | 5.23534 | 5.23534 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
8 | CORE_TOP | Heating | 46947.58333 | 46947.58333 | 2.01938 | 2.01938 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 10431.76105 | 10431.76105 | 0.76889 | 0.76889 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 29.40000 | 8.79438E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 4178.78657 | 4178.78657 | 0.17918 | 0.17918 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 16652.44964 | 16652.44964 | 1.22737 | 1.22737 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 22.36267 | 8.79438E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 3227.37584 | 3227.37584 | 0.13864 | 0.13864 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 19895.55908 | 19895.55908 | 1.46642 | 1.46642 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 28.88000 | 8.79438E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 6182.01535 | 6182.01535 | 0.26601 | 0.26601 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 19904.25224 | 19904.25224 | 1.46706 | 1.46706 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 27.77067 | 8.79438E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 1725.43494 | 1725.43494 | 7.36312E-002 | 8.72074E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 92374.98601 | 92374.98601 | 6.80866 | 6.80866 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 29.40000 | 8.79438E-003 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 113769.68493 | 113769.68493 | 4.91301 | 4.91301 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 171958.54889 | 171958.54889 | 12.67434 | 12.67434 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 23.02133 | 8.79438E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 76091.20584 | 76091.20584 | 3.28642 | 3.28642 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 202179.22809 | 202179.22809 | 14.90184 | 14.90184 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 28.96667 | 8.79438E-003 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 113552.40608 | 113552.40608 | 4.90359 | 4.90359 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 180010.98611 | 180010.98611 | 13.26785 | 13.26785 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 27.59733 | 8.79438E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 69766.97783 | 69766.97783 | 3.01217 | 3.01217 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 10500.40999 | 10500.40999 | 0.77395 | 0.77395 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.79438E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 14545.20986 | 14545.20986 | 0.62868 | 0.62868 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 17017.40828 | 17017.40828 | 1.25428 | 1.25428 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 23.02133 | 8.79438E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 9639.54422 | 9639.54422 | 0.41668 | 0.41668 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 21386.04391 | 21386.04391 | 1.57628 | 1.57628 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.79438E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 14503.37459 | 14503.37459 | 0.62687 | 0.62687 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 18807.13838 | 18807.13838 | 1.38619 | 1.38619 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 27.77067 | 8.79438E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 9088.47750 | 9088.47750 | 0.39279 | 0.39279 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8553.06580 | 8553.06580 | 0.49718 | 0.49718 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 25.60400 | 8.79438E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20000 | 2.69032E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 81964.12819 | 81964.12819 | 4.76448 | 4.76448 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 25.60400 | 8.79438E-003 | 36.20274 | 0.00000 | 0.15631 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15631 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20000 | 2.69032E-003 | 36.20274 | 0.00000 | 0.15631 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8314.27033 | 8314.27033 | 0.48330 | 0.48330 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 25.86400 | 8.79438E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20000 | 2.69032E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370291.60322 | 370291.60322 | 21.52460 | 21.52460 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:00:00 | 19.20800 | 8.79438E-003 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33837 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20000 | 2.69032E-003 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | CAV_BAS | Cooling | Sensible | 72959.26 | 5.56168 | 5.56168 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | CAV_BAS | Heating | Sensible | 63268.17 | 1.20008 | 1.20008 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | VAV_BOT WITH REHEAT | Cooling | Sensible | 130645.39 | 9.13064 | 9.13064 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_BOT WITH REHEAT | Heating | Sensible | 35460.03 | 1.74879 | 1.74879 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
5 | VAV_MID WITH REHEAT | Cooling | Sensible | 1190622.12 | 84.17863 | 84.17863 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_MID WITH REHEAT | Heating | Sensible | 514302.62 | 26.89276 | 26.89276 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:40:00 |
7 | VAV_TOP WITH REHEAT | Cooling | Sensible | 133147.19 | 8.75794 | 8.75794 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
8 | VAV_TOP WITH REHEAT | Heating | Sensible | 51432.65 | 4.08439 | 4.08439 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 364983.39 | 21.52460 | 21.52460 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 17838.92 | 0.33837 | 0.33837 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8394.78 | 0.49718 | 0.49718 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 824.08 | 1.56314E-002 | 1.56314E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 80436.42 | 4.76448 | 4.76448 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8240.84 | 0.15631 | 0.15631 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8164.52 | 0.48330 | 0.48330 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 824.08 | 1.56314E-002 | 1.56314E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.56168 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.77352 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32944 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32900 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.89949 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87851 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.15650E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.16529E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.89949 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18852.77090 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.16529E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 328.13733 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 54.05674 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35186 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34300 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.54146 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93830 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08282E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.21776E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.54146 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 371948.94316 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.21776E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6999.43167 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.23534 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36331 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35900 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.87949 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96882 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04869E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.48007E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.01938 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 66990.25828 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.48007E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1399.04792 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76889 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31060 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31100 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23912 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82828 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.22664E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.44575E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23912 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6543.71328 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.44575E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 130.00946 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.22737 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12539 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24547 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33439 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.03841E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.24969E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24547 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5656.27689 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.24969E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 108.70568 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.46642 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16286 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29328 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43430 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.33939E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.00745E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29328 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9086.02108 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.00745E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 186.07236 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.46706 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10491 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29341 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.63177E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02131E-004 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29341 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4622.62800 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02131E-004 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 84.65182 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.80866 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35076 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34200 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.32856 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93536 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08621E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.59005E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.91301 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 162491.59436 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.59005E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3390.42969 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.67434 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12143 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.53487 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32381 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.13760E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.40124E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.28642 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 108684.13917 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.40124E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2267.66040 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.90184 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16027 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.98037 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42738 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.37730E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.58318E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.90359 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 162180.62680 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.58318E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3383.94655 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.26785 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11600 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.65357 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30933 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.28453E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.20129E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.01217 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 99633.95636 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.20129E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2078.95423 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77395 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30857 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30500 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23605 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82286 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.23471E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.59141E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.62868 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20781.47136 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.59141E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 433.53960 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.25428 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12270 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25086 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32721 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.10504E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.04296E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41668 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13772.91588 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.04296E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 287.32309 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.57628 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15151 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31526 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40403 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.51465E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.57819E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.62687 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20721.61560 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.57819E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 432.29174 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.38619 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11103 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27724 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.43160E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.86878E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39279 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12984.56712 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.86878E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 270.88603 |
212 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BOT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49718 |
213 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER MID DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.76448 |
214 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER TOP DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48330 |
215 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.52460 |
216 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.56168 |
217 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.56168 |
218 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.56168 |
219 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.56168 |
220 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.56168 |
221 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.56168 |
222 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
223 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.35163 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.97078 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.70326 |
227 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.97078 |
228 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.13064 |
229 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.13064 |
230 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32536 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 50.85472 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 29.03883 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 101.70943 |
235 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 29.03883 |
236 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 84.17863 |
237 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 84.17863 |
238 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.34497 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.11302 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.95889 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.22604 |
243 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.08439 |
244 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.75794 |
245 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.75794 |
246 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
247 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.46636 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.52460 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.52460 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.52460 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.52460 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.52460 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.52460 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49718 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49718 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49718 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49718 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49718 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.49718 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.76448 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.76448 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.76448 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.76448 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.76448 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.76448 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48330 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48330 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48330 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48330 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48330 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.48330 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.56168 |
281 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.13064 |
282 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 84.17863 |
283 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.75794 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.52460 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.49718 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.76448 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.48330 |
288 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.56168 |
289 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20008 |
290 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Coil Load [W] | 98927.72790 |
291 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 2.82932E-003 |
292 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 5.56168 |
293 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.94772E-003 |
294 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Temperature [C] | 24.96513 |
295 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
296 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Temperature [C] | 11.40150 |
297 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.39822E-003 |
298 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Rated Capacity [W] | 271361.41444 |
299 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 5.99540E-003 |
300 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 5012.66427 |
301 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.56168 |
302 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.82932E-003 |
303 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.68306E-004 |
304 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.99540E-003 |
305 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.13064 |
306 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 170926.32330 |
307 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 4.88847E-003 |
308 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 9.13064 |
309 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.84742E-003 |
310 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 25.60088 |
311 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
312 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.40124 |
313 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.39822E-003 |
314 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 52612.27283 |
315 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 1.16240E-003 |
316 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 760.53944 |
317 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.13064 |
318 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.88847E-003 |
319 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.74109E-005 |
320 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.16240E-003 |
321 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 84.17863 |
322 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 1611057.81418 |
323 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 4.60760E-002 |
324 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 84.17863 |
325 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.87277E-003 |
326 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 25.78153 |
327 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
328 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.40131 |
329 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.39822E-003 |
330 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 512064.08783 |
331 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 1.13134E-002 |
332 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 7348.48302 |
333 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 84.17863 |
334 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.60760E-002 |
335 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.03349E-005 |
336 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.13134E-002 |
337 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.75794 |
338 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 163458.78003 |
339 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 4.67490E-003 |
340 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 8.75794 |
341 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.84266E-003 |
342 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 25.56656 |
343 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
344 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.40123 |
345 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.39822E-003 |
346 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 50825.35561 |
347 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 1.12292E-003 |
348 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 733.99200 |
349 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.75794 |
350 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.67490E-003 |
351 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.01861E-004 |
352 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.12292E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.52460 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33837 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.52460 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Total Cooling Capacity [W] | 423781.16691 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Sensible Cooling Capacity [W] | 303777.32062 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.03784E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.52460 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.52460 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.52460 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.52460 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 423781.16691 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 423781.16691 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 17838.91681 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.52460 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.52460 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Heating Capacity [W] | 423781.16691 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.03784E-002 |
371 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Design Size Nominal Capacity [W] | 17838.91681 |
372 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.43002E-004 |
373 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | Design Size Nominal Capacity [W] | 423781.16691 |
377 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | User-Specified Nominal Capacity [W] | 10000000.00000 |
378 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Rated Capacity [W] | 1028640.65213 |
379 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Maximum Water Flow Rate [m3/s] | 2.27266E-002 |
380 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size U-Factor Times Area Value [W/K] | 19136.89091 |
381 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.27266E-002 |
382 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Controller Convergence Tolerance | 2.09530E-005 |
383 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49718 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.49718 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Total Cooling Capacity [W] | 9505.35104 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Sensible Cooling Capacity [W] | 6917.29446 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.32785E-004 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49718 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49718 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49718 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49718 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9505.35104 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9505.35104 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 824.08405 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
396 | Fan:OnOff | DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49718 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.49718 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Heating Capacity [W] | 9505.35104 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.32785E-004 |
400 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Design Size Nominal Capacity [W] | 824.08405 |
401 | Controller:OutdoorAir | AIRLOOP DATACENTER MID OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.76448 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.76448 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Total Cooling Capacity [W] | 91085.73166 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Sensible Cooling Capacity [W] | 66286.97936 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.23068E-003 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.76448 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.76448 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.76448 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.76448 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 91085.73166 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 91085.73166 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8240.84054 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
414 | Fan:OnOff | DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.76448 |
415 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.76448 |
416 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Heating Capacity [W] | 91085.73166 |
417 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.23068E-003 |
418 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Design Size Nominal Capacity [W] | 8240.84054 |
419 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48330 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.48330 |
421 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Total Cooling Capacity [W] | 9243.86193 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Sensible Cooling Capacity [W] | 6725.47602 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.26382E-004 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.48330 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.48330 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.48330 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.48330 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9243.86193 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9243.86193 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 824.08405 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
432 | Fan:OnOff | DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48330 |
433 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.48330 |
434 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Heating Capacity [W] | 9243.86193 |
435 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.26382E-004 |
436 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Design Size Nominal Capacity [W] | 824.08405 |
437 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 5.84687E-002 |
438 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 11184.33976 |
439 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 5.84687E-002 |
440 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 7.01625 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 5.84687E-002 |
442 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 5.84687E-002 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 245422.64651 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
445 | PlantLoop | SHWSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
446 | PlantLoop | SHWSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
447 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
448 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Power Consumption [W] | 56.20535 |
449 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
450 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 6.62914E-002 |
451 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 7.95497 |
452 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 6.62914E-002 |
453 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 16936.60086 |
454 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3000455.28108 |
455 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1500227.64000 |
456 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 6.62914E-002 |
457 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 5.84687E-002 |
458 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 7.01625 |
459 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 2.92344E-002 |
460 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 1864.05663 |
461 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 2.92344E-002 |
462 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 1864.05663 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.84687E-002 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.94458E-002 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1030729.23414 |
466 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1037003.00000 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.25738E-002 |
468 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.84687E-002 |
469 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.94458E-002 |
470 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1030729.23414 |
471 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1037003.00000 |
472 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.25738E-002 |
473 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.30682E-002 |
474 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.56819 |
475 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.30682E-002 |
476 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3333.05069 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.30682E-002 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 60218.25280 |
480 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
481 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
482 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21506.23625 |
483 | Boiler:HotWater | DUMMY BOILER | Design Size Nominal Capacity [W] | 538298.80364 |
484 | Boiler:HotWater | DUMMY BOILER | User-Specified Nominal Capacity [W] | 93894.07000 |
485 | Boiler:HotWater | DUMMY BOILER | Design Size Design Water Flow Rate [m3/s] | 1.30682E-002 |
486 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10515 |
487 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.61772 |
488 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10515 |
489 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 22251.26089 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 40.23864 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 985532.84916 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 8.04773 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 123191.60614 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 40.23864 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 985532.84916 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 8.04773 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 123191.60614 |
498 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 4.26420E-002 |
499 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 4.26420E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 17886.01 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 353120.87 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 63560.77 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6210.31 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5369.33 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8621.47 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4389.79 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 154173.42 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 103120.46 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 153878.37 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 94533.55 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19717.65 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13067.87 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 19660.86 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12319.87 |
16 | Coil:Heating:Water | CAV_BAS_HEATC | 215599.37 |
17 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | 40544.69 |
18 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | 390507.38 |
19 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | 39113.81 |
20 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | 825837.88 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | CAV_BAS_COOLC | 138072.37 | 97951.17 | 40121.19 | 0.71 | 37826.39 | 383.66 |
2 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | 233757.93 | 163689.21 | 70068.72 | 0.70 | 62352.58 | 632.41 |
3 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | 2180811.84 | 1519617.50 | 661194.34 | 0.70 | 571388.36 | 5795.34 |
4 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | 223968.22 | 156907.95 | 67060.27 | 0.70 | 60111.89 | 609.69 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.67 | 22.78 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.67 | 22.78 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 25 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.4061658635 | 0.4594099447 | Pass | Pass | 2.9310074566 | 5.4171056409 | Pass | Fail |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.0776728520E-003 | 5.5822203639E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.3329115907E-002 | 3.4571685132E-002 | Pass | Pass | 0.3331114696 | 0.4722061330 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.7917788966E-002 | 1.2407256596E-002 | Pass | Pass | 0.5124898826 | 0.6429051670 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.6209520667E-002 | 1.4446212606E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.7243806310E-002 | 1.5736809090E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 1.5246483740E-002 | 1.5619711595E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.6784556526E-002 | 1.4666275792E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1368545944 | 0.1595122557 | Pass | Fail | 16.1035423360 | 104.6081663787 | Fail | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1518038648 | 0.1773431429 | Pass | Fail | 37.3377337555 | 386.9147328068 | Fail | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1362047363 | 0.1588208319 | Pass | Fail | 30.2430189302 | 294.3427128181 | Fail | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.9984901095E-002 | 6.0283637043E-002 | Pass | Pass | 6.8566671076 | 28.5216035844 | Fail | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2501410019 | 0.2490103439 | Pass | Fail | 8.6374590338 | 24.2713092087 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2688663661 | 0.2639722100 | Pass | Fail | 6.7516733811 | 18.0177673875 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2515495259 | 0.2498123276 | Pass | Fail | 7.4505390099 | 20.1842497480 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1507596826 | 0.1703850152 | Pass | Fail | 6.1523079196 | 17.4738422476 | Fail | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.3118976209E-003 | 4.9382757506E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.0563323972E-002 | 1.7083758039E-002 | Pass | Pass | 0.3891419042 | 0.5566583139 | Fail | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.6088372788E-002 | 4.9256090590E-002 | Pass | Pass | 0.4583625110 | 0.4820236326 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.1464311809E-014 | 1.9722427961E-014 | Pass | Pass | 1.5364180575E-003 | 1.1796819364E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.7473883062E-003 | 4.3972977571E-003 | Pass | Pass | 1.9137494233E-003 | 2.2126484099E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.5786872230E-003 | 4.3218348202E-003 | Pass | Pass | 2.2344271510E-003 | 2.3337688901E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 9.5951911844E-004 | 7.1593400764E-004 | Pass | Pass | 8.7500949873E-005 | 7.9868882710E-005 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S | |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.38_SHGC_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.355 | 0.397 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.38_SHGC_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.355 | 0.397 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.38_SHGC_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.355 | 0.397 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.38_SHGC_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.355 | 0.397 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.38_SHGC_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.355 | 0.397 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.38_SHGC_0.36 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.355 | 0.397 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.38_SHGC_0.36 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.355 | 0.397 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.38_SHGC_0.36 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.355 | 0.397 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.38_SHGC_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.355 | 0.397 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.38_SHGC_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.355 | 0.397 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.38_SHGC_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.355 | 0.397 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.38_SHGC_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.355 | 0.397 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.38_SHGC_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.355 | 0.397 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.38_SHGC_0.36 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.355 | 0.397 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.38_SHGC_0.36 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.355 | 0.397 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.38_SHGC_0.36 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.355 | 0.397 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_0.36 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.159 | 0.355 | 0.397 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_0.36 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.159 | 0.355 | 0.397 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_0.36 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.159 | 0.355 | 0.397 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_0.36 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.159 | 0.355 | 0.397 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_0.36 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.159 | 0.355 | 0.397 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_0.36 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.159 | 0.355 | 0.397 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_0.36 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.159 | 0.355 | 0.397 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_0.36 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.159 | 0.355 | 0.397 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
Total or Average | 4635.80 | 2.159 | 0.355 | 0.397 | ||||||||||||
North Total or Average | 1390.74 | 2.159 | 0.355 | 0.397 | ||||||||||||
Non-North Total or Average | 3245.06 | 2.159 | 0.355 | 0.397 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 8.5035 | 2779.43 | 23634.82 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 48.39 | 0.0000 | Y | 214.69 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | 8.5035 | 2496.12 | 21225.73 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 48.39 | 0.0000 | Y | 192.81 |
CORE_MID_LIGHTS | CORE_MID | 8.5035 | 24961.20 | 212257.33 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 48.39 | 0.0000 | Y | 1928.09 |
CORE_TOP_LIGHTS | CORE_TOP | 8.5035 | 2496.12 | 21225.73 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 48.39 | 0.0000 | Y | 192.81 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | 8.5035 | 313.41 | 2665.10 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 28.99 | 0.0000 | Y | 14.50 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | 8.5035 | 201.98 | 1717.49 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 28.52 | 0.0000 | Y | 9.19 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | 8.5035 | 313.42 | 2665.16 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 28.11 | 0.0000 | Y | 14.06 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | 8.5035 | 201.98 | 1717.49 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 28.47 | 0.0000 | Y | 9.18 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | 8.5035 | 3134.13 | 26651.03 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 28.89 | 0.0000 | Y | 144.52 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | 8.5035 | 2019.75 | 17174.94 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 28.44 | 0.0000 | Y | 91.70 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | 8.5035 | 3134.20 | 26651.61 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 28.07 | 0.0000 | Y | 140.42 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | 8.5035 | 2019.75 | 17174.94 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 28.40 | 0.0000 | Y | 91.56 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | 8.5035 | 313.41 | 2665.10 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 28.88 | 0.0000 | Y | 14.45 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | 8.5035 | 201.98 | 1717.49 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 28.44 | 0.0000 | Y | 9.17 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | 8.5035 | 313.42 | 2665.16 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 28.07 | 0.0000 | Y | 14.04 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | 8.5035 | 201.98 | 1717.49 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 28.40 | 0.0000 | Y | 9.15 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | 8.5035 | 783.68 | 6664.01 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 62.55 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | 8.5035 | 36.20 | 307.85 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 2.89 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | 8.5035 | 362.03 | 3078.50 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 28.90 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | 8.5035 | 36.20 | 307.85 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 2.89 |
Interior Lighting Total | 8.5035 | 46320.38 | 393884.84 | 1004.91 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2665.10 | 1027.93 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2665.10 | 369.12 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1717.49 | 662.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1717.49 | 237.87 |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2665.16 | 1027.95 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2665.16 | 369.12 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1717.49 | 662.44 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1717.49 | 237.87 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2665.10 | 1027.93 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2665.10 | 369.12 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1717.49 | 662.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1717.49 | 237.87 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2665.16 | 1027.95 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2665.16 | 369.12 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1717.49 | 662.44 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1717.49 | 237.87 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2665.10 | 1027.93 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2665.10 | 369.12 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1717.49 | 662.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1717.49 | 237.87 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2665.16 | 1027.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2665.16 | 369.12 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1717.49 | 662.44 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1717.49 | 237.87 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12979.20 | AstronomicalClock | - | 42.59 | 42.59 | 103.77 | |
EXTERIOR_LIGHTS_B | 968.00 | AstronomicalClock | - | 83.55 | 63.07 | 11.46 | |
EXTERIOR_LIGHTS_C | 26027.00 | AstronomicalClock | - | 83.55 | 47.80 | 233.52 | |
Exterior Lighting Total | 39974.20 | 348.75 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2038073.80 | |||
HEATSYS1 BOILER | Boiler:HotWater | 1500227.64 | 0.81 | ||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1037003.00 | 5.33 | 6.67 | 22.78 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1037003.00 | 5.33 | 6.67 | 22.78 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||
DUMMY BOILER | Boiler:HotWater | 93894.07 | 0.80 | ||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 985532.85 | |||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 985532.85 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CAV_BAS_COOLC | Coil:Cooling:Water | 98927.73 | 138072.37 | 97951.17 | 40121.19 | 0.71 | - | 37826.39 | 383.66 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | 170926.32 | 233757.93 | 163689.21 | 70068.72 | 0.70 | - | 62352.58 | 632.41 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | 1611057.81 | 2180811.84 | 1519617.50 | 661194.34 | 0.70 | - | 571388.36 | 5795.34 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | 163458.78 | 223968.22 | 156907.95 | 67060.27 | 0.70 | - | 60111.89 | 609.69 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 423781.17 | 303777.32 | 120003.85 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9505.35 | 6917.29 | 2588.06 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Coil:Cooling:WaterToAirHeatPump:EquationFit | 91085.73 | 66286.98 | 24798.75 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9243.86 | 6725.48 | 2518.39 | 0.73 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 18852.77 | 17886.01 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 371948.94 | 353120.87 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 66990.26 | 63560.77 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 6543.71 | 6210.31 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 5656.28 | 5369.33 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9086.02 | 8621.47 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 4622.63 | 4389.79 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 162491.59 | 154173.42 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 108684.14 | 103120.46 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 162180.63 | 153878.37 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 99633.96 | 94533.55 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 20781.47 | 19717.65 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 13772.92 | 13067.87 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 20721.62 | 19660.86 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 12984.57 | 12319.87 | - |
CAV_BAS_HEATC | Coil:Heating:Water | 271361.41 | 215599.37 | - |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | 52612.27 | 40544.69 | - |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | 512064.09 | 390507.38 | - |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | 50825.36 | 39113.81 | - |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Coil:Heating:WaterToAirHeatPump:EquationFit | 423781.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Coil:Heating:WaterToAirHeatPump:EquationFit | 9505.35 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Coil:Heating:WaterToAirHeatPump:EquationFit | 91085.73 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Coil:Heating:WaterToAirHeatPump:EquationFit | 9243.86 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | 17838.92 | 1.00 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | 10000000.00 | 1.00 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | 1028640.65 | 825837.88 | - |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | 824.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | 8240.84 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | 824.08 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.56 | 9430.69 | 1695.65 | 1.00 | 1.16 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.13 | 19730.82 | 2160.95 | 1.00 | 1.12 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 84.18 | 192241.08 | 2283.73 | 1.00 | 1.07 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.76 | 18925.44 | 2160.95 | 1.00 | 1.12 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 |
DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.52 | 35687.21 | 1657.97 | 1.00 | 1.13 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 556.89 | 1120.11 | 1.00 | 1.61 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.76 | 5336.73 | 1120.11 | 1.00 | 1.16 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 541.35 | 1120.11 | 1.00 | 1.62 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 134283.83 | 0.058469 | 11184.34 | 191287.51 | 0.90 | General |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.066291 | 16936.60 | 255487.18 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 44761.28 | 0.029234 | 1864.06 | 63762.50 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 44761.28 | 0.029234 | 1864.06 | 63762.50 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013068 | 3333.05 | 255050.01 | 0.90 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.105148 | 22251.26 | 211619.12 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 76148.78 | 76148.78 | 27.40 | 5.562 | 5.562 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 21.70 | 0.00879 | 1.200 | 0.00 |
CORE_BOTTOM | 79057.24 | 79057.24 | 31.67 | 5.774 | 5.774 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 21.70 | 0.00879 | 1.078 | 0.00 |
CORE_MID | 740411.98 | 740411.98 | 296.63 | 54.057 | 54.057 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 21.70 | 0.00879 | 10.778 | 0.00 |
CORE_TOP | 71713.86 | 71713.86 | 28.73 | 5.235 | 5.235 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 21.70 | 0.00879 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 10431.76 | 10431.76 | 33.28 | 0.769 | 0.769 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00887 | 29.40 | 0.00879 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 16652.45 | 16652.45 | 82.45 | 1.227 | 1.227 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 24.00 | 24.00 | 0.00865 | 22.36 | 0.00879 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 19895.56 | 19895.56 | 63.48 | 1.466 | 1.466 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 24.00 | 24.00 | 0.00869 | 28.88 | 0.00879 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 19904.25 | 19904.25 | 98.55 | 1.467 | 1.467 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00862 | 27.77 | 0.00879 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 92374.99 | 92374.99 | 294.74 | 6.809 | 6.809 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00891 | 29.40 | 0.00879 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 171958.55 | 171958.55 | 851.38 | 12.674 | 12.674 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 24.00 | 24.00 | 0.00864 | 23.02 | 0.00879 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 202179.23 | 202179.23 | 645.08 | 14.902 | 14.902 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00869 | 28.97 | 0.00879 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 180010.99 | 180010.99 | 891.25 | 13.268 | 13.268 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 24.00 | 24.00 | 0.00864 | 27.60 | 0.00879 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 10500.41 | 10500.41 | 33.50 | 0.774 | 0.774 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00886 | 29.40 | 0.00879 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 17017.41 | 17017.41 | 84.25 | 1.254 | 1.254 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 24.00 | 24.00 | 0.00865 | 23.02 | 0.00879 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 21386.04 | 21386.04 | 68.23 | 1.576 | 1.576 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00868 | 29.05 | 0.00879 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 18807.14 | 18807.14 | 93.12 | 1.386 | 1.386 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00863 | 27.77 | 0.00879 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8553.07 | 8553.07 | 236.25 | 0.497 | 0.497 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00850 | 25.60 | 0.00879 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 81964.13 | 81964.13 | 2264.03 | 4.764 | 4.764 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00850 | 25.60 | 0.00879 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8314.27 | 8314.27 | 229.66 | 0.483 | 0.483 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00850 | 25.86 | 0.00879 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370291.60 | 370291.60 | 472.50 | 21.525 | 21.525 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:00:00 | 27.00 | 27.00 | 0.00850 | 19.21 | 0.00879 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 1.078 | 0.00 | |
CORE_MID | 187921.54 | 187921.54 | 75.29 | 7.990 | 10.778 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 10.778 | 0.00 |
CORE_TOP | 46947.58 | 46947.58 | 18.81 | 2.019 | 2.019 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 4178.79 | 4178.79 | 13.33 | 0.179 | 0.179 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00623 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 3227.38 | 3227.38 | 15.98 | 0.139 | 0.139 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00650 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 6182.02 | 6182.02 | 19.72 | 0.266 | 0.266 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00686 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 1725.43 | 1725.43 | 8.54 | 0.074 | 0.087 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00533 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 113769.68 | 113769.68 | 363.00 | 4.913 | 4.913 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -4.20 | 0.00269 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 76091.21 | 76091.21 | 376.74 | 3.286 | 3.286 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -4.20 | 0.00269 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 113552.41 | 113552.41 | 362.30 | 4.904 | 4.904 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -4.20 | 0.00269 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 69766.98 | 69766.98 | 345.42 | 3.012 | 3.012 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00757 | -4.20 | 0.00269 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14545.21 | 14545.21 | 46.41 | 0.629 | 0.629 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 9639.54 | 9639.54 | 47.73 | 0.417 | 0.417 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 14503.37 | 14503.37 | 46.27 | 0.627 | 0.627 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 9088.48 | 9088.48 | 45.00 | 0.393 | 0.393 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -4.20 | 0.00269 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -4.20 | 0.00269 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -4.20 | 0.00269 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -4.20 | 0.00269 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -4.20 | 0.00269 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CAV_BAS | 5.56 | 5.56 | 1.20 | 1.20 | 5.5617 | 5.5617 | 5.5617 | 1.0000 | 1.0000 |
VAV_BOT WITH REHEAT | 9.13 | 9.13 | 1.75 | 1.75 | 9.1306 | 2.9708 | 9.1306 | 0.3254 | 0.3000 |
VAV_MID WITH REHEAT | 84.18 | 84.18 | 26.89 | 26.89 | 84.1786 | 29.0388 | 84.1786 | 0.3450 | 0.3000 |
VAV_TOP WITH REHEAT | 8.76 | 8.76 | 4.08 | 4.08 | 8.7579 | 4.0844 | 8.7579 | 0.4664 | 0.3000 |
AIRLOOP DATACENTER BASEMENT | 21.52 | 21.52 | 0.34 | 0.34 | 21.5246 | 21.5246 | 21.5246 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.50 | 0.50 | 0.02 | 0.02 | 0.4972 | 0.4972 | 0.4972 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.76 | 4.76 | 0.16 | 0.16 | 4.7645 | 4.7645 | 4.7645 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.48 | 0.48 | 0.02 | 0.02 | 0.4833 | 0.4833 | 0.4833 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18852.771 | 18852.771 | 1.899488 | 0.00041653 | 328.137 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17886.01 | 18852.77 | 1.899488 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 18928.61 | 18928.61 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 371948.943 | 371948.943 | 18.541461 | 0.00821776 | 6999.432 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 353120.87 | 371948.94 | 18.541461 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 187921.54 | 0.00 | 373726.82 | 373726.82 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 66990.258 | 66990.258 | 2.019376 | 0.00148007 | 1399.048 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 63560.77 | 66990.26 | 2.019376 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 46947.58 | 0.00 | 67296.14 | 67296.14 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 6543.713 | 6543.713 | 0.239125 | 0.00014458 | 130.009 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6210.31 | 6543.71 | 0.239125 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00623421 | 39.8457 | 4178.79 | 0.00 | 6574.10 | 6574.10 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 5656.277 | 5656.277 | 0.245474 | 0.00012497 | 108.706 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5369.33 | 5656.28 | 0.245474 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00650285 | 41.5449 | 3227.38 | 0.00 | 5683.13 | 5683.13 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 9086.021 | 9086.021 | 0.293285 | 0.00020074 | 186.072 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8621.47 | 9086.02 | 0.293285 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00686409 | 43.8268 | 6182.02 | 0.00 | 9127.51 | 9127.51 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4622.628 | 4622.628 | 0.293411 | 0.00010213 | 84.652 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4389.79 | 4622.63 | 0.293411 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00533037 | 34.1168 | 1725.43 | 0.00 | 4645.40 | 4645.40 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 162491.594 | 162491.594 | 4.913013 | 0.00359005 | 3390.430 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 154173.42 | 162491.59 | 4.913013 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00763410 | 48.6803 | 113769.68 | 0.00 | 163233.44 | 163233.44 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 108684.139 | 108684.139 | 3.286419 | 0.00240124 | 2267.660 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 103120.46 | 108684.14 | 3.286419 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00766009 | 48.8439 | 76091.21 | 0.00 | 109180.33 | 109180.33 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 162180.627 | 162180.627 | 4.903586 | 0.00358318 | 3383.947 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 153878.37 | 162180.63 | 4.903586 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00763220 | 48.6684 | 113552.41 | 0.00 | 162921.06 | 162921.06 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 99633.956 | 99633.956 | 3.012167 | 0.00220129 | 2078.954 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 94533.55 | 99633.96 | 3.012167 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00756605 | 48.2522 | 69766.98 | 0.00 | 100088.83 | 100088.83 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 20781.471 | 20781.471 | 0.628680 | 0.00045914 | 433.540 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19717.65 | 20781.47 | 0.628680 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00776181 | 49.4837 | 14545.21 | 0.00 | 20876.35 | 20876.35 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 13772.916 | 13772.916 | 0.416683 | 0.00030430 | 287.323 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13067.87 | 13772.92 | 0.416683 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00776702 | 49.5165 | 9639.54 | 0.00 | 13835.79 | 13835.79 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 20721.616 | 20721.616 | 0.626865 | 0.00045782 | 432.292 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19660.86 | 20721.62 | 0.626865 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00776041 | 49.4749 | 14503.37 | 0.00 | 20816.22 | 20816.22 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12984.567 | 12984.567 | 0.392789 | 0.00028688 | 270.886 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12319.87 | 12984.57 | 0.392789 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00773665 | 49.3256 | 9088.48 | 0.00 | 13043.85 | 13043.85 |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 98927.728 | -999.000 | 5.561680 | 0.00282932 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 98927.73 | 89961.47 | 5.561680 | 24.97 | 16.94 | 0.00894772 | 11.40 | 11.39 | 0.00839822 | 28.05 | 0.00879438 | 17.86 | 21.5777 | 24.00 | 0.00895929 | 47.5100 | 68217.90 | 0.00 | 111414.35 | 95879.28 |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 271361.414 | 271361.414 | 5.561680 | 0.00599540 | 5012.664 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 215599.37 | 271361.41 | 5.561680 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 21.5777 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 227449.06 | 227449.06 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 170926.323 | -999.000 | 9.130635 | 0.00488847 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 170926.32 | 158571.34 | 9.130635 | 25.60 | 17.07 | 0.00884742 | 11.40 | 11.97 | 0.00839822 | 29.40 | 0.00879438 | 18.30 | 27.7970 | 24.00 | 0.00880001 | 46.6766 | 116089.60 | 0.00 | 191470.04 | 166257.57 |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 52612.273 | 52612.273 | 2.739191 | 0.00116240 | 760.539 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 40544.69 | 52612.27 | 2.739191 | -4.20 | -4.20 | 0.00269032 | 12.80 | 11.46 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 92.6566 | 21.00 | 0.00739448 | 47.1692 | 15313.61 | 0.00 | 42872.81 | 42872.81 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1611057.814 | -999.000 | 84.178629 | 0.04607605 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1611057.81 | 1489924.54 | 84.178629 | 25.78 | 17.16 | 0.00887277 | 11.40 | 11.97 | 0.00839822 | 29.40 | 0.00879438 | 18.30 | 30.1506 | 24.00 | 0.00881553 | 46.7578 | 1043244.59 | 0.00 | 1800726.48 | 1555844.15 |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 512064.088 | 512064.088 | 25.253589 | 0.01131343 | 7348.483 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 390507.38 | 512064.09 | 25.253589 | -4.17 | -4.17 | 0.00269723 | 12.80 | 11.46 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 100.5020 | 21.00 | 0.00777595 | 49.5721 | 496389.52 | 0.00 | 412918.72 | 412918.72 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 163458.780 | -999.000 | 8.757940 | 0.00467490 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 163458.78 | 151734.29 | 8.757940 | 25.57 | 17.06 | 0.00884266 | 11.40 | 11.97 | 0.00839822 | 29.40 | 0.00879438 | 18.30 | 28.9799 | 24.00 | 0.00881427 | 46.7512 | 118630.68 | 0.00 | 183166.73 | 159108.69 |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 50825.356 | 50825.356 | 2.627382 | 0.00112292 | 733.992 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 39113.81 | 50825.36 | 2.627382 | -4.16 | -4.16 | 0.00269872 | 12.80 | 11.46 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 96.5996 | 21.00 | 0.00787747 | 50.2103 | 59366.72 | 0.00 | 41360.73 | 41360.73 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 423781.167 | 303777.321 | 21.524602 | 0.01037837 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:00:00 | 456200.42 | 455890.82 | -999.0 | 28.46 | 17.76 | 0.00850463 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | -999.0000 | 27.00 | 0.00850000 | 37.7427 | 369732.04 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9505.351 | 6917.294 | 0.497179 | 0.00023279 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 10282.39 | 10268.01 | -999.0 | 27.92 | 17.58 | 0.00850926 | 12.80 | 11.97 | 0.00850000 | 25.60 | 0.00879438 | 17.03 | -999.0000 | 27.00 | 0.00850000 | 37.7427 | 8553.07 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 91085.732 | 66286.979 | 4.764475 | 0.00223068 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 98532.59 | 98388.82 | -999.0 | 27.91 | 17.58 | 0.00850966 | 12.80 | 11.97 | 0.00850000 | 25.60 | 0.00879438 | 17.03 | -999.0000 | 27.00 | 0.00850000 | 37.7427 | 81964.13 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9243.862 | 6725.476 | 0.483298 | 0.00022638 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 9998.80 | 9984.43 | -999.0 | 27.92 | 17.58 | 0.00850952 | 12.80 | 11.97 | 0.00850000 | 25.86 | 0.00879438 | 17.12 | -999.0000 | 27.00 | 0.00850000 | 37.7427 | 8314.27 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 423781.167 | 423781.167 | 21.524602 | 0.01037837 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 423781.17 | 423781.17 | 21.524602 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.5720 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9505.351 | 9505.351 | 0.497179 | 0.00023279 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9505.35 | 9505.35 | 0.497179 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1440 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 91085.732 | 91085.732 | 4.764475 | 0.00223068 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 91085.73 | 91085.73 | 4.764475 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.2808 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9243.862 | 9243.862 | 0.483298 | 0.00022638 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9243.86 | 9243.86 | 0.483298 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.2343 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 17838.917 | 17838.917 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17838.92 | 17838.92 | 21.524602 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.5720 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10000000.00 | 1151548.16 | 21.524602 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.5720 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 1028640.652 | 1028640.652 | 21.524602 | 0.02272656 | 19136.891 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 825837.88 | 1028640.65 | 21.524602 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.5720 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | 0.00 | 0.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 824.084 | 824.084 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.08 | 824.08 | 0.497179 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1440 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8240.841 | 8240.841 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8240.84 | 8240.84 | 4.764475 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.2808 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 824.084 | 824.084 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.08 | 824.08 | 0.483298 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.2343 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 18852.771 | 18852.771 | 1.899488 | 0.00041653 | 328.137 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 66.28463066 | 71.00 | 82.00 | 11.00 | 3060840.64 | 0.5843 | 0.628330 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17886.01 | 18852.77 | 1.0000 | 2.25467515 | 1.899488 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.41648645 | 60.00 | 49.00 | 11.00 | 0.000 | 17886.01 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 18928.61 | 18928.61 | 2.25467515 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 21.03 | 14.85 | 0.00800000 | 41455.1 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 371948.943 | 371948.943 | 18.541461 | 0.00821776 | 6999.432 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 66.28463066 | 71.00 | 82.00 | 11.00 | 3060840.64 | 11.5367 | 12.396417 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 353120.87 | 371948.94 | 1.0000 | 22.00854284 | 18.541461 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 8.21691911 | 60.00 | 49.00 | 11.00 | 0.000 | 353120.87 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.56 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 187921.54 | 0.00 | 373726.82 | 373726.82 | 22.00854284 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 29.45 | 17.83 | 0.00800000 | 50040.8 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 66990.258 | 66990.258 | 2.019376 | 0.00148007 | 1399.048 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 66.28463066 | 71.00 | 82.00 | 11.00 | 3060840.64 | 2.0766 | 2.232670 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 63560.77 | 66990.26 | 1.0000 | 2.39698033 | 2.019376 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 1.47991692 | 60.00 | 49.00 | 11.00 | 0.000 | 63560.77 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 46947.58 | 0.00 | 67296.14 | 67296.14 | 2.39698033 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.33 | 21.25 | 0.00800000 | 61135.2 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6543.713 | 6543.713 | 0.239125 | 0.00014458 | 130.009 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 66.28463066 | 71.00 | 82.00 | 11.00 | 3060840.64 | 0.2029 | 0.218091 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6210.31 | 6543.71 | 1.0000 | 0.28383893 | 0.239125 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.14456060 | 60.00 | 49.00 | 11.00 | 0.000 | 6210.31 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.87 | 0.00623421 | 21.00 | 0.00623421 | 39.8457 | 4178.79 | 0.00 | 6574.10 | 6574.10 | 0.28383893 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 35.51 | 19.79 | 0.00800000 | 56221.2 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5656.277 | 5656.277 | 0.245474 | 0.00012497 | 108.706 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 66.28463066 | 71.00 | 82.00 | 11.00 | 3060840.64 | 0.1754 | 0.188514 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5369.33 | 5656.28 | 1.0000 | 0.29137487 | 0.245474 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.12495578 | 60.00 | 49.00 | 11.00 | 0.000 | 5369.33 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.86 | 0.00650285 | 21.00 | 0.00650285 | 41.5449 | 3227.38 | 0.00 | 5683.13 | 5683.13 | 0.29137487 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 31.93 | 18.65 | 0.00800000 | 52564.4 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9086.021 | 9086.021 | 0.293285 | 0.00020074 | 186.072 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 66.28463066 | 71.00 | 82.00 | 11.00 | 3060840.64 | 0.2817 | 0.302821 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8621.47 | 9086.02 | 1.0000 | 0.34812634 | 0.293285 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.20072406 | 60.00 | 49.00 | 11.00 | 0.000 | 8621.47 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00686409 | 21.00 | 0.00686409 | 43.8268 | 6182.02 | 0.00 | 9127.51 | 9127.51 | 0.34812634 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 38.51 | 20.71 | 0.00800000 | 59278.8 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4622.628 | 4622.628 | 0.293411 | 0.00010213 | 84.652 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 66.28463066 | 71.00 | 82.00 | 11.00 | 3060840.64 | 0.1434 | 0.154064 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4389.79 | 4622.63 | 1.0000 | 0.34827629 | 0.293411 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.10212090 | 60.00 | 49.00 | 11.00 | 0.000 | 4389.79 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.84 | 0.00533037 | 21.00 | 0.00533037 | 34.1168 | 1725.43 | 0.00 | 4645.40 | 4645.40 | 0.34827629 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 25.88 | 16.61 | 0.00800000 | 46398.1 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 162491.594 | 162491.594 | 4.913013 | 0.00359005 | 3390.430 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 66.28463066 | 71.00 | 82.00 | 11.00 | 3060840.64 | 5.0370 | 5.415565 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 154173.42 | 162491.59 | 1.0000 | 5.83170173 | 4.913013 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 3.58968700 | 60.00 | 49.00 | 11.00 | 0.000 | 154173.42 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00763410 | 21.00 | 0.00763410 | 48.6803 | 113769.68 | 0.00 | 163233.44 | 163233.44 | 5.83170173 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61050.5 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 108684.139 | 108684.139 | 3.286419 | 0.00240124 | 2267.660 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 66.28463066 | 71.00 | 82.00 | 11.00 | 3060840.64 | 3.3690 | 3.622255 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 103120.46 | 108684.14 | 1.0000 | 3.90094931 | 3.286419 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 2.40099830 | 60.00 | 49.00 | 11.00 | 0.000 | 103120.46 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00766009 | 21.00 | 0.00766009 | 48.8439 | 76091.21 | 0.00 | 109180.33 | 109180.33 | 3.90094931 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61048.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 162180.627 | 162180.627 | 4.903586 | 0.00358318 | 3383.947 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 66.28463066 | 71.00 | 82.00 | 11.00 | 3060840.64 | 5.0273 | 5.405201 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 153878.37 | 162180.63 | 1.0000 | 5.82051128 | 4.903586 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 3.58281725 | 60.00 | 49.00 | 11.00 | 0.000 | 153878.37 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00763220 | 21.00 | 0.00763220 | 48.6684 | 113552.41 | 0.00 | 162921.06 | 162921.06 | 5.82051128 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61050.7 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 99633.956 | 99633.956 | 3.012167 | 0.00220129 | 2078.954 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 66.28463066 | 71.00 | 82.00 | 11.00 | 3060840.64 | 3.0885 | 3.320628 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 94533.55 | 99633.96 | 1.0000 | 3.57541439 | 3.012167 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 2.20106597 | 60.00 | 49.00 | 11.00 | 0.000 | 94533.55 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00756605 | 21.00 | 0.00756605 | 48.2522 | 69766.98 | 0.00 | 100088.83 | 100088.83 | 3.57541439 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61053.5 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20781.471 | 20781.471 | 0.628680 | 0.00045914 | 433.540 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 66.28463066 | 71.00 | 82.00 | 11.00 | 3060840.64 | 0.6442 | 0.692611 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19717.65 | 20781.47 | 1.0000 | 0.74623761 | 0.628680 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.45909438 | 60.00 | 49.00 | 11.00 | 0.000 | 19717.65 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00776181 | 21.00 | 0.00776181 | 49.4837 | 14545.21 | 0.00 | 20876.35 | 20876.35 | 0.74623761 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.23 | 21.22 | 0.00800000 | 61035.3 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13772.916 | 13772.916 | 0.416683 | 0.00030430 | 287.323 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 66.28463066 | 71.00 | 82.00 | 11.00 | 3060840.64 | 0.4269 | 0.459028 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13067.87 | 13772.92 | 1.0000 | 0.49459843 | 0.416683 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.30426471 | 60.00 | 49.00 | 11.00 | 0.000 | 13067.87 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00776702 | 21.00 | 0.00776702 | 49.5165 | 9639.54 | 0.00 | 13835.79 | 13835.79 | 0.49459843 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.23 | 21.22 | 0.00800000 | 61033.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20721.616 | 20721.616 | 0.626865 | 0.00045782 | 432.292 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 66.28463066 | 71.00 | 82.00 | 11.00 | 3060840.64 | 0.6423 | 0.690616 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19660.86 | 20721.62 | 1.0000 | 0.74408346 | 0.626865 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.45777207 | 60.00 | 49.00 | 11.00 | 0.000 | 19660.86 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00776041 | 21.00 | 0.00776041 | 49.4749 | 14503.37 | 0.00 | 20816.22 | 20816.22 | 0.74408346 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.23 | 21.22 | 0.00800000 | 61035.5 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12984.567 | 12984.567 | 0.392789 | 0.00028688 | 270.886 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 66.28463066 | 71.00 | 82.00 | 11.00 | 3060840.64 | 0.4025 | 0.432753 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12319.87 | 12984.57 | 1.0000 | 0.46623648 | 0.392789 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.28684888 | 60.00 | 49.00 | 11.00 | 0.000 | 12319.87 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00773665 | 21.00 | 0.00773665 | 49.3256 | 9088.48 | 0.00 | 13043.85 | 13043.85 | 0.46623648 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61036.7 | |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 98927.728 | -999.000 | 5.561680 | 0.00282932 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4734 | 1004.8586 | 1.1870 | CAV_BAS FAN | Fan:ConstantVolume | 5.561680 | 6.60166291 | 4197.9300 | 999.8980 | 58.46277725 | 15.00 | 6.67 | 8.33 | 2044370.65 | 4.8390 | 4.839031 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 98927.73 | 89961.47 | 1.0000 | 6.60166291 | 5.561680 | 24.97 | 16.94 | 0.00894772 | 47878.9 | 11.40 | 11.39 | 0.00839822 | 32894.8 | 2.82903188 | 6.67 | 13.38 | 8.33 | 9430.687 | 89497.04 | 28.05 | 0.00879438 | 17.86 | 1.20008137 | 21.5777 | 24.00 | 0.00899580 | 24.00 | 0.00895929 | 47.5100 | 68217.90 | 0.00 | 111414.35 | 95879.28 | 6.60166291 | 24.97 | 17.09 | 0.00894772 | 47878.9 | 10.75 | 10.73 | 0.00801425 | 31002.2 | |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 271361.414 | 271361.414 | 5.561680 | 0.00599540 | 5012.664 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | CAV_BAS FAN | Fan:ConstantVolume | 5.561680 | 6.60166291 | 4197.9300 | 999.8980 | 66.28463066 | 71.00 | 82.00 | 11.00 | 3060840.64 | 7.0438 | 9.044008 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 215599.37 | 271361.41 | 1.0000 | 6.60166291 | 5.561680 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 5.99478727 | 60.00 | 49.00 | 11.00 | 0.000 | 215599.37 | -4.20 | 0.00269032 | -4.20 | 1.20008137 | 21.5777 | 0.00 | 0.00000000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 227449.06 | 227449.06 | 6.60166291 | 12.80 | 2.76 | 0.00058051 | 14327.6 | 47.05 | 17.57 | 0.00058051 | 48780.9 | |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 170926.323 | -999.000 | 9.130635 | 0.00488847 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2869 | 1004.8586 | 1.1870 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.130635 | 10.83798000 | 4197.9300 | 999.8980 | 58.46277725 | 15.00 | 6.67 | 8.33 | 2044370.65 | 8.3608 | 8.360828 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 170926.32 | 158571.34 | 1.0000 | 10.83798000 | 9.130635 | 25.60 | 17.07 | 0.00884742 | 48272.7 | 11.40 | 11.97 | 0.00839822 | 34322.2 | 4.88797253 | 6.67 | 13.38 | 8.33 | 19730.817 | 151195.51 | 29.40 | 0.00879438 | 18.30 | 2.53804000 | 27.7970 | 24.00 | 0.00886979 | 24.00 | 0.00880001 | 46.6766 | 116089.60 | 0.00 | 191470.04 | 166257.57 | 10.83798000 | 25.60 | 17.23 | 0.00884742 | 48272.7 | 10.58 | 10.57 | 0.00792451 | 30606.1 | |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 52612.273 | 52612.273 | 2.739191 | 0.00116240 | 760.539 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.130635 | 10.83798000 | 4197.9300 | 999.8980 | 66.28463066 | 71.00 | 82.00 | 11.00 | 3060840.64 | 1.3246 | 1.753476 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 40544.69 | 52612.27 | 1.0000 | 3.25139400 | 2.739191 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 1.16228530 | 60.00 | 49.00 | 11.00 | 0.000 | 40544.69 | -4.20 | 0.00269032 | -4.20 | 2.53804000 | 92.6566 | 8.01 | 0.00246418 | 21.00 | 0.00739448 | 47.1692 | 15313.61 | 0.00 | 42872.81 | 42872.81 | 3.25139400 | 12.80 | 5.53 | 0.00267371 | 19612.4 | 25.86 | 11.57 | 0.00267371 | 32798.3 | |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1611057.814 | -999.000 | 84.178629 | 0.04607605 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3340 | 1004.8586 | 1.1870 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 84.178629 | 99.91925645 | 4197.9300 | 999.8980 | 58.46277725 | 15.00 | 6.67 | 8.33 | 2044370.65 | 78.8046 | 78.804586 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1611057.81 | 1489924.54 | 1.0000 | 99.91925645 | 84.178629 | 25.78 | 17.16 | 0.00887277 | 48521.8 | 11.40 | 11.97 | 0.00839822 | 34322.2 | 46.07134931 | 6.67 | 13.38 | 8.33 | 192241.075 | 1418816.74 | 29.40 | 0.00879438 | 18.30 | 25.38036000 | 30.1506 | 24.00 | 0.00891139 | 24.00 | 0.00881553 | 46.7578 | 1043244.59 | 0.00 | 1800726.48 | 1555844.15 | 99.91925645 | 25.78 | 17.31 | 0.00887277 | 48521.8 | 10.54 | 10.52 | 0.00790043 | 30500.0 | |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 512064.088 | 512064.088 | 25.253589 | 0.01131343 | 7348.483 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 84.178629 | 99.91925645 | 4197.9300 | 999.8980 | 66.28463066 | 71.00 | 82.00 | 11.00 | 3060840.64 | 12.7582 | 17.066213 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 390507.38 | 512064.09 | 1.0000 | 29.97577694 | 25.253589 | -4.17 | -4.17 | 0.00269723 | 2538.2 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 11.31227622 | 60.00 | 49.00 | 11.00 | 0.000 | 390507.38 | -4.20 | 0.00269032 | -4.20 | 25.38036000 | 100.5020 | 21.00 | 0.00786362 | 21.00 | 0.00777595 | 49.5721 | 496389.52 | 0.00 | 412918.72 | 412918.72 | 29.97577694 | 12.80 | 5.55 | 0.00269032 | 19654.3 | 26.44 | 11.83 | 0.00269032 | 33429.4 | |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 163458.780 | -999.000 | 8.757940 | 0.00467490 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2781 | 1004.8586 | 1.1870 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.757940 | 10.39559432 | 4197.9300 | 999.8980 | 58.46277725 | 15.00 | 6.67 | 8.33 | 2044370.65 | 7.9956 | 7.995555 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 163458.78 | 151734.29 | 1.0000 | 10.39559432 | 8.757940 | 25.57 | 17.06 | 0.00884266 | 48225.5 | 11.40 | 11.97 | 0.00839822 | 34322.2 | 4.67442353 | 6.67 | 13.38 | 8.33 | 18925.442 | 144533.34 | 29.40 | 0.00879438 | 18.30 | 2.53804000 | 28.9799 | 24.00 | 0.00886240 | 24.00 | 0.00881427 | 46.7512 | 118630.68 | 0.00 | 183166.73 | 159108.69 | 10.39559432 | 25.57 | 17.21 | 0.00884266 | 48225.5 | 10.58 | 10.57 | 0.00792453 | 30605.9 | |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 50825.356 | 50825.356 | 2.627382 | 0.00112292 | 733.992 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.757940 | 10.39559432 | 4197.9300 | 999.8980 | 66.28463066 | 71.00 | 82.00 | 11.00 | 3060840.64 | 1.2779 | 1.693921 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 39113.81 | 50825.36 | 1.0000 | 3.11867830 | 2.627382 | -4.16 | -4.16 | 0.00269872 | 2547.4 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 1.12280958 | 60.00 | 49.00 | 11.00 | 0.000 | 39113.81 | -4.20 | 0.00269032 | -4.20 | 2.53804000 | 96.5996 | 18.79 | 0.00762746 | 21.00 | 0.00787747 | 50.2103 | 59366.72 | 0.00 | 41360.73 | 41360.73 | 3.11867830 | 12.80 | 5.77 | 0.00285820 | 20078.2 | 25.93 | 11.79 | 0.00285820 | 33340.4 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 423781.167 | 303777.321 | 21.524602 | 0.01037837 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6497 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:00:00 | 456200.42 | 455890.82 | 0.9289 | -999.0 | -999.0 | 28.46 | 17.76 | 0.00850463 | 50315.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 456200.42 | 29.40 | 0.00879438 | 18.30 | 0.33837161 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 369732.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9505.351 | 6917.294 | 0.497179 | 0.00023279 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6583 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 10282.39 | 10268.01 | 0.9244 | -999.0 | -999.0 | 27.92 | 17.58 | 0.00850926 | 49773.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10282.39 | 25.60 | 0.00879438 | 17.03 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 8553.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 91085.732 | 66286.979 | 4.764475 | 0.00223068 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6590 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 98532.59 | 98388.82 | 0.9244 | -999.0 | -999.0 | 27.91 | 17.58 | 0.00850966 | 49772.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 98532.59 | 25.60 | 0.00879438 | 17.03 | 0.15631366 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 81964.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9243.862 | 6725.476 | 0.483298 | 0.00022638 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6588 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 9998.80 | 9984.43 | 0.9245 | -999.0 | -999.0 | 27.92 | 17.58 | 0.00850952 | 49781.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9998.80 | 25.86 | 0.00879438 | 17.12 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 8314.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 423781.167 | 423781.167 | 21.524602 | 0.01037837 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 423781.17 | 423781.17 | 1.0000 | 25.54950423 | 21.524602 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 423781.17 | -4.20 | 0.00269032 | -4.20 | 0.33837161 | 1.5720 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9505.351 | 9505.351 | 0.497179 | 0.00023279 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9505.35 | 9505.35 | 1.0000 | 0.59014730 | 0.497179 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9505.35 | -4.20 | 0.00269032 | -4.20 | 0.01563137 | 3.1440 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 91085.732 | 91085.732 | 4.764475 | 0.00223068 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 91085.73 | 91085.73 | 1.0000 | 5.65538841 | 4.764475 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 91085.73 | -4.20 | 0.00269032 | -4.20 | 0.15631366 | 3.2808 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9243.862 | 9243.862 | 0.483298 | 0.00022638 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9243.86 | 9243.86 | 1.0000 | 0.57367081 | 0.483298 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9243.86 | -4.20 | 0.00269032 | -4.20 | 0.01563137 | 3.2343 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17838.917 | 17838.917 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.524602 | 25.54950423 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17838.92 | 17838.92 | 1.0000 | 25.54950423 | 21.524602 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17838.92 | -4.20 | 0.00269032 | -4.20 | 0.33837161 | 1.5720 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | No | No | unknown | No | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.524602 | 25.54950423 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10000000.00 | 1151548.16 | 1.0000 | 25.54950423 | 21.524602 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10000000.00 | -4.20 | 0.00269032 | -4.20 | 0.33837161 | 1.5720 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1028640.652 | 1028640.652 | 21.524602 | 0.02272656 | 19136.891 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.524602 | 25.54950423 | 4197.9300 | 999.8980 | 66.28463066 | 71.00 | 82.00 | 11.00 | 3060840.64 | 26.9808 | 34.282819 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 825837.88 | 1028640.65 | 1.0000 | 25.54950423 | 21.524602 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 22.72423993 | 60.00 | 49.00 | 11.00 | 0.000 | 825837.88 | -4.20 | 0.00269032 | -4.20 | 0.33837161 | 1.5720 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | 0.00 | 0.00 | 25.54950423 | 16.60 | 4.09 | 0.00004229 | 16787.4 | 16.60 | 4.09 | 0.00004229 | 16787.4 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 824.084 | 824.084 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.497179 | 0.59014730 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.08 | 824.08 | 1.0000 | 0.59014730 | 0.497179 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 824.08 | -4.20 | 0.00269032 | -4.20 | 0.01563137 | 3.1440 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8240.841 | 8240.841 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.764475 | 5.65538841 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8240.84 | 8240.84 | 1.0000 | 5.65538841 | 4.764475 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8240.84 | -4.20 | 0.00269032 | -4.20 | 0.15631366 | 3.2808 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 824.084 | 824.084 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.483298 | 0.57367081 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.08 | 824.08 | 1.0000 | 0.57367081 | 0.483298 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 824.08 | -4.20 | 0.00269032 | -4.20 | 0.01563137 | 3.2343 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.56 | - | |||
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.13 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 84.18 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 8.76 | - | |||
AIRLOOP DATACENTER BASEMENT OA CONTROLLER | DifferentialDryBulb | 0.34 | 21.52 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2614.33 | 203.00 | 2.33 |
CORE_BOTTOM | 2579.83 | 405.33 | 13.00 |
CORE_MID | 1098.50 | 2893.67 | 17.67 |
CORE_TOP | 1203.17 | 3999.00 | 344.67 |
PERIMETER_BOT_ZN_3 | 1259.17 | 3128.50 | 17.17 |
PERIMETER_BOT_ZN_2 | 1312.83 | 3708.00 | 56.67 |
PERIMETER_BOT_ZN_1 | 1743.50 | 3096.83 | 80.83 |
PERIMETER_BOT_ZN_4 | 2763.83 | 1702.50 | 101.50 |
PERIMETER_MID_ZN_3 | 1358.83 | 4680.00 | 802.83 |
PERIMETER_MID_ZN_2 | 1469.67 | 3893.67 | 771.83 |
PERIMETER_MID_ZN_1 | 1742.50 | 3873.00 | 523.50 |
PERIMETER_MID_ZN_4 | 1626.17 | 4391.00 | 621.67 |
PERIMETER_TOP_ZN_3 | 2020.50 | 4842.50 | 1471.00 |
PERIMETER_TOP_ZN_2 | 2314.00 | 4528.33 | 1384.50 |
PERIMETER_TOP_ZN_1 | 2109.17 | 4191.33 | 1047.00 |
PERIMETER_TOP_ZN_4 | 2052.33 | 4619.33 | 1149.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4622.33 | 5232.83 | 1664.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 68.50 | 0.00 | 5.00 |
CORE_BOTTOM | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_MID | 2.00 | 0.00 | 1.17 | 0.00 |
CORE_TOP | 3.83 | 0.00 | 0.67 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 7.67 | 0.00 | 7.67 |
PERIMETER_BOT_ZN_1 | 0.00 | 18.67 | 0.00 | 18.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 38.67 | 0.00 | 18.83 |
PERIMETER_MID_ZN_3 | 7.17 | 0.00 | 1.83 | 0.00 |
PERIMETER_MID_ZN_2 | 4.67 | 7.00 | 0.00 | 7.00 |
PERIMETER_MID_ZN_1 | 3.17 | 18.50 | 0.00 | 18.50 |
PERIMETER_MID_ZN_4 | 2.00 | 15.00 | 0.00 | 6.83 |
PERIMETER_TOP_ZN_3 | 70.50 | 0.00 | 19.50 | 0.00 |
PERIMETER_TOP_ZN_2 | 39.67 | 5.83 | 2.67 | 5.83 |
PERIMETER_TOP_ZN_1 | 27.00 | 7.00 | 1.67 | 7.00 |
PERIMETER_TOP_ZN_4 | 16.33 | 15.17 | 1.00 | 7.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 16.50 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 11.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 9.67 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 62.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 75.33 | 229.00 | 20.50 | 79.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 1.453 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.978 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.724 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.678 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.819 | 0.042 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 1.252 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 1.178 | 0.042 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 1.744 | 0.043 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.652 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 1.114 | 0.105 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 1.074 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 1.255 | 0.098 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.656 | 0.118 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 1.166 | 0.122 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 1.068 | 0.118 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 1.288 | 0.122 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 25160.60 | 295663.17 | 29-MAY-02:30 | 1803500.90 | 29-AUG-15:10 |
Electricity:Building | 17863.90 | 217323.05 | 07-MAY-17:20 | 1099403.99 | 01-DEC-16:20 |
Electricity:Zone:BASEMENT | 639.09 | 14055.89 | 01-JAN-00:10 | 32720.90 | 02-JAN-08:10 |
InteriorLights:Electricity | 3187.59 | 10066.89 | 23-APR-17:20 | 321032.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 214.69 | 598.35 | 01-JAN-00:10 | 19263.35 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3187.59 | 10066.89 | 23-APR-17:20 | 321032.30 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 482.42 | 4990.59 | 01-JAN-00:10 | 34506.47 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 192.81 | 537.36 | 01-JAN-00:10 | 17299.84 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4824.17 | 49905.77 | 01-JAN-00:10 | 345064.06 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1928.10 | 5373.60 | 01-JAN-00:10 | 172998.44 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 482.42 | 4990.58 | 01-JAN-00:10 | 34506.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 192.81 | 537.36 | 01-JAN-00:10 | 17299.84 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 50.87 | 622.57 | 09-APR-17:10 | 4332.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.50 | 57.42 | 08-JAN-11:10 | 2172.17 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 32.63 | 401.21 | 23-APR-17:10 | 2792.17 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.19 | 37.00 | 01-JAN-10:10 | 1399.83 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 50.43 | 622.58 | 19-MAR-17:10 | 4332.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 14.06 | 57.42 | 01-JAN-10:00 | 2172.22 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 32.61 | 401.21 | 19-MAR-17:10 | 2792.16 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 9.18 | 37.00 | 01-JAN-13:20 | 1399.83 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 508.17 | 6225.74 | 02-APR-17:10 | 43327.20 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 144.52 | 574.18 | 08-JAN-10:40 | 21721.68 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 326.05 | 4012.10 | 23-APR-17:10 | 27921.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 91.70 | 370.02 | 01-JAN-10:10 | 13998.28 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 504.08 | 6225.83 | 19-MAR-17:10 | 43328.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 140.42 | 574.19 | 01-JAN-10:00 | 21722.16 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 325.91 | 4012.08 | 19-MAR-17:10 | 27921.60 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 91.56 | 370.02 | 01-JAN-13:20 | 13998.28 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 50.81 | 622.57 | 02-APR-17:10 | 4332.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.45 | 57.42 | 08-JAN-10:40 | 2172.17 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 32.60 | 401.21 | 23-APR-17:10 | 2792.17 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 9.17 | 37.00 | 01-JAN-10:10 | 1399.83 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 50.41 | 622.58 | 19-MAR-17:10 | 4332.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 14.04 | 57.42 | 01-JAN-10:00 | 2172.22 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 32.59 | 401.21 | 19-MAR-17:10 | 2792.16 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 9.15 | 37.00 | 01-JAN-13:20 | 1399.83 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7557.41 | 95209.88 | 01-JAN-06:10 | 385063.96 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.55 | 301.75 | 01-JAN-06:10 | 5431.44 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 156.77 | 1962.54 | 01-JAN-06:10 | 8045.33 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 2.89 | 13.94 | 01-JAN-06:10 | 250.91 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1567.70 | 19625.45 | 01-JAN-06:10 | 80453.32 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 28.90 | 139.39 | 01-JAN-06:10 | 2509.10 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 156.77 | 1962.54 | 01-JAN-06:10 | 8045.33 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 2.89 | 13.94 | 01-JAN-06:10 | 250.91 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.31 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.88 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.07 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.36 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.43 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.43 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.65 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.36 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.43 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.43 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 01-APR-00:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
Electricity:HVAC | 3953.99 | 47282.93 | 12-JAN-02:20 | 333949.38 | 01-APR-16:00 |
ExteriorEquipment:Electricity | 1955.90 | 13239.62 | 01-JAN-00:10 | 126050.31 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 55.00 | 979.82 | 01-JAN-00:10 | 3452.33 | 01-DEC-16:30 |
ElectricityPurchased:Facility | 25160.60 | 295663.17 | 29-MAY-02:30 | 1803500.90 | 29-AUG-15:10 |
ElectricityPurchased:Plant | 25160.60 | 295663.17 | 29-MAY-02:30 | 1803500.90 | 29-AUG-15:10 |
Cogeneration:ElectricityPurchased | 25160.60 | 295663.17 | 29-MAY-02:30 | 1803500.90 | 29-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 25160.60 | 295663.17 | 29-MAY-02:30 | 1803500.90 | 29-AUG-15:10 |
ElectricityNet:Plant | 25160.60 | 295663.17 | 29-MAY-02:30 | 1803500.90 | 29-AUG-15:10 |
Cogeneration:ElectricityNet | 25160.60 | 295663.17 | 29-MAY-02:30 | 1803500.90 | 29-AUG-15:10 |
Fans:Electricity | 2076.54 | 42122.18 | 01-JAN-09:20 | 142073.54 | 10-AUG-16:00 |
General:Fans:Electricity | 2076.54 | 42122.18 | 01-JAN-09:20 | 142073.54 | 10-AUG-16:00 |
ExteriorLights:Electricity | 348.75 | 0.00 | 01-JAN-08:10 | 39974.20 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 348.75 | 0.00 | 01-JAN-08:10 | 39974.20 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1895.08 | 12222.20 | 01-JAN-00:10 | 122221.98 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 1353.80 | 1467.50 | 03-JAN-06:00 | 409580.16 | 29-AUG-14:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 880.75 | 0.00 | 11-JAN-20:10 | 100000.00 | 11-FEB-17:10 |
Electricity:Plant | 1093.06 | 3494.16 | 16-JAN-05:30 | 353157.83 | 29-AUG-14:40 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:Electricity | 412.09 | 0.00 | 01-JAN-00:10 | 241566.33 | 29-AUG-14:40 |
HeatRejection:Electricity | 461.68 | 161.07 | 16-JAN-06:00 | 79389.88 | 27-APR-12:50 |
General:HeatRejection:Electricity | 31.86 | 0.00 | 01-JAN-00:10 | 30141.61 | 27-APR-12:50 |
Pumps:Electricity | 219.29 | 3333.05 | 03-JAN-00:10 | 39886.96 | 11-SEP-15:20 |
General:Pumps:Electricity | 219.29 | 3333.05 | 03-JAN-00:10 | 39886.96 | 11-SEP-15:20 |
WIRED_LTG_ELECTRICITY | 89.57 | 0.00 | 01-JAN-00:10 | 9021.01 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.88 | 88964.76 | 01-APR-00:10 | 305206.10 | 03-APR-07:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1561.90 | 7280.88 | 01-JAN-14:40 | 1413997.58 | 02-JAN-05:20 |
Gas:Plant | 1561.90 | 7280.88 | 01-JAN-14:40 | 1413997.58 | 02-JAN-05:20 |
WaterSystems:Gas | 592.25 | 7280.88 | 01-JAN-05:00 | 78591.00 | 13-FEB-12:50 |
Water Heater:WaterSystems:Gas | 592.25 | 7280.88 | 01-JAN-05:00 | 78591.00 | 13-FEB-12:50 |
Heating:Gas | 969.65 | 0.00 | 01-JAN-09:20 | 1406716.70 | 02-JAN-05:20 |
Boiler:Heating:Gas | 969.65 | 0.00 | 01-JAN-09:20 | 1406716.70 | 02-JAN-05:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 6876.15 | 2619.77 | 03-JAN-06:00 | 2164952.48 | 29-AUG-14:40 |
PlantLoopCoolingDemand:HVAC | 6876.15 | 2619.77 | 03-JAN-06:00 | 2164952.48 | 29-AUG-14:40 |
CoolingCoils:PlantLoopCoolingDemand | 6876.15 | 2619.77 | 03-JAN-06:00 | 2164952.48 | 29-AUG-14:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 4643.64 | 0.00 | 12-JAN-01:20 | 0.00 | 10-AUG-16:00 |
Water:Plant | 4316.01 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
MainsWater:Facility | 4643.64 | 0.00 | 12-JAN-01:20 | 0.00 | 10-AUG-16:00 |
MainsWater:Plant | 4316.01 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:HVAC | 327.64 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:30 |
Humidifier:Water | 327.64 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:30 |
MainsWater:HVAC | 327.64 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:30 |
Humidifier:MainsWater | 327.64 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:30 |
HeatRejection:Water | 2035.84 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
HeatRejection:MainsWater | 2035.84 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 1158.07 | 0.00 | 03-JAN-00:10 | 1074031.87 | 02-JAN-06:10 |
PlantLoopHeatingDemand:Plant | 425.04 | 0.00 | 01-JAN-00:10 | 50360.09 | 09-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 425.04 | 0.00 | 01-JAN-00:10 | 50360.09 | 09-FEB-12:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 33713.60 | 96507.34 | 22-JAN-02:00 | 8339306.18 | 29-AUG-14:40 |
EnergyTransfer:Building | 17384.25 | 88493.29 | 22-JAN-13:50 | 1537564.65 | 10-AUG-16:00 |
EnergyTransfer:Zone:BASEMENT | 691.17 | 0.00 | 01-JAN-00:10 | 79812.85 | 29-MAY-19:40 |
Heating:EnergyTransfer | 207.69 | 0.00 | 10-JAN-22:10 | 953318.53 | 02-JAN-05:50 |
Heating:EnergyTransfer:Zone:BASEMENT | 6.12 | 0.00 | 01-JAN-00:10 | 58363.17 | 20-AUG-18:40 |
Cooling:EnergyTransfer | 17176.56 | 87373.24 | 16-JAN-08:10 | 1537564.65 | 10-AUG-16:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 685.05 | 0.00 | 01-JAN-00:10 | 79245.44 | 10-OCT-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 605.93 | 0.00 | 01-JAN-00:10 | 50487.75 | 28-AUG-13:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 605.93 | 0.00 | 01-JAN-00:10 | 50487.75 | 28-AUG-13:10 |
EnergyTransfer:Zone:CORE_MID | 4144.42 | 0.00 | 01-JAN-00:10 | 408860.92 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 3.49 | 0.00 | 01-JAN-00:10 | 341673.64 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4140.93 | 0.00 | 01-JAN-00:10 | 408860.92 | 10-AUG-16:00 |
EnergyTransfer:Zone:CORE_TOP | 370.64 | 0.00 | 01-JAN-00:40 | 66581.28 | 02-JAN-05:30 |
Heating:EnergyTransfer:Zone:CORE_TOP | 4.85 | 0.00 | 01-JAN-00:20 | 66581.28 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 365.80 | 0.00 | 01-JAN-00:10 | 48408.80 | 10-AUG-15:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 60.53 | 0.00 | 01-JAN-00:10 | 8827.53 | 24-JUL-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 60.53 | 0.00 | 01-JAN-00:10 | 8827.53 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 56.53 | 0.00 | 01-JAN-00:10 | 14421.55 | 31-JUL-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 586.72 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 56.53 | 0.00 | 01-JAN-00:10 | 14421.55 | 31-JUL-08:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 86.12 | 0.00 | 01-JAN-00:10 | 20616.33 | 04-OCT-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.04 | 0.00 | 01-JAN-00:10 | 4872.59 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 86.08 | 0.00 | 01-JAN-00:10 | 20616.33 | 04-OCT-12:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 86.41 | 0.00 | 01-JAN-00:10 | 18390.17 | 10-AUG-16:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 86.41 | 0.00 | 01-JAN-00:10 | 18390.17 | 10-AUG-16:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 408.54 | 0.00 | 01-JAN-00:10 | 92600.00 | 02-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 29.78 | 0.00 | 01-JAN-00:10 | 92600.00 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 378.75 | 0.00 | 01-JAN-00:10 | 73246.04 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 450.98 | 0.00 | 01-JAN-00:10 | 146837.16 | 10-AUG-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 21.98 | 0.00 | 01-JAN-00:10 | 93609.17 | 02-JAN-05:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 429.00 | 0.00 | 01-JAN-00:10 | 146837.16 | 10-AUG-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 717.79 | 0.00 | 01-JAN-00:10 | 216283.54 | 04-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 21.55 | 0.00 | 01-JAN-00:10 | 139364.90 | 02-JAN-05:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 696.25 | 0.00 | 01-JAN-00:10 | 216283.54 | 04-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 498.10 | 0.00 | 01-JAN-00:10 | 164544.07 | 10-AUG-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 11.70 | 0.00 | 01-JAN-00:10 | 86806.90 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 486.41 | 0.00 | 01-JAN-00:10 | 164544.07 | 10-AUG-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 45.31 | 0.00 | 01-JAN-00:40 | 10774.67 | 02-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 11.87 | 0.00 | 01-JAN-00:40 | 10774.67 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 33.44 | 0.00 | 01-JAN-00:10 | 8542.97 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 46.40 | 0.00 | 01-JAN-00:40 | 14493.16 | 10-AUG-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 7.61 | 0.00 | 01-JAN-00:40 | 12455.59 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 38.79 | 0.00 | 01-JAN-00:10 | 14493.16 | 10-AUG-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 71.98 | 0.00 | 01-JAN-00:40 | 22203.48 | 04-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 8.83 | 0.00 | 01-JAN-00:40 | 18282.88 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 63.15 | 0.00 | 01-JAN-00:10 | 22203.48 | 04-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 49.91 | 0.00 | 01-JAN-00:40 | 17076.78 | 10-AUG-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.75 | 0.00 | 01-JAN-00:40 | 11291.95 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 45.16 | 0.00 | 01-JAN-00:10 | 17076.78 | 10-AUG-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 53.51 | 0.00 | 01-JAN-00:10 | 6466.52 | 14-AUG-16:00 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.78 | 0.00 | 01-JAN-00:10 | 3557.71 | 10-DEC-13:50 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 52.73 | 0.00 | 01-JAN-00:10 | 6466.52 | 14-AUG-16:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 321.45 | 0.00 | 01-JAN-00:10 | 127075.57 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 46.87 | 0.00 | 01-JAN-00:10 | 127075.57 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 274.58 | 0.00 | 01-JAN-00:10 | 50357.23 | 10-AUG-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 61.49 | 0.00 | 01-JAN-00:40 | 18774.34 | 02-JAN-05:40 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 24.04 | 0.00 | 01-JAN-00:40 | 18774.34 | 02-JAN-05:40 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 37.45 | 0.00 | 01-JAN-00:10 | 15658.08 | 10-AUG-14:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.65 | 750.92 | 15-JAN-06:30 | 8194.29 | 06-AUG-19:30 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.65 | 750.92 | 15-JAN-06:30 | 8194.29 | 06-AUG-19:30 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1158.12 | 7.31 | 29-JAN-22:30 | 77663.96 | 06-AUG-19:10 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 2.65 | 0.00 | 03-JAN-10:50 | 5443.03 | 03-JAN-00:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1155.47 | 0.00 | 01-JAN-00:10 | 77663.96 | 06-AUG-19:10 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 106.37 | 0.04 | 24-JAN-10:50 | 7849.45 | 06-AUG-19:10 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.80 | 0.00 | 02-JAN-16:50 | 595.12 | 08-JAN-17:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 105.56 | 0.00 | 01-JAN-00:10 | 7849.45 | 06-AUG-19:10 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7155.89 | 86579.71 | 16-JAN-10:10 | 367570.61 | 29-AUG-20:30 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7155.89 | 86579.71 | 16-JAN-10:10 | 367570.61 | 29-AUG-20:30 |
EnergyTransfer:Plant | 9553.76 | 0.00 | 03-JAN-00:10 | 4822584.88 | 29-AUG-14:40 |
WaterSystems:EnergyTransfer | 425.04 | 0.00 | 01-JAN-00:10 | 50360.09 | 09-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 425.04 | 0.00 | 01-JAN-00:10 | 50360.09 | 09-FEB-12:20 |
EnergyTransfer:HVAC | 6775.59 | 2145.10 | 03-JAN-05:50 | 1996938.65 | 29-AUG-14:40 |
HeatingCoils:EnergyTransfer | 733.04 | 0.00 | 01-JAN-09:20 | 1067836.94 | 02-JAN-06:10 |
PlantLoopHeatingDemand:HVAC | 733.04 | 0.00 | 01-JAN-09:20 | 1067836.94 | 02-JAN-06:10 |
HeatingCoils:PlantLoopHeatingDemand | 733.04 | 0.00 | 01-JAN-09:20 | 1067836.94 | 02-JAN-06:10 |
CoolingCoils:EnergyTransfer | 6042.55 | 2144.63 | 03-JAN-06:00 | 1996938.65 | 29-AUG-14:40 |
LoopToLoop:EnergyTransfer | 2666.91 | 0.00 | 01-JAN-00:10 | 1518574.25 | 29-AUG-14:40 |
Boilers:EnergyTransfer | 729.52 | 0.00 | 01-JAN-09:20 | 1155638.17 | 02-JAN-05:20 |
Chillers:EnergyTransfer | 2660.10 | 0.00 | 01-JAN-00:10 | 1518742.15 | 29-AUG-14:40 |
HeatRejection:EnergyTransfer | 3072.19 | 0.00 | 01-JAN-00:10 | 1760308.48 | 29-AUG-14:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 6.119 | -685.054 | 0.000 | 0.000 | 92.713 | 214.693 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -52.867 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -605.932 | 0.000 | 0.000 | 83.435 | 192.810 | 289.609 | 0.000 | 0.000 | 0.000 | 40.079 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 3.492 | -4140.907 | 0.000 | 0.000 | 846.583 | 1928.097 | 2896.074 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1533.341 |
CORE_TOP | 0.000 | 0.000 | 4.847 | -365.793 | 0.000 | 0.000 | 87.568 | 192.810 | 289.607 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -209.038 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -60.530 | 0.000 | 0.000 | 10.714 | 14.501 | 36.365 | 15.703 | 0.000 | 0.017 | 56.208 | 0.000 | -66.180 | 0.000 | -6.798 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.001 | -56.530 | 0.000 | 0.000 | 7.067 | 9.194 | 23.435 | 36.516 | 0.000 | 0.012 | 24.874 | 0.000 | -40.242 | 0.000 | -4.328 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.035 | -86.082 | 0.000 | 0.000 | 10.819 | 14.063 | 36.365 | 74.960 | 0.000 | 0.015 | 16.738 | 0.000 | -60.249 | 0.000 | -6.664 | 0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -86.406 | 0.000 | 0.000 | 6.841 | 9.180 | 23.435 | 39.236 | 0.000 | 0.009 | 59.689 | 0.000 | -47.071 | 0.000 | -4.912 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 29.784 | -378.752 | 0.000 | 0.000 | 114.073 | 144.519 | 363.647 | 170.063 | 0.000 | 0.469 | 262.210 | 0.000 | -573.995 | 0.000 | -132.019 | -0.008 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 21.976 | -429.004 | 0.000 | 0.000 | 54.466 | 91.697 | 234.348 | 370.432 | 0.000 | 0.270 | 107.026 | 0.000 | -363.046 | 0.000 | -88.164 | -0.002 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 21.546 | -696.241 | 0.000 | 0.000 | 111.757 | 140.424 | 363.653 | 754.555 | 0.000 | 0.335 | 8.676 | 0.000 | -566.018 | 0.000 | -138.687 | -0.008 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 11.696 | -486.404 | 0.000 | 0.000 | 74.226 | 91.561 | 234.347 | 407.687 | 0.000 | 0.225 | 149.244 | 0.000 | -390.150 | 0.000 | -92.432 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 11.871 | -33.439 | 0.000 | 0.000 | 11.642 | 14.449 | 36.365 | 17.498 | 0.000 | 0.052 | 10.150 | 0.000 | -53.317 | 0.000 | -15.271 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 7.613 | -38.787 | 0.000 | 0.000 | 7.468 | 9.169 | 23.435 | 37.419 | 0.000 | 0.029 | 0.003 | 0.000 | -34.075 | 0.000 | -10.273 | -1.996 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 8.828 | -63.152 | 0.000 | 0.000 | 11.411 | 14.041 | 36.365 | 76.303 | 0.000 | 0.038 | 0.000 | 0.000 | -52.926 | 0.000 | -16.055 | -14.853 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 4.749 | -45.163 | 0.000 | 0.000 | 7.545 | 9.155 | 23.435 | 41.024 | 0.000 | 0.026 | 6.908 | 0.000 | -36.842 | 0.000 | -10.837 | -0.001 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -136.649 | 0.000 | 0.000 | 0.000 | 2.890 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -20.121 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 2.646 | -1155.470 | 0.000 | 0.000 | 0.000 | 28.897 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -414.879 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.803 | -105.562 | 0.000 | 0.000 | 0.000 | 2.890 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -52.012 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7155.898 | 0.000 | 0.000 | 0.000 | 62.553 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -401.511 |
GROUNDFLOOR_PLENUM | 0.780 | -52.728 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.025 | 65.907 | 0.000 | 0.000 | 0.000 | -13.983 | 0.000 |
MIDFLOOR_PLENUM | 46.872 | -274.581 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.554 | 459.155 | 0.000 | 0.000 | 0.000 | -232.000 | -0.002 |
TOPFLOOR_PLENUM | 24.040 | -37.452 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.029 | 37.789 | 0.000 | 0.000 | 0.000 | -24.406 | -0.001 |
Total Facility | 71.692 | -364.761 | 136.004 | -16811.755 | 0.000 | 0.000 | 1538.327 | 3187.590 | 14676.305 | 2041.396 | 0.000 | 2.106 | 1304.656 | 0.000 | -2284.110 | 0.000 | -796.829 | -2700.642 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 30-MAY-03:53 | 0.00 | 0.00 | 0.00 | -120770.91 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 106715.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 30-AUG-04:12 | 0.00 | 0.00 | 0.00 | -82346.56 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 75871.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 25-AUG-04:12 | 0.00 | 0.00 | 0.00 | -757462.36 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 692712.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 25-AUG-04:11 | 0.00 | 0.00 | 0.00 | -70722.36 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 64247.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -8827.47 | 0.00 | 0.00 | 1114.39 | 1033.52 | 2160.55 | 5492.65 | 0.00 | 36.47 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1010.11 |
PERIMETER_BOT_ZN_2 | 13-AUG-08:21 | 0.00 | 0.00 | 0.00 | -22999.64 | 0.00 | 0.00 | 20.97 | 37.00 | 464.11 | 18904.47 | 0.00 | 0.00 | 3762.67 | 0.00 | -0.00 | 0.00 | -189.58 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-SEP-14:02 | 0.00 | 0.00 | 0.00 | -26455.30 | 0.00 | 0.00 | 36.03 | 57.42 | 720.19 | 18679.18 | 0.00 | 0.00 | 7073.96 | 0.00 | -0.00 | 0.00 | -111.48 | 0.00 |
PERIMETER_BOT_ZN_4 | 23-JUL-17:01 | 0.00 | 0.00 | 0.00 | -27576.53 | 0.00 | 0.00 | 0.00 | 40.86 | 360.35 | 20785.95 | 0.00 | 0.00 | 6443.22 | 0.00 | -0.00 | 0.00 | -53.86 | 0.00 |
PERIMETER_MID_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -73245.17 | 0.00 | 0.00 | 11143.91 | 10335.18 | 21605.52 | 55741.35 | 0.00 | 809.70 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26390.48 |
PERIMETER_MID_ZN_2 | 13-AUG-09:01 | 0.00 | 0.00 | 0.00 | -240873.26 | 0.00 | 0.00 | 207.27 | 370.02 | 4641.14 | 162070.73 | 0.00 | 0.00 | 77668.14 | 0.00 | -0.00 | 0.00 | -4084.04 | 0.00 |
PERIMETER_MID_ZN_1 | 10-SEP-12:22 | 0.00 | 0.00 | 0.00 | -277694.19 | 0.00 | 0.00 | 334.60 | 574.19 | 7201.95 | 253439.98 | 0.00 | 0.00 | 19903.53 | 0.00 | -0.00 | 0.00 | -3760.05 | 0.00 |
PERIMETER_MID_ZN_4 | 30-JUL-18:11 | 0.00 | 0.00 | 0.00 | -268034.90 | 0.00 | 0.00 | 0.00 | 408.59 | 3603.49 | 164334.75 | 0.00 | 0.00 | 101797.73 | 0.00 | -0.00 | 0.00 | -2109.66 | 0.00 |
PERIMETER_TOP_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -8542.89 | 0.00 | 0.00 | 1114.39 | 1033.52 | 2160.55 | 5500.69 | 0.00 | 98.84 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1365.10 |
PERIMETER_TOP_ZN_2 | 30-JUL-09:02 | 0.00 | 0.00 | 0.00 | -21731.41 | 0.00 | 0.00 | 21.28 | 37.00 | 464.11 | 16005.85 | 0.00 | 0.00 | 5439.72 | 0.00 | -0.00 | 0.00 | -236.55 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-13:12 | 0.00 | 0.00 | 0.00 | -29594.24 | 0.00 | 0.00 | 33.66 | 57.42 | 720.19 | 22318.55 | 0.00 | 0.00 | 6917.93 | 0.00 | -0.00 | 0.00 | -453.51 | 0.00 |
PERIMETER_TOP_ZN_4 | 30-JUL-17:41 | 0.00 | 0.00 | 0.00 | -28753.16 | 0.00 | 0.00 | 0.00 | 40.86 | 360.35 | 19124.04 | 0.00 | 0.00 | 9473.45 | 0.00 | -0.00 | 0.00 | -245.54 | 0.00 |
DATACENTER_BOT_ZN_6 | 06-AUG-19:30 | 0.00 | 0.00 | 0.00 | -8198.73 | 0.00 | 0.00 | 0.00 | 15.39 | 7794.42 | 0.00 | 0.00 | 0.00 | 388.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 06-AUG-19:12 | 0.00 | 0.00 | 0.00 | -77783.45 | 0.00 | 0.00 | 0.00 | 153.92 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -314.69 |
DATACENTER_TOP_ZN_6 | 06-AUG-19:06 | 0.00 | 0.00 | 0.00 | -7870.51 | 0.00 | 0.00 | 0.00 | 15.39 | 7794.42 | 0.00 | 0.00 | 0.00 | 60.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 13-AUG-18:22 | 0.00 | 0.00 | 0.00 | -368737.23 | 0.00 | 0.00 | 0.00 | 333.20 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -11228.49 |
GROUNDFLOOR_PLENUM | 12-JUN-05:03 | 0.00 | -7770.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7896.95 | 0.00 | -0.00 | 0.00 | -126.75 | 0.00 |
MIDFLOOR_PLENUM | 14-JAN-05:11 | 0.00 | -65032.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93206.07 | 0.00 | -0.00 | 0.00 | -28173.63 | 0.00 |
TOPFLOOR_PLENUM | 10-AUG-14:50 | 0.00 | -15657.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.53 | 15576.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-AUG-04:11 | 0.00 | 58202.84 | 0.00 | -1642112.31 | 0.00 | 0.00 | 0.00 | 10745.36 | 587299.42 | 0.00 | 0.00 | 0.00 | 1087564.31 | 0.00 | -78108.73 | 0.00 | -23590.88 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 30-JUL-17:42 | 0.00 | 0.00 | 130155.16 | 0.00 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -144211.05 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-05:11 | 0.00 | 0.00 | 376647.75 | -0.00 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -441397.58 |
CORE_TOP | 02-JAN-04:01 | 0.00 | 0.00 | 73020.59 | -0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -79495.57 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 09-JAN-06:01 | 0.00 | 0.00 | 4870.98 | -0.00 | 0.00 | 0.00 | 91.04 | 43.48 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3381.81 | 0.00 | -90.47 | -2152.03 |
PERIMETER_BOT_ZN_1 | 17-JAN-06:02 | 0.00 | 0.00 | 10010.36 | -0.00 | 0.00 | 0.00 | 148.90 | 67.47 | 960.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3991.47 | 0.00 | -91.77 | -7103.76 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JAN-04:56 | 0.00 | 0.00 | 100835.02 | -0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20409.79 | 0.00 | -8555.49 | -80000.06 |
PERIMETER_MID_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 142367.86 | -0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -14102.97 | 0.00 | -6798.78 | -126705.60 |
PERIMETER_MID_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 191538.29 | -0.00 | 0.00 | 0.00 | 0.00 | 674.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21233.16 | 0.00 | -10116.88 | -168318.70 |
PERIMETER_MID_ZN_4 | 02-JAN-05:11 | 0.00 | 0.00 | 137672.81 | -0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -14653.06 | 0.00 | -6805.49 | -121453.71 |
PERIMETER_TOP_ZN_3 | 02-JAN-05:21 | 0.00 | 0.00 | 11648.51 | -0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1961.91 | 0.00 | -1180.63 | -9319.00 |
PERIMETER_TOP_ZN_2 | 02-JAN-05:21 | 0.00 | 0.00 | 16751.60 | -0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1338.09 | 0.00 | -819.54 | -15117.91 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:21 | 0.00 | 0.00 | 22997.32 | -0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2015.72 | 0.00 | -1223.47 | -20571.17 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:21 | 0.00 | 0.00 | 16761.53 | -0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1402.59 | 0.00 | -849.82 | -15033.05 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 03-JAN-00:50 | 0.00 | 0.00 | 5443.03 | 0.00 | 0.00 | 0.00 | 0.00 | 153.92 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25083.01 |
DATACENTER_TOP_ZN_6 | 08-JAN-17:30 | 0.00 | 0.00 | 595.12 | 0.00 | 0.00 | 0.00 | 0.00 | 13.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2557.67 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 29-DEC-05:11 | 11471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1270.38 | -10200.84 |
MIDFLOOR_PLENUM | 02-JAN-06:03 | 143797.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5005.82 | -138791.32 |
TOPFLOOR_PLENUM | 02-JAN-05:32 | 21519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2029.97 | -19489.75 |
Total Facility | 02-JAN-05:31 | -116238.75 | 224076.77 | 1006914.83 | -224076.77 | 0.00 | 0.00 | 0.00 | 10745.36 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -96446.21 | 0.00 | -69348.75 | -968051.71 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.5617 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.5617 | 0.2158 | 1.0000 | 1.2001 | 0.2158 | ||
VAV_BOT WITH REHEAT | 10.7033 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 9.1306 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 101.7094 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 84.1786 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.2260 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 8.7579 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.5246 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.5246 | 0.0157 | 1.0000 | 0.3384 | 0.0157 | ||
AIRLOOP DATACENTER BOT | 0.4972 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4972 | 0.0314 | 1.0000 | 0.0156 | 0.0314 | ||
AIRLOOP DATACENTER MID | 4.7645 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.7645 | 0.0328 | 1.0000 | 0.1563 | 0.0328 | ||
AIRLOOP DATACENTER TOP | 0.4833 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4833 | 0.0323 | 1.0000 | 0.0156 | 0.0323 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.5617 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.5617 | 1.0000 | 1.0000 | 1.2001 | 0.2158 | ||
VAV_BOT WITH REHEAT | 5.3516 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.9708 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 50.8547 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 29.0388 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.1130 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.9589 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.5246 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.5246 | 1.0000 | 1.0000 | 0.3384 | 0.0157 | ||
AIRLOOP DATACENTER BOT | 0.4972 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4972 | 1.0000 | 1.0000 | 0.0156 | 0.0314 | ||
AIRLOOP DATACENTER MID | 4.7645 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.7645 | 1.0000 | 1.0000 | 0.1563 | 0.0328 | ||
AIRLOOP DATACENTER TOP | 0.4833 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4833 | 1.0000 | 1.0000 | 0.0156 | 0.0323 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2001 | 1.0000 | 1.2001 | 1.000 | 1.2001 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 0.0000 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 0.0000 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2001 | 1.2001 | 1.2001 |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
AIRLOOP DATACENTER BASEMENT | 0.00 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 | |
AIRLOOP DATACENTER BOT | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 | |
AIRLOOP DATACENTER MID | 0.00 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 | |
AIRLOOP DATACENTER TOP | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.5617 | 5.5617 | 5.5617 | 1.2001 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7735 | 5.7735 | 1.8995 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 54.0567 | 54.0567 | 18.5415 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2353 | 5.2353 | 1.8795 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7689 | 0.7689 | 0.2391 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2274 | 1.2274 | 0.2455 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4664 | 1.4664 | 0.2933 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4671 | 1.4671 | 0.2934 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.8087 | 6.8087 | 2.3286 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.6743 | 12.6743 | 2.5349 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.9018 | 14.9018 | 2.9804 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.2678 | 13.2678 | 2.6536 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7739 | 0.7739 | 0.2361 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2543 | 1.2543 | 0.2509 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5763 | 1.5763 | 0.3153 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3862 | 1.3862 | 0.2772 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4972 | 0.4972 | 0.4972 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.7645 | 4.7645 | 4.7645 | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4833 | 0.4833 | 0.4833 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.5246 | 21.5246 | 21.5246 | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.5617 | 5.5617 | 5.5617 | 5.5617 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 10.7033 | 9.1306 | 10.7033 | 2.9708 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 101.7094 | 84.1786 | 101.7094 | 29.0388 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.2260 | 8.7579 | 10.2260 | 2.9589 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.5246 | 21.5246 | 21.5246 | 21.5246 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4972 | 0.4972 | 0.4972 | 0.4972 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.7645 | 4.7645 | 4.7645 | 4.7645 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4833 | 0.4833 | 0.4833 | 0.4833 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.5617 | 5.5617 | 5.5617 | 1.2001 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8868 | 2.8868 | 1.8995 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 27.0284 | 27.0284 | 18.5415 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6177 | 2.6177 | 1.8795 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3844 | 0.3844 | 0.2391 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6137 | 0.6137 | 0.2455 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7332 | 0.7332 | 0.2933 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7335 | 0.7335 | 0.2934 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.4043 | 3.4043 | 2.3286 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.3372 | 6.3372 | 2.5349 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.4509 | 7.4509 | 2.9804 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.6339 | 6.6339 | 2.6536 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3870 | 0.3870 | 0.2361 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6271 | 0.6271 | 0.2509 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7881 | 0.7881 | 0.3153 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6931 | 0.6931 | 0.2772 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4972 | 0.4972 | 0.4972 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.7645 | 4.7645 | 4.7645 | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4833 | 0.4833 | 0.4833 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.5246 | 21.5246 | 21.5246 | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.5617 | 5.5617 | 5.5617 | 5.5617 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 5.3516 | 2.9708 | 2.9708 | 2.9708 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 50.8547 | 29.0388 | 29.0388 | 29.0388 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.1130 | 2.9589 | 2.9589 | 2.9589 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.5246 | 21.5246 | 21.5246 | 21.5246 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4972 | 0.4972 | 0.4972 | 0.4972 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.7645 | 4.7645 | 4.7645 | 4.7645 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4833 | 0.4833 | 0.4833 | 0.4833 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:58:48
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 20.50 |
Number of hours cooling loads not met | 79.33 |
Number of hours not met | 99.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 969.65 | 1406716.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 412.09 | 241566.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Other | 941.70 | 168013.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3187.59 | 321032.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 348.75 | 39974.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.88 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 55.00 | 3452.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1895.08 | 122221.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2076.54 | 142073.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 219.29 | 39886.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 31.86 | 30141.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Other | 429.83 | 49248.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 880.75 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 592.25 | 78591.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.31 | 25160.60 |
Natural Gas | 0.00 | 1561.90 |
Additional | 0.00 | 0.00 |
Total | 14676.31 | 26722.50 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 68.82 |
Space Heating | 0.00 |
Space Cooling | 29.23 |
Fans (All) | 44.83 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.84 |
Miscellaneous (All) | 543.19 |
Subtotal | 543.19 |
Natural Gas [MJ/m2] | |
Space Heating | 20.93 |
Service Water Heating | 12.79 |
Miscellaneous (All) | 33.72 |
Subtotal | 33.72 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.93 |
Space Heating | 3.63 |
Space Cooling | 5.07 |
Fans (All) | 7.77 |
Service Water Heating | 2.22 |
Receptacle Equipment | 54.92 |
Miscellaneous | 14.47 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
BLDG_LIGHT_SCH | 2676. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.335089E+12 |
February | 0.000 | 0.177922E+12 |
March | 0.000 | 0.600956E+11 |
April | 0.000 | 0.226347E+11 |
May | 0.000 | 0.355293E+10 |
June | 0.000 | 0.238240E+09 |
July | 0.000 | 0.106002E+10 |
August | 0.000 | 0.880973E+09 |
September | 0.000 | 0.154530E+10 |
October | 0.000 | 0.193206E+11 |
November | 0.000 | 0.115682E+12 |
December | 0.000 | 0.231630E+12 |
Annual Sum or Average | 0.969652E+12 | |
Minimum of Months | 0.000 | 0.238240E+09 |
Maximum of Months | 0.000 | 0.335089E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.335089E+12 |
February | 0.000 | 0.177922E+12 |
March | 0.000 | 0.600956E+11 |
April | 0.000 | 0.226347E+11 |
May | 0.000 | 0.355293E+10 |
June | 0.000 | 0.238240E+09 |
July | 0.000 | 0.106002E+10 |
August | 0.000 | 0.880973E+09 |
September | 0.000 | 0.154530E+10 |
October | 0.000 | 0.193206E+11 |
November | 0.000 | 0.115682E+12 |
December | 0.000 | 0.231630E+12 |
Annual Sum or Average | 0.969652E+12 | |
Minimum of Months | 0.000 | 0.238240E+09 |
Maximum of Months | 0.000 | 0.335089E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Meter
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.335089E+12 |
February | 0.000 | 0.177922E+12 |
March | 0.000 | 0.600956E+11 |
April | 0.000 | 0.226347E+11 |
May | 0.000 | 0.355293E+10 |
June | 0.000 | 0.238240E+09 |
July | 0.000 | 0.106002E+10 |
August | 0.000 | 0.880973E+09 |
September | 0.000 | 0.154530E+10 |
October | 0.000 | 0.193206E+11 |
November | 0.000 | 0.115682E+12 |
December | 0.000 | 0.231630E+12 |
Annual Sum or Average | 0.969652E+12 | |
Minimum of Months | 0.000 | 0.238240E+09 |
Maximum of Months | 0.000 | 0.335089E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.335089E+12 |
February | 0.000 | 0.177922E+12 |
March | 0.000 | 0.600956E+11 |
April | 0.000 | 0.226347E+11 |
May | 0.000 | 0.355293E+10 |
June | 0.000 | 0.238240E+09 |
July | 0.000 | 0.106002E+10 |
August | 0.000 | 0.880973E+09 |
September | 0.000 | 0.154530E+10 |
October | 0.000 | 0.193206E+11 |
November | 0.000 | 0.115682E+12 |
December | 0.000 | 0.231630E+12 |
Annual Sum or Average | 0.969652E+12 | |
Minimum of Months | 0.000 | 0.238240E+09 |
Maximum of Months | 0.000 | 0.335089E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Meter
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.335089E+12 |
February | 0.000 | 0.177922E+12 |
March | 0.000 | 0.600956E+11 |
April | 0.000 | 0.226347E+11 |
May | 0.000 | 0.355293E+10 |
June | 0.000 | 0.238240E+09 |
July | 0.000 | 0.106002E+10 |
August | 0.000 | 0.880973E+09 |
September | 0.000 | 0.154530E+10 |
October | 0.000 | 0.193206E+11 |
November | 0.000 | 0.115682E+12 |
December | 0.000 | 0.231630E+12 |
Annual Sum or Average | 0.969652E+12 | |
Minimum of Months | 0.000 | 0.238240E+09 |
Maximum of Months | 0.000 | 0.335089E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.335089E+12 |
February | 0.000 | 0.177922E+12 |
March | 0.000 | 0.600956E+11 |
April | 0.000 | 0.226347E+11 |
May | 0.000 | 0.355293E+10 |
June | 0.000 | 0.238240E+09 |
July | 0.000 | 0.106002E+10 |
August | 0.000 | 0.880973E+09 |
September | 0.000 | 0.154530E+10 |
October | 0.000 | 0.193206E+11 |
November | 0.000 | 0.115682E+12 |
December | 0.000 | 0.231630E+12 |
Annual Sum or Average | 0.969652E+12 | |
Minimum of Months | 0.000 | 0.238240E+09 |
Maximum of Months | 0.000 | 0.335089E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.335089E+12 |
February | 0.000 | 0.177922E+12 |
March | 0.000 | 0.600956E+11 |
April | 0.000 | 0.226347E+11 |
May | 0.000 | 0.355293E+10 |
June | 0.000 | 0.238240E+09 |
July | 0.000 | 0.106002E+10 |
August | 0.000 | 0.880973E+09 |
September | 0.000 | 0.154530E+10 |
October | 0.000 | 0.193206E+11 |
November | 0.000 | 0.115682E+12 |
December | 0.000 | 0.231630E+12 |
Annual Sum or Average | 0.969652E+12 | |
Minimum of Months | 0.000 | 0.238240E+09 |
Maximum of Months | 0.000 | 0.335089E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Meter
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.335089E+12 |
February | 0.000 | 0.177922E+12 |
March | 0.000 | 0.600956E+11 |
April | 0.000 | 0.226347E+11 |
May | 0.000 | 0.355293E+10 |
June | 0.000 | 0.238240E+09 |
July | 0.000 | 0.106002E+10 |
August | 0.000 | 0.880973E+09 |
September | 0.000 | 0.154530E+10 |
October | 0.000 | 0.193206E+11 |
November | 0.000 | 0.115682E+12 |
December | 0.000 | 0.231630E+12 |
Annual Sum or Average | 0.969652E+12 | |
Minimum of Months | 0.000 | 0.238240E+09 |
Maximum of Months | 0.000 | 0.335089E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Meter
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.335089E+12 |
February | 0.000 | 0.177922E+12 |
March | 0.000 | 0.600956E+11 |
April | 0.000 | 0.226347E+11 |
May | 0.000 | 0.355293E+10 |
June | 0.000 | 0.238240E+09 |
July | 0.000 | 0.106002E+10 |
August | 0.000 | 0.880973E+09 |
September | 0.000 | 0.154530E+10 |
October | 0.000 | 0.193206E+11 |
November | 0.000 | 0.115682E+12 |
December | 0.000 | 0.231630E+12 |
Annual Sum or Average | 0.969652E+12 | |
Minimum of Months | 0.000 | 0.238240E+09 |
Maximum of Months | 0.000 | 0.335089E+12 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.492707E+11 | 119628.29 | 01-JAN-22:43 | 6.10 | 5.29 | 0.566074E+10 | 7499.17 | 05-JAN-10:09 | 2.70 | 2.49 |
February | 0.466316E+11 | 118486.01 | 21-FEB-02:50 | 2.38 | 1.47 | 0.513602E+10 | 7499.15 | 08-FEB-10:09 | 2.48 | 1.47 |
March | 0.583477E+11 | 113191.31 | 27-MAR-03:53 | 5.00 | 3.72 | 0.613217E+10 | 7499.14 | 02-MAR-10:09 | 7.07 | 5.03 |
April | 0.558148E+11 | 113273.14 | 30-APR-23:11 | 9.97 | 9.03 | 0.544973E+10 | 7499.09 | 26-APR-09:00 | 16.10 | 10.79 |
May | 0.576016E+11 | 120776.98 | 30-MAY-03:53 | 10.60 | 9.73 | 0.590048E+10 | 7499.14 | 05-MAY-09:20 | 16.33 | 13.63 |
June | 0.597954E+11 | 115966.79 | 19-JUN-01:52 | 11.70 | 9.31 | 0.588196E+10 | 7499.17 | 09-JUN-13:20 | 21.87 | 13.50 |
July | 0.611099E+11 | 119549.54 | 04-JUL-19:40 | 14.27 | 10.48 | 0.547378E+10 | 7499.13 | 11-JUL-09:20 | 16.13 | 15.49 |
August | 0.668244E+11 | 115090.50 | 21-AUG-00:32 | 14.27 | 12.35 | 0.613730E+10 | 7499.54 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.580845E+11 | 120686.93 | 11-SEP-03:53 | 13.30 | 11.37 | 0.545161E+10 | 7499.12 | 14-SEP-09:20 | 17.57 | 15.53 |
October | 0.595189E+11 | 117105.22 | 09-OCT-18:12 | 15.53 | 11.92 | 0.566889E+10 | 7499.10 | 12-OCT-09:09 | 9.18 | 7.85 |
November | 0.573191E+11 | 120178.31 | 12-NOV-16:10 | 4.72 | 3.82 | 0.561344E+10 | 7499.06 | 10-NOV-10:09 | 6.88 | 5.74 |
December | 0.547360E+11 | 115448.97 | 25-DEC-23:42 | -0.5 | -0.5 | 0.546849E+10 | 7499.27 | 13-DEC-14:20 | 6.90 | 5.04 |
Annual Sum or Average | 0.685054E+12 | 0.679746E+11 | ||||||||
Minimum of Months | 0.466316E+11 | 113191.31 | -0.5 | -0.5 | 0.513602E+10 | 7499.06 | 2.48 | 1.47 | ||
Maximum of Months | 0.668244E+11 | 120776.98 | 15.53 | 12.35 | 0.613730E+10 | 7499.54 | 23.80 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.367217E+11 | 67885.96 | 02-JAN-05:12 | 6.10 | 5.29 | 0.505500E+10 | 6734.78 | 20-JAN-10:09 | 4.18 | 2.79 |
February | 0.378867E+11 | 71142.56 | 24-FEB-05:11 | 13.90 | 12.04 | 0.459851E+10 | 6734.79 | 08-FEB-10:09 | 2.48 | 1.47 |
March | 0.513447E+11 | 71975.29 | 09-MAR-05:12 | 11.33 | 9.25 | 0.550115E+10 | 6734.79 | 02-MAR-10:09 | 7.07 | 5.03 |
April | 0.540628E+11 | 75610.35 | 28-APR-03:02 | 11.70 | 10.15 | 0.488330E+10 | 6734.74 | 26-APR-09:50 | 15.73 | 10.54 |
May | 0.512090E+11 | 75601.65 | 05-MAY-04:12 | 13.13 | 10.58 | 0.528468E+10 | 6734.80 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.556825E+11 | 78188.22 | 12-JUN-03:02 | 15.00 | 13.35 | 0.526953E+10 | 6734.84 | 05-JUN-09:00 | 14.40 | 11.88 |
July | 0.605783E+11 | 82092.44 | 11-JUL-03:02 | 15.00 | 13.39 | 0.489556E+10 | 6734.69 | 12-JUL-13:09 | 16.05 | 14.01 |
August | 0.690867E+11 | 82344.23 | 30-AUG-04:12 | 17.13 | 15.27 | 0.549413E+10 | 6735.20 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.493350E+11 | 79265.09 | 01-SEP-04:12 | 15.93 | 13.70 | 0.488094E+10 | 6734.76 | 22-SEP-09:09 | 14.37 | 14.11 |
October | 0.486940E+11 | 76333.86 | 10-OCT-03:02 | 12.20 | 10.91 | 0.507874E+10 | 6734.77 | 12-OCT-09:09 | 9.18 | 7.85 |
November | 0.460934E+11 | 75434.31 | 04-NOV-04:12 | 13.13 | 11.87 | 0.503063E+10 | 6734.74 | 13-NOV-10:00 | 2.80 | 2.80 |
December | 0.452388E+11 | 68640.96 | 30-DEC-05:12 | 5.73 | 5.57 | 0.490180E+10 | 6734.86 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.605934E+12 | 0.608740E+11 | ||||||||
Minimum of Months | 0.367217E+11 | 67885.96 | 5.73 | 5.29 | 0.459851E+10 | 6734.69 | 2.48 | 1.47 | ||
Maximum of Months | 0.690867E+11 | 82344.23 | 17.13 | 15.27 | 0.550115E+10 | 6735.20 | 23.80 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234144E+11 | 26007.44 | 12-JAN-17:00 | 7.20 | 5.40 | 0.467423E+10 | 6734.61 | 27-JAN-14:09 | 9.72 | 8.08 |
February | 0.245838E+11 | 44238.32 | 10-FEB-06:02 | 2.43 | 1.36 | 0.442906E+10 | 6734.78 | 08-FEB-10:09 | 2.48 | 1.47 |
March | 0.330978E+11 | 57187.12 | 02-MAR-06:02 | 0.60 | -0.2 | 0.542122E+10 | 6734.78 | 02-MAR-10:09 | 7.07 | 5.03 |
April | 0.336319E+11 | 62152.40 | 28-APR-05:02 | 11.10 | 9.92 | 0.483312E+10 | 6734.72 | 26-APR-09:00 | 16.10 | 10.79 |
May | 0.400779E+11 | 64510.33 | 05-MAY-05:02 | 12.98 | 10.75 | 0.524893E+10 | 6734.77 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.424551E+11 | 66428.88 | 23-JUN-04:11 | 14.23 | 11.91 | 0.524000E+10 | 6734.75 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.431901E+11 | 67870.73 | 11-JUL-04:11 | 15.00 | 13.39 | 0.486461E+10 | 6734.70 | 12-JUL-13:09 | 16.05 | 14.01 |
August | 0.472326E+11 | 75747.06 | 25-AUG-04:12 | 17.93 | 15.41 | 0.546741E+10 | 6735.01 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.393006E+11 | 68936.72 | 01-SEP-04:11 | 15.93 | 13.70 | 0.484902E+10 | 6734.73 | 22-SEP-09:09 | 14.37 | 14.11 |
October | 0.335981E+11 | 61026.11 | 10-OCT-05:03 | 12.20 | 11.22 | 0.501804E+10 | 6734.78 | 12-OCT-09:09 | 9.18 | 7.85 |
November | 0.278086E+11 | 55524.57 | 07-NOV-06:02 | 12.12 | 9.84 | 0.491298E+10 | 6734.75 | 15-NOV-10:09 | 7.30 | 5.71 |
December | 0.257025E+11 | 29036.67 | 06-DEC-16:20 | 2.57 | 2.27 | 0.469149E+10 | 6734.75 | 12-DEC-10:00 | 5.00 | 4.51 |
Annual Sum or Average | 0.414093E+12 | 0.596501E+11 | ||||||||
Minimum of Months | 0.234144E+11 | 26007.44 | 0.60 | -0.2 | 0.442906E+10 | 6734.61 | 2.48 | 1.47 | ||
Maximum of Months | 0.472326E+11 | 75747.06 | 17.93 | 15.41 | 0.546741E+10 | 6735.01 | 23.80 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187438E+11 | 20399.96 | 11-JAN-16:00 | 14.40 | 10.48 | 0.423618E+10 | 6479.88 | 12-JAN-14:00 | 7.20 | 5.88 |
February | 0.196603E+11 | 27165.01 | 28-FEB-17:00 | 14.40 | 10.81 | 0.399531E+10 | 6734.41 | 03-FEB-14:00 | 10.00 | 7.00 |
March | 0.266398E+11 | 31131.62 | 15-MAR-16:00 | 11.10 | 7.71 | 0.506811E+10 | 6734.66 | 02-MAR-14:50 | 13.30 | 8.48 |
April | 0.294226E+11 | 54829.93 | 28-APR-05:02 | 11.10 | 9.92 | 0.466359E+10 | 6734.70 | 26-APR-09:50 | 15.73 | 10.54 |
May | 0.370404E+11 | 57924.54 | 05-MAY-05:02 | 12.98 | 10.75 | 0.517023E+10 | 6734.74 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.415222E+11 | 64451.35 | 12-JUN-04:12 | 14.80 | 13.60 | 0.520948E+10 | 6734.73 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.435663E+11 | 65743.40 | 24-JUL-05:02 | 15.87 | 13.14 | 0.484545E+10 | 6734.66 | 20-JUL-13:09 | 26.20 | 16.64 |
August | 0.468171E+11 | 70721.86 | 25-AUG-04:11 | 17.93 | 15.41 | 0.544219E+10 | 6735.00 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.351124E+11 | 59566.96 | 01-SEP-05:03 | 15.50 | 13.56 | 0.476210E+10 | 6734.68 | 08-SEP-09:20 | 16.47 | 13.27 |
October | 0.268934E+11 | 38284.89 | 04-OCT-16:00 | 21.10 | 11.38 | 0.475627E+10 | 6734.60 | 03-OCT-13:00 | 18.30 | 10.43 |
November | 0.212635E+11 | 25358.78 | 02-NOV-16:00 | 13.30 | 10.88 | 0.444313E+10 | 6734.53 | 03-NOV-13:00 | 13.30 | 12.64 |
December | 0.191150E+11 | 18729.01 | 06-DEC-17:00 | 1.10 | 0.98 | 0.414878E+10 | 6554.15 | 06-DEC-14:00 | 5.00 | 4.36 |
Annual Sum or Average | 0.365797E+12 | 0.567408E+11 | ||||||||
Minimum of Months | 0.187438E+11 | 18729.01 | 1.10 | 0.98 | 0.399531E+10 | 6479.88 | 5.00 | 4.36 | ||
Maximum of Months | 0.468171E+11 | 70721.86 | 21.10 | 15.41 | 0.544219E+10 | 6735.00 | 26.20 | 16.64 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272341E+10 | 2695.32 | 11-JAN-16:00 | 14.40 | 10.48 | 0.565550E+09 | 827.94 | 11-JAN-14:00 | 14.40 | 10.48 |
February | 0.288603E+10 | 4639.34 | 27-FEB-15:30 | 19.70 | 12.29 | 0.534296E+09 | 845.61 | 27-FEB-14:39 | 19.43 | 11.91 |
March | 0.413279E+10 | 5002.17 | 10-MAR-14:30 | 16.40 | 11.75 | 0.670422E+09 | 845.63 | 31-MAR-13:09 | 8.98 | 7.52 |
April | 0.521910E+10 | 7214.57 | 27-APR-15:20 | 27.20 | 17.14 | 0.604809E+09 | 845.62 | 27-APR-13:20 | 26.10 | 16.44 |
May | 0.582375E+10 | 6885.97 | 05-MAY-13:30 | 23.85 | 16.50 | 0.656883E+09 | 845.63 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.683588E+10 | 8212.86 | 12-JUN-05:01 | 14.40 | 13.42 | 0.659418E+09 | 845.64 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.797076E+10 | 8827.53 | 24-JUL-15:00 | 30.60 | 18.76 | 0.613625E+09 | 845.63 | 28-JUL-13:00 | 20.00 | 15.25 |
August | 0.892130E+10 | 8463.89 | 25-AUG-14:00 | 27.40 | 18.72 | 0.688556E+09 | 845.69 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.535861E+10 | 6419.07 | 12-SEP-14:30 | 24.40 | 16.61 | 0.606408E+09 | 845.62 | 22-SEP-09:09 | 14.37 | 14.11 |
October | 0.420596E+10 | 5094.13 | 04-OCT-15:00 | 21.70 | 11.47 | 0.623364E+09 | 845.62 | 25-OCT-09:20 | 12.07 | 9.96 |
November | 0.339342E+10 | 4424.49 | 06-NOV-11:50 | 13.80 | 9.99 | 0.606216E+09 | 845.62 | 03-NOV-09:20 | 11.30 | 10.68 |
December | 0.305945E+10 | 3029.76 | 29-DEC-13:20 | 11.10 | 9.04 | 0.575379E+09 | 845.61 | 05-DEC-14:00 | 10.00 | 7.00 |
Annual Sum or Average | 0.605305E+11 | 0.740493E+10 | ||||||||
Minimum of Months | 0.272341E+10 | 2695.32 | 11.10 | 9.04 | 0.534296E+09 | 827.94 | 8.98 | 7.00 | ||
Maximum of Months | 0.892130E+10 | 8827.53 | 30.60 | 18.76 | 0.688556E+09 | 845.69 | 26.10 | 16.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239422E+10 | 2488.31 | 11-JAN-14:20 | 14.40 | 10.48 | 0.341188E+09 | 520.50 | 05-JAN-10:09 | 2.70 | 2.49 |
February | 0.260865E+10 | 4077.38 | 08-FEB-09:35 | 1.67 | 0.56 | 0.326725E+09 | 544.95 | 08-FEB-10:09 | 2.48 | 1.47 |
March | 0.378437E+10 | 8784.67 | 14-MAR-08:55 | 7.80 | 5.89 | 0.416219E+09 | 544.96 | 02-MAR-10:09 | 7.07 | 5.03 |
April | 0.500504E+10 | 11737.49 | 27-APR-08:20 | 16.67 | 12.15 | 0.384011E+09 | 544.96 | 20-APR-09:00 | 10.00 | 7.48 |
May | 0.556136E+10 | 19949.40 | 14-MAY-08:42 | 16.32 | 11.32 | 0.418575E+09 | 544.97 | 15-MAY-09:00 | 18.90 | 13.24 |
June | 0.670837E+10 | 18010.78 | 25-JUN-08:62 | 15.78 | 11.62 | 0.422180E+09 | 544.96 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.732903E+10 | 20783.76 | 30-JUL-08:32 | 19.83 | 15.42 | 0.392193E+09 | 544.96 | 18-JUL-09:09 | 17.07 | 11.94 |
August | 0.820654E+10 | 23002.24 | 13-AUG-08:21 | 20.20 | 15.49 | 0.439748E+09 | 545.04 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.537547E+10 | 19249.15 | 04-SEP-08:41 | 16.52 | 12.44 | 0.384703E+09 | 544.96 | 15-SEP-09:30 | 17.25 | 14.68 |
October | 0.395174E+10 | 9470.66 | 04-OCT-08:40 | 15.03 | 10.24 | 0.387185E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.27 |
November | 0.294617E+10 | 3997.43 | 15-NOV-08:35 | 5.93 | 4.79 | 0.360466E+09 | 544.95 | 02-NOV-09:09 | 11.20 | 10.21 |
December | 0.265919E+10 | 2569.89 | 05-DEC-09:35 | 6.13 | 4.74 | 0.336118E+09 | 542.61 | 04-DEC-10:09 | 8.30 | 4.43 |
Annual Sum or Average | 0.565301E+11 | 0.460931E+10 | ||||||||
Minimum of Months | 0.239422E+10 | 2488.31 | 1.67 | 0.56 | 0.326725E+09 | 520.50 | 2.48 | 1.47 | ||
Maximum of Months | 0.820654E+10 | 23002.24 | 20.20 | 15.49 | 0.439748E+09 | 545.04 | 23.80 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366170E+10 | 15711.32 | 20-JAN-13:20 | 6.70 | 4.71 | 0.554873E+09 | 848.64 | 20-JAN-14:09 | 6.78 | 4.75 |
February | 0.491876E+10 | 20492.42 | 12-FEB-14:13 | 6.70 | 1.45 | 0.530219E+09 | 885.66 | 07-FEB-14:09 | 7.88 | 4.77 |
March | 0.714934E+10 | 17660.89 | 14-MAR-13:30 | 15.00 | 9.99 | 0.657944E+09 | 911.76 | 01-MAR-14:09 | 11.97 | 6.48 |
April | 0.761036E+10 | 18597.58 | 02-APR-11:53 | 17.20 | 10.91 | 0.596750E+09 | 845.66 | 27-APR-13:20 | 26.10 | 16.44 |
May | 0.719533E+10 | 12098.18 | 15-MAY-12:40 | 22.60 | 13.48 | 0.649836E+09 | 845.66 | 15-MAY-13:09 | 22.88 | 13.74 |
June | 0.773279E+10 | 10080.37 | 21-JUN-13:30 | 22.50 | 15.03 | 0.655043E+09 | 845.66 | 28-JUN-13:50 | 24.90 | 15.64 |
July | 0.945419E+10 | 14776.79 | 31-JUL-12:40 | 26.83 | 18.24 | 0.611192E+09 | 845.66 | 28-JUL-13:50 | 20.55 | 15.37 |
August | 0.117442E+11 | 25085.92 | 13-AUG-12:23 | 26.30 | 18.22 | 0.686574E+09 | 845.73 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.921873E+10 | 26454.28 | 10-SEP-14:02 | 22.30 | 14.57 | 0.602039E+09 | 845.66 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.777619E+10 | 24291.64 | 08-OCT-13:22 | 18.90 | 13.90 | 0.614093E+09 | 902.80 | 03-OCT-13:09 | 18.30 | 10.43 |
November | 0.484530E+10 | 19854.43 | 11-NOV-12:23 | 5.85 | 4.71 | 0.586914E+09 | 857.26 | 15-NOV-14:09 | 9.82 | 6.79 |
December | 0.477565E+10 | 16343.12 | 05-DEC-12:30 | 10.30 | 6.12 | 0.555445E+09 | 859.05 | 05-DEC-11:00 | 10.00 | 6.06 |
Annual Sum or Average | 0.860826E+11 | 0.730092E+10 | ||||||||
Minimum of Months | 0.366170E+10 | 10080.37 | 5.85 | 1.45 | 0.530219E+09 | 845.66 | 6.78 | 4.75 | ||
Maximum of Months | 0.117442E+11 | 26454.28 | 26.83 | 18.24 | 0.686574E+09 | 911.76 | 26.10 | 16.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.335321E+10 | 4810.96 | 05-JAN-15:40 | 6.30 | 4.80 | 0.361509E+09 | 544.83 | 05-JAN-14:00 | 6.70 | 5.17 |
February | 0.394291E+10 | 10423.23 | 27-FEB-15:30 | 19.70 | 12.29 | 0.353591E+09 | 544.95 | 22-FEB-14:09 | 10.00 | 9.05 |
March | 0.624291E+10 | 15178.44 | 11-MAR-05:11 | 10.60 | 10.60 | 0.441490E+09 | 544.96 | 09-MAR-14:09 | 14.90 | 12.34 |
April | 0.855590E+10 | 22791.09 | 23-APR-18:02 | 15.13 | 9.16 | 0.395513E+09 | 544.96 | 27-APR-13:20 | 26.10 | 16.44 |
May | 0.751632E+10 | 25844.85 | 07-MAY-16:22 | 21.95 | 16.23 | 0.423898E+09 | 544.96 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.899825E+10 | 25235.71 | 25-JUN-15:42 | 21.70 | 13.10 | 0.426563E+09 | 544.97 | 28-JUN-13:50 | 24.90 | 15.64 |
July | 0.120465E+11 | 27576.35 | 23-JUL-17:01 | 26.60 | 15.62 | 0.397546E+09 | 544.96 | 28-JUL-13:50 | 20.55 | 15.37 |
August | 0.135224E+11 | 27511.19 | 06-AUG-16:31 | 23.53 | 15.25 | 0.445758E+09 | 545.03 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.712346E+10 | 25504.58 | 10-SEP-16:42 | 22.20 | 14.21 | 0.391211E+09 | 544.95 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.567269E+10 | 14438.94 | 02-OCT-05:01 | 9.40 | 8.23 | 0.405907E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.27 |
November | 0.470871E+10 | 16798.23 | 04-NOV-04:11 | 13.13 | 11.87 | 0.401504E+09 | 544.95 | 03-NOV-09:09 | 11.20 | 10.58 |
December | 0.472304E+10 | 11690.88 | 30-DEC-05:11 | 5.73 | 5.57 | 0.391695E+09 | 544.97 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.864063E+11 | 0.483619E+10 | ||||||||
Minimum of Months | 0.335321E+10 | 4810.96 | 5.73 | 4.80 | 0.353591E+09 | 544.83 | 6.70 | 5.11 | ||
Maximum of Months | 0.135224E+11 | 27576.35 | 26.60 | 16.23 | 0.445758E+09 | 545.03 | 26.10 | 16.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.871341E+09 | 2190.13 | 11-JAN-16:00 | 14.40 | 10.48 | 0.474521E+09 | 706.43 | 11-JAN-14:00 | 14.40 | 10.48 |
February | 0.138483E+10 | 2765.43 | 27-FEB-15:40 | 19.60 | 12.33 | 0.448322E+09 | 798.20 | 28-FEB-14:00 | 13.90 | 10.80 |
March | 0.250189E+10 | 2736.49 | 10-MAR-14:20 | 16.50 | 11.84 | 0.578790E+09 | 823.05 | 10-MAR-14:00 | 16.10 | 11.49 |
April | 0.297911E+10 | 5644.37 | 27-APR-15:50 | 27.20 | 16.95 | 0.550090E+09 | 845.62 | 27-APR-13:00 | 26.10 | 16.81 |
May | 0.420531E+10 | 6013.41 | 05-MAY-13:30 | 23.85 | 16.50 | 0.631448E+09 | 845.62 | 26-MAY-13:09 | 12.48 | 11.47 |
June | 0.486846E+10 | 6541.22 | 21-JUN-15:40 | 24.80 | 15.83 | 0.645095E+09 | 845.63 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.545976E+10 | 7324.60 | 24-JUL-15:00 | 30.60 | 18.76 | 0.603796E+09 | 845.62 | 28-JUL-13:00 | 20.00 | 15.25 |
August | 0.588034E+10 | 7312.65 | 25-AUG-14:00 | 27.40 | 18.72 | 0.677229E+09 | 845.66 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.401748E+10 | 5383.17 | 12-SEP-14:50 | 24.40 | 16.67 | 0.582627E+09 | 845.61 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.277881E+10 | 3336.30 | 04-OCT-15:30 | 21.40 | 11.43 | 0.554216E+09 | 845.59 | 05-OCT-13:50 | 16.10 | 10.62 |
November | 0.183031E+10 | 2497.15 | 04-NOV-14:00 | 21.10 | 15.93 | 0.501830E+09 | 774.79 | 02-NOV-13:00 | 14.40 | 11.36 |
December | 0.109771E+10 | 1963.34 | 14-DEC-12:00 | 13.30 | 8.42 | 0.464056E+09 | 699.21 | 29-DEC-14:00 | 10.60 | 8.76 |
Annual Sum or Average | 0.378753E+11 | 0.671202E+10 | ||||||||
Minimum of Months | 0.871341E+09 | 1963.34 | 13.30 | 8.42 | 0.448322E+09 | 699.21 | 10.60 | 8.76 | ||
Maximum of Months | 0.588034E+10 | 7324.60 | 30.60 | 18.76 | 0.677229E+09 | 845.66 | 26.10 | 16.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.654464E+09 | 2129.02 | 11-JAN-16:00 | 14.40 | 10.48 | 0.221279E+09 | 419.73 | 05-JAN-09:50 | 2.23 | 2.02 |
February | 0.129862E+10 | 2858.98 | 27-FEB-15:30 | 19.70 | 12.29 | 0.210183E+09 | 495.64 | 08-FEB-09:00 | 2.20 | 1.26 |
March | 0.269808E+10 | 6625.88 | 14-MAR-08:55 | 7.80 | 5.89 | 0.271491E+09 | 521.21 | 14-MAR-10:09 | 10.28 | 7.91 |
April | 0.379694E+10 | 11506.45 | 27-APR-08:50 | 17.52 | 12.19 | 0.265275E+09 | 521.22 | 27-APR-12:20 | 25.37 | 15.71 |
May | 0.483380E+10 | 14344.41 | 14-MAY-08:53 | 16.70 | 11.52 | 0.293171E+09 | 521.23 | 15-MAY-10:09 | 19.18 | 13.23 |
June | 0.599590E+10 | 21260.98 | 25-JUN-08:32 | 16.33 | 11.86 | 0.302212E+09 | 521.22 | 07-JUN-10:09 | 13.40 | 10.32 |
July | 0.634750E+10 | 24047.78 | 30-JUL-08:51 | 20.60 | 15.78 | 0.283471E+09 | 521.22 | 06-JUL-10:00 | 18.30 | 13.78 |
August | 0.701458E+10 | 24092.27 | 13-AUG-09:01 | 21.20 | 16.01 | 0.317251E+09 | 521.30 | 09-AUG-10:09 | 23.92 | 15.99 |
September | 0.481095E+10 | 20417.92 | 10-SEP-08:22 | 15.25 | 13.15 | 0.269455E+09 | 521.21 | 14-SEP-07:10 | 14.18 | 13.39 |
October | 0.297299E+10 | 8323.21 | 04-OCT-09:00 | 15.60 | 10.48 | 0.257603E+09 | 521.22 | 05-OCT-10:09 | 14.08 | 9.35 |
November | 0.156390E+10 | 2659.70 | 04-NOV-13:00 | 20.60 | 16.04 | 0.228298E+09 | 479.47 | 15-NOV-09:30 | 6.95 | 5.42 |
December | 0.912685E+09 | 2005.63 | 05-DEC-09:45 | 6.42 | 4.92 | 0.215448E+09 | 435.90 | 05-DEC-09:50 | 6.42 | 4.92 |
Annual Sum or Average | 0.429004E+11 | 0.313514E+10 | ||||||||
Minimum of Months | 0.654464E+09 | 2005.63 | 6.42 | 4.92 | 0.210183E+09 | 419.73 | 2.20 | 1.26 | ||
Maximum of Months | 0.701458E+10 | 24092.27 | 21.20 | 16.04 | 0.317251E+09 | 521.30 | 25.37 | 15.99 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224026E+10 | 15859.74 | 20-JAN-13:30 | 6.70 | 4.71 | 0.509824E+09 | 849.08 | 20-JAN-14:09 | 6.78 | 4.75 |
February | 0.387525E+10 | 21670.00 | 12-FEB-13:22 | 6.40 | 1.11 | 0.494076E+09 | 909.53 | 08-FEB-14:09 | 6.88 | 3.84 |
March | 0.591418E+10 | 18210.20 | 14-MAR-13:40 | 15.20 | 10.16 | 0.617799E+09 | 933.50 | 01-MAR-14:09 | 11.97 | 6.48 |
April | 0.583883E+10 | 17449.45 | 27-APR-13:00 | 26.10 | 16.26 | 0.567183E+09 | 845.66 | 27-APR-13:30 | 26.10 | 16.53 |
May | 0.620403E+10 | 11808.26 | 04-MAY-13:10 | 22.48 | 15.27 | 0.629364E+09 | 845.66 | 15-MAY-13:09 | 22.88 | 13.74 |
June | 0.633126E+10 | 9595.48 | 21-JUN-13:30 | 22.50 | 15.03 | 0.638445E+09 | 845.66 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.754760E+10 | 24381.79 | 30-JUL-13:32 | 26.50 | 17.69 | 0.599255E+09 | 845.66 | 28-JUL-13:50 | 20.55 | 15.37 |
August | 0.941997E+10 | 25070.42 | 13-AUG-12:23 | 26.30 | 18.22 | 0.675267E+09 | 845.70 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.883515E+10 | 27766.81 | 10-SEP-14:22 | 22.50 | 14.47 | 0.587442E+09 | 845.66 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.691570E+10 | 26632.24 | 08-OCT-13:12 | 18.53 | 13.80 | 0.585029E+09 | 929.01 | 03-OCT-13:20 | 18.30 | 10.43 |
November | 0.351258E+10 | 20066.35 | 11-NOV-13:02 | 6.88 | 5.23 | 0.534585E+09 | 861.90 | 15-NOV-14:09 | 9.82 | 6.79 |
December | 0.299001E+10 | 17211.47 | 03-DEC-13:23 | 12.20 | 6.23 | 0.505807E+09 | 845.65 | 05-DEC-14:00 | 10.00 | 7.00 |
Annual Sum or Average | 0.696248E+11 | 0.694408E+10 | ||||||||
Minimum of Months | 0.224026E+10 | 9595.48 | 6.40 | 1.11 | 0.494076E+09 | 845.65 | 6.78 | 3.84 | ||
Maximum of Months | 0.941997E+10 | 27766.81 | 26.50 | 18.22 | 0.675267E+09 | 933.50 | 26.10 | 16.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100573E+10 | 2414.01 | 05-JAN-15:50 | 6.20 | 4.70 | 0.305090E+09 | 480.18 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.170080E+10 | 6452.95 | 27-FEB-15:40 | 19.60 | 12.33 | 0.290579E+09 | 544.90 | 27-FEB-14:00 | 20.00 | 12.15 |
March | 0.305772E+10 | 9727.81 | 14-MAR-16:00 | 17.20 | 10.93 | 0.367655E+09 | 544.94 | 02-MAR-14:00 | 13.30 | 8.56 |
April | 0.406886E+10 | 13932.80 | 01-APR-17:07 | 26.52 | 12.37 | 0.349053E+09 | 544.95 | 27-APR-13:20 | 26.10 | 16.44 |
May | 0.550942E+10 | 25796.46 | 14-MAY-16:31 | 22.97 | 11.83 | 0.396071E+09 | 544.95 | 15-MAY-13:09 | 22.88 | 13.74 |
June | 0.600712E+10 | 23185.21 | 25-JUN-16:42 | 21.70 | 13.37 | 0.404798E+09 | 544.95 | 28-JUN-13:30 | 24.70 | 15.67 |
July | 0.768098E+10 | 26803.92 | 30-JUL-18:11 | 25.93 | 17.30 | 0.384365E+09 | 544.95 | 28-JUL-13:00 | 20.00 | 15.25 |
August | 0.763456E+10 | 24015.85 | 06-AUG-17:11 | 23.53 | 15.14 | 0.429687E+09 | 544.99 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.533929E+10 | 24761.72 | 10-SEP-16:21 | 22.20 | 14.31 | 0.364146E+09 | 544.93 | 06-SEP-13:00 | 15.00 | 11.80 |
October | 0.332094E+10 | 11212.75 | 04-OCT-16:00 | 21.10 | 11.38 | 0.347355E+09 | 544.64 | 04-OCT-13:00 | 21.10 | 11.38 |
November | 0.196906E+10 | 4295.12 | 04-NOV-15:50 | 20.18 | 15.91 | 0.316212E+09 | 530.59 | 10-NOV-14:00 | 10.00 | 6.83 |
December | 0.134639E+10 | 2614.06 | 05-DEC-15:40 | 7.40 | 5.39 | 0.299238E+09 | 509.59 | 05-DEC-15:50 | 6.75 | 4.97 |
Annual Sum or Average | 0.486409E+11 | 0.425425E+10 | ||||||||
Minimum of Months | 0.100573E+10 | 2414.01 | 6.20 | 4.70 | 0.290579E+09 | 480.18 | 6.10 | 4.61 | ||
Maximum of Months | 0.768098E+10 | 26803.92 | 26.52 | 17.30 | 0.429687E+09 | 544.99 | 26.10 | 16.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.421363E+09 | 2078.17 | 11-JAN-16:00 | 14.40 | 10.48 | 0.465753E+09 | 668.14 | 11-JAN-14:00 | 14.40 | 10.48 |
February | 0.819742E+09 | 2672.02 | 27-FEB-15:50 | 19.50 | 12.37 | 0.433332E+09 | 772.43 | 28-FEB-14:00 | 13.90 | 10.80 |
March | 0.183804E+10 | 2709.20 | 10-MAR-14:40 | 16.30 | 11.67 | 0.545472E+09 | 807.38 | 10-MAR-14:00 | 16.10 | 11.49 |
April | 0.260883E+10 | 6386.33 | 27-APR-15:30 | 27.20 | 17.08 | 0.525150E+09 | 845.62 | 27-APR-13:00 | 26.10 | 16.81 |
May | 0.397464E+10 | 6420.88 | 05-MAY-13:30 | 23.85 | 16.50 | 0.610357E+09 | 845.62 | 26-MAY-13:20 | 12.77 | 11.65 |
June | 0.486403E+10 | 7360.51 | 21-JUN-15:40 | 24.80 | 15.83 | 0.632751E+09 | 845.63 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.559730E+10 | 8542.97 | 24-JUL-15:00 | 30.60 | 18.76 | 0.596339E+09 | 845.63 | 20-JUL-13:09 | 26.20 | 16.64 |
August | 0.593414E+10 | 8151.08 | 09-AUG-15:30 | 28.70 | 18.81 | 0.667872E+09 | 845.66 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.375888E+10 | 5877.75 | 14-SEP-15:50 | 24.32 | 17.01 | 0.558022E+09 | 845.61 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.213351E+10 | 3244.57 | 04-OCT-15:30 | 21.40 | 11.43 | 0.517971E+09 | 827.63 | 04-OCT-13:00 | 21.10 | 11.38 |
November | 0.104009E+10 | 2411.48 | 04-NOV-14:50 | 21.10 | 15.93 | 0.474566E+09 | 737.76 | 02-NOV-13:00 | 14.40 | 11.36 |
December | 0.448457E+09 | 1774.50 | 29-DEC-16:00 | 10.60 | 8.76 | 0.449748E+09 | 662.71 | 29-DEC-14:00 | 10.60 | 8.76 |
Annual Sum or Average | 0.334390E+11 | 0.647733E+10 | ||||||||
Minimum of Months | 0.421363E+09 | 1774.50 | 10.60 | 8.76 | 0.433332E+09 | 662.71 | 10.60 | 8.76 | ||
Maximum of Months | 0.593414E+10 | 8542.97 | 30.60 | 18.81 | 0.667872E+09 | 845.66 | 26.20 | 16.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.359866E+09 | 2023.54 | 11-JAN-16:00 | 14.40 | 10.48 | 0.299611E+09 | 407.54 | 11-JAN-14:00 | 14.40 | 10.48 |
February | 0.891080E+09 | 2735.90 | 27-FEB-15:00 | 20.00 | 12.15 | 0.279128E+09 | 467.45 | 03-FEB-10:30 | 9.15 | 6.87 |
March | 0.209523E+10 | 5094.68 | 14-MAR-09:25 | 8.90 | 6.82 | 0.359422E+09 | 544.96 | 02-MAR-10:09 | 7.07 | 5.03 |
April | 0.339308E+10 | 10946.67 | 27-APR-09:00 | 17.80 | 12.19 | 0.356209E+09 | 544.96 | 27-APR-13:09 | 26.10 | 16.35 |
May | 0.455940E+10 | 13447.87 | 14-MAY-09:12 | 17.43 | 11.76 | 0.395675E+09 | 544.97 | 15-MAY-09:00 | 18.90 | 13.24 |
June | 0.591648E+10 | 18395.43 | 25-JUN-09:02 | 16.88 | 12.17 | 0.410682E+09 | 544.97 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.639658E+10 | 21732.52 | 30-JUL-09:02 | 20.87 | 15.87 | 0.384543E+09 | 544.97 | 20-JUL-13:09 | 26.20 | 16.64 |
August | 0.700332E+10 | 21385.70 | 13-AUG-09:12 | 21.50 | 16.13 | 0.431383E+09 | 545.04 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.446224E+10 | 17133.76 | 10-SEP-08:32 | 15.53 | 13.26 | 0.361097E+09 | 544.96 | 15-SEP-09:30 | 17.25 | 14.68 |
October | 0.235314E+10 | 7096.07 | 04-OCT-09:00 | 15.60 | 10.48 | 0.339963E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.27 |
November | 0.942821E+09 | 2532.78 | 04-NOV-14:00 | 21.10 | 15.93 | 0.302016E+09 | 463.42 | 02-NOV-13:00 | 14.40 | 11.36 |
December | 0.414078E+09 | 1721.98 | 05-DEC-14:00 | 10.60 | 6.37 | 0.289408E+09 | 411.67 | 05-DEC-14:00 | 10.00 | 7.00 |
Annual Sum or Average | 0.387873E+11 | 0.420914E+10 | ||||||||
Minimum of Months | 0.359866E+09 | 1721.98 | 8.90 | 6.37 | 0.279128E+09 | 407.54 | 7.07 | 5.03 | ||
Maximum of Months | 0.700332E+10 | 21732.52 | 21.50 | 16.13 | 0.431383E+09 | 545.04 | 26.20 | 16.64 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154928E+10 | 15694.11 | 20-JAN-13:20 | 6.70 | 4.71 | 0.493257E+09 | 845.64 | 20-JAN-14:20 | 6.87 | 4.79 |
February | 0.298884E+10 | 16962.08 | 27-FEB-14:10 | 18.58 | 11.53 | 0.476170E+09 | 862.86 | 08-FEB-14:09 | 6.88 | 3.84 |
March | 0.493442E+10 | 18560.96 | 14-MAR-13:40 | 15.20 | 10.16 | 0.590811E+09 | 894.44 | 01-MAR-14:09 | 11.97 | 6.48 |
April | 0.529287E+10 | 18049.82 | 27-APR-13:10 | 26.10 | 16.35 | 0.547154E+09 | 845.67 | 27-APR-13:09 | 26.10 | 16.35 |
May | 0.594545E+10 | 12392.11 | 04-MAY-13:10 | 22.48 | 15.27 | 0.609299E+09 | 845.66 | 15-MAY-13:09 | 22.88 | 13.74 |
June | 0.638607E+10 | 10360.85 | 21-JUN-13:30 | 22.50 | 15.03 | 0.624230E+09 | 845.66 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.775283E+10 | 25077.39 | 30-JUL-13:02 | 26.20 | 17.72 | 0.589659E+09 | 845.68 | 20-JUL-13:09 | 26.20 | 16.64 |
August | 0.953179E+10 | 26835.99 | 13-AUG-13:13 | 26.73 | 18.51 | 0.664022E+09 | 845.70 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.845011E+10 | 29593.68 | 10-SEP-13:12 | 21.13 | 14.28 | 0.566484E+09 | 845.66 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.587365E+10 | 26866.40 | 08-OCT-13:42 | 19.63 | 14.08 | 0.557771E+09 | 896.76 | 03-OCT-13:20 | 18.30 | 10.43 |
November | 0.244352E+10 | 16846.90 | 04-NOV-13:30 | 20.85 | 15.99 | 0.504834E+09 | 845.64 | 15-NOV-14:00 | 8.90 | 6.48 |
December | 0.200401E+10 | 14879.72 | 05-DEC-12:30 | 10.30 | 6.12 | 0.485382E+09 | 845.65 | 05-DEC-14:00 | 10.00 | 7.00 |
Annual Sum or Average | 0.631528E+11 | 0.670907E+10 | ||||||||
Minimum of Months | 0.154928E+10 | 10360.85 | 6.70 | 4.71 | 0.476170E+09 | 845.64 | 6.87 | 3.84 | ||
Maximum of Months | 0.953179E+10 | 29593.68 | 26.73 | 18.51 | 0.664022E+09 | 896.76 | 26.20 | 16.64 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.618765E+09 | 2457.14 | 05-JAN-15:50 | 6.20 | 4.70 | 0.301782E+09 | 471.25 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.119824E+10 | 5937.72 | 27-FEB-15:40 | 19.60 | 12.33 | 0.284434E+09 | 537.22 | 27-FEB-14:00 | 20.00 | 12.15 |
March | 0.252563E+10 | 9714.29 | 14-MAR-16:00 | 17.20 | 10.93 | 0.352913E+09 | 544.89 | 02-MAR-14:00 | 13.30 | 8.56 |
April | 0.377876E+10 | 14162.16 | 26-APR-16:40 | 24.40 | 14.10 | 0.336111E+09 | 544.96 | 27-APR-13:09 | 26.10 | 16.35 |
May | 0.539430E+10 | 24698.19 | 07-MAY-16:42 | 21.78 | 16.18 | 0.383091E+09 | 544.95 | 15-MAY-13:09 | 22.88 | 13.74 |
June | 0.607513E+10 | 22972.13 | 18-JUN-17:01 | 17.12 | 12.22 | 0.395299E+09 | 544.94 | 09-JUN-13:39 | 22.03 | 13.52 |
July | 0.783567E+10 | 28753.08 | 30-JUL-17:41 | 26.70 | 17.69 | 0.377765E+09 | 544.96 | 20-JUL-13:09 | 26.20 | 16.64 |
August | 0.773390E+10 | 25073.36 | 06-AUG-17:11 | 23.53 | 15.14 | 0.421397E+09 | 544.99 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.518216E+10 | 25493.72 | 10-SEP-17:11 | 21.67 | 14.05 | 0.349837E+09 | 544.93 | 12-SEP-13:00 | 24.40 | 16.53 |
October | 0.278895E+10 | 11188.96 | 04-OCT-16:00 | 21.10 | 11.38 | 0.330590E+09 | 541.28 | 04-OCT-13:00 | 21.10 | 11.38 |
November | 0.128688E+10 | 3946.60 | 04-NOV-15:40 | 20.37 | 15.92 | 0.305124E+09 | 508.07 | 15-NOV-14:00 | 8.90 | 6.48 |
December | 0.744690E+09 | 2571.16 | 05-DEC-15:40 | 7.40 | 5.39 | 0.293398E+09 | 487.15 | 05-DEC-15:50 | 6.75 | 4.97 |
Annual Sum or Average | 0.451631E+11 | 0.413174E+10 | ||||||||
Minimum of Months | 0.618765E+09 | 2457.14 | 6.20 | 4.70 | 0.284434E+09 | 471.25 | 6.10 | 4.61 | ||
Maximum of Months | 0.783567E+10 | 28753.08 | 26.70 | 17.69 | 0.421397E+09 | 544.99 | 26.20 | 16.64 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161666E+10 | 3791.11 | 04-JAN-06:10 | 5.18 | 4.57 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.212242E+10 | 4437.05 | 28-FEB-06:15 | 10.60 | 9.73 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.388874E+10 | 4801.69 | 01-MAR-06:10 | -0.1 | -1.4 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.479783E+10 | 5786.11 | 29-APR-05:15 | 8.50 | 8.50 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.487734E+10 | 6482.15 | 01-MAY-05:15 | 12.20 | 10.44 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.580522E+10 | 7769.92 | 12-JUN-05:03 | 14.40 | 13.42 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.679133E+10 | 7534.82 | 05-JUL-05:03 | 11.78 | 8.57 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.759110E+10 | 7510.85 | 28-AUG-05:03 | 14.83 | 13.93 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.520923E+10 | 7352.94 | 05-SEP-05:15 | 10.77 | 9.27 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.419961E+10 | 7418.01 | 10-OCT-05:15 | 12.20 | 11.16 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.318410E+10 | 5975.10 | 06-NOV-06:03 | 11.28 | 8.35 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.264447E+10 | 4297.65 | 04-DEC-06:10 | 3.22 | 1.95 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.527280E+11 | 0.00 | ||||||||
Minimum of Months | 0.161666E+10 | 3791.11 | -0.1 | -1.4 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.759110E+10 | 7769.92 | 14.83 | 13.93 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.341355E+09 | 6503.23 | 14-JAN-05:11 | 2.20 | 1.36 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.727408E+09 | 6088.86 | 18-FEB-05:01 | -1.2 | -2.3 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.140671E+10 | 4830.39 | 06-MAR-05:11 | 6.70 | 6.18 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.192366E+10 | 4588.86 | 29-APR-05:10 | 8.40 | 8.40 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.292813E+10 | 4511.88 | 06-MAY-05:10 | 13.07 | 11.42 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.362597E+10 | 4396.07 | 13-JUN-05:10 | 11.70 | 10.14 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.426845E+10 | 4482.52 | 15-JUL-20:45 | 18.40 | 15.89 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.483258E+10 | 5035.72 | 10-AUG-16:00 | 31.20 | 18.72 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.361275E+10 | 4683.79 | 12-SEP-05:13 | 12.03 | 11.22 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.207141E+10 | 4341.89 | 05-OCT-05:10 | 8.30 | 5.22 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.104339E+10 | 5689.83 | 24-NOV-05:11 | 2.60 | 1.97 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.676453E+09 | 6185.37 | 09-DEC-05:11 | 1.67 | 1.26 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.274583E+11 | 0.00 | ||||||||
Minimum of Months | 0.341355E+09 | 4341.89 | -1.2 | -2.3 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.483258E+10 | 6503.23 | 31.20 | 18.72 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1490473.03 | 338.46 | 11-JAN-17:30 | 12.50 | 9.43 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.194880E+09 | 3184.84 | 27-FEB-15:30 | 19.70 | 12.29 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.109174E+10 | 5411.62 | 14-MAR-15:10 | 16.28 | 10.40 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.296642E+10 | 13083.53 | 27-APR-14:30 | 26.65 | 17.04 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.504342E+10 | 13246.42 | 04-MAY-14:40 | 24.23 | 14.99 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.635225E+10 | 13798.08 | 28-JUN-14:50 | 25.92 | 15.54 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.803347E+10 | 14682.67 | 24-JUL-14:00 | 29.40 | 18.10 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.790733E+10 | 15658.08 | 10-AUG-14:50 | 30.07 | 18.93 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.434083E+10 | 11984.46 | 14-SEP-14:30 | 23.90 | 17.02 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.135946E+10 | 8078.23 | 04-OCT-14:40 | 21.50 | 11.44 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.160078E+09 | 4233.93 | 04-NOV-13:50 | 21.02 | 15.95 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 1788801.78 | 351.86 | 30-DEC-12:40 | 8.70 | 7.56 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.374531E+11 | 0.00 | ||||||||
Minimum of Months | 1490473.03 | 338.46 | 8.70 | 7.56 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.803347E+10 | 15658.08 | 30.07 | 18.93 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.291596E+10 | 1825.34 | 05-JAN-16:20 | 5.37 | 4.14 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.769753E+10 | 3920.16 | 07-FEB-16:50 | 7.30 | 3.82 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.140868E+11 | 5985.67 | 14-MAR-17:20 | 16.33 | 10.61 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.187536E+11 | 8069.78 | 26-APR-18:20 | 21.30 | 12.83 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.417563E+10 | 2528.11 | 29-MAY-18:38 | 15.77 | 12.18 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.911481E+10 | 4301.05 | 18-JUN-18:52 | 16.10 | 12.56 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.146439E+11 | 6754.12 | 30-JUL-18:49 | 24.78 | 16.74 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.195995E+11 | 8198.73 | 06-AUG-19:30 | 20.70 | 14.39 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.410825E+10 | 2466.65 | 10-SEP-17:38 | 21.13 | 13.93 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.908239E+10 | 4312.19 | 03-OCT-17:00 | 17.20 | 10.00 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.135378E+11 | 5746.71 | 12-NOV-15:53 | 5.00 | 4.01 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.189330E+11 | 7641.81 | 05-DEC-16:00 | 6.10 | 4.53 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.136649E+12 | 0.00 | ||||||||
Minimum of Months | 0.291596E+10 | 1825.34 | 5.00 | 3.82 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.195995E+11 | 8198.73 | 24.78 | 16.74 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.684305E+09 | 1336.60 | 20-JAN-16:20 | 5.20 | 3.48 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.553013E+10 | 3558.80 | 08-FEB-17:00 | 6.70 | 3.25 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.119332E+11 | 5585.80 | 14-MAR-17:20 | 16.33 | 10.61 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.168790E+11 | 7697.46 | 26-APR-18:10 | 22.05 | 13.16 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.319967E+10 | 2264.42 | 07-MAY-18:38 | 19.63 | 14.84 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.808647E+10 | 4002.69 | 22-JUN-19:00 | 23.30 | 15.81 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.135256E+11 | 6260.29 | 30-JUL-18:34 | 25.17 | 16.93 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.183436E+11 | 7778.35 | 06-AUG-19:12 | 21.07 | 14.57 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.321091E+10 | 2238.71 | 10-SEP-17:30 | 21.40 | 13.99 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.733838E+10 | 4051.10 | 04-OCT-17:00 | 20.60 | 11.34 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.110578E+11 | 5183.01 | 10-NOV-16:10 | 8.53 | 6.27 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.157580E+11 | 6983.18 | 05-DEC-16:10 | 6.10 | 4.53 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.115547E+12 | 0.00 | ||||||||
Minimum of Months | 0.684305E+09 | 1336.60 | 5.20 | 3.25 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.183436E+11 | 7778.35 | 25.17 | 16.93 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259082E+09 | 1271.66 | 05-JAN-16:20 | 5.37 | 4.14 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.408498E+10 | 3470.26 | 08-FEB-17:00 | 6.70 | 3.25 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.107122E+11 | 5594.50 | 14-MAR-17:20 | 16.33 | 10.61 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.161080E+11 | 7789.52 | 26-APR-18:10 | 22.05 | 13.16 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.266952E+10 | 2354.65 | 07-MAY-18:26 | 20.00 | 15.11 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.783812E+10 | 4091.74 | 22-JUN-19:00 | 23.30 | 15.81 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.133578E+11 | 6426.57 | 30-JUL-18:31 | 25.17 | 16.93 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.181399E+11 | 7870.51 | 06-AUG-19:06 | 21.43 | 14.75 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.263297E+10 | 2272.00 | 08-SEP-17:40 | 21.10 | 14.31 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.621296E+10 | 4074.84 | 04-OCT-17:00 | 20.60 | 11.34 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.956889E+10 | 5051.62 | 10-NOV-16:10 | 8.53 | 6.27 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.139772E+11 | 6827.90 | 05-DEC-16:10 | 6.10 | 4.53 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.105562E+12 | 0.00 | ||||||||
Minimum of Months | 0.259082E+09 | 1271.66 | 5.37 | 3.25 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.181399E+11 | 7870.51 | 25.17 | 16.93 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235847E+12 | 89818.58 | 12-JAN-17:00 | 7.20 | 5.40 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.434419E+12 | 182064.02 | 27-FEB-17:00 | 18.90 | 12.15 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.728066E+12 | 273930.48 | 14-MAR-16:00 | 17.20 | 10.93 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.943350E+12 | 367445.90 | 01-APR-18:13 | 24.67 | 11.72 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.239383E+12 | 103942.92 | 01-MAY-00:02 | 10.38 | 9.30 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.468723E+12 | 182648.93 | 20-JUN-16:00 | 24.40 | 15.00 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.730838E+12 | 274679.00 | 05-JUL-16:00 | 18.30 | 11.95 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.976923E+12 | 368765.96 | 13-AUG-18:22 | 25.35 | 17.45 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.233320E+12 | 104926.35 | 01-SEP-00:05 | 16.38 | 13.40 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.484515E+12 | 183275.40 | 04-OCT-16:00 | 21.10 | 11.38 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.706141E+12 | 274507.20 | 06-NOV-17:00 | 11.70 | 10.79 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.974367E+12 | 366181.78 | 05-DEC-17:00 | 6.10 | 4.53 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.715589E+13 | 0.00 | ||||||||
Minimum of Months | 0.233320E+12 | 89818.58 | 6.10 | 4.53 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.976923E+12 | 368765.96 | 25.35 | 17.45 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.613663E+09 | 119709.97 | 01-JAN-00:37 | 5.37 |
February | 0.123641E+09 | 120370.34 | 21-FEB-02:47 | 2.38 |
March | 0.247844E+09 | 116132.08 | 27-MAR-03:50 | 5.00 |
April | 0.324685E+09 | 115334.44 | 30-APR-24:00 | 10.30 |
May | 0.408164E+09 | 124892.70 | 29-MAY-17:30 | 16.40 |
June | 0.381190E+09 | 119656.37 | 11-JUN-19:30 | 19.45 |
July | 0.813771E+09 | 130156.50 | 30-JUL-17:42 | 26.70 |
August | 0.736901E+09 | 129567.20 | 13-AUG-17:39 | 26.77 |
September | 0.889105E+09 | 121187.64 | 04-SEP-07:30 | 14.75 |
October | 0.538196E+09 | 115131.29 | 02-OCT-01:50 | 10.18 |
November | 0.664844E+09 | 119438.85 | 12-NOV-14:47 | 6.02 |
December | 0.376895E+09 | 116282.45 | 25-DEC-19:40 | 0.37 |
Annual Sum or Average | 0.611890E+10 | |||
Minimum of Months | 0.123641E+09 | 115131.29 | 0.37 | |
Maximum of Months | 0.889105E+09 | 130156.50 | 26.77 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345908E+09 | 37664.81 | 02-JAN-05:11 | 6.10 |
February | 2337435.30 | 15582.90 | 21-FEB-06:03 | 1.70 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 984432.94 | 8203.61 | 26-DEC-06:02 | -0.8 |
Annual Sum or Average | 0.349230E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.345908E+09 | 37664.81 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.211471E+10 | 73020.70 | 02-JAN-04:01 | 6.60 |
February | 0.895092E+09 | 70868.61 | 21-FEB-04:31 | 1.70 |
March | 0.195531E+09 | 64068.65 | 06-MAR-05:11 | 6.70 |
April | 1533415.99 | 10222.77 | 17-APR-05:03 | 6.10 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 38249446.71 | 59012.63 | 30-OCT-05:02 | 7.20 |
November | 0.482866E+09 | 65580.25 | 13-NOV-05:01 | 1.20 |
December | 0.111905E+10 | 71234.21 | 26-DEC-04:11 | -0.9 |
Annual Sum or Average | 0.484703E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.9 | |
Maximum of Months | 0.211471E+10 | 73020.70 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 542027.87 | 4870.89 | 09-JAN-06:01 | -1.5 |
February | 121037.25 | 1960.99 | 13-FEB-06:01 | 2.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 663065.13 | |||
Minimum of Months | 0.00 | 0.00 | -1.5 | |
Maximum of Months | 542027.87 | 4870.89 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26443577.63 | 10010.47 | 17-JAN-06:02 | 1.20 |
February | 5423630.60 | 7604.36 | 21-FEB-06:03 | 1.70 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 199256.65 | 2656.76 | 13-NOV-06:01 | 1.70 |
December | 3099861.88 | 7984.85 | 26-DEC-06:02 | -0.8 |
Annual Sum or Average | 35166326.75 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 26443577.63 | 10010.47 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140935E+10 | 10083.50 | 02-JAN-04:56 | 6.10 |
February | 0.532649E+09 | 9232.18 | 21-FEB-04:52 | 1.70 |
March | 0.120195E+09 | 8569.25 | 06-MAR-05:11 | 6.70 |
April | 23763430.95 | 8203.57 | 11-APR-04:11 | 5.20 |
May | 664766.21 | 4431.77 | 18-MAY-05:03 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 24136580.54 | 8142.82 | 30-OCT-05:02 | 7.20 |
November | 0.213146E+09 | 8535.73 | 13-NOV-05:01 | 1.20 |
December | 0.654445E+09 | 9202.57 | 26-DEC-04:03 | -1.0 |
Annual Sum or Average | 0.297834E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.140935E+10 | 10083.50 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100872E+10 | 14236.77 | 02-JAN-05:11 | 6.10 |
February | 0.354686E+09 | 12648.42 | 13-FEB-05:01 | 1.28 |
March | 84510847.78 | 12017.35 | 06-MAR-05:11 | 6.70 |
April | 22574214.42 | 11368.87 | 11-APR-04:11 | 5.20 |
May | 1332274.99 | 5732.50 | 18-MAY-05:03 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 8950.93 | 44.75 | 27-SEP-05:10 | 7.38 |
October | 21746512.30 | 10793.36 | 30-OCT-05:02 | 7.20 |
November | 0.176878E+09 | 11895.56 | 24-NOV-05:11 | 2.60 |
December | 0.527085E+09 | 12824.83 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.219755E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.100872E+10 | 14236.77 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105460E+10 | 19153.81 | 02-JAN-05:11 | 6.10 |
February | 0.313862E+09 | 17085.02 | 21-FEB-05:01 | 1.70 |
March | 65021772.77 | 16327.51 | 06-MAR-05:11 | 6.70 |
April | 19219493.26 | 13671.49 | 18-APR-05:03 | 3.30 |
May | 1364984.74 | 6875.15 | 18-MAY-05:03 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 9338779.33 | 11478.18 | 28-OCT-05:03 | 8.22 |
November | 0.169256E+09 | 16162.02 | 30-NOV-05:11 | 5.60 |
December | 0.521940E+09 | 17231.69 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.215460E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.105460E+10 | 19153.81 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.597097E+09 | 13767.27 | 02-JAN-05:11 | 6.10 |
February | 0.202028E+09 | 11940.44 | 21-FEB-05:01 | 1.70 |
March | 35308441.71 | 11001.23 | 06-MAR-05:11 | 6.70 |
April | 6430039.61 | 6547.33 | 18-APR-05:03 | 3.30 |
May | 619515.39 | 3718.10 | 18-MAY-05:03 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 4693123.79 | 6278.19 | 28-OCT-05:03 | 8.22 |
November | 80442311.95 | 10982.77 | 30-NOV-05:11 | 5.60 |
December | 0.242948E+09 | 11825.40 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.116957E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.597097E+09 | 13767.27 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.372463E+10 | 11648.64 | 02-JAN-05:21 | 6.10 |
February | 0.230218E+10 | 11613.95 | 19-FEB-07:23 | -5.0 |
March | 0.908127E+09 | 11256.61 | 06-MAR-04:01 | 6.70 |
April | 0.339600E+09 | 10192.58 | 11-APR-04:11 | 5.20 |
May | 37384267.94 | 9572.13 | 18-MAY-04:11 | 6.33 |
June | 1619371.34 | 6867.08 | 14-JUN-05:03 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 7063903.13 | 6645.10 | 27-SEP-05:03 | 7.38 |
October | 0.390586E+09 | 10414.56 | 30-OCT-04:11 | 7.20 |
November | 0.135660E+10 | 11197.89 | 13-NOV-04:01 | 1.60 |
December | 0.280290E+10 | 11521.80 | 26-DEC-04:11 | -0.9 |
Annual Sum or Average | 0.118707E+11 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.372463E+10 | 11648.64 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244692E+10 | 16751.91 | 02-JAN-05:21 | 6.10 |
February | 0.136898E+10 | 16410.09 | 13-FEB-04:01 | 0.68 |
March | 0.540808E+09 | 16271.42 | 06-MAR-04:01 | 6.70 |
April | 0.195685E+09 | 14623.14 | 11-APR-04:11 | 5.20 |
May | 30264781.35 | 13667.52 | 18-MAY-04:11 | 6.33 |
June | 3113798.17 | 7069.70 | 14-JUN-05:03 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 6315551.59 | 6058.72 | 27-SEP-05:03 | 7.38 |
October | 0.262900E+09 | 14651.42 | 30-OCT-04:11 | 7.20 |
November | 0.909622E+09 | 16056.60 | 13-NOV-04:01 | 1.60 |
December | 0.184806E+10 | 16685.95 | 26-DEC-04:11 | -0.9 |
Annual Sum or Average | 0.761267E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.9 | |
Maximum of Months | 0.244692E+10 | 16751.91 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.277868E+10 | 22997.77 | 02-JAN-05:21 | 6.10 |
February | 0.147730E+10 | 22317.73 | 21-FEB-04:31 | 1.70 |
March | 0.693635E+09 | 22226.08 | 06-MAR-04:01 | 6.70 |
April | 0.289034E+09 | 20083.20 | 11-APR-04:11 | 5.20 |
May | 42039772.99 | 19040.87 | 18-MAY-04:11 | 6.33 |
June | 2427561.40 | 7688.89 | 14-JUN-05:03 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 6110325.47 | 6731.51 | 27-SEP-05:03 | 7.38 |
October | 0.275163E+09 | 19948.91 | 16-OCT-04:11 | 7.20 |
November | 0.106891E+10 | 21792.18 | 24-NOV-05:11 | 2.60 |
December | 0.219414E+10 | 22862.66 | 26-DEC-04:11 | -0.9 |
Annual Sum or Average | 0.882743E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.9 | |
Maximum of Months | 0.277868E+10 | 22997.77 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169316E+10 | 16761.80 | 02-JAN-05:21 | 6.10 |
February | 0.839067E+09 | 16395.32 | 21-FEB-04:31 | 1.70 |
March | 0.347991E+09 | 15452.68 | 06-MAR-04:01 | 6.70 |
April | 0.115030E+09 | 13982.65 | 11-APR-04:11 | 5.20 |
May | 16520322.86 | 13367.38 | 18-MAY-04:11 | 6.33 |
June | 175702.95 | 1171.35 | 14-JUN-05:03 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 21785.60 | 145.24 | 18-SEP-05:08 | 12.20 |
October | 0.130491E+09 | 13827.38 | 30-OCT-04:11 | 7.20 |
November | 0.522900E+09 | 15277.55 | 24-NOV-05:11 | 2.60 |
December | 0.108359E+10 | 16623.34 | 26-DEC-04:11 | -0.9 |
Annual Sum or Average | 0.474894E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.9 | |
Maximum of Months | 0.169316E+10 | 16761.80 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55579419.44 | 9726.80 | 02-JAN-05:11 | 6.10 |
February | 54313840.60 | 10378.87 | 21-FEB-05:01 | 1.70 |
March | 55559062.67 | 10269.11 | 06-MAR-05:11 | 6.70 |
April | 0.102956E+09 | 10518.34 | 14-APR-03:01 | 9.40 |
May | 56071707.93 | 9007.22 | 01-MAY-03:02 | 11.78 |
June | 61725506.82 | 8669.86 | 19-JUN-03:01 | 11.02 |
July | 87341301.17 | 9142.10 | 17-JUL-03:02 | 14.90 |
August | 90414191.30 | 10154.93 | 04-AUG-03:01 | 13.92 |
September | 36920618.15 | 9385.44 | 01-SEP-03:01 | 16.18 |
October | 60399289.23 | 9150.12 | 30-OCT-04:11 | 7.20 |
November | 57995883.04 | 11226.45 | 27-NOV-05:11 | 12.03 |
December | 60610433.04 | 11470.93 | 29-DEC-05:11 | 10.00 |
Annual Sum or Average | 0.779887E+09 | |||
Minimum of Months | 36920618.15 | 8669.86 | 1.70 | |
Maximum of Months | 0.102956E+09 | 11470.93 | 16.18 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.213353E+10 | 14379.74 | 02-JAN-06:03 | 6.10 |
February | 0.790762E+09 | 8800.74 | 12-FEB-13:22 | 6.40 |
March | 0.229282E+09 | 6125.93 | 15-MAR-05:02 | 8.03 |
April | 55598881.33 | 5592.47 | 10-APR-05:02 | 8.80 |
May | 41488144.86 | 6485.45 | 29-MAY-15:20 | 15.77 |
June | 31541782.05 | 5701.52 | 18-JUN-17:12 | 17.03 |
July | 34352117.81 | 5502.12 | 17-JUL-05:01 | 13.98 |
August | 27751945.02 | 5732.71 | 06-AUG-16:31 | 23.53 |
September | 28974772.88 | 8148.66 | 10-SEP-16:21 | 22.20 |
October | 0.102526E+09 | 6104.54 | 29-OCT-12:53 | 11.10 |
November | 0.377619E+09 | 6480.18 | 11-NOV-13:02 | 6.88 |
December | 0.833626E+09 | 5805.80 | 03-DEC-13:23 | 12.20 |
Annual Sum or Average | 0.468705E+10 | |||
Minimum of Months | 27751945.02 | 5502.12 | 6.10 | |
Maximum of Months | 0.213353E+10 | 14379.74 | 23.53 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.632644E+10 | 21519.74 | 02-JAN-05:32 | 6.10 |
February | 0.387661E+10 | 20705.28 | 21-FEB-05:11 | 1.70 |
March | 0.211958E+10 | 13352.06 | 06-MAR-06:03 | 6.70 |
April | 0.104012E+10 | 12674.99 | 27-APR-05:03 | 9.37 |
May | 0.443428E+09 | 11360.11 | 05-MAY-05:02 | 12.98 |
June | 0.178268E+09 | 14319.59 | 02-JUN-05:02 | 10.18 |
July | 94734203.30 | 12630.76 | 18-JUL-05:02 | 12.80 |
August | 0.121618E+09 | 13080.98 | 21-AUG-05:01 | 11.20 |
September | 0.359671E+09 | 12570.83 | 08-SEP-05:02 | 10.18 |
October | 0.133017E+10 | 7893.36 | 30-OCT-05:02 | 7.20 |
November | 0.295653E+10 | 15495.76 | 13-NOV-06:13 | 1.70 |
December | 0.519290E+10 | 18980.99 | 26-DEC-05:13 | -0.6 |
Annual Sum or Average | 0.240401E+11 | |||
Minimum of Months | 94734203.30 | 7893.36 | -0.6 | |
Maximum of Months | 0.632644E+10 | 21519.74 | 12.98 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.264587E+09 | 544.30 | 03-JAN-00:50 | 7.20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.264587E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.264587E+09 | 544.30 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.781707E+09 | 595.12 | 08-JAN-17:30 | 2.75 |
February | 19851326.02 | 406.41 | 19-FEB-06:50 | -5.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 1859445.72 | 512.70 | 18-MAY-04:13 | 6.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.803418E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.781707E+09 | 595.12 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.179018E+11 | 19263.35 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.162411E+11 | 19263.35 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.193470E+11 | 19263.35 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.172320E+11 | 19263.35 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.186244E+11 | 19263.35 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.185523E+11 | 19263.35 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.173042E+11 | 19263.35 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.193467E+11 | 19263.35 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.172320E+11 | 19263.35 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.179021E+11 | 19263.35 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.177053E+11 | 19263.35 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.173045E+11 | 19263.35 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.214693E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.162411E+11 | 19263.35 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.193470E+11 | 19263.35 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.160770E+11 | 17299.84 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.145856E+11 | 17299.84 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.173750E+11 | 17299.84 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.154756E+11 | 17299.84 | 03-APR-07:10 | 0.235253E+11 | 17206.63 | 03-APR-07:10 |
May | 0.167260E+11 | 17299.84 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.166612E+11 | 17299.84 | 01-JUN-07:10 | 0.244214E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.155404E+11 | 17299.84 | 03-JUL-07:10 | 0.239654E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.173747E+11 | 17299.84 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.154756E+11 | 17299.84 | 01-SEP-07:10 | 0.235253E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.160774E+11 | 17299.84 | 02-OCT-07:10 | 0.243681E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.159006E+11 | 17299.84 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.155407E+11 | 17299.84 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.192810E+12 | 0.289609E+12 | ||||
Minimum of Months | 0.145856E+11 | 17299.84 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.173750E+11 | 17299.84 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.160770E+11 | 17299.84 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.145856E+11 | 17299.84 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.173750E+11 | 17299.84 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.154756E+11 | 17299.84 | 03-APR-07:10 | 0.235252E+11 | 17206.56 | 03-APR-07:10 |
May | 0.167260E+11 | 17299.84 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.166612E+11 | 17299.84 | 01-JUN-07:10 | 0.244213E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.155404E+11 | 17299.84 | 03-JUL-07:10 | 0.239653E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.173747E+11 | 17299.84 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.154756E+11 | 17299.84 | 01-SEP-07:10 | 0.235252E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.160774E+11 | 17299.84 | 02-OCT-07:10 | 0.243680E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.159006E+11 | 17299.84 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.155407E+11 | 17299.84 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.192810E+12 | 0.289607E+12 | ||||
Minimum of Months | 0.145856E+11 | 17299.84 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.173750E+11 | 17299.84 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.160770E+11 | 17299.84 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.145856E+11 | 17299.84 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.173750E+11 | 17299.84 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.154756E+11 | 17299.84 | 03-APR-07:10 | 0.235252E+11 | 17206.56 | 03-APR-07:10 |
May | 0.167260E+11 | 17299.84 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.166612E+11 | 17299.84 | 01-JUN-07:10 | 0.244213E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.155404E+11 | 17299.84 | 03-JUL-07:10 | 0.239653E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.173747E+11 | 17299.84 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.154756E+11 | 17299.84 | 01-SEP-07:10 | 0.235252E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.160774E+11 | 17299.84 | 02-OCT-07:10 | 0.243680E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.159006E+11 | 17299.84 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.155407E+11 | 17299.84 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.192810E+12 | 0.289607E+12 | ||||
Minimum of Months | 0.145856E+11 | 17299.84 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.173750E+11 | 17299.84 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.145220E+10 | 2172.17 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.117195E+10 | 2172.17 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.126624E+10 | 1892.90 | 07-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.105608E+10 | 1513.35 | 03-APR-07:10 | 0.295395E+10 | 2160.55 | 03-APR-07:10 |
May | 0.110789E+10 | 1133.80 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.108184E+10 | 1133.80 | 16-JUN-07:10 | 0.306647E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.101536E+10 | 1513.35 | 12-JUL-07:40 | 0.300922E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.115199E+10 | 1234.08 | 02-AUG-07:19 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.109672E+10 | 1892.90 | 21-SEP-07:10 | 0.295395E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.124981E+10 | 2172.17 | 20-OCT-07:10 | 0.305979E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.139542E+10 | 2172.17 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.145529E+10 | 2172.17 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.145008E+11 | 0.363647E+11 | ||||
Minimum of Months | 0.101536E+10 | 1133.80 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.145529E+10 | 2172.17 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.896081E+09 | 1399.83 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.737244E+09 | 1399.83 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.806733E+09 | 1219.86 | 03-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.679712E+09 | 795.29 | 03-APR-07:10 | 0.190364E+10 | 1392.34 | 03-APR-07:10 |
May | 0.717950E+09 | 730.66 | 05-MAY-14:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.702557E+09 | 730.66 | 08-JUN-15:30 | 0.197615E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.657870E+09 | 730.66 | 12-JUL-07:49 | 0.193926E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.746590E+09 | 795.29 | 02-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.698308E+09 | 1219.86 | 21-SEP-07:10 | 0.190364E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.785607E+09 | 1399.83 | 26-OCT-07:10 | 0.197184E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.870572E+09 | 1399.83 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.894421E+09 | 1399.83 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.919365E+10 | 0.234348E+11 | ||||
Minimum of Months | 0.657870E+09 | 730.66 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.896081E+09 | 1399.83 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.134401E+10 | 2172.22 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.110914E+10 | 2172.22 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.123998E+10 | 1892.94 | 13-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.105526E+10 | 1513.38 | 03-APR-07:10 | 0.295400E+10 | 2160.58 | 03-APR-07:10 |
May | 0.111403E+10 | 1133.82 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.108968E+10 | 1133.82 | 16-JUN-07:10 | 0.306652E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.102640E+10 | 1513.38 | 12-JUL-07:30 | 0.300927E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.116104E+10 | 1234.11 | 02-AUG-07:19 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.108436E+10 | 1892.94 | 21-SEP-07:10 | 0.295400E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.119737E+10 | 2172.22 | 26-OCT-07:10 | 0.305983E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.130879E+10 | 2172.22 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.133289E+10 | 2172.22 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.140629E+11 | 0.363653E+11 | ||||
Minimum of Months | 0.102640E+10 | 1133.82 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.134401E+10 | 2172.22 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.894860E+09 | 1399.83 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.728437E+09 | 1399.83 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.806739E+09 | 1219.86 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.680551E+09 | 975.26 | 03-APR-07:10 | 0.190363E+10 | 1392.33 | 03-APR-07:10 |
May | 0.715392E+09 | 795.29 | 02-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.698348E+09 | 730.66 | 05-JUN-07:10 | 0.197614E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.658583E+09 | 975.26 | 12-JUL-07:19 | 0.193924E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.744334E+09 | 975.26 | 02-AUG-07:30 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.705900E+09 | 1219.86 | 21-SEP-07:10 | 0.190363E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.786778E+09 | 1399.83 | 20-OCT-07:10 | 0.197183E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.865920E+09 | 1399.83 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.893734E+09 | 1399.83 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.917958E+10 | 0.234347E+11 | ||||
Minimum of Months | 0.658583E+09 | 730.66 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.894860E+09 | 1399.83 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.144453E+10 | 2172.17 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.116594E+10 | 2172.17 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.126178E+10 | 1892.90 | 07-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.105407E+10 | 1513.35 | 03-APR-07:10 | 0.295395E+10 | 2160.55 | 03-APR-07:10 |
May | 0.110691E+10 | 1133.80 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.108057E+10 | 1133.80 | 16-JUN-07:10 | 0.306647E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.101350E+10 | 1513.35 | 12-JUL-07:49 | 0.300922E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.115004E+10 | 1234.08 | 02-AUG-07:19 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.109416E+10 | 1892.90 | 21-SEP-07:10 | 0.295395E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.124314E+10 | 2172.17 | 20-OCT-07:10 | 0.305979E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.138856E+10 | 2172.17 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.144870E+10 | 2172.17 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.144519E+11 | 0.363647E+11 | ||||
Minimum of Months | 0.101350E+10 | 1133.80 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.144870E+10 | 2172.17 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.892350E+09 | 1399.83 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.734334E+09 | 1399.83 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.805077E+09 | 1219.86 | 03-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.678469E+09 | 795.29 | 03-APR-07:10 | 0.190364E+10 | 1392.34 | 03-APR-07:10 |
May | 0.717048E+09 | 730.66 | 05-MAY-14:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.701842E+09 | 666.04 | 01-JUN-07:10 | 0.197615E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.657167E+09 | 730.66 | 12-JUL-07:49 | 0.193926E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.745583E+09 | 795.29 | 02-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.697193E+09 | 1219.86 | 21-SEP-07:10 | 0.190364E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.783230E+09 | 1399.83 | 27-OCT-07:10 | 0.197184E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.866402E+09 | 1399.83 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.891024E+09 | 1399.83 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.916972E+10 | 0.234348E+11 | ||||
Minimum of Months | 0.657167E+09 | 666.04 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.892350E+09 | 1399.83 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.134191E+10 | 2172.22 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.110654E+10 | 2172.22 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.123820E+10 | 1892.94 | 13-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.105394E+10 | 1513.38 | 03-APR-07:10 | 0.295400E+10 | 2160.58 | 03-APR-07:10 |
May | 0.111293E+10 | 1133.82 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.108863E+10 | 1133.82 | 16-JUN-07:10 | 0.306652E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.102493E+10 | 1513.38 | 12-JUL-07:30 | 0.300927E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.115966E+10 | 1234.11 | 02-AUG-07:19 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.108301E+10 | 1892.94 | 21-SEP-07:10 | 0.295400E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.119578E+10 | 2172.22 | 26-OCT-07:10 | 0.305983E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.130657E+10 | 2172.22 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.133026E+10 | 2172.22 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.140424E+11 | 0.363653E+11 | ||||
Minimum of Months | 0.102493E+10 | 1133.82 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.134191E+10 | 2172.22 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.891044E+09 | 1399.83 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.726329E+09 | 1399.83 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.804747E+09 | 1219.86 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.679188E+09 | 975.26 | 03-APR-07:10 | 0.190363E+10 | 1392.33 | 03-APR-07:10 |
May | 0.714410E+09 | 795.29 | 02-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.697745E+09 | 730.66 | 05-JUN-07:10 | 0.197614E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.657781E+09 | 975.26 | 12-JUL-07:19 | 0.193924E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.743508E+09 | 975.26 | 02-AUG-07:30 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.704159E+09 | 1219.86 | 21-SEP-07:10 | 0.190363E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.784806E+09 | 1399.83 | 20-OCT-07:10 | 0.197183E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.862622E+09 | 1399.83 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.889802E+09 | 1399.83 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.915614E+10 | 0.234347E+11 | ||||
Minimum of Months | 0.657781E+09 | 730.66 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.891044E+09 | 1399.83 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.144391E+10 | 2172.17 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.116557E+10 | 2172.17 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.126165E+10 | 1892.90 | 07-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.105401E+10 | 1513.35 | 03-APR-07:10 | 0.295395E+10 | 2160.55 | 03-APR-07:10 |
May | 0.110680E+10 | 1133.80 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.108051E+10 | 1133.80 | 16-JUN-07:10 | 0.306647E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.101346E+10 | 1513.35 | 12-JUL-07:49 | 0.300922E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.115004E+10 | 1234.08 | 02-AUG-07:19 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.109352E+10 | 1892.90 | 21-SEP-07:10 | 0.295395E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.124270E+10 | 2172.17 | 20-OCT-07:10 | 0.305979E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.138823E+10 | 2172.17 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.144828E+10 | 2172.17 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.144487E+11 | 0.363647E+11 | ||||
Minimum of Months | 0.101346E+10 | 1133.80 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.144828E+10 | 2172.17 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.892113E+09 | 1399.83 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.734256E+09 | 1399.83 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.804978E+09 | 1219.86 | 03-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.678282E+09 | 795.29 | 03-APR-07:10 | 0.190364E+10 | 1392.34 | 03-APR-07:10 |
May | 0.717021E+09 | 730.66 | 05-MAY-14:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.701842E+09 | 666.04 | 01-JUN-07:10 | 0.197615E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.657154E+09 | 730.66 | 12-JUL-07:49 | 0.193926E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.745581E+09 | 795.29 | 02-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.697193E+09 | 1219.86 | 21-SEP-07:10 | 0.190364E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.783143E+09 | 1399.83 | 27-OCT-07:10 | 0.197184E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.866130E+09 | 1399.83 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.890821E+09 | 1399.83 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.916852E+10 | 0.234348E+11 | ||||
Minimum of Months | 0.657154E+09 | 666.04 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.892113E+09 | 1399.83 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.134151E+10 | 2172.22 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.110648E+10 | 2172.22 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.123812E+10 | 1892.94 | 13-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.105392E+10 | 1513.38 | 03-APR-07:10 | 0.295400E+10 | 2160.58 | 03-APR-07:10 |
May | 0.111282E+10 | 1133.82 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.108861E+10 | 1133.82 | 16-JUN-07:10 | 0.306652E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.102483E+10 | 1513.38 | 12-JUL-07:30 | 0.300927E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.115947E+10 | 1234.11 | 02-AUG-07:19 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.108299E+10 | 1892.94 | 21-SEP-07:10 | 0.295400E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.119553E+10 | 2172.22 | 26-OCT-07:10 | 0.305983E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.130651E+10 | 2172.22 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.133009E+10 | 2172.22 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.140409E+11 | 0.363653E+11 | ||||
Minimum of Months | 0.102483E+10 | 1133.82 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.134151E+10 | 2172.22 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.890951E+09 | 1399.83 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.726272E+09 | 1399.83 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.804515E+09 | 1219.86 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.679106E+09 | 975.26 | 03-APR-07:10 | 0.190363E+10 | 1392.33 | 03-APR-07:10 |
May | 0.714413E+09 | 795.29 | 02-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.697734E+09 | 730.66 | 05-JUN-07:10 | 0.197614E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.657693E+09 | 975.26 | 12-JUL-07:19 | 0.193924E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.743474E+09 | 975.26 | 02-AUG-07:30 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.703810E+09 | 1219.86 | 21-SEP-07:10 | 0.190363E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.784783E+09 | 1399.83 | 20-OCT-07:10 | 0.197183E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.862501E+09 | 1399.83 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.889717E+09 | 1399.83 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.915497E+10 | 0.234347E+11 | ||||
Minimum of Months | 0.657693E+09 | 730.66 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.890951E+09 | 1399.83 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.522007E+10 | 5431.44 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.473481E+10 | 5431.44 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.562303E+10 | 5431.44 | 01-MAR-08:09 | 0.762606E+12 | 284724.39 | 01-MAR-00:10 |
April | 0.502580E+10 | 5431.44 | 03-APR-07:10 | 0.984007E+12 | 379632.52 | 01-APR-00:10 |
May | 0.542155E+10 | 5431.44 | 01-MAY-07:10 | 0.254202E+12 | 94908.13 | 01-MAY-00:10 |
June | 0.539412E+10 | 5431.44 | 01-JUN-07:10 | 0.492004E+12 | 189816.26 | 01-JUN-00:10 |
July | 0.505323E+10 | 5431.44 | 03-JUL-07:10 | 0.762606E+12 | 284724.39 | 01-JUL-00:10 |
August | 0.562303E+10 | 5431.44 | 01-AUG-07:10 | 0.101681E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.502580E+10 | 5431.44 | 01-SEP-07:10 | 0.246002E+12 | 94908.13 | 01-SEP-00:10 |
October | 0.522007E+10 | 5431.44 | 02-OCT-07:10 | 0.508404E+12 | 189816.26 | 01-OCT-00:10 |
November | 0.515799E+10 | 5431.44 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.505323E+10 | 5431.44 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.625527E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.473481E+10 | 5431.44 | 0.246002E+12 | 94908.13 | ||
Maximum of Months | 0.562303E+10 | 5431.44 | 0.101681E+13 | 379632.52 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.241145E+09 | 250.91 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.218729E+09 | 250.91 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.259761E+09 | 250.91 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.232171E+09 | 250.91 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.250453E+09 | 250.91 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.249186E+09 | 250.91 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.233438E+09 | 250.91 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.259761E+09 | 250.91 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.232171E+09 | 250.91 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.241145E+09 | 250.91 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.238278E+09 | 250.91 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.233438E+09 | 250.91 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.288968E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.218729E+09 | 250.91 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.259761E+09 | 250.91 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.241145E+09 | 250.91 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.218729E+09 | 250.91 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.259761E+09 | 250.91 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.232171E+09 | 250.91 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.250453E+09 | 250.91 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.249186E+09 | 250.91 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.233438E+09 | 250.91 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.259761E+09 | 250.91 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.232171E+09 | 250.91 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.241145E+09 | 250.91 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.238278E+09 | 250.91 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.233438E+09 | 250.91 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.288968E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.218729E+09 | 250.91 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.259761E+09 | 250.91 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.241145E+09 | 250.91 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.218729E+09 | 250.91 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.259761E+09 | 250.91 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.232171E+09 | 250.91 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.250453E+09 | 250.91 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.249186E+09 | 250.91 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.233438E+09 | 250.91 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.259761E+09 | 250.91 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.232171E+09 | 250.91 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.241145E+09 | 250.91 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.238278E+09 | 250.91 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.233438E+09 | 250.91 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.288968E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.218729E+09 | 250.91 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.259761E+09 | 250.91 | 0.208766E+11 | 7794.42 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.179018E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.162411E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.193470E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.172320E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.186244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.185523E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.173042E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.193467E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.172320E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.179021E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.177053E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.173045E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.214693E+12 | 0.424397E+12 | ||||||
Minimum of Months | 0.121482E+11 | 0.162411E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.193470E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.160770E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.145856E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.173750E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.154756E+11 | 0.235253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.167260E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.166612E+11 | 0.244214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.155404E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.173747E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.154756E+11 | 0.235253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.160774E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.159006E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.155407E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.192810E+12 | 0.289609E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.145856E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.173750E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.160770E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.145856E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.173750E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.154756E+11 | 0.235252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.167260E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.166612E+11 | 0.244213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.155404E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.173747E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.154756E+11 | 0.235252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.160774E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.159006E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.155407E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.192810E+12 | 0.289607E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.145856E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.173750E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.160770E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.145856E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.173750E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.154756E+11 | 0.235252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.167260E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.166612E+11 | 0.244213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.155404E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.173747E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.154756E+11 | 0.235252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.160774E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.159006E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.155407E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.192810E+12 | 0.289607E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.145856E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.173750E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.145220E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.846357E+09 |
February | 0.136985E+10 | 0.117195E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.752179E+09 |
March | 0.163685E+10 | 0.126624E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720294E+09 |
April | 0.145243E+10 | 0.105608E+10 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1093647.96 | 0.676811E+09 |
May | 0.157338E+10 | 0.110789E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39929.00 | 0.512822E+09 |
June | 0.156900E+10 | 0.108184E+10 | 0.306647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 401027.60 | 0.424500E+09 |
July | 0.145680E+10 | 0.101536E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6395472.86 | 0.351657E+09 |
August | 0.163685E+10 | 0.115199E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9221109.07 | 0.283248E+09 |
September | 0.145243E+10 | 0.109672E+10 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39776.32 | 0.239531E+09 |
October | 0.150991E+10 | 0.124981E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576514E+09 |
November | 0.149516E+10 | 0.139542E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674930E+09 |
December | 0.145680E+10 | 0.145529E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739306E+09 |
Annual Sum or Average | 0.181194E+11 | 0.145008E+11 | 0.363647E+11 | 17190962.80 | 0.679815E+10 | ||||
Minimum of Months | 0.136985E+10 | 0.101536E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239531E+09 |
Maximum of Months | 0.163685E+10 | 0.145529E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9221109.07 | 0.846357E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.896081E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544153E+09 |
February | 0.882782E+09 | 0.737244E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485145E+09 |
March | 0.105485E+10 | 0.806733E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459601E+09 |
April | 0.936002E+09 | 0.679712E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 959017.81 | 0.429677E+09 |
May | 0.101394E+10 | 0.717950E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27381.67 | 0.333130E+09 |
June | 0.101113E+10 | 0.702557E+09 | 0.197615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 283506.55 | 0.273821E+09 |
July | 0.938820E+09 | 0.657870E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4399879.09 | 0.219780E+09 |
August | 0.105485E+10 | 0.746590E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6303814.16 | 0.173023E+09 |
September | 0.936002E+09 | 0.698308E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27373.52 | 0.154185E+09 |
October | 0.973041E+09 | 0.785607E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367005E+09 |
November | 0.963541E+09 | 0.870572E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424024E+09 |
December | 0.938820E+09 | 0.894421E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463962E+09 |
Annual Sum or Average | 0.116768E+11 | 0.919365E+10 | 0.234348E+11 | 12000972.81 | 0.432751E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.657870E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154185E+09 |
Maximum of Months | 0.105485E+10 | 0.896081E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6303814.16 | 0.544153E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.134401E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.813979E+09 |
February | 0.136988E+10 | 0.110914E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749073E+09 |
March | 0.163688E+10 | 0.123998E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708416E+09 |
April | 0.145246E+10 | 0.105526E+10 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 995493.19 | 0.665285E+09 |
May | 0.157341E+10 | 0.111403E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39923.07 | 0.506971E+09 |
June | 0.156904E+10 | 0.108968E+10 | 0.306652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 401013.48 | 0.417749E+09 |
July | 0.145684E+10 | 0.102640E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5215647.46 | 0.346056E+09 |
August | 0.163688E+10 | 0.116104E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8414083.74 | 0.280810E+09 |
September | 0.145246E+10 | 0.108436E+10 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39766.81 | 0.241858E+09 |
October | 0.150994E+10 | 0.119737E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572742E+09 |
November | 0.149520E+10 | 0.130879E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650020E+09 |
December | 0.145684E+10 | 0.133289E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711452E+09 |
Annual Sum or Average | 0.181198E+11 | 0.140629E+11 | 0.363653E+11 | 15105927.76 | 0.666441E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.102640E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241858E+09 |
Maximum of Months | 0.163688E+10 | 0.134401E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8414083.74 | 0.813979E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.894860E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576689E+09 |
February | 0.882782E+09 | 0.728437E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532056E+09 |
March | 0.105485E+10 | 0.806739E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520397E+09 |
April | 0.936002E+09 | 0.680551E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 359682.33 | 0.500060E+09 |
May | 0.101394E+10 | 0.715392E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26370.19 | 0.366140E+09 |
June | 0.101113E+10 | 0.698348E+09 | 0.197614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 264829.57 | 0.310319E+09 |
July | 0.938820E+09 | 0.658583E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2513091.46 | 0.271261E+09 |
August | 0.105485E+10 | 0.744334E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5463945.98 | 0.221879E+09 |
September | 0.936002E+09 | 0.705900E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26265.46 | 0.173527E+09 |
October | 0.973041E+09 | 0.786778E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413479E+09 |
November | 0.963541E+09 | 0.865920E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485842E+09 |
December | 0.938820E+09 | 0.893734E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540356E+09 |
Annual Sum or Average | 0.116768E+11 | 0.917958E+10 | 0.234347E+11 | 8654184.99 | 0.491200E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.658583E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173527E+09 |
Maximum of Months | 0.105485E+10 | 0.894860E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5463945.98 | 0.576689E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.144453E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158876E+10 |
February | 0.136985E+10 | 0.116594E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143212E+10 |
March | 0.163685E+10 | 0.126178E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139256E+10 |
April | 0.145243E+10 | 0.105407E+10 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3697293.94 | 0.132516E+10 |
May | 0.157338E+10 | 0.110691E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64329.06 | 0.105092E+10 |
June | 0.156900E+10 | 0.108057E+10 | 0.306647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 795041.10 | 0.870781E+09 |
July | 0.145680E+10 | 0.101350E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19271954.59 | 0.721317E+09 |
August | 0.163685E+10 | 0.115004E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23040872.25 | 0.586908E+09 |
September | 0.145243E+10 | 0.109416E+10 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72857.29 | 0.484611E+09 |
October | 0.150991E+10 | 0.124314E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110897E+10 |
November | 0.149516E+10 | 0.138856E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126523E+10 |
December | 0.145680E+10 | 0.144870E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137455E+10 |
Annual Sum or Average | 0.181194E+11 | 0.144519E+11 | 0.363647E+11 | 46942348.23 | 0.132019E+11 | ||||
Minimum of Months | 0.136985E+10 | 0.101350E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484611E+09 |
Maximum of Months | 0.163685E+10 | 0.144870E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23040872.25 | 0.158876E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.892350E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105376E+10 |
February | 0.649041E+09 | 0.734334E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.963864E+09 |
March | 0.773965E+09 | 0.805077E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929214E+09 |
April | 0.688021E+09 | 0.678469E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2440401.91 | 0.893600E+09 |
May | 0.744847E+09 | 0.717048E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48833.62 | 0.704178E+09 |
June | 0.742030E+09 | 0.701842E+09 | 0.197615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 609993.53 | 0.590326E+09 |
July | 0.690839E+09 | 0.657167E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9841748.15 | 0.482754E+09 |
August | 0.773965E+09 | 0.745583E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13989541.57 | 0.395396E+09 |
September | 0.688021E+09 | 0.697193E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53335.10 | 0.322873E+09 |
October | 0.715730E+09 | 0.783230E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736845E+09 |
November | 0.708685E+09 | 0.866402E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.832951E+09 |
December | 0.690839E+09 | 0.891024E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.910640E+09 |
Annual Sum or Average | 0.858171E+10 | 0.916972E+10 | 0.234348E+11 | 26983853.88 | 0.881640E+10 | ||||
Minimum of Months | 0.649041E+09 | 0.657167E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322873E+09 |
Maximum of Months | 0.773965E+09 | 0.892350E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13989541.57 | 0.105376E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.134191E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165301E+10 |
February | 0.136988E+10 | 0.110654E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156048E+10 |
March | 0.163688E+10 | 0.123820E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147479E+10 |
April | 0.145246E+10 | 0.105394E+10 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2229015.05 | 0.138718E+10 |
May | 0.157341E+10 | 0.111293E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63987.29 | 0.108032E+10 |
June | 0.156904E+10 | 0.108863E+10 | 0.306652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 796776.15 | 0.882961E+09 |
July | 0.145684E+10 | 0.102493E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12038318.59 | 0.738246E+09 |
August | 0.163688E+10 | 0.115966E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18313443.26 | 0.613828E+09 |
September | 0.145246E+10 | 0.108301E+10 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67065.26 | 0.521126E+09 |
October | 0.150994E+10 | 0.119578E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120263E+10 |
November | 0.149520E+10 | 0.130657E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131681E+10 |
December | 0.145684E+10 | 0.133026E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143736E+10 |
Annual Sum or Average | 0.181198E+11 | 0.140424E+11 | 0.363653E+11 | 33508605.60 | 0.138687E+11 | ||||
Minimum of Months | 0.136988E+10 | 0.102493E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521126E+09 |
Maximum of Months | 0.163688E+10 | 0.134191E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18313443.26 | 0.165301E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.891044E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108212E+10 |
February | 0.882782E+09 | 0.726329E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.993668E+09 |
March | 0.105485E+10 | 0.804747E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.965324E+09 |
April | 0.936002E+09 | 0.679188E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 937315.66 | 0.931586E+09 |
May | 0.101394E+10 | 0.714410E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65763.56 | 0.750841E+09 |
June | 0.101113E+10 | 0.697745E+09 | 0.197614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 535074.44 | 0.616892E+09 |
July | 0.938820E+09 | 0.657781E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7501207.58 | 0.541229E+09 |
August | 0.105485E+10 | 0.743508E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13430127.73 | 0.437155E+09 |
September | 0.936002E+09 | 0.704159E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44721.98 | 0.350591E+09 |
October | 0.973041E+09 | 0.784806E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769773E+09 |
November | 0.963541E+09 | 0.862622E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.861500E+09 |
December | 0.938820E+09 | 0.889802E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.942521E+09 |
Annual Sum or Average | 0.116768E+11 | 0.915614E+10 | 0.234347E+11 | 22514210.95 | 0.924320E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.657781E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350591E+09 |
Maximum of Months | 0.105485E+10 | 0.891044E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13430127.73 | 0.108212E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.144391E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184931E+10 |
February | 0.136985E+10 | 0.116557E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164161E+10 |
March | 0.163685E+10 | 0.126165E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158933E+10 |
April | 0.145243E+10 | 0.105401E+10 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4616785.26 | 0.153359E+10 |
May | 0.157338E+10 | 0.110680E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51955.23 | 0.124191E+10 |
June | 0.156900E+10 | 0.108051E+10 | 0.306647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 860777.68 | 0.104992E+10 |
July | 0.145680E+10 | 0.101346E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20604590.59 | 0.873101E+09 |
August | 0.163685E+10 | 0.115004E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26248702.76 | 0.705524E+09 |
September | 0.145243E+10 | 0.109352E+10 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63007.87 | 0.563456E+09 |
October | 0.150991E+10 | 0.124270E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124652E+10 |
November | 0.149516E+10 | 0.138823E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142421E+10 |
December | 0.145680E+10 | 0.144828E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155203E+10 |
Annual Sum or Average | 0.181194E+11 | 0.144487E+11 | 0.363647E+11 | 52445819.39 | 0.152705E+11 | ||||
Minimum of Months | 0.136985E+10 | 0.101346E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563456E+09 |
Maximum of Months | 0.163685E+10 | 0.144828E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26248702.76 | 0.184931E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.892113E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123079E+10 |
February | 0.882782E+09 | 0.734256E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110357E+10 |
March | 0.105485E+10 | 0.804978E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106870E+10 |
April | 0.936002E+09 | 0.678282E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2968329.82 | 0.104282E+10 |
May | 0.101394E+10 | 0.717021E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35318.15 | 0.840162E+09 |
June | 0.101113E+10 | 0.701842E+09 | 0.197615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 588100.35 | 0.717946E+09 |
July | 0.938820E+09 | 0.657154E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9856615.57 | 0.588415E+09 |
August | 0.105485E+10 | 0.745581E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15742868.72 | 0.480680E+09 |
September | 0.936002E+09 | 0.697193E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40168.24 | 0.381289E+09 |
October | 0.973041E+09 | 0.783143E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839739E+09 |
November | 0.963541E+09 | 0.866130E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.945854E+09 |
December | 0.938820E+09 | 0.890821E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103351E+10 |
Annual Sum or Average | 0.116768E+11 | 0.916852E+10 | 0.234348E+11 | 29231400.85 | 0.102735E+11 | ||||
Minimum of Months | 0.882782E+09 | 0.657154E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381289E+09 |
Maximum of Months | 0.105485E+10 | 0.892113E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15742868.72 | 0.123079E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.134151E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190816E+10 |
February | 0.136988E+10 | 0.110648E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177352E+10 |
March | 0.163688E+10 | 0.123812E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169281E+10 |
April | 0.145246E+10 | 0.105392E+10 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2707361.60 | 0.161311E+10 |
May | 0.157341E+10 | 0.111282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51940.70 | 0.127791E+10 |
June | 0.156904E+10 | 0.108861E+10 | 0.306652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 860730.16 | 0.106224E+10 |
July | 0.145684E+10 | 0.102483E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12950720.89 | 0.891130E+09 |
August | 0.163688E+10 | 0.115947E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21700853.66 | 0.736382E+09 |
September | 0.145246E+10 | 0.108299E+10 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57833.91 | 0.610902E+09 |
October | 0.150994E+10 | 0.119553E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137180E+10 |
November | 0.149520E+10 | 0.130651E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149031E+10 |
December | 0.145684E+10 | 0.133009E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162640E+10 |
Annual Sum or Average | 0.181198E+11 | 0.140409E+11 | 0.363653E+11 | 38329440.92 | 0.160547E+11 | ||||
Minimum of Months | 0.136988E+10 | 0.102483E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.610902E+09 |
Maximum of Months | 0.163688E+10 | 0.134151E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21700853.66 | 0.190816E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.890951E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126478E+10 |
February | 0.882782E+09 | 0.726272E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115011E+10 |
March | 0.105485E+10 | 0.804515E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112274E+10 |
April | 0.936002E+09 | 0.679106E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1124215.68 | 0.109442E+10 |
May | 0.101394E+10 | 0.714413E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62682.56 | 0.895019E+09 |
June | 0.101113E+10 | 0.697734E+09 | 0.197614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 573794.07 | 0.744614E+09 |
July | 0.938820E+09 | 0.657693E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8698672.29 | 0.655738E+09 |
August | 0.105485E+10 | 0.743474E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15887721.24 | 0.526695E+09 |
September | 0.936002E+09 | 0.703810E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38568.78 | 0.414179E+09 |
October | 0.973041E+09 | 0.784783E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.889026E+09 |
November | 0.963541E+09 | 0.862501E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994619E+09 |
December | 0.938820E+09 | 0.889717E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108500E+10 |
Annual Sum or Average | 0.116768E+11 | 0.915497E+10 | 0.234347E+11 | 26385654.62 | 0.108369E+11 | ||||
Minimum of Months | 0.882782E+09 | 0.657693E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414179E+09 |
Maximum of Months | 0.105485E+10 | 0.890951E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15887721.24 | 0.126478E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.522007E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.473481E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.562303E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.502580E+10 | 0.984007E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.542155E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.539412E+10 | 0.492004E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.505323E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.562303E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.502580E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.522007E+10 | 0.508404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.515799E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.505323E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.625527E+11 | 0.749486E+13 | |||||||
Minimum of Months | 0.00 | 0.473481E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.562303E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.241145E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.218729E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.259761E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.232171E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.250453E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.249186E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.233438E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.259761E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.232171E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.241145E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.238278E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.233438E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288968E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.218729E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.259761E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.241145E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.218729E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.259761E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.232171E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.250453E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.249186E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.233438E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.259761E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.232171E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.241145E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.238278E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.233438E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288968E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.218729E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.259761E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.241145E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.218729E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.259761E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.232171E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.250453E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.249186E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.233438E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.259761E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.232171E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.241145E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.238278E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.233438E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288968E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.218729E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.259761E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175702E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155669E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147783E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1474116.25 | 0.137868E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3228.75 | 0.104875E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274850.91 | 0.864049E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9327297.15 | 0.720018E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13569618.72 | 0.593959E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1717.58 | 0.494517E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118677E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138320E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152188E+10 |
Annual Sum or Average | 24650829.37 | 0.139834E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494517E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13569618.72 | 0.175702E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278277E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256325E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247547E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4088664.67 | 0.231176E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7670.44 | 0.180110E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 580269.59 | 0.147450E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23023144.03 | 0.121998E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27715106.94 | 0.101210E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3849.50 | 0.846541E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198339E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226330E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246583E+10 |
Annual Sum or Average | 55418705.17 | 0.232000E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.846541E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27715106.94 | 0.278277E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284588E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259844E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256362E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3328414.65 | 0.248436E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201048E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61539.63 | 0.169321E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8213287.27 | 0.140642E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17106477.35 | 0.113380E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913306E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203508E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227244E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244891E+10 |
Annual Sum or Average | 28709718.90 | 0.244060E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913306E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17106477.35 | 0.284588E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 19263.35 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 19263.35 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 19263.35 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 19263.35 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 19263.35 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 19263.35 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 19263.35 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 19263.35 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 19263.35 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 19263.35 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 19263.35 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 19263.35 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 17832.21 | 19263.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 19263.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17299.84 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17299.84 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17299.84 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17299.84 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17299.84 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17299.84 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17299.84 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17299.84 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17299.84 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17299.84 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17299.84 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17299.84 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 17299.84 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17299.84 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17299.84 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17299.84 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17299.84 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17299.84 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17299.84 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17299.84 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17299.84 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17299.84 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17299.84 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17299.84 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17299.84 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17299.84 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 17299.84 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17299.84 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17299.84 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17299.84 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17299.84 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17299.84 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17299.84 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17299.84 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17299.84 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17299.84 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17299.84 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17299.84 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17299.84 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17299.84 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 17299.84 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17299.84 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2172.17 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1366.76 | 28-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 2172.17 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1285.04 | 16-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1892.90 | 07-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1196.71 | 28-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 1513.35 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.54 | 01-APR-17:02 | 1231.86 | 07-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 1133.80 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 | 05-MAY-16:00 | 882.37 | 18-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 1133.80 | 16-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.55 | 28-JUN-16:00 | 1189.09 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1513.35 | 12-JUL-07:40 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.96 | 23-JUL-15:50 | 611.92 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 1234.08 | 02-AUG-07:19 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.86 | 13-AUG-15:10 | 798.65 | 11-AUG-04:00 |
September | 2010.79 | 01-SEP-09:09 | 1892.90 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 14-SEP-17:00 | 583.40 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2172.17 | 20-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1083.03 | 31-OCT-21:10 |
November | 2010.79 | 01-NOV-09:09 | 2172.17 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1313.85 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 2172.17 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1086.63 | 17-DEC-20:55 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1133.80 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.40 | |||||
Maximum of Months | 2010.79 | 2172.17 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 171.96 | 1366.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1399.83 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 875.59 | 28-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 1399.83 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 820.93 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1219.86 | 03-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 771.27 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 795.29 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.12 | 01-APR-17:02 | 792.31 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 730.66 | 05-MAY-14:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 | 05-MAY-16:00 | 566.24 | 18-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 730.66 | 08-JUN-15:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.59 | 28-JUN-16:00 | 761.52 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 730.66 | 12-JUL-07:49 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.30 | 23-JUL-15:50 | 384.84 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 795.29 | 02-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.85 | 13-AUG-15:10 | 504.99 | 11-AUG-04:00 |
September | 1295.83 | 01-SEP-09:09 | 1219.86 | 21-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 14-SEP-17:00 | 372.80 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1399.83 | 26-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 677.61 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 1399.83 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 826.40 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1399.83 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 687.37 | 17-DEC-20:55 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 730.66 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.80 | |||||
Maximum of Months | 1295.83 | 1399.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 123.30 | 875.59 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2172.22 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1305.85 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 2172.22 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1301.51 | 19-FEB-12:00 |
March | 2010.83 | 01-MAR-10:09 | 1892.94 | 13-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1193.96 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1513.38 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.58 | 01-APR-17:02 | 1218.35 | 07-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 1133.82 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 | 05-MAY-16:00 | 853.15 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 1133.82 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.55 | 28-JUN-16:00 | 1153.54 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1513.38 | 12-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.58 | 23-JUL-15:50 | 590.66 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 1234.11 | 02-AUG-07:19 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.79 | 08-AUG-17:00 | 805.29 | 11-AUG-04:00 |
September | 2010.83 | 01-SEP-09:09 | 1892.94 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 14-SEP-17:00 | 562.79 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 2172.22 | 26-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1033.58 | 31-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 2172.22 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1257.24 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 2172.22 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 995.50 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1133.82 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.79 | |||||
Maximum of Months | 2010.83 | 2172.22 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 161.58 | 1305.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1399.83 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 941.72 | 28-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 1399.83 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 903.44 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1219.86 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 874.22 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 975.26 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.38 | 01-APR-16:00 | 910.79 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 795.29 | 02-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 | 05-MAY-16:00 | 606.34 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 730.66 | 05-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.59 | 28-JUN-16:00 | 856.04 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 975.26 | 12-JUL-07:19 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.99 | 23-JUL-13:50 | 468.53 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 975.26 | 02-AUG-07:30 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.09 | 08-AUG-17:00 | 631.14 | 11-AUG-04:00 |
September | 1295.83 | 01-SEP-09:09 | 1219.86 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.74 | 14-SEP-17:00 | 408.05 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1399.83 | 20-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 747.80 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 1399.83 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 939.24 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1399.83 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 800.66 | 17-DEC-20:55 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 730.66 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.05 | |||||
Maximum of Months | 1295.83 | 1399.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 79.99 | 941.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2172.17 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2618.43 | 12-JAN-24:00 |
February | 2010.79 | 01-FEB-10:09 | 2172.17 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2402.10 | 16-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1892.90 | 07-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2273.94 | 28-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 1513.35 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 463.11 | 01-APR-17:02 | 2409.89 | 07-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 1133.80 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 05-MAY-16:00 | 1776.49 | 18-MAY-04:51 |
June | 2010.79 | 01-JUN-09:09 | 1133.80 | 16-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.56 | 28-JUN-16:00 | 2298.60 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1513.35 | 12-JUL-07:49 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 477.53 | 23-JUL-15:50 | 1166.47 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 1234.08 | 02-AUG-07:19 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.39 | 13-AUG-15:10 | 1649.40 | 11-AUG-04:00 |
September | 2010.79 | 01-SEP-09:09 | 1892.90 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.38 | 14-SEP-17:00 | 1160.65 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2172.17 | 20-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2166.99 | 31-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 2172.17 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2496.29 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 2172.17 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2022.49 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1133.80 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1160.65 | |||||
Maximum of Months | 2010.79 | 2172.17 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 477.53 | 2618.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1399.83 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1718.68 | 12-JAN-24:00 |
February | 1239.33 | 01-FEB-08:09 | 1399.83 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1581.56 | 16-FEB-04:00 |
March | 1239.33 | 01-MAR-08:09 | 1219.86 | 03-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1534.14 | 28-MAR-24:00 |
April | 1239.33 | 03-APR-07:10 | 795.29 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 312.32 | 01-APR-17:02 | 1627.01 | 07-APR-24:00 |
May | 1239.33 | 01-MAY-07:10 | 730.66 | 05-MAY-14:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 | 05-MAY-16:00 | 1158.80 | 18-MAY-04:51 |
June | 1239.33 | 01-JUN-07:10 | 666.04 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.04 | 28-JUN-16:00 | 1515.46 | 13-JUN-03:00 |
July | 1239.33 | 03-JUL-07:10 | 730.66 | 12-JUL-07:49 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.07 | 23-JUL-16:10 | 762.93 | 02-JUL-04:00 |
August | 1239.33 | 01-AUG-07:10 | 795.29 | 02-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.63 | 13-AUG-15:10 | 1111.66 | 11-AUG-04:00 |
September | 1239.33 | 01-SEP-07:10 | 1219.86 | 21-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 | 14-SEP-17:00 | 743.57 | 18-SEP-23:00 |
October | 1239.33 | 02-OCT-07:10 | 1399.83 | 27-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1440.09 | 31-OCT-21:03 |
November | 1239.33 | 01-NOV-07:10 | 1399.83 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1645.55 | 29-NOV-23:00 |
December | 1239.33 | 01-DEC-08:09 | 1399.83 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1338.61 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1239.33 | 666.04 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 743.57 | |||||
Maximum of Months | 1239.33 | 1399.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 312.32 | 1718.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2172.22 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2620.60 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 2172.22 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2770.55 | 19-FEB-12:20 |
March | 2010.83 | 01-MAR-10:09 | 1892.94 | 13-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2414.22 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1513.38 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.70 | 01-APR-17:02 | 2466.86 | 07-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 1133.82 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 05-MAY-16:00 | 1763.16 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 1133.82 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.56 | 28-JUN-16:00 | 2284.04 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1513.38 | 12-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.16 | 23-JUL-16:10 | 1181.65 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 1234.11 | 02-AUG-07:19 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.58 | 08-AUG-17:00 | 1697.10 | 11-AUG-04:00 |
September | 2010.83 | 01-SEP-09:09 | 1892.94 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.38 | 14-SEP-17:00 | 1158.98 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 2172.22 | 26-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2166.09 | 31-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 2172.22 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2492.81 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 2172.22 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2044.94 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1133.82 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1158.98 | |||||
Maximum of Months | 2010.83 | 2172.22 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 373.16 | 2770.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1399.83 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1750.84 | 12-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 1399.83 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1613.77 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1219.86 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1567.11 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 975.26 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.27 | 01-APR-16:00 | 1627.40 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 795.29 | 02-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.42 | 06-MAY-13:00 | 1196.29 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 730.66 | 05-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.04 | 28-JUN-15:00 | 1533.96 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 975.26 | 12-JUL-07:19 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.52 | 23-JUL-13:30 | 829.37 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 975.26 | 02-AUG-07:30 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.09 | 13-AUG-13:10 | 1198.71 | 11-AUG-04:00 |
September | 1295.83 | 01-SEP-09:09 | 1219.86 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.58 | 14-SEP-17:00 | 764.68 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1399.83 | 20-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1445.19 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1399.83 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1677.32 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1399.83 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1367.24 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 730.66 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 764.68 | |||||
Maximum of Months | 1295.83 | 1399.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 268.52 | 1750.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2172.17 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3093.69 | 12-JAN-22:03 |
February | 2010.79 | 01-FEB-10:09 | 2172.17 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2908.14 | 16-FEB-22:03 |
March | 2010.79 | 01-MAR-10:09 | 1892.90 | 07-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2819.18 | 29-MAR-04:57 |
April | 2010.79 | 03-APR-09:09 | 1513.35 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 582.87 | 01-APR-17:02 | 2905.04 | 10-APR-21:03 |
May | 2010.79 | 01-MAY-09:09 | 1133.80 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 | 05-MAY-16:00 | 2130.60 | 18-MAY-04:58 |
June | 2010.79 | 01-JUN-09:09 | 1133.80 | 16-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.08 | 28-JUN-16:00 | 2639.95 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1513.35 | 12-JUL-07:49 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 519.06 | 23-JUL-15:50 | 1316.07 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 1234.08 | 02-AUG-07:19 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 304.07 | 13-AUG-14:51 | 1976.89 | 11-AUG-04:00 |
September | 2010.79 | 01-SEP-09:09 | 1892.90 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 14-SEP-17:00 | 1297.64 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2172.17 | 20-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2675.69 | 31-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 2172.17 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2908.38 | 29-NOV-22:03 |
December | 2010.79 | 01-DEC-10:09 | 2172.17 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2404.40 | 22-DEC-22:03 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1133.80 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1297.64 | |||||
Maximum of Months | 2010.79 | 2172.17 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 582.87 | 3093.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1399.83 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2059.50 | 12-JAN-22:03 |
February | 1295.83 | 01-FEB-10:09 | 1399.83 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1936.97 | 16-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1219.86 | 03-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1879.47 | 29-MAR-04:57 |
April | 1295.83 | 03-APR-09:09 | 795.29 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.48 | 01-APR-17:02 | 1932.49 | 10-APR-21:03 |
May | 1295.83 | 01-MAY-09:09 | 730.66 | 05-MAY-14:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.92 | 05-MAY-16:00 | 1434.78 | 18-MAY-04:52 |
June | 1295.83 | 01-JUN-09:09 | 666.04 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.39 | 28-JUN-16:00 | 1741.26 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 730.66 | 12-JUL-07:49 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.73 | 23-JUL-15:50 | 861.30 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 795.29 | 02-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.61 | 13-AUG-15:20 | 1333.77 | 11-AUG-04:00 |
September | 1295.83 | 01-SEP-09:09 | 1219.86 | 21-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.27 | 14-SEP-17:00 | 837.41 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1399.83 | 27-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1781.89 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1399.83 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1936.33 | 29-NOV-22:03 |
December | 1295.83 | 01-DEC-10:09 | 1399.83 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1601.44 | 22-DEC-22:03 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 666.04 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 837.41 | |||||
Maximum of Months | 1295.83 | 1399.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 386.48 | 2059.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2172.22 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3094.51 | 12-JAN-22:03 |
February | 2010.83 | 01-FEB-10:09 | 2172.22 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2993.57 | 19-FEB-12:00 |
March | 2010.83 | 01-MAR-10:09 | 1892.94 | 13-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2828.38 | 29-MAR-04:52 |
April | 2010.83 | 03-APR-09:09 | 1513.38 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.50 | 01-APR-17:02 | 2911.19 | 10-APR-21:03 |
May | 2010.83 | 01-MAY-09:09 | 1133.82 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 | 05-MAY-16:00 | 2149.78 | 18-MAY-04:52 |
June | 2010.83 | 01-JUN-09:09 | 1133.82 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.08 | 28-JUN-16:00 | 2619.76 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1513.38 | 12-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 445.49 | 23-JUL-15:50 | 1333.82 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 1234.11 | 02-AUG-07:19 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.24 | 08-AUG-17:00 | 2032.42 | 11-AUG-04:00 |
September | 2010.83 | 01-SEP-09:09 | 1892.94 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 14-SEP-17:00 | 1294.63 | 30-SEP-04:51 |
October | 2010.83 | 02-OCT-09:09 | 2172.22 | 26-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2676.18 | 31-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 2172.22 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2908.28 | 29-NOV-22:03 |
December | 2010.83 | 01-DEC-10:09 | 2172.22 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2407.28 | 22-DEC-22:03 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1133.82 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1294.63 | |||||
Maximum of Months | 2010.83 | 2172.22 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 445.49 | 3094.51 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1399.83 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2065.76 | 12-JAN-22:03 |
February | 1295.83 | 01-FEB-10:09 | 1399.83 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1941.69 | 16-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1219.86 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1893.29 | 29-MAR-04:52 |
April | 1295.83 | 03-APR-09:09 | 975.26 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.19 | 01-APR-16:00 | 1956.15 | 10-APR-21:03 |
May | 1295.83 | 01-MAY-09:09 | 795.29 | 02-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.38 | 06-MAY-13:00 | 1452.05 | 27-MAY-17:20 |
June | 1295.83 | 01-JUN-09:09 | 730.66 | 05-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.38 | 28-JUN-15:40 | 1767.38 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 975.26 | 12-JUL-07:19 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 313.73 | 23-JUL-14:00 | 968.51 | 22-JUL-22:53 |
August | 1295.83 | 01-AUG-09:09 | 975.26 | 02-AUG-07:30 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.45 | 13-AUG-12:05 | 1435.58 | 11-AUG-04:00 |
September | 1295.83 | 01-SEP-09:09 | 1219.86 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.27 | 14-SEP-17:00 | 875.26 | 30-SEP-04:51 |
October | 1295.83 | 02-OCT-09:09 | 1399.83 | 20-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1788.41 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1399.83 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1969.04 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1399.83 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1622.20 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 730.66 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 875.26 | |||||
Maximum of Months | 1295.83 | 1399.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 313.73 | 2065.76 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 5431.44 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 5431.44 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 5431.44 | 01-MAR-08:09 | 284724.39 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 5431.44 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 5431.44 | 01-MAY-07:10 | 94908.13 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 5431.44 | 01-JUN-07:10 | 189816.26 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 5431.44 | 03-JUL-07:10 | 284724.39 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 5431.44 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 5431.44 | 01-SEP-07:10 | 94908.13 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 5431.44 | 02-OCT-07:10 | 189816.26 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 5431.44 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 5431.44 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 5431.44 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 5431.44 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 250.91 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 250.91 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 250.91 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 250.91 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 250.91 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 250.91 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 250.91 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 250.91 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 250.91 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 250.91 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 250.91 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 250.91 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 250.91 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 250.91 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 250.91 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 250.91 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 250.91 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 250.91 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 250.91 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 250.91 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 250.91 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 250.91 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 250.91 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 250.91 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 250.91 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 250.91 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 250.91 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 250.91 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 250.91 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 250.91 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 250.91 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 250.91 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 250.91 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 250.91 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 250.91 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 250.91 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 250.91 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 250.91 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 250.91 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 250.91 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 250.91 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 250.91 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2871.21 | 28-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2673.88 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2483.56 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.20 | 01-APR-17:02 | 2519.99 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 | 05-MAY-16:00 | 1856.90 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.35 | 28-JUN-15:00 | 2469.49 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.47 | 23-JUL-16:00 | 1246.40 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.52 | 13-AUG-14:51 | 1625.77 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.86 | 14-SEP-17:00 | 1176.29 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2237.81 | 31-OCT-21:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2722.09 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2245.99 | 17-DEC-20:55 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.29 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.47 | 2871.21 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4790.36 | 28-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4430.96 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4160.44 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 559.18 | 01-APR-17:02 | 4293.14 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.49 | 05-MAY-16:00 | 3236.00 | 18-MAY-04:51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.00 | 28-JUN-15:00 | 4195.22 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648.26 | 23-JUL-15:51 | 2094.94 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.33 | 13-AUG-14:51 | 2861.35 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 | 14-SEP-17:00 | 1995.23 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3767.03 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4483.73 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3600.88 | 22-DEC-23:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1995.23 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648.26 | 4790.36 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4888.04 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4425.75 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4238.01 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.15 | 01-APR-17:02 | 4589.25 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 3275.43 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.25 | 28-JUN-17:00 | 4269.67 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.43 | 23-JUL-16:00 | 2094.18 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.80 | 13-AUG-15:40 | 3138.62 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 2037.95 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4101.78 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4660.63 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3833.91 | 22-DEC-23:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2037.95 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.15 | 4888.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 119628.29 | 01-JAN-22:43 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 118486.01 | 21-FEB-02:50 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 113191.31 | 27-MAR-03:53 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 113273.14 | 30-APR-23:11 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 120776.98 | 30-MAY-03:53 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 115966.79 | 19-JUN-01:52 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 119549.54 | 04-JUL-19:40 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 115090.50 | 21-AUG-00:32 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 120686.93 | 11-SEP-03:53 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 117105.22 | 09-OCT-18:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 120178.31 | 12-NOV-16:10 | 2692.84 | 3210.56 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 115448.97 | 25-DEC-23:42 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 113191.31 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 120776.98 | 2692.84 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 67885.96 | 02-JAN-05:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 71142.56 | 24-FEB-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 71975.29 | 09-MAR-05:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 75610.35 | 28-APR-03:02 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75601.65 | 05-MAY-04:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 78188.22 | 12-JUN-03:02 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82092.44 | 11-JUL-03:02 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82344.23 | 30-AUG-04:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79265.09 | 01-SEP-04:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 76333.86 | 10-OCT-03:02 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 75434.31 | 04-NOV-04:12 | 0.00 | 5373.60 | 44532.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 68640.96 | 30-DEC-05:12 | 0.00 | 5373.60 | 44532.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 67885.96 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82344.23 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 26007.44 | 12-JAN-17:00 | 15316.26 | 17299.84 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 44238.32 | 10-FEB-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 57187.12 | 02-MAR-06:02 | 16122.38 | 5373.60 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 62152.40 | 28-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 64510.33 | 05-MAY-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 66428.88 | 23-JUN-04:11 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 67870.73 | 11-JUL-04:11 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75747.06 | 25-AUG-04:12 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 68936.72 | 01-SEP-04:11 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 61026.11 | 10-OCT-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 55524.57 | 07-NOV-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 29036.67 | 06-DEC-16:20 | 15316.26 | 17299.84 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 26007.44 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75747.06 | 16122.38 | 17299.84 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 20399.96 | 11-JAN-16:00 | 15316.26 | 17299.84 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27165.01 | 28-FEB-17:00 | 15316.26 | 17299.84 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31131.62 | 15-MAR-16:00 | 15316.26 | 17299.84 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 54829.93 | 28-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 57924.54 | 05-MAY-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 64451.35 | 12-JUN-04:12 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 65743.40 | 24-JUL-05:02 | 16122.38 | 5373.60 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 70721.86 | 25-AUG-04:11 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 59566.96 | 01-SEP-05:03 | 4836.72 | 1612.08 | 22942.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38284.89 | 04-OCT-16:00 | 15316.26 | 17299.84 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 25358.78 | 02-NOV-16:00 | 15316.26 | 17299.84 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18729.01 | 06-DEC-17:00 | 15316.26 | 17299.84 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 18729.01 | 0.00 | 1612.08 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 70721.86 | 16122.38 | 17299.84 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2695.32 | 11-JAN-16:00 | 1923.11 | 1892.90 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.79 |
February | 4639.34 | 27-FEB-15:30 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.71 |
March | 5002.17 | 10-MAR-14:30 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.02 |
April | 7214.57 | 27-APR-15:20 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 | 0.00 |
May | 6885.97 | 05-MAY-13:30 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 |
June | 8212.86 | 12-JUN-05:01 | 2024.33 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.35 |
July | 8827.53 | 24-JUL-15:00 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 36.47 | 0.00 |
August | 8463.89 | 25-AUG-14:00 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 | 0.00 |
September | 6419.07 | 12-SEP-14:30 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2.27 | 0.00 |
October | 5094.13 | 04-OCT-15:00 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.85 |
November | 4424.49 | 06-NOV-11:50 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.99 |
December | 3029.76 | 29-DEC-13:20 | 1923.11 | 1133.80 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.70 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2695.32 | 1923.11 | 674.71 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8827.53 | 2024.33 | 1892.90 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 36.47 | 145.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2488.31 | 11-JAN-14:20 | 1295.83 | 730.66 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.47 |
February | 4077.38 | 08-FEB-09:35 | 2478.65 | 1332.08 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.61 |
March | 8784.67 | 14-MAR-08:55 | 2478.65 | 1332.08 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.08 |
April | 11737.49 | 27-APR-08:20 | 1239.33 | 666.04 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.55 |
May | 19949.40 | 14-MAY-08:42 | 326.14 | 185.01 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.86 |
June | 18010.78 | 25-JUN-08:62 | 326.14 | 185.01 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.76 |
July | 20783.76 | 30-JUL-08:32 | 326.14 | 185.01 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.45 |
August | 23002.24 | 13-AUG-08:21 | 456.59 | 259.01 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.58 |
September | 19249.15 | 04-SEP-08:41 | 652.28 | 370.02 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.54 |
October | 9470.66 | 04-OCT-08:40 | 2478.65 | 1332.08 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.24 |
November | 3997.43 | 15-NOV-08:35 | 2478.65 | 1332.08 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.44 |
December | 2569.89 | 05-DEC-09:35 | 2478.65 | 1332.08 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.08 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2488.31 | 326.14 | 185.01 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.55 | |
Maximum of Months | 23002.24 | 2478.65 | 1332.08 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15711.32 | 20-JAN-13:20 | 1923.15 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.43 |
February | 20492.42 | 12-FEB-14:13 | 404.87 | 229.68 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 927.27 |
March | 17660.89 | 14-MAR-13:30 | 2010.83 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.35 |
April | 18597.58 | 02-APR-11:53 | 404.87 | 229.68 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.50 |
May | 12098.18 | 15-MAY-12:40 | 1923.15 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.08 |
June | 10080.37 | 21-JUN-13:30 | 2010.83 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 |
July | 14776.79 | 31-JUL-12:40 | 1923.15 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 21.11 | 0.00 |
August | 25085.92 | 13-AUG-12:23 | 404.87 | 229.68 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.69 |
September | 26454.28 | 10-SEP-14:02 | 506.09 | 287.09 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.48 |
October | 24291.64 | 08-OCT-13:22 | 506.09 | 287.09 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.23 |
November | 19854.43 | 11-NOV-12:23 | 404.87 | 229.68 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.78 |
December | 16343.12 | 05-DEC-12:30 | 1058.33 | 1033.54 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.58 |
Annual Sum or Average | |||||||||||
Minimum of Months | 10080.37 | 404.87 | 229.68 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26454.28 | 2010.83 | 1033.54 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 21.11 | 927.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4810.96 | 05-JAN-15:40 | 1239.33 | 666.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.42 |
February | 10423.23 | 27-FEB-15:30 | 1239.33 | 666.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.68 |
March | 15178.44 | 11-MAR-05:11 | 0.00 | 434.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.98 |
April | 22791.09 | 23-APR-18:02 | 0.00 | 204.30 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.36 |
May | 25844.85 | 07-MAY-16:22 | 391.37 | 222.01 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.72 |
June | 25235.71 | 25-JUN-15:42 | 326.14 | 185.01 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.29 |
July | 27576.35 | 23-JUL-17:01 | 0.00 | 286.01 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.86 |
August | 27511.19 | 06-AUG-16:31 | 456.59 | 259.01 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.99 |
September | 25504.58 | 10-SEP-16:42 | 391.37 | 222.01 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.75 |
October | 14438.94 | 02-OCT-05:01 | 1304.55 | 434.81 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.97 |
November | 16798.23 | 04-NOV-04:11 | 0.00 | 434.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.75 |
December | 11690.88 | 30-DEC-05:11 | 0.00 | 434.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.97 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4810.96 | 0.00 | 185.01 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.68 | |
Maximum of Months | 27576.35 | 1304.55 | 666.04 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2190.13 | 11-JAN-16:00 | 1923.11 | 1892.90 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.15 |
February | 2765.43 | 27-FEB-15:40 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.19 |
March | 2736.49 | 10-MAR-14:20 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.19 |
April | 5644.37 | 27-APR-15:50 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 51.52 | 0.00 |
May | 6013.41 | 05-MAY-13:30 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 |
June | 6541.22 | 21-JUN-15:40 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 | 0.00 |
July | 7324.60 | 24-JUL-15:00 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 80.97 | 0.00 |
August | 7312.65 | 25-AUG-14:00 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 34.68 | 0.00 |
September | 5383.17 | 12-SEP-14:50 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 3.73 | 0.00 |
October | 3336.30 | 04-OCT-15:30 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.14 |
November | 2497.15 | 04-NOV-14:00 | 211.66 | 172.25 | 840.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1963.34 | 14-DEC-12:00 | 1923.11 | 1133.80 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.73 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1963.34 | 211.66 | 172.25 | 840.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7324.60 | 2010.79 | 1892.90 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 80.97 | 503.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2129.02 | 11-JAN-16:00 | 1239.33 | 1219.86 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.58 |
February | 2858.98 | 27-FEB-15:30 | 1239.33 | 666.04 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 |
March | 6625.88 | 14-MAR-08:55 | 2478.65 | 1332.08 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.07 |
April | 11506.45 | 27-APR-08:50 | 1239.33 | 666.04 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.60 |
May | 14344.41 | 14-MAY-08:53 | 260.91 | 148.01 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.13 |
June | 21260.98 | 25-JUN-08:32 | 391.37 | 222.01 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.32 |
July | 24047.78 | 30-JUL-08:51 | 456.59 | 259.01 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.96 |
August | 24092.27 | 13-AUG-09:01 | 456.59 | 259.01 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.40 |
September | 20417.92 | 10-SEP-08:22 | 326.14 | 185.01 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.71 |
October | 8323.21 | 04-OCT-09:00 | 1239.33 | 666.04 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.52 |
November | 2659.70 | 04-NOV-13:00 | 130.46 | 111.01 | 541.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2005.63 | 05-DEC-09:45 | 2478.65 | 1332.08 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.07 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2005.63 | 130.46 | 111.01 | 541.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24092.27 | 2478.65 | 1332.08 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15859.74 | 20-JAN-13:30 | 1923.15 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.21 |
February | 21670.00 | 12-FEB-13:22 | 506.09 | 287.09 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2217.92 |
March | 18210.20 | 14-MAR-13:40 | 2010.83 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.29 |
April | 17449.45 | 27-APR-13:00 | 1923.15 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 29.27 | 0.00 |
May | 11808.26 | 04-MAY-13:10 | 2010.83 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.43 |
June | 9595.48 | 21-JUN-13:30 | 2010.83 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.35 |
July | 24381.79 | 30-JUL-13:32 | 404.87 | 229.68 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.25 |
August | 25070.42 | 13-AUG-12:23 | 404.87 | 229.68 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.47 |
September | 27766.81 | 10-SEP-14:22 | 607.31 | 344.51 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.13 |
October | 26632.24 | 08-OCT-13:12 | 607.31 | 344.51 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.49 |
November | 20066.35 | 11-NOV-13:02 | 404.87 | 229.68 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 886.70 |
December | 17211.47 | 03-DEC-13:23 | 303.66 | 172.26 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 905.34 |
Annual Sum or Average | |||||||||||
Minimum of Months | 9595.48 | 303.66 | 172.26 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27766.81 | 2010.83 | 1033.54 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 29.27 | 2217.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2414.01 | 05-JAN-15:50 | 1239.33 | 666.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.97 |
February | 6452.95 | 27-FEB-15:40 | 1239.33 | 666.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.69 |
March | 9727.81 | 14-MAR-16:00 | 1239.33 | 666.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.87 |
April | 13932.80 | 01-APR-17:07 | 391.37 | 222.01 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.57 |
May | 25796.46 | 14-MAY-16:31 | 521.82 | 296.02 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.10 |
June | 23185.21 | 25-JUN-16:42 | 326.14 | 185.01 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.61 |
July | 26803.92 | 30-JUL-18:11 | 0.00 | 367.73 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.97 |
August | 24015.85 | 06-AUG-17:11 | 0.00 | 286.01 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.70 |
September | 24761.72 | 10-SEP-16:21 | 456.59 | 259.01 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.83 |
October | 11212.75 | 04-OCT-16:00 | 1239.33 | 666.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.08 |
November | 4295.12 | 04-NOV-15:50 | 130.46 | 111.01 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 |
December | 2614.06 | 05-DEC-15:40 | 1239.33 | 666.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.64 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2414.01 | 0.00 | 111.01 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | |
Maximum of Months | 26803.92 | 1239.33 | 666.04 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2078.17 | 11-JAN-16:00 | 1923.11 | 1892.90 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.22 |
February | 2672.02 | 27-FEB-15:50 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.36 |
March | 2709.20 | 10-MAR-14:40 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.43 |
April | 6386.33 | 27-APR-15:30 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 61.72 | 0.00 |
May | 6420.88 | 05-MAY-13:30 | 2010.79 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.82 |
June | 7360.51 | 21-JUN-15:40 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 | 0.00 |
July | 8542.97 | 24-JUL-15:00 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 98.84 | 0.00 |
August | 8151.08 | 09-AUG-15:30 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 116.37 | 0.00 |
September | 5877.75 | 14-SEP-15:50 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 0.00 |
October | 3244.57 | 04-OCT-15:30 | 1923.11 | 1033.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.10 |
November | 2411.48 | 04-NOV-14:50 | 202.43 | 188.97 | 840.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 |
December | 1774.50 | 29-DEC-16:00 | 1923.11 | 2172.17 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.41 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1774.50 | 202.43 | 188.97 | 840.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8542.97 | 2010.79 | 2172.17 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 116.37 | 248.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2023.54 | 11-JAN-16:00 | 1239.33 | 1219.86 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.26 |
February | 2735.90 | 27-FEB-15:00 | 1295.83 | 666.04 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.99 |
March | 5094.68 | 14-MAR-09:25 | 2591.66 | 1332.08 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.21 |
April | 10946.67 | 27-APR-09:00 | 1239.33 | 666.04 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.14 |
May | 13447.87 | 14-MAY-09:12 | 326.14 | 185.01 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 569.94 |
June | 18395.43 | 25-JUN-09:02 | 391.37 | 222.01 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.49 |
July | 21732.52 | 30-JUL-09:02 | 391.37 | 222.01 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.55 |
August | 21385.70 | 13-AUG-09:12 | 326.14 | 185.01 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.43 |
September | 17133.76 | 10-SEP-08:32 | 391.37 | 222.01 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.33 |
October | 7096.07 | 04-OCT-09:00 | 1239.33 | 666.04 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.80 |
November | 2532.78 | 04-NOV-14:00 | 136.40 | 111.01 | 541.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1721.98 | 05-DEC-14:00 | 1239.33 | 666.04 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.23 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1721.98 | 136.40 | 111.01 | 541.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21732.52 | 2591.66 | 1332.08 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 569.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15694.11 | 20-JAN-13:20 | 1923.15 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.09 |
February | 16962.08 | 27-FEB-14:10 | 2010.83 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.34 |
March | 18560.96 | 14-MAR-13:40 | 2010.83 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.32 |
April | 18049.82 | 27-APR-13:10 | 2010.83 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 32.76 | 0.00 |
May | 12392.11 | 04-MAY-13:10 | 2010.83 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.69 |
June | 10360.85 | 21-JUN-13:30 | 2010.83 | 1033.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.01 |
July | 25077.39 | 30-JUL-13:02 | 404.87 | 229.68 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.87 |
August | 26835.99 | 13-AUG-13:13 | 404.87 | 229.68 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.61 |
September | 29593.68 | 10-SEP-13:12 | 607.31 | 344.51 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.51 |
October | 26866.40 | 08-OCT-13:42 | 506.09 | 287.09 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.75 |
November | 16846.90 | 04-NOV-13:30 | 211.67 | 172.26 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14879.72 | 05-DEC-12:30 | 1058.33 | 1033.54 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.79 |
Annual Sum or Average | |||||||||||
Minimum of Months | 10360.85 | 211.67 | 172.26 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29593.68 | 2010.83 | 1033.54 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 32.76 | 579.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2457.14 | 05-JAN-15:50 | 1239.33 | 666.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.29 |
February | 5937.72 | 27-FEB-15:40 | 1239.33 | 666.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.57 |
March | 9714.29 | 14-MAR-16:00 | 1239.33 | 666.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.55 |
April | 14162.16 | 26-APR-16:40 | 391.37 | 370.02 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 | 0.00 |
May | 24698.19 | 07-MAY-16:42 | 391.37 | 222.01 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.59 |
June | 22972.13 | 18-JUN-17:01 | 0.00 | 326.87 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 752.93 |
July | 28753.08 | 30-JUL-17:41 | 0.00 | 408.59 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.54 |
August | 25073.36 | 06-AUG-17:11 | 0.00 | 286.01 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.80 |
September | 25493.72 | 10-SEP-17:11 | 0.00 | 286.01 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.07 |
October | 11188.96 | 04-OCT-16:00 | 1239.33 | 666.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.43 |
November | 3946.60 | 04-NOV-15:40 | 130.46 | 111.01 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 |
December | 2571.16 | 05-DEC-15:40 | 1239.33 | 666.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.84 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2457.14 | 0.00 | 111.01 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28753.08 | 1239.33 | 666.04 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 | 752.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3791.11 | 04-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.89 |
February | 4437.05 | 28-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.32 |
March | 4801.69 | 01-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.31 |
April | 5786.11 | 29-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.09 |
May | 6482.15 | 01-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.57 |
June | 7769.92 | 12-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.75 |
July | 7534.82 | 05-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.93 |
August | 7510.85 | 28-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.67 |
September | 7352.94 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.61 |
October | 7418.01 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.55 |
November | 5975.10 | 06-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.79 |
December | 4297.65 | 04-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3791.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7769.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6503.23 | 14-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2817.36 |
February | 6088.86 | 18-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 956.56 |
March | 4830.39 | 06-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1979.18 |
April | 4588.86 | 29-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.51 |
May | 4511.88 | 06-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.71 |
June | 4396.07 | 13-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.95 |
July | 4482.52 | 15-JUL-20:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.03 |
August | 5035.72 | 10-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.54 | 0.00 |
September | 4683.79 | 12-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.90 |
October | 4341.89 | 05-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.45 |
November | 5689.83 | 24-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1420.19 |
December | 6185.37 | 09-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1596.92 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4341.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6503.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.54 | 2817.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 338.46 | 11-JAN-17:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.29 |
February | 3184.84 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.01 |
March | 5411.62 | 14-MAR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.99 |
April | 13083.53 | 27-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.08 | 0.00 |
May | 13246.42 | 04-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.10 |
June | 13798.08 | 28-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.08 |
July | 14682.67 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.34 | 0.00 |
August | 15658.08 | 10-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.53 | 0.00 |
September | 11984.46 | 14-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.74 |
October | 8078.23 | 04-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.29 |
November | 4233.93 | 04-NOV-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 351.86 | 30-DEC-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.87 |
Annual Sum or Average | |||||||||||
Minimum of Months | 338.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15658.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.34 | 448.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1825.34 | 05-JAN-16:20 | 0.00 | 250.91 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3920.16 | 07-FEB-16:50 | 0.00 | 250.91 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5985.67 | 14-MAR-17:20 | 0.00 | 83.64 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8069.78 | 26-APR-18:20 | 0.00 | 83.64 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2528.11 | 29-MAY-18:38 | 0.00 | 61.57 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4301.05 | 18-JUN-18:52 | 0.00 | 76.96 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6754.12 | 30-JUL-18:49 | 0.00 | 107.75 | 40920.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8198.73 | 06-AUG-19:30 | 0.00 | 153.92 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2466.65 | 10-SEP-17:38 | 0.00 | 76.96 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4312.19 | 03-OCT-17:00 | 0.00 | 139.39 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5746.71 | 12-NOV-15:53 | 0.00 | 41.82 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7641.81 | 05-DEC-16:00 | 0.00 | 250.91 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1825.34 | 0.00 | 41.82 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8198.73 | 0.00 | 250.91 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1336.60 | 20-JAN-16:20 | 0.00 | 250.91 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3558.80 | 08-FEB-17:00 | 0.00 | 250.91 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5585.80 | 14-MAR-17:20 | 0.00 | 83.64 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7697.46 | 26-APR-18:10 | 0.00 | 83.64 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2264.42 | 07-MAY-18:38 | 0.00 | 92.35 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4002.69 | 22-JUN-19:00 | 0.00 | 83.64 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6260.29 | 30-JUL-18:34 | 0.00 | 107.75 | 40920.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7778.35 | 06-AUG-19:12 | 0.00 | 92.35 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2238.71 | 10-SEP-17:30 | 0.00 | 76.96 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4051.10 | 04-OCT-17:00 | 0.00 | 139.39 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5183.01 | 10-NOV-16:10 | 0.00 | 250.91 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6983.18 | 05-DEC-16:10 | 0.00 | 250.91 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1336.60 | 0.00 | 76.96 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7778.35 | 0.00 | 250.91 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1271.66 | 05-JAN-16:20 | 0.00 | 250.91 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3470.26 | 08-FEB-17:00 | 0.00 | 250.91 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5594.50 | 14-MAR-17:20 | 0.00 | 83.64 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7789.52 | 26-APR-18:10 | 0.00 | 83.64 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2354.65 | 07-MAY-18:26 | 0.00 | 76.96 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4091.74 | 22-JUN-19:00 | 0.00 | 83.64 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6426.57 | 30-JUL-18:31 | 0.00 | 107.75 | 40920.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7870.51 | 06-AUG-19:06 | 0.00 | 107.75 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2272.00 | 08-SEP-17:40 | 0.00 | 83.64 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4074.84 | 04-OCT-17:00 | 0.00 | 139.39 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5051.62 | 10-NOV-16:10 | 0.00 | 250.91 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6827.90 | 05-DEC-16:10 | 0.00 | 250.91 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1271.66 | 0.00 | 76.96 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7870.51 | 0.00 | 250.91 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 89818.58 | 12-JAN-17:00 | 0.00 | 5431.44 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182064.02 | 27-FEB-17:00 | 0.00 | 5431.44 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 273930.48 | 14-MAR-16:00 | 0.00 | 5431.44 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367445.90 | 01-APR-18:13 | 0.00 | 999.60 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 103942.92 | 01-MAY-00:02 | 0.00 | 1666.00 | 474540.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 182648.93 | 20-JUN-16:00 | 0.00 | 5431.44 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 274679.00 | 05-JUL-16:00 | 0.00 | 5431.44 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 368765.96 | 13-AUG-18:22 | 0.00 | 1666.00 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 104926.35 | 01-SEP-00:05 | 0.00 | 1332.80 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 183275.40 | 04-OCT-16:00 | 0.00 | 5431.44 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 274507.20 | 06-NOV-17:00 | 0.00 | 5431.44 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 366181.78 | 05-DEC-17:00 | 0.00 | 5431.44 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 89818.58 | 0.00 | 999.60 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 368765.96 | 0.00 | 5431.44 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.152629E+13 | 1028988.25 | 10-JAN-16:00 | 0.387771E+12 | 1413997.58 | 02-JAN-05:19 |
February | 0.173078E+13 | 1179569.95 | 27-FEB-14:00 | 0.226088E+12 | 755959.72 | 13-FEB-05:10 |
March | 0.232444E+13 | 1350791.48 | 14-MAR-15:00 | 0.115588E+12 | 621396.04 | 06-MAR-05:19 |
April | 0.257292E+13 | 1696622.14 | 26-APR-15:20 | 0.720774E+11 | 479280.22 | 18-APR-05:10 |
May | 0.156169E+13 | 1281710.48 | 15-MAY-15:00 | 0.544428E+11 | 910022.43 | 23-MAY-19:40 |
June | 0.190811E+13 | 1391995.61 | 27-JUN-15:50 | 0.487107E+11 | 210166.43 | 19-JUN-01:49 |
July | 0.237486E+13 | 1599826.13 | 31-JUL-15:00 | 0.466590E+11 | 172200.80 | 04-JUL-18:19 |
August | 0.293219E+13 | 1803500.90 | 29-AUG-15:09 | 0.496947E+11 | 155648.42 | 06-AUG-21:19 |
September | 0.149898E+13 | 1217121.52 | 14-SEP-15:30 | 0.467405E+11 | 199757.26 | 24-SEP-23:30 |
October | 0.186261E+13 | 1369778.32 | 04-OCT-15:09 | 0.674838E+11 | 466981.47 | 28-OCT-05:10 |
November | 0.219778E+13 | 1317584.44 | 16-NOV-16:30 | 0.164622E+12 | 569856.92 | 24-NOV-06:10 |
December | 0.266994E+13 | 1450329.15 | 05-DEC-16:19 | 0.282021E+12 | 715002.40 | 18-DEC-05:19 |
Annual Sum or Average | 0.251606E+14 | 0.156190E+13 | ||||
Minimum of Months | 0.149898E+13 | 1028988.25 | 0.466590E+11 | 155648.42 | ||
Maximum of Months | 0.293219E+13 | 1803500.90 | 0.387771E+12 | 1413997.58 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.273794E+12 | 0.431737E+11 | 0.766053E+12 | 0.166082E+12 | 0.164695E+12 | 0.981697E+10 | 0.00 | 0.100718E+11 | 0.145313E+10 | 0.911484E+11 | 0.00 | 0.00 | 0.00 |
February | 0.243439E+12 | 0.336238E+11 | 0.978954E+12 | 0.150014E+12 | 0.150867E+12 | 0.945691E+10 | 0.00 | 0.290853E+11 | 0.647098E+10 | 0.128873E+12 | 0.00 | 0.00 | 0.00 |
March | 0.285914E+12 | 0.300497E+11 | 0.141645E+13 | 0.166252E+12 | 0.176219E+12 | 0.110835E+11 | 0.00 | 0.474046E+11 | 0.113056E+11 | 0.179762E+12 | 0.00 | 0.00 | 0.00 |
April | 0.252344E+12 | 0.226151E+11 | 0.166021E+13 | 0.160704E+12 | 0.171593E+12 | 0.151489E+11 | 0.00 | 0.101697E+12 | 0.327495E+11 | 0.155859E+12 | 0.00 | 0.00 | 0.00 |
May | 0.271583E+12 | 0.190179E+11 | 0.774418E+12 | 0.166164E+12 | 0.179922E+12 | 0.202155E+11 | 0.00 | 0.776917E+11 | 0.298080E+11 | 0.228726E+11 | 0.00 | 0.00 | 0.00 |
June | 0.269700E+12 | 0.165177E+11 | 0.106218E+13 | 0.160867E+12 | 0.178157E+12 | 0.252038E+11 | 0.00 | 0.119838E+12 | 0.549515E+11 | 0.206882E+11 | 0.00 | 0.00 | 0.00 |
July | 0.251888E+12 | 0.177480E+11 | 0.139289E+13 | 0.166001E+12 | 0.183644E+12 | 0.325369E+11 | 0.00 | 0.218367E+12 | 0.903302E+11 | 0.214611E+11 | 0.00 | 0.00 | 0.00 |
August | 0.282174E+12 | 0.210823E+11 | 0.173328E+13 | 0.166251E+12 | 0.191973E+12 | 0.373056E+11 | 0.00 | 0.370020E+12 | 0.129182E+12 | 0.921261E+09 | 0.00 | 0.00 | 0.00 |
September | 0.253699E+12 | 0.260388E+11 | 0.740378E+12 | 0.160705E+12 | 0.176522E+12 | 0.238807E+11 | 0.00 | 0.784023E+11 | 0.376111E+11 | 0.174421E+10 | 0.00 | 0.00 | 0.00 |
October | 0.267039E+12 | 0.341795E+11 | 0.108288E+13 | 0.166079E+12 | 0.174930E+12 | 0.143832E+11 | 0.00 | 0.571205E+11 | 0.186243E+11 | 0.473723E+11 | 0.00 | 0.00 | 0.00 |
November | 0.269635E+12 | 0.397825E+11 | 0.135889E+13 | 0.160774E+12 | 0.162352E+12 | 0.105835E+11 | 0.00 | 0.873674E+11 | 0.184250E+11 | 0.899704E+11 | 0.00 | 0.00 | 0.00 |
December | 0.266380E+12 | 0.449245E+11 | 0.170972E+13 | 0.166007E+12 | 0.165666E+12 | 0.967150E+10 | 0.00 | 0.156730E+12 | 0.307719E+11 | 0.120074E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318759E+13 | 0.348753E+12 | 0.146763E+14 | 0.195590E+13 | 0.207654E+13 | 0.219287E+12 | 0.00 | 0.135380E+13 | 0.461683E+12 | 0.880747E+12 | |||
Minimum of Months | 0.243439E+12 | 0.165177E+11 | 0.740378E+12 | 0.150014E+12 | 0.150867E+12 | 0.945691E+10 | 0.00 | 0.100718E+11 | 0.145313E+10 | 0.921261E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.285914E+12 | 0.449245E+11 | 0.173328E+13 | 0.166252E+12 | 0.191973E+12 | 0.373056E+11 | 0.00 | 0.370020E+12 | 0.129182E+12 | 0.179762E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.335089E+12 | 0.00 | 0.526822E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.177922E+12 | 0.00 | 0.481656E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.600956E+11 | 0.00 | 0.554929E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.226347E+11 | 0.00 | 0.494427E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.355293E+10 | 0.00 | 0.508899E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.238240E+09 | 0.00 | 0.484724E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.106002E+10 | 0.00 | 0.455990E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.880973E+09 | 0.00 | 0.488137E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.154530E+10 | 0.00 | 0.451952E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.193206E+11 | 0.00 | 0.481632E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.115682E+12 | 0.00 | 0.489400E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.231630E+12 | 0.00 | 0.503904E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.969652E+12 | 0.592247E+12 | |||||
Minimum of Months | 0.00 | 0.00 | 0.238240E+09 | 0.00 | 0.451952E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.335089E+12 | 0.00 | 0.554929E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 321032.30 | 02-JAN-08:09 | 39974.20 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 126050.31 | 02-JAN-08:20 | 101972.95 | 02-JAN-06:10 | 16455.86 | 09-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 321032.30 | 02-FEB-16:00 | 39974.20 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 126049.16 | 02-FEB-08:20 | 116502.49 | 08-FEB-15:20 | 16982.17 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 310010.48 | 22-MAR-07:10 | 39974.20 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 126044.41 | 22-MAR-07:19 | 126740.51 | 01-MAR-15:30 | 16464.79 | 18-MAR-11:00 | 0.00 | 01-MAR-00:10 |
April | 292871.20 | 03-APR-07:10 | 39974.20 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 126035.25 | 03-APR-07:19 | 123334.60 | 27-APR-14:39 | 32640.30 | 26-APR-15:20 | 0.00 | 01-APR-00:10 |
May | 280051.24 | 02-MAY-07:10 | 26960.70 | 01-MAY-19:19 | 423497.50 | 01-MAY-07:10 | 126028.41 | 02-MAY-07:19 | 123988.15 | 25-MAY-15:00 | 33241.33 | 04-MAY-15:50 | 0.00 | 01-MAY-00:10 |
June | 279275.73 | 16-JUN-07:10 | 26960.70 | 01-JUN-19:00 | 541788.89 | 01-JUN-07:10 | 126028.00 | 16-JUN-07:19 | 123642.87 | 28-JUN-15:00 | 32751.33 | 28-JUN-13:39 | 0.00 | 01-JUN-00:10 |
July | 288744.41 | 12-JUL-07:49 | 26960.70 | 01-JUL-20:10 | 660080.29 | 03-JUL-07:10 | 126033.05 | 12-JUL-07:00 | 126104.38 | 31-JUL-15:00 | 33137.38 | 07-JUL-13:39 | 0.00 | 01-JUL-00:10 |
August | 286168.69 | 02-AUG-07:30 | 39974.20 | 16-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 126031.68 | 02-AUG-07:40 | 142073.54 | 10-AUG-15:00 | 39847.57 | 30-AUG-15:50 | 0.00 | 01-AUG-00:10 |
September | 310010.48 | 21-SEP-07:10 | 39974.20 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 126044.41 | 21-SEP-07:19 | 129334.68 | 14-SEP-14:39 | 39886.96 | 11-SEP-15:20 | 0.00 | 01-SEP-00:10 |
October | 321032.30 | 27-OCT-07:10 | 39974.20 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 126050.31 | 27-OCT-07:19 | 128695.30 | 11-OCT-14:30 | 17088.41 | 04-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 321032.30 | 01-NOV-07:10 | 39974.20 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 126050.31 | 01-NOV-07:19 | 113483.43 | 15-NOV-14:09 | 16785.59 | 04-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 321032.30 | 01-DEC-16:19 | 39974.20 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 126050.31 | 08-DEC-08:20 | 107969.77 | 06-DEC-13:09 | 16490.21 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 279275.73 | 26960.70 | 423497.50 | 126028.00 | 101972.95 | 16455.86 | 0.00 | |||||||
Maximum of Months | 321032.30 | 39974.20 | 778371.69 | 126050.31 | 142073.54 | 39886.96 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum}[W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum}[W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 12763.72 | 11-JAN-15:00 | 2538.26 | 11-JAN-15:30 | 63658.75 | 09-JAN-11:00 | 0.00 | 0.00 | 0.00 |
February | 93074.74 | 27-FEB-15:00 | 50386.42 | 27-FEB-15:09 | 100000.00 | 11-FEB-17:10 | 0.00 | 0.00 | 0.00 |
March | 121316.04 | 18-MAR-15:00 | 49713.61 | 18-MAR-14:09 | 100000.00 | 01-MAR-04:10 | 0.00 | 0.00 | 0.00 |
April | 329000.11 | 26-APR-15:20 | 79389.88 | 27-APR-12:50 | 100000.00 | 01-APR-17:10 | 0.00 | 0.00 | 0.00 |
May | 213527.71 | 04-MAY-15:50 | 79389.88 | 05-MAY-12:00 | 100000.00 | 14-MAY-14:09 | 0.00 | 0.00 | 0.00 |
June | 249008.14 | 21-JUN-15:09 | 79389.88 | 21-JUN-16:10 | 100000.00 | 01-JUN-14:09 | 0.00 | 0.00 | 0.00 |
July | 337327.07 | 31-JUL-15:00 | 79389.88 | 07-JUL-12:30 | 100000.00 | 18-JUL-14:39 | 0.00 | 0.00 | 0.00 |
August | 409580.16 | 29-AUG-14:39 | 79389.88 | 07-AUG-10:30 | 97749.67 | 09-AUG-08:00 | 0.00 | 0.00 | 0.00 |
September | 198392.78 | 14-SEP-13:09 | 79389.88 | 11-SEP-15:30 | 31155.01 | 20-SEP-15:00 | 0.00 | 0.00 | 0.00 |
October | 171909.39 | 04-OCT-14:00 | 53033.27 | 04-OCT-14:39 | 100000.00 | 03-OCT-11:20 | 0.00 | 0.00 | 0.00 |
November | 152220.97 | 04-NOV-13:50 | 53013.91 | 04-NOV-13:39 | 100000.00 | 13-NOV-22:10 | 0.00 | 0.00 | 0.00 |
December | 105697.77 | 02-DEC-16:00 | 43163.70 | 03-DEC-14:39 | 100000.00 | 02-DEC-04:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 12763.72 | 2538.26 | 31155.01 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 409580.16 | 79389.88 | 100000.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1028988.25 | 10-JAN-16:00 | 321032.30 | 423497.50 | 39974.20 | 89270.92 | 78383.41 | 16297.07 | 0.00 | 6260.91 | 1290.01 |
February | 1179569.95 | 27-FEB-14:00 | 276093.44 | 541788.89 | 0.00 | 40207.72 | 94728.06 | 16523.90 | 0.00 | 91719.38 | 50354.01 |
March | 1350791.48 | 14-MAR-15:00 | 276093.44 | 660080.29 | 0.00 | 89246.91 | 107020.62 | 16418.35 | 0.00 | 79510.78 | 49489.40 |
April | 1696622.14 | 26-APR-15:20 | 276093.44 | 778371.69 | 0.00 | 89246.91 | 113056.47 | 32640.30 | 0.00 | 329000.11 | 54173.47 |
May | 1281710.48 | 15-MAY-15:00 | 276093.44 | 423497.50 | 0.00 | 89246.91 | 114372.09 | 30724.41 | 0.00 | 196896.23 | 50879.91 |
June | 1391995.61 | 27-JUN-15:50 | 276093.44 | 541788.89 | 0.00 | 89246.91 | 116350.72 | 31546.43 | 0.00 | 246873.24 | 53430.37 |
July | 1599826.13 | 31-JUL-15:00 | 276093.44 | 660080.29 | 0.00 | 89246.91 | 126104.38 | 31584.17 | 0.00 | 337327.07 | 79389.88 |
August | 1803500.90 | 29-AUG-15:09 | 276093.44 | 778371.69 | 0.00 | 89246.91 | 140767.33 | 32158.02 | 0.00 | 407473.63 | 79389.88 |
September | 1217121.52 | 14-SEP-15:30 | 276093.44 | 423497.50 | 0.00 | 89246.91 | 127884.95 | 31057.63 | 0.00 | 189951.22 | 79389.88 |
October | 1369778.32 | 04-OCT-15:09 | 276093.44 | 541788.89 | 0.00 | 89246.91 | 123418.99 | 17058.77 | 0.00 | 169182.15 | 52989.17 |
November | 1317584.44 | 16-NOV-16:30 | 321032.30 | 660080.29 | 39974.20 | 89270.92 | 88296.96 | 3389.38 | 0.00 | 16876.77 | 2976.09 |
December | 1450329.15 | 05-DEC-16:19 | 321032.30 | 778371.69 | 39974.20 | 89267.59 | 91817.02 | 3389.42 | 0.00 | 22796.77 | 3680.17 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1028988.25 | 276093.44 | 423497.50 | 0.00 | 40207.72 | 78383.41 | 3389.38 | 0.00 | 6260.91 | 1290.01 | |
Maximum of Months | 1803500.90 | 321032.30 | 778371.69 | 39974.20 | 89270.92 | 140767.33 | 32640.30 | 0.00 | 407473.63 | 79389.88 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 1406716.70 | 02-JAN-05:19 | 0.00 | 78537.37 | 30-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 748678.84 | 13-FEB-05:10 | 0.00 | 78591.00 | 13-FEB-12:50 | 0.00 |
March | 0.00 | 0.00 | 614115.16 | 06-MAR-05:19 | 0.00 | 78427.58 | 01-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 471999.34 | 18-APR-05:10 | 0.00 | 77476.40 | 03-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 879886.22 | 23-MAY-19:40 | 0.00 | 75970.58 | 01-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 202885.55 | 19-JUN-01:49 | 0.00 | 73844.12 | 05-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 164919.92 | 04-JUL-18:19 | 0.00 | 72171.55 | 06-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 148367.54 | 06-AUG-21:19 | 0.00 | 71413.25 | 28-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 192476.38 | 24-SEP-23:30 | 0.00 | 72482.23 | 27-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 459700.59 | 28-OCT-05:10 | 0.00 | 74488.52 | 30-OCT-11:50 | 0.00 |
November | 0.00 | 0.00 | 562576.04 | 24-NOV-06:10 | 0.00 | 76334.33 | 30-NOV-12:50 | 0.00 |
December | 0.00 | 0.00 | 707721.52 | 18-DEC-05:19 | 0.00 | 77711.84 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 148367.54 | 0.00 | 71413.25 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1406716.70 | 0.00 | 78591.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.34 | 0.83 | 27.90 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 26.07 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 26.15 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.35 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 26.68 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 26.20 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 26.61 | 0.33 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 26.49 | 0.33 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 26.81 | 1.50 | 27.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.55 | 0.33 | 28.36 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 26.83 | 1.50 | 27.89 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 26.60 | 0.17 | 27.27 |
Annual Sum or Average | 0.00 | 0.00 | 68.50 | 26.60 | 5.00 | 27.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 26.07 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.34 | 1.50 | 28.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 19.39 | 1.17 | 20.06 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.00 | 19.39 | 1.17 | 20.06 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 19.39 | 1.17 | 20.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 18.86 | 0.67 | 20.21 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.67 | 18.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 18.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.83 | 18.76 | 0.67 | 20.21 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.35 | 0.67 | 20.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.90 | 1.00 | 27.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.97 | 1.17 | 27.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.28 | 2.33 | 28.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.38 | 1.83 | 28.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.01 | 1.17 | 28.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.67 | 28.14 | 7.67 | 28.14 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.38 | 2.33 | 28.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.43 | 0.33 | 27.43 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 25.98 | 2.33 | 25.98 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.78 | 2.67 | 24.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.56 | 0.83 | 27.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.56 | 0.83 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.65 | 1.50 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.09 | 1.33 | 28.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 25.94 | 4.50 | 25.94 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 26.63 | 1.83 | 26.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 25.93 | 2.33 | 25.93 |
Annual Sum or Average | 0.00 | 0.00 | 18.67 | 26.32 | 18.67 | 26.32 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.09 | 4.50 | 28.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.65 | 2.33 | 28.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.23 | 3.33 | 28.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.21 | 2.00 | 28.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.19 | 4.67 | 28.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.45 | 3.67 | 28.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.03 | 2.17 | 28.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.40 | 0.17 | 27.40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.33 | 27.30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 38.67 | 27.88 | 18.83 | 28.16 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 28.23 | 4.67 | 28.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.33 | 19.00 | 1.83 | 19.84 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.17 | 18.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 19.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7.17 | 19.00 | 1.83 | 19.84 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.33 | 19.29 | 1.83 | 19.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 18.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.00 | 18.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.95 | 0.83 | 27.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.09 | 0.83 | 28.09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.30 | 2.33 | 28.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.22 | 2.17 | 28.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.02 | 0.83 | 28.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.67 | 18.83 | 0.00 | 7.00 | 28.18 | 7.00 | 28.18 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.23 | 0.00 | 0.00 | 2.33 | 28.30 | 2.33 | 28.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 18.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 19.33 | 0.00 | 0.00 | 4.00 | 25.51 | 4.00 | 25.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.94 | 2.67 | 24.94 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.47 | 0.50 | 27.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.61 | 0.50 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.56 | 1.33 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.20 | 1.50 | 28.20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 25.60 | 6.67 | 25.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.82 | 1.00 | 27.82 |
December | 0.50 | 19.33 | 0.00 | 0.00 | 0.33 | 27.47 | 0.33 | 27.47 |
Annual Sum or Average | 3.17 | 18.86 | 0.00 | 18.50 | 26.10 | 18.50 | 26.10 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.33 | 0.00 | 0.00 | 6.67 | 28.20 | 6.67 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 18.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 19.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.29 | 2.00 | 28.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.17 | 0.67 | 27.98 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.63 | 1.83 | 28.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.35 | 1.17 | 28.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.96 | 1.17 | 28.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.00 | 18.81 | 0.00 | 15.00 | 28.36 | 6.83 | 28.33 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.39 | 0.00 | 0.00 | 4.50 | 28.63 | 2.00 | 28.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.00 | 17.55 | 8.50 | 18.94 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17.67 | 17.57 | 5.67 | 18.02 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.83 | 19.08 | 0.33 | 19.97 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.83 | 19.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.83 | 19.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5.33 | 19.09 | 1.17 | 20.05 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14.00 | 18.39 | 3.83 | 19.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70.50 | 17.94 | 19.50 | 18.86 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 29.00 | 19.34 | 8.50 | 20.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.33 | 16.17 | 1.67 | 14.91 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8.50 | 16.73 | 1.00 | 14.86 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.17 | 19.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.83 | 19.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 19.40 | 0.00 | 0.00 | 0.67 | 27.66 | 0.67 | 27.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.92 | 0.67 | 27.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.27 | 2.00 | 28.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.18 | 1.83 | 28.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.80 | 0.67 | 27.80 |
October | 0.83 | 19.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.83 | 18.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7.00 | 17.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.67 | 17.02 | 2.67 | 14.89 | 5.83 | 28.08 | 5.83 | 28.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.33 | 19.40 | 1.67 | 14.91 | 2.00 | 28.27 | 2.00 | 28.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.33 | 16.69 | 1.17 | 15.72 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4.00 | 17.41 | 0.50 | 14.84 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.50 | 19.16 | 0.00 | 0.00 | 1.00 | 24.61 | 1.00 | 24.61 |
April | 0.33 | 19.26 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
May | 0.17 | 19.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.59 | 0.67 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.73 | 1.00 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.20 | 1.33 | 28.20 |
October | 0.50 | 19.38 | 0.00 | 0.00 | 2.50 | 25.05 | 2.50 | 25.05 |
November | 2.67 | 18.94 | 0.00 | 0.00 | 0.33 | 27.33 | 0.33 | 27.33 |
December | 4.50 | 18.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 27.00 | 17.53 | 1.67 | 15.45 | 7.00 | 26.37 | 7.00 | 26.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.33 | 19.43 | 1.17 | 15.72 | 2.50 | 28.20 | 2.50 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.00 | 17.57 | 0.67 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.17 | 18.18 | 0.33 | 15.01 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.17 | 19.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 19.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.27 | 2.17 | 28.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.14 | 0.83 | 28.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.59 | 2.33 | 28.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.42 | 1.17 | 28.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.94 | 1.00 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.50 | 19.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.33 | 18.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16.33 | 18.23 | 1.00 | 14.99 | 15.17 | 28.36 | 7.50 | 28.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.00 | 19.41 | 0.67 | 15.01 | 4.67 | 28.59 | 2.33 | 28.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.89 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.50 | 27.89 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.89 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.95 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.00 | 27.95 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.95 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.97 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.67 | 27.97 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.97 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.32 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 59.17 | 28.18 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 62.00 | 28.19 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 59.17 | 28.32 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 76.50 | 24.02 | 87.17 | 26.04 | 0.50 | 26.81 |
February | 56.17 | 24.02 | 106.67 | 25.63 | 0.00 | 0.00 |
March | 39.17 | 24.03 | 102.83 | 25.82 | 0.00 | 0.00 |
April | 3.33 | 24.03 | 151.83 | 25.55 | 0.00 | 0.00 |
May | 0.83 | 24.00 | 220.33 | 25.07 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 257.83 | 24.86 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 396.17 | 24.75 | 0.00 | 0.00 |
August | 0.50 | 25.96 | 468.17 | 24.52 | 0.50 | 25.96 |
September | 0.67 | 26.83 | 353.67 | 24.72 | 0.67 | 26.83 |
October | 0.33 | 26.83 | 176.50 | 25.55 | 0.33 | 26.83 |
November | 2.00 | 24.53 | 187.17 | 25.44 | 0.33 | 26.82 |
December | 23.50 | 24.03 | 106.00 | 26.32 | 0.00 | 0.00 |
Annual Sum or Average | 203.00 | 24.05 | 2614.33 | 25.08 | 2.33 | 26.64 |
Minimum of Months | 0.00 | 0.00 | 87.17 | 24.52 | 0.00 | 0.00 |
Maximum of Months | 76.50 | 26.83 | 468.17 | 26.32 | 0.67 | 26.83 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 180.00 | 23.90 | 26.67 | 25.35 | 13.00 | 25.70 |
February | 94.00 | 23.89 | 74.33 | 24.99 | 0.00 | 0.00 |
March | 35.50 | 23.94 | 111.17 | 25.26 | 0.00 | 0.00 |
April | 8.67 | 23.72 | 159.50 | 24.95 | 0.00 | 0.00 |
May | 18.83 | 23.61 | 214.67 | 24.65 | 0.00 | 0.00 |
June | 6.33 | 23.60 | 287.33 | 24.46 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 409.67 | 24.36 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 475.00 | 24.22 | 0.00 | 0.00 |
September | 1.33 | 23.63 | 347.17 | 24.45 | 0.00 | 0.00 |
October | 9.83 | 23.67 | 191.33 | 24.95 | 0.00 | 0.00 |
November | 10.50 | 23.91 | 183.67 | 25.01 | 0.00 | 0.00 |
December | 40.33 | 23.95 | 99.33 | 25.75 | 0.00 | 0.00 |
Annual Sum or Average | 405.33 | 23.88 | 2579.83 | 24.63 | 13.00 | 25.70 |
Minimum of Months | 0.00 | 0.00 | 26.67 | 24.22 | 0.00 | 0.00 |
Maximum of Months | 180.00 | 23.95 | 475.00 | 25.75 | 13.00 | 25.70 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 479.50 | 22.64 | 17.67 | 18.50 | 17.67 | 18.50 |
February | 393.00 | 23.18 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 339.83 | 23.57 | 2.00 | 24.42 | 0.00 | 0.00 |
April | 217.83 | 23.53 | 38.17 | 24.56 | 0.00 | 0.00 |
May | 149.00 | 23.46 | 85.83 | 24.40 | 0.00 | 0.00 |
June | 95.83 | 23.40 | 143.50 | 24.44 | 0.00 | 0.00 |
July | 74.33 | 23.22 | 238.00 | 24.40 | 0.00 | 0.00 |
August | 60.17 | 23.17 | 312.00 | 24.25 | 0.00 | 0.00 |
September | 78.33 | 23.29 | 209.17 | 24.40 | 0.00 | 0.00 |
October | 215.00 | 23.43 | 37.33 | 24.74 | 0.00 | 0.00 |
November | 341.00 | 23.38 | 14.83 | 24.24 | 0.00 | 0.00 |
December | 449.83 | 23.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2893.67 | 23.23 | 1098.50 | 24.28 | 17.67 | 18.50 |
Minimum of Months | 60.17 | 22.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 479.50 | 23.57 | 312.00 | 24.74 | 17.67 | 18.50 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.36 | 123.33 | 19.30 | 123.33 | 19.30 |
February | 444.17 | 21.85 | 71.17 | 19.63 | 71.17 | 19.63 |
March | 471.17 | 22.64 | 18.17 | 20.50 | 18.17 | 20.50 |
April | 345.00 | 22.94 | 26.50 | 24.20 | 0.00 | 0.00 |
May | 248.17 | 23.14 | 59.00 | 24.14 | 0.00 | 0.00 |
June | 155.17 | 23.28 | 127.67 | 24.29 | 0.00 | 0.00 |
July | 125.67 | 23.25 | 232.83 | 24.25 | 0.00 | 0.00 |
August | 111.67 | 23.14 | 283.83 | 24.16 | 0.00 | 0.00 |
September | 221.50 | 23.08 | 124.67 | 24.13 | 0.00 | 0.00 |
October | 407.83 | 22.73 | 2.50 | 23.59 | 0.33 | 20.96 |
November | 469.67 | 22.18 | 35.50 | 20.44 | 33.67 | 20.25 |
December | 497.00 | 21.66 | 98.00 | 20.03 | 98.00 | 20.03 |
Annual Sum or Average | 3999.00 | 22.36 | 1203.17 | 22.92 | 344.67 | 19.73 |
Minimum of Months | 111.67 | 21.36 | 2.50 | 19.30 | 0.00 | 0.00 |
Maximum of Months | 502.00 | 23.28 | 283.83 | 24.29 | 123.33 | 20.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.31 | 12.67 | 20.86 | 12.67 | 20.86 |
February | 417.67 | 22.67 | 4.50 | 20.55 | 4.50 | 20.55 |
March | 407.67 | 23.29 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 234.83 | 23.51 | 48.67 | 24.30 | 0.00 | 0.00 |
May | 186.17 | 23.45 | 99.17 | 24.33 | 0.00 | 0.00 |
June | 58.83 | 23.60 | 167.33 | 24.35 | 0.00 | 0.00 |
July | 7.17 | 23.79 | 339.33 | 24.27 | 0.00 | 0.00 |
August | 11.00 | 23.57 | 389.17 | 24.17 | 0.00 | 0.00 |
September | 136.67 | 23.36 | 168.00 | 24.30 | 0.00 | 0.00 |
October | 293.00 | 23.27 | 17.67 | 25.05 | 0.00 | 0.00 |
November | 386.17 | 23.12 | 12.67 | 24.60 | 0.00 | 0.00 |
December | 487.33 | 22.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3128.50 | 23.01 | 1259.17 | 24.23 | 17.17 | 20.78 |
Minimum of Months | 7.17 | 22.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 502.00 | 23.79 | 389.17 | 25.05 | 12.67 | 20.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.74 | 17.33 | 20.64 | 17.33 | 20.64 |
February | 428.83 | 22.15 | 8.83 | 21.05 | 8.17 | 20.65 |
March | 443.50 | 22.74 | 3.67 | 24.00 | 0.00 | 0.00 |
April | 266.83 | 22.96 | 77.67 | 24.23 | 0.00 | 0.00 |
May | 214.50 | 23.06 | 150.00 | 24.40 | 3.50 | 26.85 |
June | 127.00 | 23.29 | 217.33 | 24.36 | 5.67 | 26.80 |
July | 106.33 | 23.46 | 294.83 | 24.26 | 9.00 | 27.04 |
August | 104.17 | 23.34 | 314.67 | 24.14 | 8.33 | 27.00 |
September | 196.17 | 22.97 | 180.33 | 24.35 | 4.67 | 26.93 |
October | 357.00 | 22.74 | 42.17 | 24.61 | 0.00 | 0.00 |
November | 464.67 | 22.40 | 6.00 | 24.56 | 0.00 | 0.00 |
December | 497.00 | 22.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3708.00 | 22.50 | 1312.83 | 24.22 | 56.67 | 24.11 |
Minimum of Months | 104.17 | 21.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 502.00 | 23.46 | 314.67 | 24.61 | 17.33 | 27.04 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 459.00 | 21.85 | 48.67 | 21.60 | 35.83 | 20.39 |
February | 351.33 | 22.30 | 73.67 | 23.92 | 16.17 | 20.82 |
March | 349.67 | 22.84 | 59.50 | 24.36 | 0.00 | 0.00 |
April | 238.17 | 23.17 | 107.33 | 24.35 | 1.00 | 26.60 |
May | 216.33 | 23.18 | 131.50 | 24.38 | 0.83 | 26.63 |
June | 122.67 | 23.32 | 180.50 | 24.34 | 0.33 | 26.65 |
July | 65.50 | 23.52 | 322.00 | 24.29 | 2.67 | 26.80 |
August | 49.83 | 23.76 | 372.83 | 24.21 | 6.67 | 26.77 |
September | 148.50 | 23.26 | 241.67 | 24.33 | 5.50 | 27.01 |
October | 288.17 | 23.06 | 119.67 | 24.60 | 5.50 | 26.89 |
November | 381.83 | 22.60 | 47.83 | 24.84 | 3.33 | 26.95 |
December | 425.83 | 22.26 | 38.33 | 24.39 | 3.00 | 22.38 |
Annual Sum or Average | 3096.83 | 22.66 | 1743.50 | 24.24 | 80.83 | 22.62 |
Minimum of Months | 49.83 | 21.85 | 38.33 | 21.60 | 0.00 | 0.00 |
Maximum of Months | 459.00 | 23.76 | 372.83 | 24.84 | 35.83 | 27.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.67 | 22.43 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 323.33 | 23.00 | 48.50 | 24.83 | 0.17 | 26.61 |
March | 130.17 | 23.48 | 112.50 | 24.86 | 0.17 | 26.70 |
April | 28.17 | 24.93 | 279.00 | 24.82 | 12.00 | 26.73 |
May | 103.17 | 23.71 | 256.50 | 24.57 | 13.83 | 26.96 |
June | 11.00 | 25.99 | 408.50 | 24.46 | 8.50 | 26.74 |
July | 26.17 | 26.70 | 484.50 | 24.59 | 26.17 | 26.70 |
August | 27.33 | 26.08 | 514.00 | 24.44 | 27.33 | 26.08 |
September | 66.50 | 23.73 | 325.67 | 24.51 | 10.83 | 26.67 |
October | 130.67 | 23.30 | 160.67 | 24.88 | 1.67 | 26.36 |
November | 164.67 | 23.38 | 119.83 | 24.86 | 0.83 | 26.42 |
December | 197.67 | 23.44 | 54.17 | 25.32 | 0.00 | 0.00 |
Annual Sum or Average | 1702.50 | 23.21 | 2763.83 | 24.61 | 101.50 | 26.56 |
Minimum of Months | 11.00 | 22.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 493.67 | 26.70 | 514.00 | 25.32 | 27.33 | 26.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.47 | 275.17 | 19.91 | 275.17 | 19.91 |
February | 454.00 | 20.91 | 158.83 | 19.95 | 158.83 | 19.95 |
March | 514.00 | 21.74 | 47.83 | 20.38 | 47.83 | 20.38 |
April | 448.00 | 22.38 | 13.17 | 22.84 | 4.50 | 20.60 |
May | 348.00 | 22.80 | 37.50 | 24.09 | 0.00 | 0.00 |
June | 245.83 | 23.15 | 61.67 | 24.15 | 0.00 | 0.00 |
July | 176.33 | 23.23 | 164.83 | 24.10 | 0.00 | 0.00 |
August | 182.17 | 23.09 | 225.67 | 24.10 | 0.00 | 0.00 |
September | 328.50 | 22.87 | 57.67 | 24.07 | 0.00 | 0.00 |
October | 495.17 | 22.13 | 9.17 | 20.42 | 9.17 | 20.42 |
November | 489.00 | 21.28 | 95.83 | 20.20 | 95.83 | 20.20 |
December | 497.00 | 20.76 | 211.50 | 20.16 | 211.50 | 20.16 |
Annual Sum or Average | 4680.00 | 21.82 | 1358.83 | 21.71 | 802.83 | 20.06 |
Minimum of Months | 176.33 | 20.47 | 9.17 | 19.91 | 0.00 | 0.00 |
Maximum of Months | 514.00 | 23.23 | 275.17 | 24.15 | 275.17 | 20.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.31 | 253.67 | 19.83 | 253.67 | 19.83 |
February | 385.00 | 20.88 | 142.67 | 20.15 | 142.67 | 20.15 |
March | 423.67 | 21.57 | 34.83 | 20.28 | 34.33 | 20.23 |
April | 317.50 | 22.16 | 32.33 | 23.80 | 5.00 | 20.78 |
May | 290.17 | 22.48 | 72.83 | 24.61 | 3.17 | 26.61 |
June | 204.67 | 22.86 | 133.50 | 24.56 | 3.50 | 26.85 |
July | 181.67 | 23.09 | 183.50 | 24.46 | 9.17 | 27.02 |
August | 167.50 | 22.98 | 206.00 | 24.32 | 8.67 | 26.99 |
September | 268.17 | 22.46 | 89.33 | 24.44 | 3.67 | 26.86 |
October | 389.33 | 21.78 | 22.67 | 22.76 | 9.67 | 20.32 |
November | 417.00 | 21.04 | 95.33 | 20.21 | 95.33 | 20.21 |
December | 422.00 | 20.61 | 203.00 | 20.13 | 203.00 | 20.13 |
Annual Sum or Average | 3893.67 | 21.60 | 1469.67 | 22.22 | 771.83 | 20.30 |
Minimum of Months | 167.50 | 20.31 | 22.67 | 19.83 | 3.17 | 19.83 |
Maximum of Months | 427.00 | 23.09 | 253.67 | 24.61 | 253.67 | 27.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 470.50 | 20.90 | 197.50 | 20.21 | 189.17 | 19.99 |
February | 375.83 | 21.44 | 125.33 | 21.87 | 81.33 | 20.35 |
March | 393.67 | 21.93 | 74.50 | 22.88 | 27.17 | 20.32 |
April | 317.67 | 22.32 | 81.17 | 24.35 | 2.67 | 22.17 |
May | 295.83 | 22.66 | 96.00 | 24.40 | 1.17 | 25.80 |
June | 238.67 | 22.93 | 102.83 | 24.40 | 0.17 | 26.16 |
July | 175.83 | 23.09 | 226.50 | 24.29 | 2.00 | 26.68 |
August | 159.67 | 23.10 | 277.83 | 24.25 | 5.00 | 26.69 |
September | 222.67 | 22.90 | 194.50 | 24.32 | 5.50 | 27.06 |
October | 341.33 | 22.29 | 105.50 | 24.66 | 5.67 | 26.76 |
November | 435.00 | 21.63 | 85.83 | 22.15 | 55.17 | 20.73 |
December | 446.33 | 21.16 | 175.00 | 20.95 | 148.50 | 20.29 |
Annual Sum or Average | 3873.00 | 21.97 | 1742.50 | 23.19 | 523.50 | 20.49 |
Minimum of Months | 159.67 | 20.90 | 74.50 | 20.21 | 0.17 | 19.99 |
Maximum of Months | 470.50 | 23.10 | 277.83 | 24.66 | 189.17 | 27.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.59 | 226.00 | 19.97 | 226.00 | 19.97 |
February | 443.50 | 21.06 | 111.67 | 20.15 | 109.67 | 20.07 |
March | 481.50 | 21.72 | 35.50 | 21.45 | 25.67 | 20.35 |
April | 375.00 | 22.23 | 60.17 | 24.45 | 1.00 | 21.73 |
May | 318.50 | 22.74 | 110.33 | 24.51 | 10.33 | 26.92 |
June | 240.83 | 22.90 | 153.17 | 24.38 | 3.50 | 26.69 |
July | 143.67 | 23.25 | 276.50 | 24.45 | 11.50 | 26.90 |
August | 161.33 | 23.04 | 271.50 | 24.32 | 7.67 | 26.93 |
September | 294.83 | 22.75 | 133.50 | 24.45 | 6.67 | 26.66 |
October | 450.17 | 21.97 | 28.67 | 24.20 | 2.17 | 22.58 |
November | 482.67 | 21.27 | 60.50 | 20.50 | 58.83 | 20.40 |
December | 497.00 | 20.90 | 158.67 | 20.29 | 158.67 | 20.29 |
Annual Sum or Average | 4391.00 | 21.76 | 1626.17 | 22.89 | 621.67 | 20.58 |
Minimum of Months | 143.67 | 20.59 | 28.67 | 19.97 | 1.00 | 19.97 |
Maximum of Months | 502.00 | 23.25 | 276.50 | 24.51 | 226.00 | 26.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.06 | 358.83 | 19.68 | 358.83 | 19.68 |
February | 454.00 | 20.40 | 255.17 | 19.74 | 255.17 | 19.74 |
March | 514.00 | 21.11 | 162.33 | 20.12 | 162.33 | 20.12 |
April | 457.33 | 21.87 | 65.83 | 20.80 | 56.83 | 20.29 |
May | 374.50 | 22.35 | 50.33 | 23.14 | 12.33 | 20.31 |
June | 270.50 | 22.82 | 69.50 | 24.15 | 0.00 | 0.00 |
July | 198.67 | 22.91 | 174.17 | 24.09 | 0.00 | 0.00 |
August | 210.00 | 22.78 | 210.50 | 24.08 | 0.00 | 0.00 |
September | 375.17 | 22.38 | 48.50 | 24.02 | 0.17 | 21.04 |
October | 500.33 | 21.42 | 74.17 | 19.88 | 74.17 | 19.88 |
November | 489.00 | 20.60 | 206.33 | 19.76 | 206.33 | 19.76 |
December | 497.00 | 20.19 | 344.83 | 19.82 | 344.83 | 19.82 |
Annual Sum or Average | 4842.50 | 21.33 | 2020.50 | 20.98 | 1471.00 | 19.82 |
Minimum of Months | 198.67 | 20.06 | 48.50 | 19.68 | 0.00 | 0.00 |
Maximum of Months | 514.00 | 22.91 | 358.83 | 24.15 | 358.83 | 21.04 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.07 | 352.67 | 19.68 | 352.67 | 19.68 |
February | 454.00 | 20.48 | 232.67 | 19.80 | 232.67 | 19.80 |
March | 508.83 | 21.22 | 121.00 | 19.96 | 121.00 | 19.96 |
April | 378.83 | 21.88 | 72.83 | 22.06 | 37.83 | 20.21 |
May | 320.33 | 22.17 | 106.83 | 23.89 | 13.50 | 21.15 |
June | 217.67 | 22.66 | 184.33 | 24.38 | 2.83 | 26.44 |
July | 193.33 | 22.89 | 250.50 | 24.30 | 8.33 | 26.97 |
August | 186.67 | 22.80 | 267.50 | 24.22 | 9.17 | 26.81 |
September | 311.67 | 22.09 | 117.00 | 24.26 | 2.50 | 26.10 |
October | 469.00 | 21.41 | 69.00 | 20.25 | 64.33 | 19.97 |
November | 489.00 | 20.57 | 201.67 | 19.79 | 201.67 | 19.79 |
December | 497.00 | 20.20 | 338.00 | 19.82 | 338.00 | 19.82 |
Annual Sum or Average | 4528.33 | 21.24 | 2314.00 | 21.65 | 1384.50 | 19.94 |
Minimum of Months | 186.67 | 20.07 | 69.00 | 19.68 | 2.50 | 19.68 |
Maximum of Months | 508.83 | 22.89 | 352.67 | 24.38 | 352.67 | 26.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 486.33 | 20.45 | 270.83 | 19.66 | 267.83 | 19.61 |
February | 397.17 | 20.92 | 198.33 | 20.65 | 168.83 | 20.01 |
March | 417.67 | 21.37 | 141.67 | 21.00 | 108.83 | 20.08 |
April | 348.17 | 21.86 | 105.50 | 22.61 | 45.00 | 20.35 |
May | 326.17 | 22.20 | 95.50 | 23.86 | 12.17 | 20.61 |
June | 264.50 | 22.57 | 105.00 | 24.36 | 0.17 | 26.14 |
July | 205.33 | 22.77 | 221.50 | 24.26 | 2.67 | 26.65 |
August | 193.50 | 22.71 | 247.33 | 24.23 | 5.00 | 26.70 |
September | 271.17 | 22.34 | 173.00 | 24.27 | 5.33 | 26.87 |
October | 369.33 | 21.64 | 121.67 | 23.06 | 41.00 | 20.40 |
November | 450.00 | 20.97 | 168.33 | 20.63 | 142.00 | 19.88 |
December | 462.00 | 20.56 | 260.50 | 19.99 | 248.17 | 19.76 |
Annual Sum or Average | 4191.33 | 21.49 | 2109.17 | 22.13 | 1047.00 | 19.96 |
Minimum of Months | 193.50 | 20.45 | 95.50 | 19.66 | 0.17 | 19.61 |
Maximum of Months | 486.33 | 22.77 | 270.83 | 24.36 | 267.83 | 26.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.21 | 301.83 | 19.65 | 301.83 | 19.65 |
February | 447.17 | 20.67 | 204.50 | 19.92 | 203.50 | 19.90 |
March | 490.67 | 21.27 | 116.83 | 20.58 | 107.17 | 20.25 |
April | 389.17 | 21.78 | 84.33 | 22.75 | 35.00 | 20.42 |
May | 347.67 | 22.33 | 103.83 | 24.39 | 12.67 | 25.63 |
June | 274.50 | 22.59 | 147.00 | 24.37 | 3.33 | 26.73 |
July | 183.67 | 22.94 | 257.50 | 24.41 | 11.50 | 26.95 |
August | 209.83 | 22.74 | 242.33 | 24.30 | 8.33 | 26.68 |
September | 327.17 | 22.27 | 114.00 | 24.40 | 6.00 | 26.60 |
October | 463.83 | 21.46 | 56.50 | 21.52 | 37.50 | 20.08 |
November | 486.67 | 20.82 | 148.67 | 19.98 | 147.17 | 19.94 |
December | 497.00 | 20.46 | 275.00 | 19.94 | 275.00 | 19.94 |
Annual Sum or Average | 4619.33 | 21.39 | 2052.33 | 21.96 | 1149.00 | 20.14 |
Minimum of Months | 183.67 | 20.21 | 56.50 | 19.65 | 3.33 | 19.65 |
Maximum of Months | 502.00 | 22.94 | 301.83 | 24.41 | 301.83 | 26.95 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.43934 | 26.83553 | 0.36852 | 8.19571 |
February | 454.00000 | 24.44253 | 28.13289 | 0.38482 | 8.48930 |
March | 514.00000 | 24.39319 | 28.02335 | 0.38515 | 8.43310 |
April | 485.00000 | 24.49853 | 31.63495 | 0.43672 | 9.52656 |
May | 508.00000 | 24.47095 | 36.34469 | -0.3934 | 9.14242 |
June | 496.00000 | 24.44753 | 38.46746 | -0.3748 | 8.75913 |
July | 497.00000 | 24.59514 | 43.85288 | -0.2879 | 7.92596 |
August | 514.00000 | 24.46189 | 47.87967 | -0.2908 | 7.65739 |
September | 485.00000 | 24.52150 | 43.88812 | -0.3138 | 8.15965 |
October | 502.00000 | 24.55144 | 34.84859 | 0.47456 | 10.31597 |
November | 489.00000 | 24.55874 | 32.83638 | 0.45880 | 10.02328 |
December | 497.00000 | 24.52373 | 27.42784 | 0.40596 | 8.96373 |
Annual Sum or Average | 5943.00000 | 24.49184 | 35.06765 | 0.10151 | 8.79687 |
Minimum of Months | 454.00000 | 24.39319 | 26.83553 | -0.3934 | 7.65739 |
Maximum of Months | 514.00000 | 24.59514 | 47.87967 | 0.47456 | 10.31597 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.13114 | 31.43179 | 0.32195 | 7.69123 |
February | 454.00000 | 24.23702 | 30.03871 | 0.35028 | 7.81536 |
March | 514.00000 | 24.30606 | 29.52083 | 0.38363 | 8.33641 |
April | 485.00000 | 24.32474 | 32.73586 | 0.42409 | 9.06390 |
May | 508.00000 | 24.26153 | 37.89916 | -0.4353 | 9.45995 |
June | 496.00000 | 24.25322 | 40.18738 | -0.4012 | 8.79020 |
July | 497.00000 | 24.28643 | 44.32546 | -0.3504 | 7.98826 |
August | 514.00000 | 24.20096 | 47.38941 | -0.3435 | 7.71899 |
September | 485.00000 | 24.29512 | 45.25303 | -0.3676 | 8.41548 |
October | 502.00000 | 24.36408 | 36.57005 | 0.44556 | 9.49972 |
November | 489.00000 | 24.39254 | 34.76500 | 0.43394 | 9.29893 |
December | 497.00000 | 24.37925 | 29.66267 | 0.39017 | 8.51509 |
Annual Sum or Average | 5943.00000 | 24.28583 | 36.69676 | 0.06802 | 8.55173 |
Minimum of Months | 454.00000 | 24.13114 | 29.52083 | -0.4353 | 7.69123 |
Maximum of Months | 514.00000 | 24.39254 | 47.38941 | 0.44556 | 9.49972 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.68859 | 32.96143 | -0.0669 | 6.87349 |
February | 454.00000 | 23.28340 | 33.04672 | 0.09464 | 5.89897 |
March | 514.00000 | 23.73953 | 31.90727 | 0.21522 | 6.26723 |
April | 485.00000 | 23.88405 | 35.00433 | 0.28161 | 6.96478 |
May | 508.00000 | 23.95054 | 39.14439 | -0.5720 | 12.33451 |
June | 496.00000 | 23.98607 | 41.33242 | -0.5287 | 11.27861 |
July | 497.00000 | 24.00398 | 45.94718 | -0.4894 | 10.53450 |
August | 514.00000 | 23.97928 | 48.66282 | -0.4686 | 10.07827 |
September | 485.00000 | 23.99580 | 46.54877 | -0.4979 | 10.66768 |
October | 502.00000 | 23.85021 | 38.71950 | 0.29489 | 7.12809 |
November | 489.00000 | 23.58143 | 38.14011 | 0.20606 | 6.31746 |
December | 497.00000 | 23.21381 | 33.35940 | 0.07536 | 5.66270 |
Annual Sum or Average | 5943.00000 | 23.68246 | 38.76921 | -0.1238 | 8.35599 |
Minimum of Months | 454.00000 | 22.68859 | 31.90727 | -0.5720 | 5.66270 |
Maximum of Months | 514.00000 | 24.00398 | 48.66282 | 0.29489 | 12.33451 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.34481 | 34.58670 | -0.4037 | 11.78703 |
February | 454.00000 | 21.88047 | 35.04662 | -0.2555 | 9.24934 |
March | 514.00000 | 22.73957 | 34.28945 | -0.0352 | 6.38533 |
April | 485.00000 | 23.25403 | 36.69335 | 0.12552 | 6.34228 |
May | 508.00000 | 23.60751 | 40.18239 | -0.6923 | 16.22651 |
June | 496.00000 | 23.85919 | 41.70284 | -0.5704 | 12.48724 |
July | 497.00000 | 23.91408 | 46.12562 | -0.5128 | 11.12141 |
August | 514.00000 | 23.86001 | 49.05455 | -0.5054 | 11.02551 |
September | 485.00000 | 23.59617 | 48.12658 | -0.6420 | 14.63314 |
October | 502.00000 | 22.95229 | 41.54622 | 0.06955 | 6.17958 |
November | 489.00000 | 22.23102 | 41.62406 | -0.1300 | 6.90718 |
December | 497.00000 | 21.64236 | 36.11873 | -0.3189 | 8.92284 |
Annual Sum or Average | 5943.00000 | 22.91514 | 40.45654 | -0.3237 | 10.11560 |
Minimum of Months | 454.00000 | 21.34481 | 34.28945 | -0.6923 | 6.17958 |
Maximum of Months | 514.00000 | 23.91408 | 49.05455 | 0.12552 | 16.22651 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.30706 | 31.17885 | -0.1519 | 6.37048 |
February | 454.00000 | 22.77407 | 31.21672 | -0.0306 | 6.15178 |
March | 514.00000 | 23.43999 | 30.63989 | 0.13579 | 5.90651 |
April | 485.00000 | 23.81741 | 33.07093 | 0.26621 | 6.88877 |
May | 508.00000 | 23.87920 | 37.81075 | -0.5922 | 13.14435 |
June | 496.00000 | 24.08187 | 39.73155 | -0.4843 | 10.27719 |
July | 497.00000 | 24.18420 | 43.58010 | -0.4021 | 8.65974 |
August | 514.00000 | 24.09974 | 46.87734 | -0.4008 | 8.60596 |
September | 485.00000 | 23.90457 | 45.52688 | -0.5390 | 11.72372 |
October | 502.00000 | 23.61505 | 37.69229 | 0.22844 | 6.53497 |
November | 489.00000 | 23.31268 | 36.29777 | 0.13270 | 6.01831 |
December | 497.00000 | 22.94952 | 31.28340 | 0.00537 | 5.46553 |
Annual Sum or Average | 5943.00000 | 23.53584 | 37.11610 | -0.1544 | 7.99191 |
Minimum of Months | 454.00000 | 22.30706 | 30.63989 | -0.5922 | 5.46553 |
Maximum of Months | 514.00000 | 24.18420 | 46.87734 | 0.26621 | 13.14435 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.73803 | 31.38654 | -0.2687 | 7.14821 |
February | 454.00000 | 22.25138 | 31.46977 | -0.1311 | 6.51211 |
March | 514.00000 | 22.91351 | 31.00416 | 0.04204 | 5.88057 |
April | 485.00000 | 23.44996 | 33.41920 | 0.22289 | 7.00015 |
May | 508.00000 | 23.69108 | 37.85966 | -0.5948 | 14.47235 |
June | 496.00000 | 23.91891 | 39.78617 | -0.4624 | 11.12037 |
July | 497.00000 | 23.94626 | 43.94794 | -0.4113 | 10.16252 |
August | 514.00000 | 23.82631 | 47.39061 | -0.4162 | 10.28390 |
September | 485.00000 | 23.64111 | 45.77325 | -0.5585 | 13.61815 |
October | 502.00000 | 23.14137 | 38.14632 | 0.14950 | 6.42717 |
November | 489.00000 | 22.48120 | 37.22887 | -0.0396 | 5.87585 |
December | 497.00000 | 21.99734 | 32.12197 | -0.1961 | 6.30817 |
Annual Sum or Average | 5943.00000 | 23.08954 | 37.50199 | -0.2233 | 8.75090 |
Minimum of Months | 454.00000 | 21.73803 | 31.00416 | -0.5948 | 5.87585 |
Maximum of Months | 514.00000 | 23.94626 | 47.39061 | 0.22289 | 14.47235 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.05680 | 31.19997 | -0.1983 | 7.71828 |
February | 454.00000 | 22.78091 | 30.68068 | 0.00077 | 7.57594 |
March | 514.00000 | 23.24932 | 30.33380 | 0.13296 | 6.78616 |
April | 485.00000 | 23.66228 | 32.96332 | 0.26508 | 7.55542 |
May | 508.00000 | 23.73701 | 37.84659 | -0.6109 | 14.52663 |
June | 496.00000 | 23.94816 | 39.92581 | -0.5105 | 11.37954 |
July | 497.00000 | 24.09752 | 43.62522 | -0.4037 | 9.25339 |
August | 514.00000 | 24.04942 | 46.76345 | -0.3663 | 8.77739 |
September | 485.00000 | 23.89678 | 45.01510 | -0.4611 | 11.49312 |
October | 502.00000 | 23.57275 | 37.14222 | 0.26872 | 8.10005 |
November | 489.00000 | 22.96435 | 36.47339 | 0.07275 | 6.93162 |
December | 497.00000 | 22.54319 | 31.39448 | -0.0646 | 6.91484 |
Annual Sum or Average | 5943.00000 | 23.38431 | 36.99039 | -0.1582 | 8.92940 |
Minimum of Months | 454.00000 | 22.05680 | 30.33380 | -0.6109 | 6.78616 |
Maximum of Months | 514.00000 | 24.09752 | 46.76345 | 0.26872 | 14.52663 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.45834 | 29.91967 | -0.0837 | 5.79177 |
February | 454.00000 | 23.37929 | 29.20825 | 0.15595 | 6.60036 |
March | 514.00000 | 24.09303 | 28.45207 | 0.35774 | 8.19191 |
April | 485.00000 | 24.44807 | 31.06479 | 0.51802 | 11.42852 |
May | 508.00000 | 24.12984 | 36.65948 | -0.3996 | 10.30635 |
June | 496.00000 | 24.34229 | 38.56118 | -0.2641 | 7.64870 |
July | 497.00000 | 24.55774 | 42.07272 | -0.0913 | 6.92520 |
August | 514.00000 | 24.42548 | 45.35740 | -0.0933 | 6.60002 |
September | 485.00000 | 24.16775 | 44.12767 | -0.3368 | 9.13954 |
October | 502.00000 | 24.08083 | 35.76048 | 0.39762 | 9.00436 |
November | 489.00000 | 24.02265 | 33.77315 | 0.34734 | 8.24111 |
December | 497.00000 | 24.01508 | 28.29667 | 0.30371 | 7.35991 |
Annual Sum or Average | 5943.00000 | 24.01372 | 35.31489 | 0.06623 | 8.10395 |
Minimum of Months | 454.00000 | 22.45834 | 28.29667 | -0.3996 | 5.79177 |
Maximum of Months | 514.00000 | 24.55774 | 45.35740 | 0.51802 | 11.42852 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.47530 | 34.08297 | -0.6341 | 15.41531 |
February | 454.00000 | 20.90938 | 34.41096 | -0.4948 | 12.12665 |
March | 514.00000 | 21.73593 | 34.23579 | -0.2744 | 7.64706 |
April | 485.00000 | 22.49536 | 36.45616 | -0.0601 | 6.36779 |
May | 508.00000 | 23.17124 | 39.83462 | -0.8470 | 21.91101 |
June | 496.00000 | 23.58339 | 41.44449 | -0.6786 | 15.66486 |
July | 497.00000 | 23.73815 | 45.15872 | -0.5883 | 13.02832 |
August | 514.00000 | 23.68459 | 48.68142 | -0.5800 | 12.96697 |
September | 485.00000 | 23.22033 | 47.82187 | -0.7852 | 19.25811 |
October | 502.00000 | 22.14444 | 41.44798 | -0.1245 | 6.31130 |
November | 489.00000 | 21.28005 | 40.73112 | -0.3596 | 8.82602 |
December | 497.00000 | 20.75536 | 35.30263 | -0.5426 | 12.02038 |
Annual Sum or Average | 5943.00000 | 22.27727 | 40.00213 | -0.4980 | 12.63707 |
Minimum of Months | 454.00000 | 20.47530 | 34.08297 | -0.8470 | 6.31130 |
Maximum of Months | 514.00000 | 23.73815 | 48.68142 | -0.0601 | 21.91101 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.31425 | 32.93628 | -0.6749 | 16.46737 |
February | 385.00000 | 20.87175 | 33.04221 | -0.4984 | 11.62956 |
March | 433.00000 | 21.59917 | 33.14567 | -0.2859 | 7.89352 |
April | 410.00000 | 22.58168 | 34.86927 | -0.0030 | 6.90979 |
May | 430.00000 | 23.03263 | 38.88488 | -0.8335 | 23.13680 |
June | 418.00000 | 23.55772 | 40.41746 | -0.6048 | 15.71021 |
July | 422.00000 | 23.69260 | 44.23630 | -0.5260 | 13.64697 |
August | 433.00000 | 23.62869 | 47.72619 | -0.5117 | 13.24593 |
September | 410.00000 | 23.02434 | 47.09925 | -0.7826 | 21.30646 |
October | 427.00000 | 21.97112 | 40.55236 | -0.1419 | 6.82922 |
November | 417.00000 | 21.02466 | 39.86972 | -0.4158 | 9.48475 |
December | 422.00000 | 20.60324 | 34.21059 | -0.5801 | 12.81751 |
Annual Sum or Average | 5034.00000 | 22.16625 | 38.94930 | -0.4886 | 13.26697 |
Minimum of Months | 385.00000 | 20.31425 | 32.93628 | -0.8335 | 6.82922 |
Maximum of Months | 433.00000 | 23.69260 | 47.72619 | -0.0030 | 23.13680 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.11552 | 32.65542 | -0.4539 | 12.57320 |
February | 454.00000 | 21.94605 | 32.16760 | -0.2081 | 9.66886 |
March | 514.00000 | 22.44218 | 32.21473 | -0.0606 | 7.71457 |
April | 485.00000 | 22.96080 | 34.72159 | 0.09097 | 7.43586 |
May | 508.00000 | 23.27204 | 39.03011 | -0.7719 | 20.39240 |
June | 496.00000 | 23.53735 | 41.14396 | -0.6618 | 15.98335 |
July | 497.00000 | 23.76280 | 44.68412 | -0.5373 | 12.76336 |
August | 514.00000 | 23.78184 | 47.82461 | -0.4789 | 11.73642 |
September | 485.00000 | 23.56117 | 45.98694 | -0.5727 | 15.14553 |
October | 502.00000 | 22.93440 | 38.78633 | 0.11785 | 8.12348 |
November | 489.00000 | 21.92642 | 38.88249 | -0.1814 | 8.42934 |
December | 497.00000 | 21.48446 | 33.49170 | -0.3395 | 10.31736 |
Annual Sum or Average | 5943.00000 | 22.73355 | 38.50805 | -0.3397 | 11.71283 |
Minimum of Months | 454.00000 | 21.11552 | 32.16760 | -0.7719 | 7.43586 |
Maximum of Months | 514.00000 | 23.78184 | 47.82461 | 0.11785 | 20.39240 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.58651 | 33.08268 | -0.5886 | 13.81252 |
February | 454.00000 | 21.12350 | 33.27965 | -0.4183 | 10.51611 |
March | 514.00000 | 21.85904 | 33.11644 | -0.2105 | 7.36319 |
April | 485.00000 | 22.67419 | 35.19358 | 0.03281 | 7.08498 |
May | 508.00000 | 23.22618 | 38.94622 | -0.7412 | 20.33827 |
June | 496.00000 | 23.51145 | 40.92859 | -0.6090 | 15.21443 |
July | 497.00000 | 23.90470 | 44.10282 | -0.4083 | 11.20921 |
August | 514.00000 | 23.73843 | 47.87163 | -0.4479 | 11.71967 |
September | 485.00000 | 23.27839 | 46.74506 | -0.6722 | 17.64988 |
October | 502.00000 | 22.18393 | 40.40502 | -0.0784 | 6.51955 |
November | 489.00000 | 21.29686 | 39.86787 | -0.3345 | 8.30305 |
December | 497.00000 | 20.89844 | 34.18756 | -0.4883 | 10.69531 |
Annual Sum or Average | 5943.00000 | 22.36696 | 39.01378 | -0.4141 | 11.71310 |
Minimum of Months | 454.00000 | 20.58651 | 33.08268 | -0.7412 | 6.51955 |
Maximum of Months | 514.00000 | 23.90470 | 47.87163 | 0.03281 | 20.33827 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.07085 | 34.85494 | -0.7730 | 20.58828 |
February | 454.00000 | 20.40206 | 35.39828 | -0.6567 | 17.14578 |
March | 514.00000 | 21.10351 | 35.49875 | -0.4479 | 10.98488 |
April | 485.00000 | 21.97296 | 37.55328 | -0.1931 | 7.81546 |
May | 508.00000 | 22.76021 | 40.78496 | -0.9844 | 28.22623 |
June | 496.00000 | 23.35585 | 41.93519 | -0.7490 | 18.68795 |
July | 497.00000 | 23.56696 | 45.49408 | -0.6360 | 15.00817 |
August | 514.00000 | 23.49397 | 49.20092 | -0.6375 | 15.20916 |
September | 485.00000 | 22.72428 | 49.24689 | -0.9530 | 26.40526 |
October | 502.00000 | 21.42039 | 43.27368 | -0.3123 | 8.51441 |
November | 489.00000 | 20.60391 | 42.30477 | -0.5574 | 13.63103 |
December | 497.00000 | 20.19892 | 36.54811 | -0.7248 | 18.25673 |
Annual Sum or Average | 5943.00000 | 21.81828 | 41.04084 | -0.6356 | 16.70215 |
Minimum of Months | 454.00000 | 20.07085 | 34.85494 | -0.9844 | 7.81546 |
Maximum of Months | 514.00000 | 23.56696 | 49.24689 | -0.1931 | 28.22623 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.08250 | 34.16713 | -0.7683 | 20.33003 |
February | 454.00000 | 20.47869 | 34.64039 | -0.6239 | 15.72952 |
March | 514.00000 | 21.24767 | 34.57943 | -0.3891 | 10.21584 |
April | 485.00000 | 22.32347 | 36.10914 | -0.0675 | 7.73233 |
May | 508.00000 | 22.86422 | 39.87760 | -0.8845 | 25.69031 |
June | 496.00000 | 23.50067 | 40.82329 | -0.6103 | 16.14615 |
July | 497.00000 | 23.62559 | 44.78401 | -0.5270 | 13.91685 |
August | 514.00000 | 23.56629 | 48.24877 | -0.5148 | 13.65878 |
September | 485.00000 | 22.78399 | 48.27890 | -0.8617 | 24.94863 |
October | 502.00000 | 21.56349 | 42.17861 | -0.2548 | 8.31170 |
November | 489.00000 | 20.57315 | 41.67294 | -0.5585 | 13.43351 |
December | 497.00000 | 20.21054 | 35.83320 | -0.7189 | 18.00419 |
Annual Sum or Average | 5943.00000 | 21.91373 | 40.13212 | -0.5648 | 15.67122 |
Minimum of Months | 454.00000 | 20.08250 | 34.16713 | -0.8845 | 7.73233 |
Maximum of Months | 514.00000 | 23.62559 | 48.27890 | -0.0675 | 25.69031 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.57368 | 33.57266 | -0.6183 | 17.17551 |
February | 454.00000 | 21.32486 | 33.26264 | -0.3908 | 12.86403 |
March | 514.00000 | 21.85883 | 33.44655 | -0.2225 | 9.88354 |
April | 485.00000 | 22.48272 | 35.78343 | -0.0324 | 8.28173 |
May | 508.00000 | 22.86874 | 39.98127 | -0.9066 | 26.38782 |
June | 496.00000 | 23.27739 | 41.70618 | -0.7409 | 19.38806 |
July | 497.00000 | 23.55453 | 45.13331 | -0.5953 | 15.10618 |
August | 514.00000 | 23.55334 | 48.45486 | -0.5469 | 14.24002 |
September | 485.00000 | 23.10889 | 47.30531 | -0.7275 | 21.26630 |
October | 502.00000 | 22.31740 | 40.40025 | -0.0473 | 8.82716 |
November | 489.00000 | 21.24282 | 40.39963 | -0.3791 | 11.54584 |
December | 497.00000 | 20.82268 | 34.88556 | -0.5392 | 15.24692 |
Annual Sum or Average | 5943.00000 | 22.25689 | 39.56799 | -0.4800 | 15.03901 |
Minimum of Months | 454.00000 | 20.57368 | 33.26264 | -0.9066 | 8.28173 |
Maximum of Months | 514.00000 | 23.55453 | 48.45486 | -0.0324 | 26.38782 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.21306 | 33.79273 | -0.7124 | 18.45464 |
February | 454.00000 | 20.71268 | 34.05791 | -0.5490 | 14.15339 |
March | 514.00000 | 21.38741 | 34.08337 | -0.3432 | 9.52746 |
April | 485.00000 | 22.24101 | 36.14696 | -0.0768 | 7.91629 |
May | 508.00000 | 22.85305 | 39.80099 | -0.8639 | 25.72083 |
June | 496.00000 | 23.25768 | 41.47555 | -0.6854 | 18.41222 |
July | 497.00000 | 23.69665 | 44.55776 | -0.4659 | 13.27996 |
August | 514.00000 | 23.51048 | 48.48424 | -0.5150 | 14.07690 |
September | 485.00000 | 22.84731 | 47.97930 | -0.8168 | 23.49528 |
October | 502.00000 | 21.65314 | 41.78713 | -0.2199 | 7.77862 |
November | 489.00000 | 20.82669 | 40.94346 | -0.4797 | 11.34884 |
December | 497.00000 | 20.46462 | 35.14128 | -0.6326 | 15.10169 |
Annual Sum or Average | 5943.00000 | 21.98272 | 39.89011 | -0.5302 | 14.94462 |
Minimum of Months | 454.00000 | 20.21306 | 33.79273 | -0.8639 | 7.77862 |
Maximum of Months | 514.00000 | 23.69665 | 48.48424 | -0.0768 | 25.72083 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 70707994.65 | 7164.15 | 11-JAN-16:00 | 16.07 | 0.225824E+09 | 0.00 | 0.296532E+09 | 0.07 | 3.26 | 09-JAN-06:50 | 0.00 | 0.00 |
February | 0.160190E+10 | 73598.41 | 27-FEB-16:00 | 27.45 | 0.923554E+10 | 0.00 | 0.108374E+11 | 0.16 | 7.34 | 27-FEB-16:00 | 0.00 | 0.00 |
March | 0.354208E+10 | 57550.14 | 18-MAR-14:10 | 43.77 | 0.163038E+11 | 0.00 | 0.198459E+11 | 0.23 | 7.04 | 18-MAR-14:10 | 0.00 | 0.00 |
April | 0.166917E+11 | 144470.36 | 27-APR-12:10 | 130.63 | 0.101842E+12 | 0.00 | 0.118533E+12 | 0.86 | 7.47 | 27-APR-17:50 | 0.00 | 0.00 |
May | 0.341618E+11 | 151524.20 | 05-MAY-13:00 | 232.97 | 0.206411E+12 | 0.00 | 0.240573E+12 | 1.56 | 7.50 | 04-MAY-13:10 | 0.00 | 0.00 |
June | 0.560526E+11 | 149023.71 | 28-JUN-13:20 | 339.97 | 0.356677E+12 | 0.00 | 0.412730E+12 | 2.58 | 7.50 | 28-JUN-12:10 | 0.00 | 0.00 |
July | 0.890720E+11 | 153508.62 | 27-JUL-17:00 | 452.92 | 0.589209E+12 | 0.00 | 0.678281E+12 | 3.47 | 7.51 | 28-JUL-12:20 | 0.00 | 0.00 |
August | 0.104430E+12 | 154825.19 | 09-AUG-17:00 | 500.50 | 0.695590E+12 | 0.00 | 0.800020E+12 | 3.85 | 7.50 | 21-AUG-12:10 | 0.00 | 0.00 |
September | 0.494868E+11 | 149312.17 | 22-SEP-12:30 | 295.96 | 0.308259E+12 | 0.00 | 0.357746E+12 | 2.18 | 7.50 | 11-SEP-13:00 | 0.00 | 0.00 |
October | 0.115124E+11 | 129975.90 | 04-OCT-15:00 | 114.14 | 0.619748E+11 | 0.00 | 0.734872E+11 | 0.66 | 7.36 | 04-OCT-12:10 | 0.00 | 0.00 |
November | 0.196945E+10 | 79391.78 | 04-NOV-13:30 | 39.21 | 0.119226E+11 | 0.00 | 0.138920E+11 | 0.21 | 7.34 | 04-NOV-13:10 | 0.00 | 0.00 |
December | 30874093.90 | 7030.23 | 16-DEC-06:02 | 13.31 | 98813023.45 | 0.00 | 0.129687E+09 | 0.06 | 3.26 | 26-DEC-06:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.368623E+12 | 2206.91 | 0.235775E+13 | 0.272637E+13 | 1.33 | |||||||
Minimum of Months | 30874093.90 | 7030.23 | 13.31 | 98813023.45 | 0.00 | 0.129687E+09 | 0.06 | 3.26 | 0.00 | 0.00 | ||
Maximum of Months | 0.104430E+12 | 154825.19 | 500.50 | 0.695590E+12 | 0.00 | 0.800020E+12 | 3.85 | 7.51 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.117462E+10 | 95380.44 | 26-APR-15:20 | 4.50 | 0.842779E+10 | 0.00 | 0.960241E+10 | 0.04 | 7.36 | 26-APR-14:30 | 0.00 | 0.00 |
May | 0.723485E+09 | 94487.51 | 04-MAY-15:50 | 2.83 | 0.513528E+10 | 0.00 | 0.585877E+10 | 0.03 | 7.41 | 04-MAY-15:00 | 0.00 | 0.00 |
June | 0.128451E+10 | 92969.62 | 21-JUN-15:10 | 5.17 | 0.922163E+10 | 0.00 | 0.105061E+11 | 0.05 | 7.36 | 27-JUN-15:50 | 0.00 | 0.00 |
July | 0.963600E+10 | 104485.66 | 31-JUL-16:00 | 33.67 | 0.672869E+11 | 0.00 | 0.769229E+11 | 0.31 | 7.39 | 14-JUL-16:00 | 0.00 | 0.00 |
August | 0.250392E+11 | 120783.16 | 29-AUG-14:40 | 80.92 | 0.172130E+12 | 0.00 | 0.197169E+12 | 0.74 | 7.39 | 07-AUG-17:00 | 0.00 | 0.00 |
September | 0.561146E+10 | 91259.00 | 14-SEP-13:00 | 20.42 | 0.401448E+11 | 0.00 | 0.457563E+11 | 0.20 | 7.38 | 11-SEP-14:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.434692E+11 | 147.50 | 0.302346E+12 | 0.345815E+12 | 0.12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.250392E+11 | 120783.16 | 80.92 | 0.172130E+12 | 0.00 | 0.197169E+12 | 0.74 | 7.41 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.145313E+10 | 744.00 | 2538.26 | 11-JAN-15:30 | 32058.97 | 20-JAN-16:30 | 18.65 | 18.33 | 13.92 |
February | 0.645800E+10 | 672.00 | 49248.27 | 27-FEB-13:10 | 307082.24 | 26-FEB-16:30 | 19.46 | 18.34 | 13.92 |
March | 0.112908E+11 | 744.00 | 49248.27 | 09-MAR-12:00 | 272750.17 | 18-MAR-16:02 | 20.04 | 18.35 | 13.92 |
April | 0.320252E+11 | 720.00 | 49248.27 | 01-APR-10:10 | 638138.23 | 27-APR-15:10 | 22.14 | 18.89 | 13.92 |
May | 0.284523E+11 | 744.00 | 49248.27 | 02-MAY-15:40 | 195491.57 | 14-MAY-19:43 | 20.08 | 18.74 | 13.92 |
June | 0.530792E+11 | 720.00 | 49248.27 | 01-JUN-14:00 | 331775.38 | 28-JUN-17:00 | 21.34 | 19.30 | 13.92 |
July | 0.816460E+11 | 744.00 | 49248.27 | 01-JUL-12:20 | 544440.77 | 27-JUL-16:10 | 25.13 | 20.96 | 13.92 |
August | 0.114210E+12 | 744.00 | 49248.27 | 01-AUG-00:05 | 667416.05 | 29-AUG-13:00 | 31.46 | 23.03 | 13.92 |
September | 0.335329E+11 | 720.00 | 49248.27 | 01-SEP-14:20 | 192406.18 | 23-SEP-16:25 | 19.58 | 18.84 | 13.92 |
October | 0.185360E+11 | 744.00 | 49248.27 | 03-OCT-12:40 | 311807.05 | 07-OCT-17:13 | 20.04 | 18.38 | 13.92 |
November | 0.183708E+11 | 720.00 | 49248.27 | 04-NOV-10:40 | 452228.75 | 06-NOV-22:30 | 21.46 | 18.37 | 13.92 |
December | 0.307719E+11 | 744.00 | 43208.44 | 03-DEC-14:33 | 576974.37 | 10-DEC-16:00 | 24.87 | 18.33 | 13.92 |
Annual Sum or Average | 0.429826E+12 | 8760.00 | 22.05 | 19.17 | 13.92 | ||||
Minimum of Months | 0.145313E+10 | 672.00 | 2538.26 | 32058.97 | 18.65 | 18.33 | 13.92 | ||
Maximum of Months | 0.114210E+12 | 744.00 | 49248.27 | 667416.05 | 31.46 | 23.03 | 13.92 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 164239.47 | 07-JAN-06:30 | 20.88 | 20.88 | 0.11 |
February | 12979620.15 | 7.50 | 1138.15 | 27-FEB-15:10 | 596497.14 | 27-FEB-16:00 | 20.91 | 20.88 | 0.83 |
March | 14740287.04 | 22.81 | 465.34 | 18-MAR-14:10 | 470061.02 | 18-MAR-14:20 | 21.03 | 20.99 | 1.86 |
April | 0.535029E+09 | 77.64 | 15070.80 | 26-APR-15:40 | 948270.11 | 26-APR-16:00 | 21.35 | 21.09 | 5.93 |
May | 0.118396E+10 | 167.66 | 15070.80 | 04-MAY-12:50 | 991782.39 | 15-MAY-13:40 | 21.71 | 21.20 | 11.79 |
June | 0.174932E+10 | 270.98 | 15070.80 | 20-JUN-12:20 | 1000061.41 | 09-JUN-15:00 | 22.30 | 21.39 | 18.59 |
July | 0.643821E+10 | 366.39 | 15070.80 | 06-JUL-15:30 | 995341.71 | 18-JUL-15:30 | 22.74 | 21.34 | 23.92 |
August | 0.988499E+10 | 407.07 | 15070.80 | 04-AUG-12:50 | 956153.75 | 09-AUG-09:10 | 23.07 | 21.43 | 26.43 |
September | 0.287236E+10 | 243.71 | 15070.80 | 08-SEP-14:10 | 966443.63 | 08-SEP-16:00 | 22.19 | 21.41 | 16.26 |
October | 82663005.39 | 62.46 | 2157.77 | 04-OCT-14:20 | 994443.82 | 04-OCT-15:20 | 21.23 | 21.07 | 5.02 |
November | 54241645.83 | 8.10 | 3765.64 | 04-NOV-13:40 | 671956.11 | 04-NOV-13:30 | 21.10 | 21.07 | 0.98 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 164111.54 | 26-DEC-06:40 | 20.84 | 20.84 | 0.04 |
Annual Sum or Average | 0.228285E+11 | 1634.32 | 21.62 | 21.13 | 9.37 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 164111.54 | 20.84 | 20.84 | 0.04 | ||
Maximum of Months | 0.988499E+10 | 407.07 | 15070.80 | 1000061.41 | 23.07 | 21.43 | 26.43 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 20.88 | 20.88 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 20.91 | 20.91 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.03 | 21.03 | 0.00 |
April | 0.189178E+09 | 5.33 | 15070.80 | 27-APR-12:50 | 776495.00 | 26-APR-15:20 | 21.35 | 21.32 | 0.29 |
May | 0.171712E+09 | 5.67 | 15070.80 | 05-MAY-13:00 | 773132.71 | 04-MAY-15:50 | 21.71 | 21.67 | 0.26 |
June | 0.122897E+09 | 9.33 | 15070.80 | 21-JUN-16:10 | 758318.74 | 21-JUN-15:10 | 22.30 | 22.24 | 0.45 |
July | 0.224594E+10 | 49.33 | 15070.80 | 07-JUL-12:30 | 798158.22 | 31-JUL-16:00 | 22.74 | 22.47 | 2.52 |
August | 0.508731E+10 | 103.27 | 15070.80 | 07-AUG-10:30 | 893444.37 | 29-AUG-14:40 | 23.07 | 22.48 | 5.45 |
September | 0.120586E+10 | 25.92 | 15070.80 | 11-SEP-15:30 | 736261.64 | 14-SEP-13:10 | 22.19 | 22.04 | 1.41 |
October | 5620997.88 | 0.83 | 1892.50 | 04-OCT-14:40 | 626049.75 | 04-OCT-15:00 | 21.23 | 21.23 | 0.03 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.10 | 21.10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.84 | 20.84 | 0.00 |
Annual Sum or Average | 0.902852E+10 | 199.69 | 21.62 | 21.52 | 0.88 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.84 | 20.84 | 0.00 | ||
Maximum of Months | 0.508731E+10 | 103.27 | 15070.80 | 893444.37 | 23.07 | 22.48 | 5.45 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.259802E+12 | 0.00 | 480.12 | 1743411.44 | 28-JAN-05:11 | 0.00 | 51.09 | 70.72 | 0.86 | 0.00 | 0.06 | 1.16 | 28-JAN-05:11 |
February | 0.135254E+12 | 0.00 | 357.89 | 1702436.18 | 16-FEB-05:11 | 0.00 | 48.31 | 65.38 | 0.46 | 0.00 | 0.04 | 1.13 | 16-FEB-05:11 |
March | 0.424388E+11 | 0.00 | 264.89 | 1786334.83 | 13-MAR-05:01 | 0.00 | 46.31 | 58.69 | 0.12 | 0.00 | 0.01 | 1.19 | 13-MAR-05:01 |
April | 0.155464E+11 | 0.00 | 124.42 | 1254188.55 | 11-APR-05:03 | 0.00 | 46.11 | 52.21 | 0.04 | 0.00 | 0.00 | 0.84 | 11-APR-05:03 |
May | 0.263772E+10 | 0.00 | 55.48 | 1800273.17 | 23-MAY-03:04 | 0.00 | 70.16 | 71.33 | 0.03 | 0.00 | 0.00 | 1.20 | 23-MAY-03:04 |
June | 0.186011E+09 | 0.00 | 11.54 | 333965.32 | 19-JUN-01:50 | 0.00 | 70.11 | 70.30 | 0.00 | 0.00 | 0.00 | 0.22 | 19-JUN-01:50 |
July | 0.848934E+09 | 0.00 | 0.94 | 302519.33 | 02-JUL-19:30 | 0.00 | 72.15 | 72.16 | 0.01 | 0.00 | 0.00 | 0.20 | 02-JUL-19:30 |
August | 0.700739E+09 | 0.00 | 5.15 | 236161.83 | 06-AUG-21:20 | 0.00 | 72.64 | 72.71 | 0.01 | 0.00 | 0.00 | 0.16 | 06-AUG-21:20 |
September | 0.119232E+10 | 0.00 | 47.04 | 315291.62 | 24-SEP-23:30 | 0.00 | 70.10 | 71.11 | 0.01 | 0.00 | 0.00 | 0.21 | 24-SEP-23:30 |
October | 0.131722E+11 | 0.00 | 189.45 | 1800273.17 | 02-OCT-01:02 | 0.00 | 51.95 | 60.45 | 0.04 | 0.00 | 0.00 | 1.20 | 02-OCT-01:02 |
November | 0.836041E+11 | 0.00 | 336.58 | 1746294.50 | 24-NOV-05:11 | 0.00 | 46.43 | 62.68 | 0.24 | 0.00 | 0.02 | 1.16 | 24-NOV-05:11 |
December | 0.174141E+12 | 0.00 | 419.07 | 1677818.15 | 18-DEC-05:11 | 0.00 | 48.72 | 67.02 | 0.52 | 0.00 | 0.04 | 1.12 | 18-DEC-05:11 |
Annual Sum or Average | 0.729525E+12 | 2292.57 | 57.91 | 66.26 | 0.19 | 0.00 | 0.02 | ||||||
Minimum of Months | 0.186011E+09 | 0.00 | 0.94 | 236161.83 | 0.00 | 46.11 | 52.21 | 0.00 | 0.00 | 0.00 | 0.16 | ||
Maximum of Months | 0.259802E+12 | 0.00 | 480.12 | 1800273.17 | 0.00 | 72.64 | 72.71 | 0.86 | 0.00 | 0.06 | 1.20 |
Report: BoilerReportMonthly
For: DUMMY BOILER
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 18.65 | 18.65 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.46 | 19.46 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 20.04 | 20.04 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 22.14 | 22.14 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 20.08 | 20.08 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 21.34 | 21.34 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 25.13 | 25.13 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 31.46 | 31.46 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 19.58 | 19.58 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 20.04 | 20.04 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 21.46 | 21.46 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 24.87 | 24.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 22.05 | 22.05 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.65 | 18.65 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.46 | 31.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 2963085.03 | 0.00 | 0.44 | 2963085.03 | 0.00 | 0.00 | 0.00 | 0.00 | 9431.25 | 11-JAN-05:11 | 9431.25 | 11-JAN-05:11 | 0.00 | 0.00 | 0.00 |
February | 0.491220E+09 | 0.00 | 7.09 | 0.479754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53024.34 | 24-FEB-05:11 | 35492.44 | 27-FEB-03:51 | 0.00 | 0.00 | 0.00 |
March | 0.143315E+09 | 0.00 | 6.43 | 0.130237E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38493.16 | 10-MAR-05:51 | 18381.79 | 09-MAR-05:11 | 0.00 | 0.00 | 0.00 |
April | 0.400997E+10 | 0.00 | 46.66 | 0.400256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59085.00 | 27-APR-15:40 | 59085.00 | 27-APR-15:40 | 0.00 | 0.00 | 0.00 |
May | 0.762608E+10 | 0.00 | 101.33 | 0.759553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57099.84 | 15-MAY-16:00 | 57099.84 | 15-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.158774E+11 | 0.00 | 196.40 | 0.157809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77864.09 | 11-JUN-19:33 | 64265.50 | 11-JUN-19:33 | 0.00 | 0.00 | 0.00 |
July | 0.301503E+11 | 0.00 | 278.77 | 0.298040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118994.32 | 30-JUL-17:42 | 105039.79 | 30-JUL-17:42 | 0.00 | 0.00 | 0.00 |
August | 0.417266E+11 | 0.00 | 315.68 | 0.411220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123738.28 | 13-AUG-17:40 | 107877.53 | 13-AUG-15:31 | 0.00 | 0.00 | 0.00 |
September | 0.126515E+11 | 0.00 | 159.18 | 0.124258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76919.07 | 01-SEP-03:01 | 57627.98 | 11-SEP-15:00 | 0.00 | 0.00 | 0.00 |
October | 0.182541E+10 | 0.00 | 39.68 | 0.178858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66437.41 | 09-OCT-14:01 | 59638.07 | 09-OCT-11:41 | 0.00 | 0.00 | 0.00 |
November | 0.335827E+09 | 0.00 | 6.22 | 0.311433E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64112.73 | 05-NOV-16:41 | 46172.55 | 05-NOV-16:41 | 0.00 | 0.00 | 0.00 |
December | 9288233.40 | 0.00 | 0.28 | 8810054.96 | 0.00 | 0.00 | 0.00 | 0.00 | 16358.91 | 16-DEC-06:02 | 13471.95 | 16-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114850E+12 | 1158.17 | 0.113453E+12 | ||||||||||||
Minimum of Months | 2963085.03 | 0.00 | 0.28 | 2963085.03 | 0.00 | 0.00 | 0.00 | 0.00 | 9431.25 | 9431.25 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.417266E+11 | 0.00 | 315.68 | 0.411220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123738.28 | 107877.53 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 22387603.48 | 0.00 | 2.50 | 22387603.48 | 0.00 | 0.00 | 0.00 | 0.00 | 3157.99 | 11-JAN-14:00 | 3157.99 | 11-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.100719E+10 | 0.00 | 16.84 | 0.100719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55847.49 | 27-FEB-15:00 | 55847.49 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.175433E+10 | 0.00 | 34.92 | 0.175433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35256.30 | 18-MAR-16:00 | 35256.30 | 18-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.112413E+11 | 0.00 | 117.27 | 0.112277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106045.43 | 27-APR-15:20 | 103545.80 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.187991E+11 | 0.00 | 215.00 | 0.184338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87613.03 | 05-MAY-15:40 | 83973.60 | 15-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.342141E+11 | 0.00 | 325.81 | 0.340662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96007.20 | 28-JUN-16:00 | 96007.20 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.622138E+11 | 0.00 | 434.92 | 0.582603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124091.33 | 31-JUL-16:00 | 110812.26 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.843891E+11 | 0.00 | 489.63 | 0.766819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135932.06 | 29-AUG-14:40 | 120554.43 | 29-AUG-15:30 | 0.00 | 0.00 | 0.00 |
September | 0.300033E+11 | 0.00 | 275.68 | 0.276585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109321.43 | 14-SEP-13:00 | 89991.89 | 12-SEP-14:50 | 0.00 | 0.00 | 0.00 |
October | 0.611641E+10 | 0.00 | 101.38 | 0.611336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72609.40 | 04-OCT-15:00 | 72609.40 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.104050E+10 | 0.00 | 18.19 | 0.966107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47573.19 | 04-NOV-14:10 | 43355.40 | 04-NOV-14:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250802E+12 | 2032.13 | 0.236192E+12 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.843891E+11 | 0.00 | 489.63 | 0.766819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135932.06 | 120554.43 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.138767E+09 | 0.00 | 15.63 | 0.138767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18047.11 | 11-JAN-16:00 | 18047.11 | 11-JAN-16:00 | 0.00 | 0.00 | 0.00 |
February | 0.695464E+10 | 0.00 | 24.37 | 0.695464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 377177.55 | 27-FEB-15:00 | 377177.55 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.130663E+11 | 0.00 | 42.25 | 0.130663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 335720.18 | 18-MAR-14:00 | 335720.18 | 18-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.840504E+11 | 0.00 | 110.48 | 0.839773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 872123.92 | 27-APR-15:20 | 858114.00 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.162317E+12 | 0.00 | 217.34 | 0.158889E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 783927.27 | 05-MAY-15:40 | 749001.58 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.280439E+12 | 0.00 | 314.82 | 0.279477E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 844696.66 | 28-JUN-16:00 | 844696.66 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.487435E+12 | 0.00 | 387.79 | 0.456550E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1050511.75 | 31-JUL-16:00 | 909874.66 | 31-JUL-16:00 | 0.00 | 0.00 | 0.00 |
August | 0.639454E+12 | 0.00 | 410.39 | 0.581148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1179980.72 | 29-AUG-14:40 | 1047851.42 | 10-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.268418E+12 | 0.00 | 277.64 | 0.246564E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1011596.98 | 14-SEP-13:00 | 821338.48 | 14-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.481784E+11 | 0.00 | 102.29 | 0.481784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 639862.16 | 04-OCT-15:00 | 639862.16 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.945628E+10 | 0.00 | 35.01 | 0.869725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 472161.45 | 04-NOV-13:20 | 415734.55 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 34375.43 | 0.00 | 13.03 | 34375.43 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 26-DEC-06:02 | 2.33 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199991E+13 | 1951.04 | 0.188364E+13 | ||||||||||||
Minimum of Months | 34375.43 | 0.00 | 13.03 | 34375.43 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 2.33 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.639454E+12 | 0.00 | 410.39 | 0.581148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1179980.72 | 1047851.42 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 12046481.72 | 0.00 | 2.17 | 12046481.72 | 0.00 | 0.00 | 0.00 | 0.00 | 1544.92 | 11-JAN-14:00 | 1544.92 | 11-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.656995E+09 | 0.00 | 13.83 | 0.656995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35312.21 | 27-FEB-15:00 | 35312.21 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.122168E+10 | 0.00 | 33.67 | 0.122168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32970.98 | 18-MAR-14:00 | 32970.98 | 18-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.863747E+10 | 0.00 | 93.78 | 0.862678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 104863.05 | 27-APR-15:20 | 102888.83 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.166153E+11 | 0.00 | 205.62 | 0.162902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85832.91 | 04-MAY-15:00 | 85832.91 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.296182E+11 | 0.00 | 302.46 | 0.295231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103823.14 | 28-JUN-16:00 | 103823.14 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.524538E+11 | 0.00 | 380.68 | 0.491230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 129572.93 | 27-JUL-15:40 | 112957.36 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.677609E+11 | 0.00 | 399.57 | 0.618470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 134460.42 | 29-AUG-14:40 | 124611.01 | 10-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.265246E+11 | 0.00 | 262.89 | 0.243862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106174.70 | 14-SEP-13:00 | 89028.80 | 14-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.431703E+10 | 0.00 | 86.04 | 0.431703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63443.23 | 04-OCT-15:00 | 63443.23 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.896845E+09 | 0.00 | 14.83 | 0.828063E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46188.96 | 04-NOV-13:30 | 41122.73 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 10402.96 | 0.00 | 0.05 | 10402.96 | 0.00 | 0.00 | 0.00 | 0.00 | 89.43 | 26-DEC-04:17 | 89.43 | 26-DEC-04:17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208715E+12 | 1795.60 | 0.196832E+12 | ||||||||||||
Minimum of Months | 10402.96 | 0.00 | 0.05 | 10402.96 | 0.00 | 0.00 | 0.00 | 0.00 | 89.43 | 89.43 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.677609E+11 | 0.00 | 399.57 | 0.618470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 134460.42 | 124611.01 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.456543E+10 | 0.365603E+10 | 740.69 | 0.456525E+10 | 188952.05 | 0.00 | 0.02 | 09-JAN-12:00 | 0.00 | 11-JAN-20:00 | 3192.55 | 09-JAN-12:00 | 3192.55 | 09-JAN-12:00 | 12.84 | 11-JAN-23:00 | 1780.88 | 09-JAN-12:00 | 0.00 |
February | 0.216142E+11 | 0.762529E+10 | 607.17 | 0.215454E+11 | 68764673.19 | 0.00 | 0.55 | 27-FEB-04:03 | 0.00 | 24-FEB-21:10 | 207915.63 | 27-FEB-04:03 | 207915.63 | 27-FEB-04:03 | 681.60 | 27-FEB-16:00 | 49850.37 | 27-FEB-04:03 | 0.00 |
March | 0.157405E+11 | 0.717699E+10 | 702.87 | 0.149723E+11 | 0.768133E+09 | 0.00 | 0.47 | 18-MAR-16:00 | 0.01 | 11-MAR-10:40 | 146182.70 | 18-MAR-16:00 | 146182.70 | 18-MAR-16:00 | 11734.01 | 09-MAR-12:00 | 47723.11 | 18-MAR-16:00 | 0.00 |
April | 0.108149E+12 | 0.347959E+11 | 664.65 | 0.991251E+11 | 0.902415E+10 | 0.00 | 1.00 | 01-APR-15:00 | 0.01 | 15-APR-03:50 | 382461.46 | 27-APR-14:50 | 382461.46 | 27-APR-14:50 | 83197.22 | 28-APR-13:00 | 125899.81 | 27-APR-15:10 | 0.00 |
May | 0.830105E+11 | 0.285628E+11 | 490.04 | 0.825482E+11 | 0.462315E+09 | 0.00 | 0.79 | 15-MAY-20:50 | 0.00 | 03-MAY-05:03 | 139716.17 | 06-MAY-23:10 | 132376.09 | 01-MAY-00:50 | 20852.34 | 06-MAY-23:10 | 71039.45 | 15-MAY-21:10 | 0.00 |
June | 0.910128E+11 | 0.346324E+11 | 434.19 | 0.887757E+11 | 0.223710E+10 | 0.00 | 0.64 | 05-JUN-09:10 | 0.00 | 06-JUN-17:10 | 229938.53 | 12-JUN-01:10 | 208422.25 | 09-JUN-21:05 | 22603.27 | 12-JUN-01:10 | 67014.29 | 28-JUN-17:00 | 0.00 |
July | 0.247277E+12 | 0.751129E+11 | 606.93 | 0.205284E+12 | 0.419928E+11 | 0.00 | 0.87 | 27-JUL-16:00 | 0.01 | 07-JUL-00:20 | 342196.83 | 27-JUL-16:00 | 298672.28 | 24-JUL-15:00 | 89604.20 | 27-JUL-19:00 | 107724.28 | 24-JUL-15:00 | 0.00 |
August | 0.622920E+12 | 0.179745E+12 | 735.50 | 0.479255E+12 | 0.143665E+12 | 0.00 | 1.00 | 07-AUG-11:50 | 0.01 | 06-AUG-03:00 | 406789.31 | 30-AUG-13:00 | 385296.81 | 07-AUG-15:30 | 185448.72 | 30-AUG-08:30 | 137586.53 | 10-AUG-17:00 | 0.00 |
September | 0.156301E+11 | 0.913276E+10 | 230.45 | 0.146861E+11 | 0.944004E+09 | 0.00 | 0.51 | 01-SEP-00:03 | 0.00 | 02-SEP-00:10 | 143121.12 | 23-SEP-18:20 | 121534.12 | 02-SEP-04:40 | 23596.67 | 23-SEP-18:20 | 46233.01 | 01-SEP-00:03 | 0.00 |
October | 0.664412E+11 | 0.204388E+11 | 539.98 | 0.663115E+11 | 0.129651E+09 | 0.00 | 0.56 | 08-OCT-16:00 | 0.00 | 05-OCT-15:50 | 211606.89 | 20-OCT-21:13 | 208801.46 | 04-OCT-21:30 | 6553.36 | 08-OCT-13:52 | 55771.91 | 08-OCT-16:00 | 0.00 |
November | 0.164538E+12 | 0.510579E+11 | 579.28 | 0.162260E+12 | 0.227821E+10 | 0.00 | 0.81 | 06-NOV-22:25 | 0.01 | 02-NOV-20:20 | 345921.61 | 06-NOV-22:25 | 296706.69 | 06-NOV-05:20 | 57869.58 | 04-NOV-16:00 | 73576.21 | 06-NOV-22:25 | 0.00 |
December | 0.484957E+12 | 0.110941E+12 | 727.22 | 0.484276E+12 | 0.680641E+09 | 0.00 | 0.99 | 02-DEC-18:03 | 0.01 | 28-DEC-20:10 | 389115.55 | 03-DEC-14:27 | 389115.55 | 03-DEC-14:27 | 2116.61 | 14-DEC-12:20 | 89578.74 | 02-DEC-18:03 | 0.00 |
Annual Sum or Average | 0.192586E+13 | 0.562878E+12 | 7058.97 | 0.172361E+13 | 0.202251E+12 | ||||||||||||||
Minimum of Months | 0.456543E+10 | 0.365603E+10 | 230.45 | 0.456525E+10 | 188952.05 | 0.00 | 0.02 | 0.00 | 3192.55 | 3192.55 | 12.84 | 1780.88 | 0.00 | ||||||
Maximum of Months | 0.622920E+12 | 0.179745E+12 | 740.69 | 0.484276E+12 | 0.143665E+12 | 0.00 | 1.00 | 0.01 | 406789.31 | 389115.55 | 185448.72 | 137586.53 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.425658E+10 | 0.111239E+10 | 744.00 | 0.425658E+10 | 0.00 | 0.00 | 0.30 | 05-JAN-16:20 | 0.17 | 15-JAN-06:30 | 2300.63 | 05-JAN-16:20 | 2300.63 | 05-JAN-16:20 | 0.00 | 01-JAN-00:03 | 583.61 | 05-JAN-16:20 | 0.00 |
February | 0.873496E+10 | 0.213048E+10 | 672.00 | 0.873496E+10 | 0.00 | 0.00 | 0.53 | 07-FEB-16:50 | 0.40 | 19-FEB-07:13 | 4323.70 | 07-FEB-16:50 | 4323.70 | 07-FEB-16:50 | 0.00 | 01-FEB-00:10 | 1074.99 | 27-FEB-16:10 | 0.00 |
March | 0.150448E+11 | 0.349876E+10 | 744.00 | 0.150448E+11 | 0.00 | 0.00 | 0.74 | 14-MAR-17:20 | 0.64 | 01-MAR-07:50 | 6318.46 | 14-MAR-17:20 | 6318.46 | 14-MAR-17:20 | 0.00 | 01-MAR-00:10 | 1543.82 | 18-MAR-17:00 | 0.00 |
April | 0.195052E+11 | 0.445806E+10 | 720.00 | 0.195052E+11 | 0.00 | 0.00 | 1.00 | 26-APR-17:20 | 0.83 | 01-APR-07:00 | 8382.48 | 26-APR-18:20 | 8382.48 | 26-APR-18:20 | 0.00 | 01-APR-00:10 | 2703.10 | 27-APR-16:00 | 0.00 |
May | 0.547309E+10 | 0.142030E+10 | 744.00 | 0.547309E+10 | 0.00 | 0.00 | 0.38 | 29-MAY-18:33 | 0.22 | 18-MAY-06:50 | 2979.33 | 29-MAY-18:33 | 2979.33 | 29-MAY-18:33 | 0.00 | 01-MAY-00:02 | 802.02 | 14-MAY-18:02 | 0.00 |
June | 0.101966E+11 | 0.255164E+10 | 720.00 | 0.101966E+11 | 0.00 | 0.00 | 0.59 | 22-JUN-19:00 | 0.46 | 14-JUN-07:00 | 4691.54 | 18-JUN-18:56 | 4691.54 | 18-JUN-18:56 | 0.00 | 01-JUN-00:10 | 1433.90 | 28-JUN-17:00 | 0.00 |
July | 0.155828E+11 | 0.396316E+10 | 744.00 | 0.155828E+11 | 0.00 | 0.00 | 0.89 | 30-JUL-18:21 | 0.66 | 01-JUL-07:00 | 7060.59 | 30-JUL-18:50 | 7060.59 | 30-JUL-18:50 | 0.00 | 01-JUL-00:10 | 2315.18 | 30-JUL-18:01 | 0.00 |
August | 0.203662E+11 | 0.535577E+10 | 744.00 | 0.203662E+11 | 0.00 | 0.00 | 1.00 | 06-AUG-17:01 | 0.85 | 03-AUG-21:17 | 8470.99 | 06-AUG-19:23 | 8470.99 | 06-AUG-19:23 | 0.00 | 01-AUG-00:05 | 2954.39 | 10-AUG-17:00 | 0.00 |
September | 0.536156E+10 | 0.139860E+10 | 720.00 | 0.536156E+10 | 0.00 | 0.00 | 0.38 | 10-SEP-17:32 | 0.23 | 28-SEP-07:00 | 2919.98 | 10-SEP-17:34 | 2919.98 | 10-SEP-17:34 | 0.00 | 01-SEP-00:03 | 816.19 | 10-SEP-17:11 | 0.00 |
October | 0.102118E+11 | 0.247989E+10 | 744.00 | 0.102118E+11 | 0.00 | 0.00 | 0.59 | 04-OCT-16:50 | 0.44 | 28-OCT-07:00 | 4702.30 | 03-OCT-17:00 | 4702.30 | 03-OCT-17:00 | 0.00 | 01-OCT-00:10 | 1261.88 | 04-OCT-16:50 | 0.00 |
November | 0.144681E+11 | 0.336831E+10 | 720.00 | 0.144681E+11 | 0.00 | 0.00 | 0.74 | 04-NOV-16:00 | 0.64 | 25-NOV-18:20 | 6087.69 | 12-NOV-16:00 | 6087.69 | 12-NOV-16:00 | 0.00 | 01-NOV-00:10 | 1613.07 | 04-NOV-15:40 | 0.00 |
December | 0.197250E+11 | 0.442584E+10 | 744.00 | 0.197250E+11 | 0.00 | 0.00 | 0.90 | 05-DEC-16:00 | 0.82 | 23-DEC-18:20 | 7917.87 | 05-DEC-16:00 | 7917.87 | 05-DEC-16:00 | 0.00 | 01-DEC-00:10 | 1762.27 | 05-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.148927E+12 | 0.361632E+11 | 8760.00 | 0.148927E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.425658E+10 | 0.111239E+10 | 672.00 | 0.425658E+10 | 0.00 | 0.00 | 0.30 | 0.17 | 2300.63 | 2300.63 | 0.00 | 583.61 | 0.00 | ||||||
Maximum of Months | 0.203662E+11 | 0.535577E+10 | 744.00 | 0.203662E+11 | 0.00 | 0.00 | 1.00 | 0.85 | 8470.99 | 8470.99 | 0.00 | 2954.39 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.178478E+11 | 0.497485E+10 | 677.17 | 0.178478E+11 | 0.00 | 0.00 | 0.25 | 05-JAN-16:20 | 0.00 | 01-JAN-00:03 | 18062.13 | 20-JAN-16:20 | 18062.13 | 20-JAN-16:20 | 0.00 | 01-JAN-00:03 | 4653.37 | 05-JAN-16:20 | 0.00 |
February | 0.658754E+11 | 0.164114E+11 | 672.00 | 0.658754E+11 | 0.00 | 0.00 | 0.51 | 08-FEB-17:00 | 0.24 | 19-FEB-08:10 | 39522.87 | 08-FEB-17:00 | 39522.87 | 08-FEB-17:00 | 0.00 | 01-FEB-00:10 | 9776.53 | 27-FEB-16:20 | 0.00 |
March | 0.129049E+12 | 0.303899E+11 | 744.00 | 0.129049E+12 | 0.00 | 0.00 | 0.73 | 14-MAR-17:20 | 0.53 | 06-MAR-06:15 | 59098.56 | 14-MAR-17:20 | 59098.56 | 14-MAR-17:20 | 0.00 | 01-MAR-00:10 | 14015.08 | 18-MAR-17:03 | 0.00 |
April | 0.176367E+12 | 0.406478E+11 | 720.00 | 0.176367E+12 | 0.00 | 0.00 | 1.00 | 26-APR-17:40 | 0.77 | 09-APR-05:40 | 79732.88 | 26-APR-18:10 | 79732.88 | 26-APR-18:10 | 0.00 | 01-APR-00:10 | 25665.41 | 27-APR-16:00 | 0.00 |
May | 0.447050E+11 | 0.117645E+11 | 744.00 | 0.447050E+11 | 0.00 | 0.00 | 0.37 | 07-MAY-18:12 | 0.16 | 18-MAY-06:00 | 27022.46 | 07-MAY-18:32 | 27022.46 | 07-MAY-18:32 | 0.00 | 01-MAY-00:02 | 7471.44 | 14-MAY-18:02 | 0.00 |
June | 0.914537E+11 | 0.230557E+11 | 720.00 | 0.914537E+11 | 0.00 | 0.00 | 0.59 | 22-JUN-19:00 | 0.41 | 14-JUN-07:00 | 43809.76 | 22-JUN-19:00 | 43809.76 | 22-JUN-19:00 | 0.00 | 01-JUN-00:10 | 13623.23 | 28-JUN-17:00 | 0.00 |
July | 0.144427E+12 | 0.369114E+11 | 744.00 | 0.144427E+12 | 0.00 | 0.00 | 0.87 | 30-JUL-18:21 | 0.63 | 02-JUL-05:10 | 65612.46 | 30-JUL-18:39 | 65612.46 | 30-JUL-18:39 | 0.00 | 01-JUL-00:10 | 21486.69 | 30-JUL-18:01 | 0.00 |
August | 0.190940E+12 | 0.504289E+11 | 744.00 | 0.190940E+12 | 0.00 | 0.00 | 1.00 | 06-AUG-17:41 | 0.82 | 06-AUG-09:12 | 80483.62 | 06-AUG-19:12 | 80483.62 | 06-AUG-19:12 | 0.00 | 01-AUG-00:05 | 28309.44 | 10-AUG-17:00 | 0.00 |
September | 0.443683E+11 | 0.117283E+11 | 720.00 | 0.443683E+11 | 0.00 | 0.00 | 0.37 | 10-SEP-17:22 | 0.17 | 28-SEP-06:55 | 26774.22 | 10-SEP-17:24 | 26774.22 | 10-SEP-17:24 | 0.00 | 01-SEP-00:03 | 7720.79 | 14-SEP-17:00 | 0.00 |
October | 0.846744E+11 | 0.208444E+11 | 744.00 | 0.846744E+11 | 0.00 | 0.00 | 0.58 | 04-OCT-16:50 | 0.35 | 29-OCT-07:10 | 44277.25 | 04-OCT-17:00 | 44277.25 | 04-OCT-17:00 | 0.00 | 01-OCT-00:10 | 11912.59 | 04-OCT-16:50 | 0.00 |
November | 0.120150E+12 | 0.284287E+11 | 720.00 | 0.120150E+12 | 0.00 | 0.00 | 0.70 | 04-NOV-16:03 | 0.52 | 26-NOV-24:00 | 55208.68 | 10-NOV-16:10 | 55208.68 | 10-NOV-16:10 | 0.00 | 01-NOV-00:10 | 14567.52 | 04-NOV-15:50 | 0.00 |
December | 0.165986E+12 | 0.378820E+11 | 744.00 | 0.165986E+12 | 0.00 | 0.00 | 0.87 | 05-DEC-16:10 | 0.66 | 26-DEC-04:57 | 72593.74 | 05-DEC-16:10 | 72593.74 | 05-DEC-16:10 | 0.00 | 01-DEC-00:10 | 16257.91 | 05-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.127584E+13 | 0.313468E+12 | 8693.17 | 0.127584E+13 | 0.00 | ||||||||||||||
Minimum of Months | 0.178478E+11 | 0.497485E+10 | 672.00 | 0.178478E+11 | 0.00 | 0.00 | 0.25 | 0.00 | 18062.13 | 18062.13 | 0.00 | 4653.37 | 0.00 | ||||||
Maximum of Months | 0.190940E+12 | 0.504289E+11 | 744.00 | 0.190940E+12 | 0.00 | 0.00 | 1.00 | 0.82 | 80483.62 | 80483.62 | 0.00 | 28309.44 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.894914E+09 | 0.257812E+09 | 444.12 | 0.894914E+09 | 0.00 | 0.00 | 0.24 | 05-JAN-16:20 | 0.00 | 01-JAN-00:03 | 1750.91 | 05-JAN-16:20 | 1750.91 | 05-JAN-16:20 | 0.00 | 01-JAN-00:03 | 453.27 | 05-JAN-16:20 | 0.00 |
February | 0.519068E+10 | 0.131619E+10 | 671.47 | 0.519068E+10 | 0.00 | 0.00 | 0.49 | 08-FEB-17:00 | 0.00 | 19-FEB-06:15 | 3874.19 | 08-FEB-17:00 | 3874.19 | 08-FEB-17:00 | 0.00 | 01-FEB-00:10 | 962.73 | 27-FEB-16:20 | 0.00 |
March | 0.117456E+11 | 0.279685E+10 | 744.00 | 0.117456E+11 | 0.00 | 0.00 | 0.72 | 14-MAR-17:20 | 0.36 | 06-MAR-05:13 | 5925.67 | 14-MAR-17:20 | 5925.67 | 14-MAR-17:20 | 0.00 | 01-MAR-00:10 | 1377.52 | 18-MAR-16:35 | 0.00 |
April | 0.169113E+11 | 0.392881E+10 | 720.00 | 0.169113E+11 | 0.00 | 0.00 | 1.00 | 26-APR-17:40 | 0.67 | 09-APR-06:20 | 8062.85 | 26-APR-18:10 | 8062.85 | 26-APR-18:10 | 0.00 | 01-APR-00:10 | 2600.89 | 27-APR-16:00 | 0.00 |
May | 0.397672E+10 | 0.105882E+10 | 743.27 | 0.397672E+10 | 0.00 | 0.00 | 0.37 | 07-MAY-18:22 | 0.00 | 18-MAY-04:11 | 2796.79 | 07-MAY-18:30 | 2796.79 | 07-MAY-18:30 | 0.00 | 01-MAY-00:02 | 768.01 | 14-MAY-18:02 | 0.00 |
June | 0.892475E+10 | 0.226104E+10 | 720.00 | 0.892475E+10 | 0.00 | 0.00 | 0.59 | 22-JUN-19:00 | 0.35 | 14-JUN-06:00 | 4474.39 | 22-JUN-19:00 | 4474.39 | 22-JUN-19:00 | 0.00 | 01-JUN-00:10 | 1394.87 | 28-JUN-17:00 | 0.00 |
July | 0.143005E+11 | 0.367152E+10 | 744.00 | 0.143005E+11 | 0.00 | 0.00 | 0.88 | 30-JUL-18:31 | 0.58 | 02-JUL-05:40 | 6729.24 | 30-JUL-18:33 | 6729.24 | 30-JUL-18:33 | 0.00 | 01-JUL-00:10 | 2207.48 | 30-JUL-18:01 | 0.00 |
August | 0.189172E+11 | 0.502155E+10 | 744.00 | 0.189172E+11 | 0.00 | 0.00 | 1.00 | 06-AUG-17:41 | 0.78 | 19-AUG-07:00 | 8147.62 | 06-AUG-19:04 | 8147.62 | 06-AUG-19:04 | 0.00 | 01-AUG-00:05 | 2872.99 | 10-AUG-17:00 | 0.00 |
September | 0.389789E+10 | 0.104439E+10 | 720.00 | 0.389789E+10 | 0.00 | 0.00 | 0.37 | 08-SEP-17:40 | 0.10 | 18-SEP-07:00 | 2716.98 | 08-SEP-17:40 | 2716.98 | 08-SEP-17:40 | 0.00 | 01-SEP-00:03 | 792.09 | 14-SEP-17:00 | 0.00 |
October | 0.740042E+10 | 0.184500E+10 | 744.00 | 0.740042E+10 | 0.00 | 0.00 | 0.58 | 04-OCT-16:50 | 0.23 | 30-OCT-04:27 | 4458.06 | 04-OCT-17:00 | 4458.06 | 04-OCT-17:00 | 0.00 | 01-OCT-00:10 | 1200.96 | 04-OCT-16:50 | 0.00 |
November | 0.105962E+11 | 0.254305E+10 | 720.00 | 0.105962E+11 | 0.00 | 0.00 | 0.68 | 04-NOV-16:03 | 0.36 | 13-NOV-05:00 | 5401.39 | 10-NOV-16:10 | 5401.39 | 10-NOV-16:10 | 0.00 | 01-NOV-00:10 | 1437.99 | 04-NOV-15:40 | 0.00 |
December | 0.148987E+11 | 0.344964E+10 | 744.00 | 0.148987E+11 | 0.00 | 0.00 | 0.85 | 05-DEC-16:10 | 0.47 | 26-DEC-04:14 | 7116.82 | 05-DEC-16:10 | 7116.82 | 05-DEC-16:10 | 0.00 | 01-DEC-00:10 | 1601.48 | 05-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.117655E+12 | 0.291947E+11 | 8458.87 | 0.117655E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.894914E+09 | 0.257812E+09 | 444.12 | 0.894914E+09 | 0.00 | 0.00 | 0.24 | 0.00 | 1750.91 | 1750.91 | 0.00 | 453.27 | 0.00 | ||||||
Maximum of Months | 0.189172E+11 | 0.502155E+10 | 744.00 | 0.189172E+11 | 0.00 | 0.00 | 1.00 | 0.78 | 8147.62 | 8147.62 | 0.00 | 2872.99 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.17 | 0.00 | 85.17 | 0.02 | 680.45 | 0.00 | 0.00 | 744.00 |
February | 132.52 | 0.00 | 132.52 | 7.28 | 606.89 | 0.00 | 0.00 | 672.00 |
March | 195.25 | 0.00 | 195.25 | 32.91 | 489.08 | 0.00 | 0.00 | 744.00 |
April | 276.29 | 0.97 | 275.32 | 106.71 | 380.57 | 0.00 | 0.00 | 720.00 |
May | 355.50 | 10.54 | 344.97 | 194.60 | 291.27 | 0.00 | 0.00 | 744.00 |
June | 373.79 | 24.65 | 349.14 | 223.82 | 220.50 | 0.00 | 0.00 | 720.00 |
July | 355.26 | 27.81 | 327.45 | 251.02 | 197.99 | 0.00 | 0.00 | 744.00 |
August | 287.59 | 7.74 | 279.85 | 221.44 | 196.69 | 0.00 | 0.00 | 744.00 |
September | 223.41 | 0.06 | 223.35 | 116.95 | 292.72 | 0.00 | 0.00 | 720.00 |
October | 153.08 | 0.00 | 153.08 | 30.34 | 424.39 | 0.00 | 0.00 | 744.00 |
November | 96.42 | 0.00 | 96.42 | 2.71 | 568.34 | 0.00 | 0.00 | 720.00 |
December | 72.37 | 0.00 | 72.37 | 0.00 | 698.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 217.64 | 6.03 | 211.62 | 99.59 | 419.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.37 | 0.00 | 72.37 | 0.00 | 196.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 373.79 | 27.81 | 349.14 | 251.02 | 698.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.17 | 0.00 | 85.17 | 0.02 | 680.45 | 0.00 | 0.00 | 744.00 |
February | 132.52 | 0.00 | 132.52 | 7.28 | 606.89 | 0.00 | 0.00 | 672.00 |
March | 195.25 | 0.00 | 195.25 | 32.91 | 489.08 | 0.00 | 0.00 | 744.00 |
April | 276.29 | 0.97 | 275.32 | 106.71 | 380.57 | 0.00 | 0.00 | 720.00 |
May | 355.50 | 10.54 | 344.97 | 194.60 | 291.27 | 0.00 | 0.00 | 744.00 |
June | 373.79 | 24.65 | 349.14 | 223.82 | 220.50 | 0.00 | 0.00 | 720.00 |
July | 355.26 | 27.81 | 327.45 | 251.02 | 197.99 | 0.00 | 0.00 | 744.00 |
August | 287.59 | 7.74 | 279.85 | 221.44 | 196.69 | 0.00 | 0.00 | 744.00 |
September | 223.41 | 0.06 | 223.35 | 116.95 | 292.72 | 0.00 | 0.00 | 720.00 |
October | 153.08 | 0.00 | 153.08 | 30.34 | 424.39 | 0.00 | 0.00 | 744.00 |
November | 96.42 | 0.00 | 96.42 | 2.71 | 568.34 | 0.00 | 0.00 | 720.00 |
December | 72.37 | 0.00 | 72.37 | 0.00 | 698.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 217.64 | 6.03 | 211.62 | 99.59 | 419.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.37 | 0.00 | 72.37 | 0.00 | 196.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 373.79 | 27.81 | 349.14 | 251.02 | 698.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.17 | 0.00 | 85.17 | 0.02 | 680.45 | 0.00 | 0.00 | 744.00 |
February | 132.52 | 0.00 | 132.52 | 7.28 | 606.89 | 0.00 | 0.00 | 672.00 |
March | 195.25 | 0.00 | 195.25 | 32.91 | 489.08 | 0.00 | 0.00 | 744.00 |
April | 276.29 | 0.97 | 275.32 | 106.71 | 380.57 | 0.00 | 0.00 | 720.00 |
May | 355.50 | 10.54 | 344.97 | 194.60 | 291.27 | 0.00 | 0.00 | 744.00 |
June | 373.79 | 24.65 | 349.14 | 223.82 | 220.50 | 0.00 | 0.00 | 720.00 |
July | 355.26 | 27.81 | 327.45 | 251.02 | 197.99 | 0.00 | 0.00 | 744.00 |
August | 287.59 | 7.74 | 279.85 | 221.44 | 196.69 | 0.00 | 0.00 | 744.00 |
September | 223.41 | 0.06 | 223.35 | 116.95 | 292.72 | 0.00 | 0.00 | 720.00 |
October | 153.08 | 0.00 | 153.08 | 30.34 | 424.39 | 0.00 | 0.00 | 744.00 |
November | 96.42 | 0.00 | 96.42 | 2.71 | 568.34 | 0.00 | 0.00 | 720.00 |
December | 72.37 | 0.00 | 72.37 | 0.00 | 698.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 217.64 | 6.03 | 211.62 | 99.59 | 419.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.37 | 0.00 | 72.37 | 0.00 | 196.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 373.79 | 27.81 | 349.14 | 251.02 | 698.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.17 | 0.00 | 85.17 | 0.02 | 680.45 | 0.00 | 0.00 | 744.00 |
February | 132.52 | 0.00 | 132.52 | 7.28 | 606.89 | 0.00 | 0.00 | 672.00 |
March | 195.25 | 0.00 | 195.25 | 32.91 | 489.08 | 0.00 | 0.00 | 744.00 |
April | 276.29 | 0.97 | 275.32 | 106.71 | 380.57 | 0.00 | 0.00 | 720.00 |
May | 355.50 | 10.54 | 344.97 | 194.60 | 291.27 | 0.00 | 0.00 | 744.00 |
June | 373.79 | 24.65 | 349.14 | 223.82 | 220.50 | 0.00 | 0.00 | 720.00 |
July | 355.26 | 27.81 | 327.45 | 251.02 | 197.99 | 0.00 | 0.00 | 744.00 |
August | 287.59 | 7.74 | 279.85 | 221.44 | 196.69 | 0.00 | 0.00 | 744.00 |
September | 223.41 | 0.06 | 223.35 | 116.95 | 292.72 | 0.00 | 0.00 | 720.00 |
October | 153.08 | 0.00 | 153.08 | 30.34 | 424.39 | 0.00 | 0.00 | 744.00 |
November | 96.42 | 0.00 | 96.42 | 2.71 | 568.34 | 0.00 | 0.00 | 720.00 |
December | 72.37 | 0.00 | 72.37 | 0.00 | 698.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 217.64 | 6.03 | 211.62 | 99.59 | 419.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.37 | 0.00 | 72.37 | 0.00 | 196.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 373.79 | 27.81 | 349.14 | 251.02 | 698.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.16 | 0.00 | 85.16 | 0.02 | 680.42 | 0.00 | 0.00 | 744.00 |
February | 132.52 | 0.00 | 132.52 | 7.28 | 606.86 | 0.00 | 0.00 | 672.00 |
March | 195.24 | 0.00 | 195.24 | 32.90 | 489.06 | 0.00 | 0.00 | 744.00 |
April | 276.28 | 0.97 | 275.31 | 106.71 | 380.55 | 0.00 | 0.00 | 720.00 |
May | 355.49 | 10.54 | 344.95 | 194.60 | 291.25 | 0.00 | 0.00 | 744.00 |
June | 373.78 | 24.65 | 349.13 | 223.81 | 220.49 | 0.00 | 0.00 | 720.00 |
July | 355.24 | 27.81 | 327.43 | 251.01 | 197.99 | 0.00 | 0.00 | 744.00 |
August | 287.58 | 7.74 | 279.84 | 221.43 | 196.69 | 0.00 | 0.00 | 744.00 |
September | 223.40 | 0.06 | 223.34 | 116.94 | 292.71 | 0.00 | 0.00 | 720.00 |
October | 153.07 | 0.00 | 153.07 | 30.34 | 424.38 | 0.00 | 0.00 | 744.00 |
November | 96.42 | 0.00 | 96.42 | 2.71 | 568.31 | 0.00 | 0.00 | 720.00 |
December | 72.37 | 0.00 | 72.37 | 0.00 | 698.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 217.63 | 6.03 | 211.61 | 99.59 | 419.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.37 | 0.00 | 72.37 | 0.00 | 196.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 373.78 | 27.81 | 349.13 | 251.01 | 698.75 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.07 | 38.56 | 113.51 | 23.97 | 700.39 | 0.00 | 0.00 | 744.00 |
February | 279.02 | 99.03 | 179.98 | 109.45 | 601.14 | 0.00 | 0.00 | 672.00 |
March | 416.59 | 150.82 | 265.78 | 243.74 | 487.78 | 0.00 | 0.00 | 744.00 |
April | 645.81 | 268.36 | 377.44 | 516.02 | 378.38 | 0.00 | 0.00 | 720.00 |
May | 687.11 | 238.86 | 448.25 | 578.44 | 308.88 | 0.00 | 0.00 | 744.00 |
June | 822.85 | 357.97 | 464.88 | 772.66 | 238.58 | 0.00 | 0.00 | 720.00 |
July | 766.25 | 343.87 | 422.37 | 756.00 | 204.23 | 0.00 | 0.00 | 744.00 |
August | 753.20 | 376.78 | 376.42 | 792.31 | 194.94 | 0.00 | 0.00 | 744.00 |
September | 556.96 | 256.91 | 300.05 | 499.10 | 298.90 | 0.00 | 0.00 | 720.00 |
October | 362.99 | 154.23 | 208.75 | 239.96 | 427.76 | 0.00 | 0.00 | 744.00 |
November | 177.92 | 50.23 | 127.69 | 49.99 | 571.26 | 0.00 | 0.00 | 720.00 |
December | 145.94 | 46.99 | 98.95 | 32.80 | 702.09 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 481.44 | 198.99 | 282.46 | 385.98 | 425.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 145.94 | 38.56 | 98.95 | 23.97 | 194.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 822.85 | 376.78 | 464.88 | 792.31 | 702.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.07 | 38.56 | 113.51 | 23.97 | 700.39 | 0.00 | 0.00 | 744.00 |
February | 279.02 | 99.03 | 179.98 | 109.45 | 601.14 | 0.00 | 0.00 | 672.00 |
March | 416.59 | 150.82 | 265.78 | 243.74 | 487.78 | 0.00 | 0.00 | 744.00 |
April | 645.81 | 268.36 | 377.44 | 516.02 | 378.38 | 0.00 | 0.00 | 720.00 |
May | 687.11 | 238.86 | 448.25 | 578.44 | 308.88 | 0.00 | 0.00 | 744.00 |
June | 822.85 | 357.97 | 464.88 | 772.66 | 238.58 | 0.00 | 0.00 | 720.00 |
July | 766.25 | 343.87 | 422.37 | 756.00 | 204.23 | 0.00 | 0.00 | 744.00 |
August | 753.20 | 376.78 | 376.42 | 792.31 | 194.94 | 0.00 | 0.00 | 744.00 |
September | 556.96 | 256.91 | 300.05 | 499.10 | 298.90 | 0.00 | 0.00 | 720.00 |
October | 362.99 | 154.23 | 208.75 | 239.96 | 427.76 | 0.00 | 0.00 | 744.00 |
November | 177.92 | 50.23 | 127.69 | 49.99 | 571.26 | 0.00 | 0.00 | 720.00 |
December | 145.94 | 46.99 | 98.95 | 32.80 | 702.09 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 481.44 | 198.99 | 282.46 | 385.98 | 425.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 145.94 | 38.56 | 98.95 | 23.97 | 194.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 822.85 | 376.78 | 464.88 | 792.31 | 702.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.06 | 38.56 | 113.50 | 23.97 | 700.38 | 0.00 | 0.00 | 744.00 |
February | 279.01 | 99.03 | 179.98 | 109.45 | 601.13 | 0.00 | 0.00 | 672.00 |
March | 416.58 | 150.81 | 265.77 | 243.74 | 487.77 | 0.00 | 0.00 | 744.00 |
April | 645.79 | 268.36 | 377.44 | 516.01 | 378.37 | 0.00 | 0.00 | 720.00 |
May | 687.10 | 238.86 | 448.24 | 578.43 | 308.88 | 0.00 | 0.00 | 744.00 |
June | 822.84 | 357.97 | 464.87 | 772.65 | 238.57 | 0.00 | 0.00 | 720.00 |
July | 766.23 | 343.87 | 422.37 | 755.99 | 204.23 | 0.00 | 0.00 | 744.00 |
August | 753.18 | 376.77 | 376.41 | 792.30 | 194.94 | 0.00 | 0.00 | 744.00 |
September | 556.95 | 256.91 | 300.05 | 499.09 | 298.89 | 0.00 | 0.00 | 720.00 |
October | 362.98 | 154.23 | 208.75 | 239.96 | 427.75 | 0.00 | 0.00 | 744.00 |
November | 177.92 | 50.23 | 127.69 | 49.99 | 571.25 | 0.00 | 0.00 | 720.00 |
December | 145.94 | 46.99 | 98.95 | 32.80 | 702.08 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 481.44 | 198.98 | 282.45 | 385.97 | 425.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 145.94 | 38.56 | 98.95 | 23.97 | 194.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 822.84 | 376.77 | 464.87 | 792.30 | 702.08 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.18 | 223.33 | 152.85 | 291.27 | 563.62 | 0.00 | 0.00 | 744.00 |
February | 578.70 | 358.23 | 220.47 | 503.40 | 509.14 | 0.00 | 0.00 | 672.00 |
March | 622.75 | 332.22 | 290.53 | 534.88 | 450.80 | 0.00 | 0.00 | 744.00 |
April | 657.29 | 285.42 | 371.87 | 522.99 | 371.30 | 0.00 | 0.00 | 720.00 |
May | 600.88 | 178.95 | 421.93 | 436.22 | 299.02 | 0.00 | 0.00 | 744.00 |
June | 549.74 | 147.54 | 402.20 | 383.84 | 237.05 | 0.00 | 0.00 | 720.00 |
July | 599.50 | 219.50 | 380.00 | 473.60 | 211.99 | 0.00 | 0.00 | 744.00 |
August | 644.15 | 300.35 | 343.80 | 590.75 | 203.47 | 0.00 | 0.00 | 744.00 |
September | 713.97 | 394.38 | 319.59 | 683.34 | 286.03 | 0.00 | 0.00 | 720.00 |
October | 646.71 | 399.36 | 247.35 | 623.94 | 390.75 | 0.00 | 0.00 | 744.00 |
November | 382.18 | 218.99 | 163.19 | 313.30 | 482.68 | 0.00 | 0.00 | 720.00 |
December | 399.81 | 258.69 | 141.12 | 350.00 | 586.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 564.08 | 275.90 | 288.17 | 475.40 | 382.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 376.18 | 147.54 | 141.12 | 291.27 | 203.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 713.97 | 399.36 | 421.93 | 683.34 | 586.77 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.18 | 223.33 | 152.85 | 291.27 | 563.62 | 0.00 | 0.00 | 744.00 |
February | 578.70 | 358.23 | 220.47 | 503.40 | 509.14 | 0.00 | 0.00 | 672.00 |
March | 622.75 | 332.22 | 290.53 | 534.88 | 450.80 | 0.00 | 0.00 | 744.00 |
April | 657.29 | 285.42 | 371.87 | 522.99 | 371.30 | 0.00 | 0.00 | 720.00 |
May | 600.88 | 178.95 | 421.93 | 436.22 | 299.02 | 0.00 | 0.00 | 744.00 |
June | 549.74 | 147.54 | 402.20 | 383.84 | 237.05 | 0.00 | 0.00 | 720.00 |
July | 599.50 | 219.50 | 380.00 | 473.60 | 211.99 | 0.00 | 0.00 | 744.00 |
August | 644.15 | 300.35 | 343.80 | 590.75 | 203.47 | 0.00 | 0.00 | 744.00 |
September | 713.97 | 394.38 | 319.59 | 683.34 | 286.03 | 0.00 | 0.00 | 720.00 |
October | 646.70 | 399.36 | 247.35 | 623.94 | 390.75 | 0.00 | 0.00 | 744.00 |
November | 382.17 | 218.99 | 163.19 | 313.30 | 482.68 | 0.00 | 0.00 | 720.00 |
December | 399.81 | 258.69 | 141.12 | 350.00 | 586.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 564.08 | 275.90 | 288.17 | 475.40 | 382.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 376.18 | 147.54 | 141.12 | 291.27 | 203.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 713.97 | 399.36 | 421.93 | 683.34 | 586.77 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.18 | 223.33 | 152.85 | 291.27 | 563.62 | 0.00 | 0.00 | 744.00 |
February | 578.70 | 358.23 | 220.47 | 503.40 | 509.14 | 0.00 | 0.00 | 672.00 |
March | 622.75 | 332.22 | 290.53 | 534.88 | 450.80 | 0.00 | 0.00 | 744.00 |
April | 657.29 | 285.42 | 371.87 | 522.99 | 371.30 | 0.00 | 0.00 | 720.00 |
May | 600.88 | 178.95 | 421.93 | 436.22 | 299.02 | 0.00 | 0.00 | 744.00 |
June | 549.74 | 147.54 | 402.20 | 383.84 | 237.05 | 0.00 | 0.00 | 720.00 |
July | 599.50 | 219.50 | 380.00 | 473.60 | 211.99 | 0.00 | 0.00 | 744.00 |
August | 644.15 | 300.35 | 343.80 | 590.75 | 203.47 | 0.00 | 0.00 | 744.00 |
September | 713.97 | 394.38 | 319.59 | 683.34 | 286.03 | 0.00 | 0.00 | 720.00 |
October | 646.71 | 399.36 | 247.35 | 623.94 | 390.75 | 0.00 | 0.00 | 744.00 |
November | 382.18 | 218.99 | 163.19 | 313.30 | 482.68 | 0.00 | 0.00 | 720.00 |
December | 399.81 | 258.69 | 141.12 | 350.00 | 586.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 564.08 | 275.90 | 288.17 | 475.40 | 382.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 376.18 | 147.54 | 141.12 | 291.27 | 203.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 713.97 | 399.36 | 421.93 | 683.34 | 586.77 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.18 | 223.33 | 152.85 | 291.27 | 563.62 | 0.00 | 0.00 | 744.00 |
February | 578.70 | 358.23 | 220.47 | 503.40 | 509.14 | 0.00 | 0.00 | 672.00 |
March | 622.75 | 332.22 | 290.53 | 534.88 | 450.80 | 0.00 | 0.00 | 744.00 |
April | 657.29 | 285.42 | 371.87 | 522.99 | 371.30 | 0.00 | 0.00 | 720.00 |
May | 600.88 | 178.95 | 421.93 | 436.22 | 299.02 | 0.00 | 0.00 | 744.00 |
June | 549.74 | 147.54 | 402.20 | 383.84 | 237.05 | 0.00 | 0.00 | 720.00 |
July | 599.50 | 219.50 | 380.00 | 473.60 | 211.99 | 0.00 | 0.00 | 744.00 |
August | 644.15 | 300.35 | 343.80 | 590.75 | 203.47 | 0.00 | 0.00 | 744.00 |
September | 713.97 | 394.38 | 319.59 | 683.34 | 286.03 | 0.00 | 0.00 | 720.00 |
October | 646.70 | 399.36 | 247.35 | 623.94 | 390.75 | 0.00 | 0.00 | 744.00 |
November | 382.17 | 218.99 | 163.19 | 313.30 | 482.68 | 0.00 | 0.00 | 720.00 |
December | 399.81 | 258.69 | 141.12 | 350.00 | 586.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 564.08 | 275.90 | 288.17 | 475.40 | 382.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 376.18 | 147.54 | 141.12 | 291.27 | 203.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 713.97 | 399.36 | 421.93 | 683.34 | 586.77 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.16 | 223.32 | 152.84 | 291.26 | 563.60 | 0.00 | 0.00 | 744.00 |
February | 578.68 | 358.22 | 220.46 | 503.38 | 509.12 | 0.00 | 0.00 | 672.00 |
March | 622.72 | 332.21 | 290.52 | 534.86 | 450.78 | 0.00 | 0.00 | 744.00 |
April | 657.27 | 285.41 | 371.86 | 522.97 | 371.29 | 0.00 | 0.00 | 720.00 |
May | 600.85 | 178.94 | 421.91 | 436.20 | 299.01 | 0.00 | 0.00 | 744.00 |
June | 549.72 | 147.53 | 402.19 | 383.82 | 237.04 | 0.00 | 0.00 | 720.00 |
July | 599.48 | 219.49 | 379.98 | 473.58 | 211.98 | 0.00 | 0.00 | 744.00 |
August | 644.12 | 300.34 | 343.78 | 590.72 | 203.46 | 0.00 | 0.00 | 744.00 |
September | 713.94 | 394.36 | 319.58 | 683.31 | 286.02 | 0.00 | 0.00 | 720.00 |
October | 646.68 | 399.34 | 247.34 | 623.92 | 390.73 | 0.00 | 0.00 | 744.00 |
November | 382.16 | 218.98 | 163.18 | 313.29 | 482.66 | 0.00 | 0.00 | 720.00 |
December | 399.80 | 258.68 | 141.12 | 349.99 | 586.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 564.05 | 275.89 | 288.16 | 475.38 | 382.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 376.16 | 147.53 | 141.12 | 291.26 | 203.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 713.94 | 399.34 | 421.91 | 683.31 | 586.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.39 | 47.31 | 113.09 | 33.36 | 746.60 | 0.00 | 0.00 | 744.00 |
February | 287.57 | 108.08 | 179.48 | 124.01 | 675.82 | 0.00 | 0.00 | 672.00 |
March | 402.95 | 136.01 | 266.94 | 228.88 | 575.79 | 0.00 | 0.00 | 744.00 |
April | 613.05 | 234.41 | 378.64 | 461.89 | 469.41 | 0.00 | 0.00 | 720.00 |
May | 788.73 | 320.36 | 468.37 | 704.91 | 354.05 | 0.00 | 0.00 | 744.00 |
June | 758.52 | 294.44 | 464.08 | 685.53 | 289.25 | 0.00 | 0.00 | 720.00 |
July | 937.02 | 492.47 | 444.55 | 974.07 | 270.28 | 0.00 | 0.00 | 744.00 |
August | 775.25 | 395.85 | 379.40 | 813.76 | 267.69 | 0.00 | 0.00 | 744.00 |
September | 631.37 | 302.96 | 328.41 | 596.10 | 348.10 | 0.00 | 0.00 | 720.00 |
October | 359.42 | 146.45 | 212.98 | 236.79 | 498.65 | 0.00 | 0.00 | 744.00 |
November | 179.00 | 50.49 | 128.51 | 52.82 | 662.36 | 0.00 | 0.00 | 720.00 |
December | 150.49 | 51.58 | 98.91 | 40.82 | 822.55 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 504.96 | 215.85 | 289.11 | 414.72 | 497.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 150.49 | 47.31 | 98.91 | 33.36 | 267.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 937.02 | 492.47 | 468.37 | 974.07 | 822.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.39 | 47.31 | 113.09 | 33.36 | 746.60 | 0.00 | 0.00 | 744.00 |
February | 287.57 | 108.08 | 179.48 | 124.01 | 675.82 | 0.00 | 0.00 | 672.00 |
March | 402.95 | 136.01 | 266.94 | 228.88 | 575.79 | 0.00 | 0.00 | 744.00 |
April | 613.05 | 234.41 | 378.64 | 461.89 | 469.41 | 0.00 | 0.00 | 720.00 |
May | 788.73 | 320.36 | 468.37 | 704.91 | 354.05 | 0.00 | 0.00 | 744.00 |
June | 758.52 | 294.44 | 464.08 | 685.53 | 289.25 | 0.00 | 0.00 | 720.00 |
July | 937.02 | 492.47 | 444.55 | 974.07 | 270.28 | 0.00 | 0.00 | 744.00 |
August | 775.25 | 395.85 | 379.40 | 813.76 | 267.69 | 0.00 | 0.00 | 744.00 |
September | 631.37 | 302.96 | 328.41 | 596.10 | 348.10 | 0.00 | 0.00 | 720.00 |
October | 359.42 | 146.45 | 212.98 | 236.79 | 498.65 | 0.00 | 0.00 | 744.00 |
November | 179.00 | 50.49 | 128.51 | 52.82 | 662.36 | 0.00 | 0.00 | 720.00 |
December | 150.49 | 51.58 | 98.91 | 40.82 | 822.55 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 504.96 | 215.85 | 289.11 | 414.72 | 497.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 150.49 | 47.31 | 98.91 | 33.36 | 267.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 937.02 | 492.47 | 468.37 | 974.07 | 822.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.39 | 47.30 | 113.09 | 33.36 | 746.59 | 0.00 | 0.00 | 744.00 |
February | 287.56 | 108.08 | 179.48 | 124.01 | 675.81 | 0.00 | 0.00 | 672.00 |
March | 402.94 | 136.01 | 266.93 | 228.87 | 575.78 | 0.00 | 0.00 | 744.00 |
April | 613.04 | 234.40 | 378.64 | 461.88 | 469.40 | 0.00 | 0.00 | 720.00 |
May | 788.71 | 320.36 | 468.36 | 704.89 | 354.04 | 0.00 | 0.00 | 744.00 |
June | 758.51 | 294.43 | 464.07 | 685.52 | 289.25 | 0.00 | 0.00 | 720.00 |
July | 937.01 | 492.46 | 444.54 | 974.06 | 270.28 | 0.00 | 0.00 | 744.00 |
August | 775.23 | 395.84 | 379.39 | 813.74 | 267.68 | 0.00 | 0.00 | 744.00 |
September | 631.36 | 302.96 | 328.41 | 596.09 | 348.09 | 0.00 | 0.00 | 720.00 |
October | 359.42 | 146.44 | 212.97 | 236.79 | 498.64 | 0.00 | 0.00 | 744.00 |
November | 179.00 | 50.49 | 128.51 | 52.82 | 662.35 | 0.00 | 0.00 | 720.00 |
December | 150.49 | 51.58 | 98.91 | 40.82 | 822.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 504.96 | 215.85 | 289.11 | 414.71 | 497.53 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 150.49 | 47.30 | 98.91 | 33.36 | 267.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 937.01 | 492.46 | 468.36 | 974.06 | 822.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 425.83 | 0.00 | 425.83 | 1.74 | 2895.66 | 0.00 | 0.00 | 744.00 |
February | 662.61 | 0.00 | 662.61 | 61.60 | 2600.34 | 0.00 | 0.00 | 672.00 |
March | 976.25 | 0.00 | 976.25 | 224.79 | 2110.62 | 0.00 | 0.00 | 744.00 |
April | 1381.44 | 4.85 | 1376.59 | 615.79 | 1663.91 | 0.00 | 0.00 | 720.00 |
May | 1777.50 | 52.68 | 1724.81 | 1025.47 | 1333.64 | 0.00 | 0.00 | 744.00 |
June | 1868.93 | 123.23 | 1745.70 | 1173.51 | 1011.01 | 0.00 | 0.00 | 720.00 |
July | 1776.27 | 139.05 | 1637.22 | 1313.71 | 899.60 | 0.00 | 0.00 | 744.00 |
August | 1437.93 | 38.72 | 1399.22 | 1161.08 | 892.54 | 0.00 | 0.00 | 744.00 |
September | 1117.05 | 0.32 | 1116.73 | 625.94 | 1331.97 | 0.00 | 0.00 | 720.00 |
October | 765.37 | 0.00 | 765.37 | 203.09 | 1831.18 | 0.00 | 0.00 | 744.00 |
November | 482.11 | 0.00 | 482.11 | 26.68 | 2381.91 | 0.00 | 0.00 | 720.00 |
December | 361.85 | 0.00 | 361.85 | 0.74 | 2935.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1088.19 | 30.13 | 1058.06 | 539.26 | 1820.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 361.85 | 0.00 | 361.85 | 0.74 | 892.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1868.93 | 139.05 | 1745.70 | 1313.71 | 2935.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 456.19 | 115.68 | 340.51 | 83.43 | 1833.73 | 0.00 | 0.00 | 744.00 |
February | 837.04 | 297.10 | 539.95 | 362.15 | 1609.35 | 0.00 | 0.00 | 672.00 |
March | 1249.76 | 452.44 | 797.32 | 765.71 | 1316.70 | 0.00 | 0.00 | 744.00 |
April | 1937.40 | 805.07 | 1132.32 | 1572.15 | 1046.34 | 0.00 | 0.00 | 720.00 |
May | 2061.32 | 716.58 | 1344.74 | 1753.81 | 865.88 | 0.00 | 0.00 | 744.00 |
June | 2468.53 | 1073.91 | 1394.62 | 2318.71 | 677.34 | 0.00 | 0.00 | 720.00 |
July | 2298.71 | 1031.61 | 1267.11 | 2272.25 | 583.00 | 0.00 | 0.00 | 744.00 |
August | 2259.57 | 1130.32 | 1129.24 | 2375.82 | 569.14 | 0.00 | 0.00 | 744.00 |
September | 1670.87 | 770.73 | 900.15 | 1511.94 | 833.06 | 0.00 | 0.00 | 720.00 |
October | 1088.94 | 462.70 | 626.25 | 748.55 | 1147.63 | 0.00 | 0.00 | 744.00 |
November | 533.76 | 150.70 | 383.06 | 169.81 | 1501.29 | 0.00 | 0.00 | 720.00 |
December | 437.82 | 140.96 | 296.85 | 110.82 | 1857.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1444.32 | 596.96 | 847.36 | 1174.63 | 1151.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 437.82 | 115.68 | 296.85 | 83.43 | 569.14 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2468.53 | 1130.32 | 1394.62 | 2375.82 | 1857.77 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1880.86 | 1116.62 | 764.24 | 1474.88 | 2610.45 | 0.00 | 0.00 | 744.00 |
February | 2893.49 | 1791.15 | 1102.34 | 2535.15 | 2403.78 | 0.00 | 0.00 | 672.00 |
March | 3113.69 | 1661.08 | 1452.62 | 2683.29 | 2116.19 | 0.00 | 0.00 | 744.00 |
April | 3286.43 | 1427.10 | 1859.33 | 2637.87 | 1744.26 | 0.00 | 0.00 | 720.00 |
May | 3004.35 | 894.73 | 2109.62 | 2195.83 | 1431.25 | 0.00 | 0.00 | 744.00 |
June | 2748.67 | 737.69 | 2010.98 | 1943.05 | 1122.11 | 0.00 | 0.00 | 720.00 |
July | 2997.47 | 1097.50 | 1899.96 | 2392.85 | 1001.15 | 0.00 | 0.00 | 744.00 |
August | 3220.71 | 1501.74 | 1718.97 | 2970.79 | 972.83 | 0.00 | 0.00 | 744.00 |
September | 3569.82 | 1971.88 | 1597.94 | 3414.12 | 1382.53 | 0.00 | 0.00 | 720.00 |
October | 3233.49 | 1996.77 | 1236.72 | 3117.11 | 1849.36 | 0.00 | 0.00 | 744.00 |
November | 1910.85 | 1094.92 | 815.94 | 1588.83 | 2231.36 | 0.00 | 0.00 | 720.00 |
December | 1999.03 | 1293.42 | 705.62 | 1772.59 | 2709.09 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2820.35 | 1379.50 | 1440.85 | 2392.68 | 1794.83 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1880.86 | 737.69 | 705.62 | 1474.88 | 972.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3569.82 | 1996.77 | 2109.62 | 3414.12 | 2709.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 481.18 | 141.91 | 339.26 | 113.72 | 1888.55 | 0.00 | 0.00 | 744.00 |
February | 862.69 | 324.25 | 538.45 | 417.08 | 1679.67 | 0.00 | 0.00 | 672.00 |
March | 1208.83 | 408.03 | 800.80 | 752.51 | 1401.44 | 0.00 | 0.00 | 744.00 |
April | 1839.14 | 703.22 | 1135.92 | 1478.36 | 1153.45 | 0.00 | 0.00 | 720.00 |
May | 2366.16 | 961.08 | 1405.09 | 2155.11 | 960.99 | 0.00 | 0.00 | 744.00 |
June | 2275.54 | 883.31 | 1392.22 | 2113.33 | 756.67 | 0.00 | 0.00 | 720.00 |
July | 2811.04 | 1477.39 | 1333.64 | 2975.70 | 701.48 | 0.00 | 0.00 | 744.00 |
August | 2325.71 | 1187.53 | 1138.18 | 2508.75 | 676.66 | 0.00 | 0.00 | 744.00 |
September | 1894.10 | 908.87 | 985.22 | 1825.72 | 933.65 | 0.00 | 0.00 | 720.00 |
October | 1078.26 | 439.34 | 638.93 | 766.49 | 1233.24 | 0.00 | 0.00 | 744.00 |
November | 537.00 | 151.48 | 385.52 | 188.21 | 1555.36 | 0.00 | 0.00 | 720.00 |
December | 451.47 | 154.73 | 296.73 | 147.53 | 1929.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1514.88 | 647.55 | 867.33 | 1292.77 | 1237.16 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 451.47 | 141.91 | 296.73 | 113.72 | 676.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2811.04 | 1477.39 | 1405.09 | 2975.70 | 1929.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 425.83 | 0.00 | 425.83 | 5.38 | 2706.46 | 0.00 | 0.00 | 744.00 |
February | 662.61 | 0.00 | 662.61 | 76.58 | 2398.21 | 0.00 | 0.00 | 672.00 |
March | 976.25 | 0.00 | 976.25 | 257.73 | 1940.33 | 0.00 | 0.00 | 744.00 |
April | 1381.44 | 4.85 | 1376.59 | 650.66 | 1557.73 | 0.00 | 0.00 | 720.00 |
May | 1777.50 | 52.68 | 1724.81 | 1048.21 | 1263.96 | 0.00 | 0.00 | 744.00 |
June | 1868.93 | 123.23 | 1745.70 | 1179.36 | 979.67 | 0.00 | 0.00 | 720.00 |
July | 1776.27 | 139.05 | 1637.22 | 1311.24 | 877.06 | 0.00 | 0.00 | 744.00 |
August | 1437.93 | 38.72 | 1399.22 | 1162.97 | 863.24 | 0.00 | 0.00 | 744.00 |
September | 1117.05 | 0.32 | 1116.73 | 649.93 | 1243.69 | 0.00 | 0.00 | 720.00 |
October | 765.37 | 0.00 | 765.37 | 239.60 | 1661.94 | 0.00 | 0.00 | 744.00 |
November | 482.11 | 0.00 | 482.11 | 36.38 | 2148.52 | 0.00 | 0.00 | 720.00 |
December | 361.85 | 0.00 | 361.85 | 3.47 | 2688.81 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1088.19 | 30.13 | 1058.06 | 554.85 | 1690.67 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 361.85 | 0.00 | 361.85 | 3.47 | 863.24 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1868.93 | 139.05 | 1745.70 | 1311.24 | 2706.46 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 456.19 | 115.68 | 340.51 | 90.99 | 1721.73 | 0.00 | 0.00 | 744.00 |
February | 837.04 | 297.10 | 539.95 | 385.99 | 1493.97 | 0.00 | 0.00 | 672.00 |
March | 1249.76 | 452.44 | 797.32 | 791.65 | 1224.84 | 0.00 | 0.00 | 744.00 |
April | 1937.40 | 805.07 | 1132.32 | 1593.95 | 990.89 | 0.00 | 0.00 | 720.00 |
May | 2061.32 | 716.58 | 1344.74 | 1765.40 | 831.38 | 0.00 | 0.00 | 744.00 |
June | 2468.53 | 1073.91 | 1394.62 | 2316.25 | 663.50 | 0.00 | 0.00 | 720.00 |
July | 2298.71 | 1031.61 | 1267.11 | 2268.00 | 574.93 | 0.00 | 0.00 | 744.00 |
August | 2259.57 | 1130.32 | 1129.24 | 2373.42 | 557.49 | 0.00 | 0.00 | 744.00 |
September | 1670.87 | 770.73 | 900.15 | 1524.03 | 789.60 | 0.00 | 0.00 | 720.00 |
October | 1088.94 | 462.70 | 626.25 | 775.64 | 1059.03 | 0.00 | 0.00 | 744.00 |
November | 533.76 | 150.70 | 383.06 | 183.48 | 1369.88 | 0.00 | 0.00 | 720.00 |
December | 437.82 | 140.96 | 296.85 | 120.48 | 1712.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1444.32 | 596.96 | 847.36 | 1186.55 | 1080.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 437.82 | 115.68 | 296.85 | 90.99 | 557.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2468.53 | 1130.32 | 1394.62 | 2373.42 | 1721.73 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1880.86 | 1116.62 | 764.24 | 1508.20 | 2433.94 | 0.00 | 0.00 | 744.00 |
February | 2893.49 | 1791.15 | 1102.34 | 2586.13 | 2224.13 | 0.00 | 0.00 | 672.00 |
March | 3113.69 | 1661.08 | 1452.62 | 2717.20 | 1961.54 | 0.00 | 0.00 | 744.00 |
April | 3286.43 | 1427.10 | 1859.33 | 2670.63 | 1645.23 | 0.00 | 0.00 | 720.00 |
May | 3004.35 | 894.73 | 2109.62 | 2218.72 | 1363.46 | 0.00 | 0.00 | 744.00 |
June | 2748.67 | 737.69 | 2010.98 | 1950.17 | 1087.74 | 0.00 | 0.00 | 720.00 |
July | 2997.47 | 1097.50 | 1899.96 | 2394.86 | 977.60 | 0.00 | 0.00 | 744.00 |
August | 3220.71 | 1501.74 | 1718.97 | 2975.55 | 942.79 | 0.00 | 0.00 | 744.00 |
September | 3569.82 | 1971.88 | 1597.94 | 3434.95 | 1301.35 | 0.00 | 0.00 | 720.00 |
October | 3233.49 | 1996.77 | 1236.72 | 3154.57 | 1703.21 | 0.00 | 0.00 | 744.00 |
November | 1910.85 | 1094.92 | 815.94 | 1630.41 | 2037.02 | 0.00 | 0.00 | 720.00 |
December | 1999.03 | 1293.42 | 705.62 | 1809.61 | 2493.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2820.35 | 1379.50 | 1440.85 | 2419.55 | 1678.27 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1880.86 | 737.69 | 705.62 | 1508.20 | 942.79 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3569.82 | 1996.77 | 2109.62 | 3434.95 | 2493.41 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 481.18 | 141.91 | 339.26 | 118.59 | 1779.99 | 0.00 | 0.00 | 744.00 |
February | 862.69 | 324.25 | 538.45 | 431.76 | 1577.42 | 0.00 | 0.00 | 672.00 |
March | 1208.83 | 408.03 | 800.80 | 767.84 | 1313.39 | 0.00 | 0.00 | 744.00 |
April | 1839.14 | 703.22 | 1135.92 | 1494.04 | 1095.26 | 0.00 | 0.00 | 720.00 |
May | 2366.16 | 961.08 | 1405.09 | 2163.52 | 919.85 | 0.00 | 0.00 | 744.00 |
June | 2275.54 | 883.31 | 1392.22 | 2112.90 | 733.90 | 0.00 | 0.00 | 720.00 |
July | 2811.04 | 1477.39 | 1333.64 | 2970.89 | 684.80 | 0.00 | 0.00 | 744.00 |
August | 2325.71 | 1187.53 | 1138.18 | 2508.41 | 657.21 | 0.00 | 0.00 | 744.00 |
September | 1894.10 | 908.87 | 985.22 | 1836.51 | 884.61 | 0.00 | 0.00 | 720.00 |
October | 1078.26 | 439.34 | 638.93 | 784.56 | 1147.63 | 0.00 | 0.00 | 744.00 |
November | 537.00 | 151.48 | 385.52 | 197.56 | 1443.75 | 0.00 | 0.00 | 720.00 |
December | 451.47 | 154.73 | 296.73 | 153.65 | 1804.27 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1514.88 | 647.55 | 867.33 | 1300.85 | 1168.26 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 451.47 | 141.91 | 296.73 | 118.59 | 657.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2811.04 | 1477.39 | 1405.09 | 2970.89 | 1804.27 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228112E+09 | 0.00 | 0.228112E+09 | 51855.86 | 0.182251E+10 |
February | 0.320599E+09 | 0.00 | 0.320599E+09 | 17623022.70 | 0.146818E+10 |
March | 0.522961E+09 | 0.00 | 0.522961E+09 | 88133895.80 | 0.130996E+10 |
April | 0.716145E+09 | 2514756.55 | 0.713630E+09 | 0.276604E+09 | 0.986426E+09 |
May | 0.952182E+09 | 28222089.67 | 0.923960E+09 | 0.521226E+09 | 0.780125E+09 |
June | 0.968867E+09 | 63885152.23 | 0.904981E+09 | 0.580134E+09 | 0.571537E+09 |
July | 0.951522E+09 | 74486115.92 | 0.877036E+09 | 0.672344E+09 | 0.530307E+09 |
August | 0.770282E+09 | 20740132.81 | 0.749542E+09 | 0.593110E+09 | 0.526823E+09 |
September | 0.579085E+09 | 165231.31 | 0.578920E+09 | 0.303122E+09 | 0.758725E+09 |
October | 0.409999E+09 | 0.00 | 0.409999E+09 | 81273839.88 | 0.113670E+10 |
November | 0.249928E+09 | 0.00 | 0.249928E+09 | 7018018.64 | 0.147313E+10 |
December | 0.193837E+09 | 0.00 | 0.193837E+09 | 0.00 | 0.187162E+10 |
Annual Sum or Average | 0.686352E+10 | 0.190013E+09 | 0.667351E+10 | 0.314064E+10 | 0.132360E+11 |
Minimum of Months | 0.193837E+09 | 0.00 | 0.193837E+09 | 0.00 | 0.526823E+09 |
Maximum of Months | 0.968867E+09 | 74486115.92 | 0.923960E+09 | 0.672344E+09 | 0.187162E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228112E+09 | 0.00 | 0.228112E+09 | 51854.79 | 0.182251E+10 |
February | 0.320599E+09 | 0.00 | 0.320599E+09 | 17622970.81 | 0.146818E+10 |
March | 0.522961E+09 | 0.00 | 0.522961E+09 | 88133659.51 | 0.130996E+10 |
April | 0.716145E+09 | 2514753.53 | 0.713630E+09 | 0.276604E+09 | 0.986426E+09 |
May | 0.952181E+09 | 28222055.80 | 0.923959E+09 | 0.521225E+09 | 0.780125E+09 |
June | 0.968866E+09 | 63885075.58 | 0.904981E+09 | 0.580133E+09 | 0.571537E+09 |
July | 0.951521E+09 | 74486026.54 | 0.877035E+09 | 0.672343E+09 | 0.530307E+09 |
August | 0.770281E+09 | 20740107.92 | 0.749541E+09 | 0.593109E+09 | 0.526823E+09 |
September | 0.579085E+09 | 165231.11 | 0.578919E+09 | 0.303122E+09 | 0.758725E+09 |
October | 0.409999E+09 | 0.00 | 0.409999E+09 | 81273650.84 | 0.113670E+10 |
November | 0.249928E+09 | 0.00 | 0.249928E+09 | 7017995.78 | 0.147313E+10 |
December | 0.193836E+09 | 0.00 | 0.193836E+09 | 0.00 | 0.187162E+10 |
Annual Sum or Average | 0.686351E+10 | 0.190013E+09 | 0.667350E+10 | 0.314064E+10 | 0.132360E+11 |
Minimum of Months | 0.193836E+09 | 0.00 | 0.193836E+09 | 0.00 | 0.526823E+09 |
Maximum of Months | 0.968866E+09 | 74486026.54 | 0.923959E+09 | 0.672343E+09 | 0.187162E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228112E+09 | 0.00 | 0.228112E+09 | 51855.86 | 0.182251E+10 |
February | 0.320599E+09 | 0.00 | 0.320599E+09 | 17623022.70 | 0.146818E+10 |
March | 0.522961E+09 | 0.00 | 0.522961E+09 | 88133895.80 | 0.130996E+10 |
April | 0.716145E+09 | 2514756.55 | 0.713630E+09 | 0.276604E+09 | 0.986426E+09 |
May | 0.952182E+09 | 28222089.67 | 0.923960E+09 | 0.521226E+09 | 0.780125E+09 |
June | 0.968867E+09 | 63885152.23 | 0.904981E+09 | 0.580134E+09 | 0.571537E+09 |
July | 0.951522E+09 | 74486115.92 | 0.877036E+09 | 0.672344E+09 | 0.530307E+09 |
August | 0.770282E+09 | 20740132.81 | 0.749542E+09 | 0.593110E+09 | 0.526823E+09 |
September | 0.579085E+09 | 165231.31 | 0.578920E+09 | 0.303122E+09 | 0.758725E+09 |
October | 0.409999E+09 | 0.00 | 0.409999E+09 | 81273839.88 | 0.113670E+10 |
November | 0.249928E+09 | 0.00 | 0.249928E+09 | 7018018.64 | 0.147313E+10 |
December | 0.193837E+09 | 0.00 | 0.193837E+09 | 0.00 | 0.187162E+10 |
Annual Sum or Average | 0.686352E+10 | 0.190013E+09 | 0.667351E+10 | 0.314064E+10 | 0.132360E+11 |
Minimum of Months | 0.193837E+09 | 0.00 | 0.193837E+09 | 0.00 | 0.526823E+09 |
Maximum of Months | 0.968867E+09 | 74486115.92 | 0.923960E+09 | 0.672344E+09 | 0.187162E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228112E+09 | 0.00 | 0.228112E+09 | 51854.79 | 0.182251E+10 |
February | 0.320599E+09 | 0.00 | 0.320599E+09 | 17622970.81 | 0.146818E+10 |
March | 0.522961E+09 | 0.00 | 0.522961E+09 | 88133659.51 | 0.130996E+10 |
April | 0.716145E+09 | 2514753.53 | 0.713630E+09 | 0.276604E+09 | 0.986426E+09 |
May | 0.952181E+09 | 28222055.80 | 0.923959E+09 | 0.521225E+09 | 0.780125E+09 |
June | 0.968866E+09 | 63885075.58 | 0.904981E+09 | 0.580133E+09 | 0.571537E+09 |
July | 0.951521E+09 | 74486026.54 | 0.877035E+09 | 0.672343E+09 | 0.530307E+09 |
August | 0.770281E+09 | 20740107.92 | 0.749541E+09 | 0.593109E+09 | 0.526823E+09 |
September | 0.579085E+09 | 165231.11 | 0.578919E+09 | 0.303122E+09 | 0.758725E+09 |
October | 0.409999E+09 | 0.00 | 0.409999E+09 | 81273650.84 | 0.113670E+10 |
November | 0.249928E+09 | 0.00 | 0.249928E+09 | 7017995.78 | 0.147313E+10 |
December | 0.193836E+09 | 0.00 | 0.193836E+09 | 0.00 | 0.187162E+10 |
Annual Sum or Average | 0.686351E+10 | 0.190013E+09 | 0.667350E+10 | 0.314064E+10 | 0.132360E+11 |
Minimum of Months | 0.193836E+09 | 0.00 | 0.193836E+09 | 0.00 | 0.526823E+09 |
Maximum of Months | 0.968866E+09 | 74486026.54 | 0.923959E+09 | 0.672343E+09 | 0.187162E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228103E+09 | 0.00 | 0.228103E+09 | 51853.77 | 0.182244E+10 |
February | 0.320586E+09 | 0.00 | 0.320586E+09 | 17622312.41 | 0.146813E+10 |
March | 0.522940E+09 | 0.00 | 0.522940E+09 | 88130343.62 | 0.130991E+10 |
April | 0.716116E+09 | 2514655.19 | 0.713602E+09 | 0.276593E+09 | 0.986386E+09 |
May | 0.952143E+09 | 28220952.19 | 0.923922E+09 | 0.521205E+09 | 0.780094E+09 |
June | 0.968828E+09 | 63882577.38 | 0.904945E+09 | 0.580110E+09 | 0.571514E+09 |
July | 0.951483E+09 | 74483113.80 | 0.877000E+09 | 0.672317E+09 | 0.530286E+09 |
August | 0.770251E+09 | 20739296.89 | 0.749511E+09 | 0.593086E+09 | 0.526802E+09 |
September | 0.579062E+09 | 165224.65 | 0.578896E+09 | 0.303110E+09 | 0.758695E+09 |
October | 0.409983E+09 | 0.00 | 0.409983E+09 | 81270564.19 | 0.113665E+10 |
November | 0.249918E+09 | 0.00 | 0.249918E+09 | 7017735.78 | 0.147307E+10 |
December | 0.193829E+09 | 0.00 | 0.193829E+09 | 0.00 | 0.187154E+10 |
Annual Sum or Average | 0.686324E+10 | 0.190006E+09 | 0.667324E+10 | 0.314051E+10 | 0.132355E+11 |
Minimum of Months | 0.193829E+09 | 0.00 | 0.193829E+09 | 0.00 | 0.526802E+09 |
Maximum of Months | 0.968828E+09 | 74483113.80 | 0.923922E+09 | 0.672317E+09 | 0.187154E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.407291E+09 | 0.103277E+09 | 0.304014E+09 | 64212517.77 | 0.187592E+10 |
February | 0.675000E+09 | 0.239583E+09 | 0.435416E+09 | 0.264780E+09 | 0.145429E+10 |
March | 0.111580E+10 | 0.403946E+09 | 0.711853E+09 | 0.652835E+09 | 0.130647E+10 |
April | 0.167393E+10 | 0.695591E+09 | 0.978337E+09 | 0.133753E+10 | 0.980761E+09 |
May | 0.184036E+10 | 0.639769E+09 | 0.120059E+10 | 0.154928E+10 | 0.827312E+09 |
June | 0.213283E+10 | 0.927867E+09 | 0.120497E+10 | 0.200274E+10 | 0.618397E+09 |
July | 0.205231E+10 | 0.921027E+09 | 0.113128E+10 | 0.202488E+10 | 0.547011E+09 |
August | 0.201736E+10 | 0.100916E+10 | 0.100820E+10 | 0.212213E+10 | 0.522131E+09 |
September | 0.144365E+10 | 0.665914E+09 | 0.777735E+09 | 0.129366E+10 | 0.774739E+09 |
October | 0.972219E+09 | 0.413101E+09 | 0.559119E+09 | 0.642712E+09 | 0.114572E+10 |
November | 0.461172E+09 | 0.130204E+09 | 0.330968E+09 | 0.129575E+09 | 0.148071E+10 |
December | 0.390885E+09 | 0.125854E+09 | 0.265031E+09 | 87862831.48 | 0.188049E+10 |
Annual Sum or Average | 0.151828E+11 | 0.627529E+10 | 0.890752E+10 | 0.121722E+11 | 0.134139E+11 |
Minimum of Months | 0.390885E+09 | 0.103277E+09 | 0.265031E+09 | 64212517.77 | 0.522131E+09 |
Maximum of Months | 0.213283E+10 | 0.100916E+10 | 0.120497E+10 | 0.212213E+10 | 0.188049E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.407291E+09 | 0.103277E+09 | 0.304014E+09 | 64212517.77 | 0.187592E+10 |
February | 0.675000E+09 | 0.239583E+09 | 0.435416E+09 | 0.264780E+09 | 0.145429E+10 |
March | 0.111580E+10 | 0.403946E+09 | 0.711853E+09 | 0.652835E+09 | 0.130647E+10 |
April | 0.167393E+10 | 0.695591E+09 | 0.978337E+09 | 0.133753E+10 | 0.980761E+09 |
May | 0.184036E+10 | 0.639769E+09 | 0.120059E+10 | 0.154928E+10 | 0.827312E+09 |
June | 0.213283E+10 | 0.927867E+09 | 0.120497E+10 | 0.200274E+10 | 0.618397E+09 |
July | 0.205231E+10 | 0.921027E+09 | 0.113128E+10 | 0.202488E+10 | 0.547011E+09 |
August | 0.201736E+10 | 0.100916E+10 | 0.100820E+10 | 0.212213E+10 | 0.522131E+09 |
September | 0.144365E+10 | 0.665914E+09 | 0.777735E+09 | 0.129366E+10 | 0.774739E+09 |
October | 0.972219E+09 | 0.413101E+09 | 0.559119E+09 | 0.642712E+09 | 0.114572E+10 |
November | 0.461172E+09 | 0.130204E+09 | 0.330968E+09 | 0.129575E+09 | 0.148071E+10 |
December | 0.390885E+09 | 0.125854E+09 | 0.265031E+09 | 87862831.48 | 0.188049E+10 |
Annual Sum or Average | 0.151828E+11 | 0.627529E+10 | 0.890752E+10 | 0.121722E+11 | 0.134139E+11 |
Minimum of Months | 0.390885E+09 | 0.103277E+09 | 0.265031E+09 | 64212517.77 | 0.522131E+09 |
Maximum of Months | 0.213283E+10 | 0.100916E+10 | 0.120497E+10 | 0.212213E+10 | 0.188049E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.407284E+09 | 0.103276E+09 | 0.304008E+09 | 64211344.46 | 0.187589E+10 |
February | 0.674987E+09 | 0.239579E+09 | 0.435408E+09 | 0.264775E+09 | 0.145426E+10 |
March | 0.111578E+10 | 0.403939E+09 | 0.711840E+09 | 0.652823E+09 | 0.130644E+10 |
April | 0.167390E+10 | 0.695578E+09 | 0.978320E+09 | 0.133750E+10 | 0.980743E+09 |
May | 0.184033E+10 | 0.639757E+09 | 0.120057E+10 | 0.154926E+10 | 0.827297E+09 |
June | 0.213280E+10 | 0.927850E+09 | 0.120495E+10 | 0.200270E+10 | 0.618385E+09 |
July | 0.205227E+10 | 0.921010E+09 | 0.113126E+10 | 0.202484E+10 | 0.547001E+09 |
August | 0.201732E+10 | 0.100914E+10 | 0.100818E+10 | 0.212209E+10 | 0.522122E+09 |
September | 0.144362E+10 | 0.665902E+09 | 0.777721E+09 | 0.129364E+10 | 0.774725E+09 |
October | 0.972202E+09 | 0.413093E+09 | 0.559108E+09 | 0.642700E+09 | 0.114570E+10 |
November | 0.461164E+09 | 0.130202E+09 | 0.330962E+09 | 0.129573E+09 | 0.148068E+10 |
December | 0.390878E+09 | 0.125852E+09 | 0.265026E+09 | 87861226.03 | 0.188045E+10 |
Annual Sum or Average | 0.151825E+11 | 0.627518E+10 | 0.890736E+10 | 0.121720E+11 | 0.134137E+11 |
Minimum of Months | 0.390878E+09 | 0.103276E+09 | 0.265026E+09 | 64211344.46 | 0.522122E+09 |
Maximum of Months | 0.213280E+10 | 0.100914E+10 | 0.120495E+10 | 0.212209E+10 | 0.188045E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100755E+10 | 0.598158E+09 | 0.409393E+09 | 0.780143E+09 | 0.150961E+10 |
February | 0.140000E+10 | 0.866639E+09 | 0.533364E+09 | 0.121782E+10 | 0.123171E+10 |
March | 0.166796E+10 | 0.889816E+09 | 0.778147E+09 | 0.143261E+10 | 0.120741E+10 |
April | 0.170371E+10 | 0.739819E+09 | 0.963887E+09 | 0.135560E+10 | 0.962410E+09 |
May | 0.160939E+10 | 0.479297E+09 | 0.113010E+10 | 0.116837E+10 | 0.800901E+09 |
June | 0.142493E+10 | 0.382423E+09 | 0.104251E+10 | 0.994903E+09 | 0.614430E+09 |
July | 0.160570E+10 | 0.587917E+09 | 0.101778E+10 | 0.126848E+10 | 0.567795E+09 |
August | 0.172529E+10 | 0.804462E+09 | 0.920830E+09 | 0.158226E+10 | 0.544971E+09 |
September | 0.185062E+10 | 0.102223E+10 | 0.828382E+09 | 0.177121E+10 | 0.741388E+09 |
October | 0.173214E+10 | 0.106964E+10 | 0.662493E+09 | 0.167116E+10 | 0.104658E+10 |
November | 0.990598E+09 | 0.567611E+09 | 0.422987E+09 | 0.812082E+09 | 0.125110E+10 |
December | 0.107086E+10 | 0.692867E+09 | 0.377989E+09 | 0.937450E+09 | 0.157159E+10 |
Annual Sum or Average | 0.177887E+11 | 0.870089E+10 | 0.908786E+10 | 0.149921E+11 | 0.120499E+11 |
Minimum of Months | 0.990598E+09 | 0.382423E+09 | 0.377989E+09 | 0.780143E+09 | 0.544971E+09 |
Maximum of Months | 0.185062E+10 | 0.106964E+10 | 0.113010E+10 | 0.177121E+10 | 0.157159E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100755E+10 | 0.598158E+09 | 0.409392E+09 | 0.780142E+09 | 0.150961E+10 |
February | 0.140000E+10 | 0.866638E+09 | 0.533364E+09 | 0.121782E+10 | 0.123171E+10 |
March | 0.166796E+10 | 0.889814E+09 | 0.778146E+09 | 0.143261E+10 | 0.120741E+10 |
April | 0.170370E+10 | 0.739818E+09 | 0.963886E+09 | 0.135560E+10 | 0.962410E+09 |
May | 0.160939E+10 | 0.479296E+09 | 0.113009E+10 | 0.116837E+10 | 0.800901E+09 |
June | 0.142493E+10 | 0.382422E+09 | 0.104250E+10 | 0.994902E+09 | 0.614430E+09 |
July | 0.160570E+10 | 0.587916E+09 | 0.101778E+10 | 0.126848E+10 | 0.567795E+09 |
August | 0.172529E+10 | 0.804461E+09 | 0.920829E+09 | 0.158226E+10 | 0.544971E+09 |
September | 0.185062E+10 | 0.102223E+10 | 0.828382E+09 | 0.177121E+10 | 0.741387E+09 |
October | 0.173213E+10 | 0.106964E+10 | 0.662493E+09 | 0.167116E+10 | 0.104658E+10 |
November | 0.990597E+09 | 0.567611E+09 | 0.422987E+09 | 0.812081E+09 | 0.125110E+10 |
December | 0.107085E+10 | 0.692866E+09 | 0.377988E+09 | 0.937449E+09 | 0.157159E+10 |
Annual Sum or Average | 0.177887E+11 | 0.870087E+10 | 0.908785E+10 | 0.149921E+11 | 0.120499E+11 |
Minimum of Months | 0.990597E+09 | 0.382422E+09 | 0.377988E+09 | 0.780142E+09 | 0.544971E+09 |
Maximum of Months | 0.185062E+10 | 0.106964E+10 | 0.113009E+10 | 0.177121E+10 | 0.157159E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100755E+10 | 0.598158E+09 | 0.409393E+09 | 0.780143E+09 | 0.150961E+10 |
February | 0.140000E+10 | 0.866639E+09 | 0.533364E+09 | 0.121782E+10 | 0.123171E+10 |
March | 0.166796E+10 | 0.889816E+09 | 0.778147E+09 | 0.143261E+10 | 0.120741E+10 |
April | 0.170371E+10 | 0.739819E+09 | 0.963887E+09 | 0.135560E+10 | 0.962410E+09 |
May | 0.160939E+10 | 0.479297E+09 | 0.113010E+10 | 0.116837E+10 | 0.800901E+09 |
June | 0.142493E+10 | 0.382423E+09 | 0.104251E+10 | 0.994903E+09 | 0.614430E+09 |
July | 0.160570E+10 | 0.587917E+09 | 0.101778E+10 | 0.126848E+10 | 0.567795E+09 |
August | 0.172529E+10 | 0.804462E+09 | 0.920830E+09 | 0.158226E+10 | 0.544971E+09 |
September | 0.185062E+10 | 0.102223E+10 | 0.828382E+09 | 0.177121E+10 | 0.741388E+09 |
October | 0.173214E+10 | 0.106964E+10 | 0.662493E+09 | 0.167116E+10 | 0.104658E+10 |
November | 0.990598E+09 | 0.567611E+09 | 0.422987E+09 | 0.812082E+09 | 0.125110E+10 |
December | 0.107086E+10 | 0.692867E+09 | 0.377989E+09 | 0.937450E+09 | 0.157159E+10 |
Annual Sum or Average | 0.177887E+11 | 0.870089E+10 | 0.908786E+10 | 0.149921E+11 | 0.120499E+11 |
Minimum of Months | 0.990598E+09 | 0.382423E+09 | 0.377989E+09 | 0.780143E+09 | 0.544971E+09 |
Maximum of Months | 0.185062E+10 | 0.106964E+10 | 0.113010E+10 | 0.177121E+10 | 0.157159E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100755E+10 | 0.598158E+09 | 0.409392E+09 | 0.780142E+09 | 0.150961E+10 |
February | 0.140000E+10 | 0.866638E+09 | 0.533364E+09 | 0.121782E+10 | 0.123171E+10 |
March | 0.166796E+10 | 0.889814E+09 | 0.778146E+09 | 0.143261E+10 | 0.120741E+10 |
April | 0.170370E+10 | 0.739818E+09 | 0.963886E+09 | 0.135560E+10 | 0.962410E+09 |
May | 0.160939E+10 | 0.479296E+09 | 0.113009E+10 | 0.116837E+10 | 0.800901E+09 |
June | 0.142493E+10 | 0.382422E+09 | 0.104250E+10 | 0.994902E+09 | 0.614430E+09 |
July | 0.160570E+10 | 0.587916E+09 | 0.101778E+10 | 0.126848E+10 | 0.567795E+09 |
August | 0.172529E+10 | 0.804461E+09 | 0.920829E+09 | 0.158226E+10 | 0.544971E+09 |
September | 0.185062E+10 | 0.102223E+10 | 0.828382E+09 | 0.177121E+10 | 0.741387E+09 |
October | 0.173213E+10 | 0.106964E+10 | 0.662493E+09 | 0.167116E+10 | 0.104658E+10 |
November | 0.990597E+09 | 0.567611E+09 | 0.422987E+09 | 0.812081E+09 | 0.125110E+10 |
December | 0.107085E+10 | 0.692866E+09 | 0.377988E+09 | 0.937449E+09 | 0.157159E+10 |
Annual Sum or Average | 0.177887E+11 | 0.870087E+10 | 0.908785E+10 | 0.149921E+11 | 0.120499E+11 |
Minimum of Months | 0.990597E+09 | 0.382422E+09 | 0.377988E+09 | 0.780142E+09 | 0.544971E+09 |
Maximum of Months | 0.185062E+10 | 0.106964E+10 | 0.113009E+10 | 0.177121E+10 | 0.157159E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100751E+10 | 0.598134E+09 | 0.409376E+09 | 0.780112E+09 | 0.150955E+10 |
February | 0.139995E+10 | 0.866604E+09 | 0.533343E+09 | 0.121777E+10 | 0.123166E+10 |
March | 0.166790E+10 | 0.889780E+09 | 0.778116E+09 | 0.143256E+10 | 0.120737E+10 |
April | 0.170364E+10 | 0.739789E+09 | 0.963848E+09 | 0.135554E+10 | 0.962371E+09 |
May | 0.160933E+10 | 0.479278E+09 | 0.113005E+10 | 0.116833E+10 | 0.800869E+09 |
June | 0.142487E+10 | 0.382408E+09 | 0.104246E+10 | 0.994863E+09 | 0.614405E+09 |
July | 0.160564E+10 | 0.587893E+09 | 0.101774E+10 | 0.126843E+10 | 0.567772E+09 |
August | 0.172522E+10 | 0.804429E+09 | 0.920792E+09 | 0.158219E+10 | 0.544950E+09 |
September | 0.185054E+10 | 0.102219E+10 | 0.828349E+09 | 0.177114E+10 | 0.741358E+09 |
October | 0.173207E+10 | 0.106960E+10 | 0.662467E+09 | 0.167110E+10 | 0.104653E+10 |
November | 0.990558E+09 | 0.567589E+09 | 0.422970E+09 | 0.812050E+09 | 0.125105E+10 |
December | 0.107081E+10 | 0.692839E+09 | 0.377973E+09 | 0.937412E+09 | 0.157153E+10 |
Annual Sum or Average | 0.177880E+11 | 0.870053E+10 | 0.908749E+10 | 0.149915E+11 | 0.120494E+11 |
Minimum of Months | 0.990558E+09 | 0.382408E+09 | 0.377973E+09 | 0.780112E+09 | 0.544950E+09 |
Maximum of Months | 0.185054E+10 | 0.106960E+10 | 0.113005E+10 | 0.177114E+10 | 0.157153E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.429601E+09 | 0.126703E+09 | 0.302898E+09 | 89356374.95 | 0.199971E+10 |
February | 0.695682E+09 | 0.261476E+09 | 0.434207E+09 | 0.300015E+09 | 0.163495E+10 |
March | 0.107926E+10 | 0.364297E+09 | 0.714960E+09 | 0.613028E+09 | 0.154221E+10 |
April | 0.158903E+10 | 0.607587E+09 | 0.981442E+09 | 0.119722E+10 | 0.121670E+10 |
May | 0.211253E+10 | 0.858059E+09 | 0.125447E+10 | 0.188802E+10 | 0.948281E+09 |
June | 0.196608E+10 | 0.763188E+09 | 0.120289E+10 | 0.177690E+10 | 0.749745E+09 |
July | 0.250972E+10 | 0.131903E+10 | 0.119069E+10 | 0.260896E+10 | 0.723919E+09 |
August | 0.207642E+10 | 0.106024E+10 | 0.101618E+10 | 0.217957E+10 | 0.716972E+09 |
September | 0.163652E+10 | 0.785276E+09 | 0.851243E+09 | 0.154508E+10 | 0.902264E+09 |
October | 0.962681E+09 | 0.392243E+09 | 0.570438E+09 | 0.634231E+09 | 0.133557E+10 |
November | 0.463974E+09 | 0.130879E+09 | 0.333095E+09 | 0.136917E+09 | 0.171684E+10 |
December | 0.403076E+09 | 0.138149E+09 | 0.264928E+09 | 0.109337E+09 | 0.220312E+10 |
Annual Sum or Average | 0.159246E+11 | 0.680713E+10 | 0.911745E+10 | 0.130786E+11 | 0.156903E+11 |
Minimum of Months | 0.403076E+09 | 0.126703E+09 | 0.264928E+09 | 89356374.95 | 0.716972E+09 |
Maximum of Months | 0.250972E+10 | 0.131903E+10 | 0.125447E+10 | 0.260896E+10 | 0.220312E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.429601E+09 | 0.126703E+09 | 0.302898E+09 | 89356374.95 | 0.199971E+10 |
February | 0.695682E+09 | 0.261476E+09 | 0.434207E+09 | 0.300015E+09 | 0.163495E+10 |
March | 0.107926E+10 | 0.364297E+09 | 0.714960E+09 | 0.613028E+09 | 0.154221E+10 |
April | 0.158903E+10 | 0.607587E+09 | 0.981442E+09 | 0.119722E+10 | 0.121670E+10 |
May | 0.211253E+10 | 0.858059E+09 | 0.125447E+10 | 0.188802E+10 | 0.948281E+09 |
June | 0.196608E+10 | 0.763188E+09 | 0.120289E+10 | 0.177690E+10 | 0.749745E+09 |
July | 0.250972E+10 | 0.131903E+10 | 0.119069E+10 | 0.260896E+10 | 0.723919E+09 |
August | 0.207642E+10 | 0.106024E+10 | 0.101618E+10 | 0.217957E+10 | 0.716972E+09 |
September | 0.163652E+10 | 0.785276E+09 | 0.851243E+09 | 0.154508E+10 | 0.902264E+09 |
October | 0.962681E+09 | 0.392243E+09 | 0.570438E+09 | 0.634231E+09 | 0.133557E+10 |
November | 0.463974E+09 | 0.130879E+09 | 0.333095E+09 | 0.136917E+09 | 0.171684E+10 |
December | 0.403076E+09 | 0.138149E+09 | 0.264928E+09 | 0.109337E+09 | 0.220312E+10 |
Annual Sum or Average | 0.159246E+11 | 0.680713E+10 | 0.911745E+10 | 0.130786E+11 | 0.156903E+11 |
Minimum of Months | 0.403076E+09 | 0.126703E+09 | 0.264928E+09 | 89356374.95 | 0.716972E+09 |
Maximum of Months | 0.250972E+10 | 0.131903E+10 | 0.125447E+10 | 0.260896E+10 | 0.220312E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.429593E+09 | 0.126700E+09 | 0.302893E+09 | 89354742.21 | 0.199967E+10 |
February | 0.695670E+09 | 0.261471E+09 | 0.434199E+09 | 0.300009E+09 | 0.163492E+10 |
March | 0.107924E+10 | 0.364290E+09 | 0.714947E+09 | 0.613017E+09 | 0.154218E+10 |
April | 0.158900E+10 | 0.607576E+09 | 0.981424E+09 | 0.119720E+10 | 0.121668E+10 |
May | 0.211249E+10 | 0.858044E+09 | 0.125445E+10 | 0.188799E+10 | 0.948263E+09 |
June | 0.196605E+10 | 0.763175E+09 | 0.120287E+10 | 0.177687E+10 | 0.749731E+09 |
July | 0.250968E+10 | 0.131901E+10 | 0.119067E+10 | 0.260891E+10 | 0.723906E+09 |
August | 0.207638E+10 | 0.106022E+10 | 0.101616E+10 | 0.217953E+10 | 0.716959E+09 |
September | 0.163649E+10 | 0.785262E+09 | 0.851227E+09 | 0.154505E+10 | 0.902248E+09 |
October | 0.962664E+09 | 0.392236E+09 | 0.570428E+09 | 0.634219E+09 | 0.133555E+10 |
November | 0.463966E+09 | 0.130877E+09 | 0.333089E+09 | 0.136915E+09 | 0.171680E+10 |
December | 0.403069E+09 | 0.138146E+09 | 0.264923E+09 | 0.109335E+09 | 0.220308E+10 |
Annual Sum or Average | 0.159243E+11 | 0.680700E+10 | 0.911728E+10 | 0.130784E+11 | 0.156900E+11 |
Minimum of Months | 0.403069E+09 | 0.126700E+09 | 0.264923E+09 | 89354742.21 | 0.716959E+09 |
Maximum of Months | 0.250968E+10 | 0.131901E+10 | 0.125445E+10 | 0.260891E+10 | 0.220308E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114055E+10 | 0.00 | 0.114055E+10 | 4651350.86 | 0.775574E+10 |
February | 0.160298E+10 | 0.00 | 0.160298E+10 | 0.149022E+09 | 0.629075E+10 |
March | 0.261478E+10 | 0.00 | 0.261478E+10 | 0.602083E+09 | 0.565308E+10 |
April | 0.358068E+10 | 12573630.71 | 0.356811E+10 | 0.159614E+10 | 0.431286E+10 |
May | 0.476085E+10 | 0.141109E+09 | 0.461974E+10 | 0.274663E+10 | 0.357202E+10 |
June | 0.484427E+10 | 0.319422E+09 | 0.452485E+10 | 0.304173E+10 | 0.262053E+10 |
July | 0.475755E+10 | 0.372426E+09 | 0.438512E+10 | 0.351865E+10 | 0.240948E+10 |
August | 0.385136E+10 | 0.103699E+09 | 0.374766E+10 | 0.310983E+10 | 0.239059E+10 |
September | 0.289539E+10 | 826146.56 | 0.289456E+10 | 0.162244E+10 | 0.345247E+10 |
October | 0.204997E+10 | 0.00 | 0.204997E+10 | 0.543966E+09 | 0.490462E+10 |
November | 0.124963E+10 | 0.00 | 0.124963E+10 | 69149787.95 | 0.617392E+10 |
December | 0.969171E+09 | 0.00 | 0.969171E+09 | 1972862.73 | 0.786342E+10 |
Annual Sum or Average | 0.343172E+11 | 0.950056E+09 | 0.333671E+11 | 0.170063E+11 | 0.573995E+11 |
Minimum of Months | 0.969171E+09 | 0.00 | 0.969171E+09 | 1972862.73 | 0.239059E+10 |
Maximum of Months | 0.484427E+10 | 0.372426E+09 | 0.461974E+10 | 0.351865E+10 | 0.786342E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122186E+10 | 0.309829E+09 | 0.912032E+09 | 0.223458E+09 | 0.491147E+10 |
February | 0.202498E+10 | 0.718743E+09 | 0.130624E+10 | 0.876118E+09 | 0.389335E+10 |
March | 0.334736E+10 | 0.121183E+10 | 0.213554E+10 | 0.205087E+10 | 0.352665E+10 |
April | 0.502173E+10 | 0.208675E+10 | 0.293498E+10 | 0.407501E+10 | 0.271212E+10 |
May | 0.552103E+10 | 0.191929E+10 | 0.360174E+10 | 0.469741E+10 | 0.231918E+10 |
June | 0.639844E+10 | 0.278357E+10 | 0.361487E+10 | 0.601009E+10 | 0.175565E+10 |
July | 0.615687E+10 | 0.276305E+10 | 0.339382E+10 | 0.608598E+10 | 0.156152E+10 |
August | 0.605202E+10 | 0.302746E+10 | 0.302457E+10 | 0.636339E+10 | 0.152438E+10 |
September | 0.433091E+10 | 0.199772E+10 | 0.233318E+10 | 0.391895E+10 | 0.215930E+10 |
October | 0.291663E+10 | 0.123929E+10 | 0.167734E+10 | 0.200492E+10 | 0.307380E+10 |
November | 0.138350E+10 | 0.390608E+09 | 0.992894E+09 | 0.440157E+09 | 0.389133E+10 |
December | 0.117264E+10 | 0.377558E+09 | 0.795086E+09 | 0.296828E+09 | 0.497585E+10 |
Annual Sum or Average | 0.455480E+11 | 0.188257E+11 | 0.267223E+11 | 0.370432E+11 | 0.363046E+11 |
Minimum of Months | 0.117264E+10 | 0.309829E+09 | 0.795086E+09 | 0.223458E+09 | 0.152438E+10 |
Maximum of Months | 0.639844E+10 | 0.302746E+10 | 0.361487E+10 | 0.636339E+10 | 0.497585E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.503770E+10 | 0.299076E+10 | 0.204694E+10 | 0.395033E+10 | 0.699184E+10 |
February | 0.699993E+10 | 0.433314E+10 | 0.266679E+10 | 0.613303E+10 | 0.581522E+10 |
March | 0.833971E+10 | 0.444902E+10 | 0.389069E+10 | 0.718691E+10 | 0.566801E+10 |
April | 0.851843E+10 | 0.369905E+10 | 0.481938E+10 | 0.683737E+10 | 0.452113E+10 |
May | 0.804686E+10 | 0.239646E+10 | 0.565041E+10 | 0.588130E+10 | 0.383346E+10 |
June | 0.712456E+10 | 0.191209E+10 | 0.521247E+10 | 0.503639E+10 | 0.290850E+10 |
July | 0.802841E+10 | 0.293955E+10 | 0.508886E+10 | 0.640902E+10 | 0.268148E+10 |
August | 0.862635E+10 | 0.402226E+10 | 0.460409E+10 | 0.795697E+10 | 0.260562E+10 |
September | 0.925297E+10 | 0.511111E+10 | 0.414186E+10 | 0.884939E+10 | 0.358353E+10 |
October | 0.866057E+10 | 0.534815E+10 | 0.331243E+10 | 0.834887E+10 | 0.495332E+10 |
November | 0.495293E+10 | 0.283802E+10 | 0.211491E+10 | 0.411826E+10 | 0.578367E+10 |
December | 0.535421E+10 | 0.346429E+10 | 0.188992E+10 | 0.474770E+10 | 0.725602E+10 |
Annual Sum or Average | 0.889426E+11 | 0.435039E+11 | 0.454387E+11 | 0.754555E+11 | 0.566018E+11 |
Minimum of Months | 0.495293E+10 | 0.191209E+10 | 0.188992E+10 | 0.395033E+10 | 0.260562E+10 |
Maximum of Months | 0.925297E+10 | 0.534815E+10 | 0.565041E+10 | 0.884939E+10 | 0.725602E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128879E+10 | 0.380104E+09 | 0.908685E+09 | 0.304586E+09 | 0.505829E+10 |
February | 0.208703E+10 | 0.784419E+09 | 0.130261E+10 | 0.100901E+10 | 0.406346E+10 |
March | 0.323774E+10 | 0.109288E+10 | 0.214486E+10 | 0.201552E+10 | 0.375363E+10 |
April | 0.476704E+10 | 0.182274E+10 | 0.294430E+10 | 0.383190E+10 | 0.298975E+10 |
May | 0.633753E+10 | 0.257415E+10 | 0.376338E+10 | 0.577224E+10 | 0.257390E+10 |
June | 0.589819E+10 | 0.228954E+10 | 0.360865E+10 | 0.547775E+10 | 0.196129E+10 |
July | 0.752909E+10 | 0.395705E+10 | 0.357203E+10 | 0.797010E+10 | 0.187884E+10 |
August | 0.622919E+10 | 0.318068E+10 | 0.304851E+10 | 0.671943E+10 | 0.181237E+10 |
September | 0.490951E+10 | 0.235580E+10 | 0.255370E+10 | 0.473225E+10 | 0.242002E+10 |
October | 0.288801E+10 | 0.117672E+10 | 0.171130E+10 | 0.205297E+10 | 0.330310E+10 |
November | 0.139191E+10 | 0.392633E+09 | 0.999275E+09 | 0.487839E+09 | 0.403149E+10 |
December | 0.120922E+10 | 0.414442E+09 | 0.794775E+09 | 0.395138E+09 | 0.516885E+10 |
Annual Sum or Average | 0.477732E+11 | 0.204212E+11 | 0.273521E+11 | 0.407687E+11 | 0.390150E+11 |
Minimum of Months | 0.120922E+10 | 0.380104E+09 | 0.794775E+09 | 0.304586E+09 | 0.181237E+10 |
Maximum of Months | 0.752909E+10 | 0.395705E+10 | 0.376338E+10 | 0.797010E+10 | 0.516885E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114055E+10 | 0.00 | 0.114055E+10 | 14408987.90 | 0.724899E+10 |
February | 0.160298E+10 | 0.00 | 0.160298E+10 | 0.185255E+09 | 0.580176E+10 |
March | 0.261478E+10 | 0.00 | 0.261478E+10 | 0.690300E+09 | 0.519699E+10 |
April | 0.358068E+10 | 12573630.71 | 0.356811E+10 | 0.168651E+10 | 0.403763E+10 |
May | 0.476085E+10 | 0.141109E+09 | 0.461974E+10 | 0.280753E+10 | 0.338538E+10 |
June | 0.484427E+10 | 0.319422E+09 | 0.452485E+10 | 0.305691E+10 | 0.253929E+10 |
July | 0.475755E+10 | 0.372426E+09 | 0.438512E+10 | 0.351202E+10 | 0.234911E+10 |
August | 0.385136E+10 | 0.103699E+09 | 0.374766E+10 | 0.311491E+10 | 0.231210E+10 |
September | 0.289539E+10 | 826146.56 | 0.289456E+10 | 0.168461E+10 | 0.322364E+10 |
October | 0.204997E+10 | 0.00 | 0.204997E+10 | 0.641749E+09 | 0.445133E+10 |
November | 0.124963E+10 | 0.00 | 0.124963E+10 | 94293881.38 | 0.556896E+10 |
December | 0.969171E+09 | 0.00 | 0.969171E+09 | 9294303.82 | 0.720172E+10 |
Annual Sum or Average | 0.343172E+11 | 0.950056E+09 | 0.333671E+11 | 0.174978E+11 | 0.533169E+11 |
Minimum of Months | 0.969171E+09 | 0.00 | 0.969171E+09 | 9294303.82 | 0.231210E+10 |
Maximum of Months | 0.484427E+10 | 0.372426E+09 | 0.461974E+10 | 0.351202E+10 | 0.724899E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122186E+10 | 0.309829E+09 | 0.912032E+09 | 0.243710E+09 | 0.461148E+10 |
February | 0.202498E+10 | 0.718743E+09 | 0.130624E+10 | 0.933780E+09 | 0.361420E+10 |
March | 0.334736E+10 | 0.121183E+10 | 0.213554E+10 | 0.212034E+10 | 0.328061E+10 |
April | 0.502173E+10 | 0.208675E+10 | 0.293498E+10 | 0.413151E+10 | 0.256838E+10 |
May | 0.552103E+10 | 0.191929E+10 | 0.360174E+10 | 0.472845E+10 | 0.222677E+10 |
June | 0.639844E+10 | 0.278357E+10 | 0.361487E+10 | 0.600372E+10 | 0.171979E+10 |
July | 0.615687E+10 | 0.276305E+10 | 0.339382E+10 | 0.607461E+10 | 0.153990E+10 |
August | 0.605202E+10 | 0.302746E+10 | 0.302457E+10 | 0.635697E+10 | 0.149318E+10 |
September | 0.433091E+10 | 0.199772E+10 | 0.233318E+10 | 0.395027E+10 | 0.204665E+10 |
October | 0.291663E+10 | 0.123929E+10 | 0.167734E+10 | 0.207746E+10 | 0.283652E+10 |
November | 0.138350E+10 | 0.390608E+09 | 0.992894E+09 | 0.475569E+09 | 0.355072E+10 |
December | 0.117264E+10 | 0.377558E+09 | 0.795086E+09 | 0.322684E+09 | 0.458709E+10 |
Annual Sum or Average | 0.455480E+11 | 0.188257E+11 | 0.267223E+11 | 0.374191E+11 | 0.340753E+11 |
Minimum of Months | 0.117264E+10 | 0.309829E+09 | 0.795086E+09 | 0.243710E+09 | 0.149318E+10 |
Maximum of Months | 0.639844E+10 | 0.302746E+10 | 0.361487E+10 | 0.635697E+10 | 0.461148E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.503770E+10 | 0.299076E+10 | 0.204694E+10 | 0.403957E+10 | 0.651905E+10 |
February | 0.699993E+10 | 0.433314E+10 | 0.266679E+10 | 0.625636E+10 | 0.538062E+10 |
March | 0.833971E+10 | 0.444902E+10 | 0.389069E+10 | 0.727776E+10 | 0.525379E+10 |
April | 0.851843E+10 | 0.369905E+10 | 0.481938E+10 | 0.692226E+10 | 0.426445E+10 |
May | 0.804686E+10 | 0.239646E+10 | 0.565041E+10 | 0.594263E+10 | 0.365189E+10 |
June | 0.712456E+10 | 0.191209E+10 | 0.521247E+10 | 0.505485E+10 | 0.281941E+10 |
July | 0.802841E+10 | 0.293955E+10 | 0.508886E+10 | 0.641439E+10 | 0.261839E+10 |
August | 0.862635E+10 | 0.402226E+10 | 0.460409E+10 | 0.796971E+10 | 0.252518E+10 |
September | 0.925297E+10 | 0.511111E+10 | 0.414186E+10 | 0.890338E+10 | 0.337309E+10 |
October | 0.866057E+10 | 0.534815E+10 | 0.331243E+10 | 0.844921E+10 | 0.456189E+10 |
November | 0.495293E+10 | 0.283802E+10 | 0.211491E+10 | 0.422601E+10 | 0.527996E+10 |
December | 0.535421E+10 | 0.346429E+10 | 0.188992E+10 | 0.484686E+10 | 0.667834E+10 |
Annual Sum or Average | 0.889426E+11 | 0.435039E+11 | 0.454387E+11 | 0.763030E+11 | 0.529261E+11 |
Minimum of Months | 0.495293E+10 | 0.191209E+10 | 0.188992E+10 | 0.403957E+10 | 0.252518E+10 |
Maximum of Months | 0.925297E+10 | 0.534815E+10 | 0.565041E+10 | 0.890338E+10 | 0.667834E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128879E+10 | 0.380104E+09 | 0.908685E+09 | 0.317632E+09 | 0.476752E+10 |
February | 0.208703E+10 | 0.784419E+09 | 0.130261E+10 | 0.104452E+10 | 0.381609E+10 |
March | 0.323774E+10 | 0.109288E+10 | 0.214486E+10 | 0.205659E+10 | 0.351778E+10 |
April | 0.476704E+10 | 0.182274E+10 | 0.294430E+10 | 0.387256E+10 | 0.283892E+10 |
May | 0.633753E+10 | 0.257415E+10 | 0.376338E+10 | 0.579477E+10 | 0.246372E+10 |
June | 0.589819E+10 | 0.228954E+10 | 0.360865E+10 | 0.547663E+10 | 0.190228E+10 |
July | 0.752909E+10 | 0.395705E+10 | 0.357203E+10 | 0.795724E+10 | 0.183418E+10 |
August | 0.622919E+10 | 0.318068E+10 | 0.304851E+10 | 0.671854E+10 | 0.176027E+10 |
September | 0.490951E+10 | 0.235580E+10 | 0.255370E+10 | 0.476023E+10 | 0.229290E+10 |
October | 0.288801E+10 | 0.117672E+10 | 0.171130E+10 | 0.210137E+10 | 0.307381E+10 |
November | 0.139191E+10 | 0.392633E+09 | 0.999275E+09 | 0.512070E+09 | 0.374221E+10 |
December | 0.120922E+10 | 0.414442E+09 | 0.794775E+09 | 0.411543E+09 | 0.483256E+10 |
Annual Sum or Average | 0.477732E+11 | 0.204212E+11 | 0.273521E+11 | 0.410237E+11 | 0.368422E+11 |
Minimum of Months | 0.120922E+10 | 0.380104E+09 | 0.794775E+09 | 0.317632E+09 | 0.176027E+10 |
Maximum of Months | 0.752909E+10 | 0.395705E+10 | 0.376338E+10 | 0.795724E+10 | 0.483256E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.10 | 3402.21 | 425.83 | 0.00 | 425.83 | 0.00 | 0.00 |
February | 36.42 | 3034.42 | 662.61 | 0.00 | 662.61 | 0.00 | 0.00 |
March | 164.53 | 2445.39 | 976.25 | 0.00 | 976.25 | 0.00 | 0.00 |
April | 533.57 | 1902.81 | 1381.44 | 4.85 | 1376.59 | 0.00 | 0.00 |
May | 973.01 | 1456.31 | 1777.50 | 52.68 | 1724.82 | 0.00 | 0.00 |
June | 1119.08 | 1102.49 | 1868.94 | 123.23 | 1745.71 | 0.00 | 0.00 |
July | 1255.11 | 989.96 | 1776.27 | 139.05 | 1637.22 | 0.00 | 0.00 |
August | 1107.20 | 983.46 | 1437.94 | 38.72 | 1399.22 | 0.00 | 0.00 |
September | 584.72 | 1463.58 | 1117.05 | 0.32 | 1116.73 | 0.00 | 0.00 |
October | 151.72 | 2121.96 | 765.37 | 0.00 | 765.37 | 0.00 | 0.00 |
November | 13.54 | 2841.66 | 482.11 | 0.00 | 482.11 | 0.00 | 0.00 |
December | 0.00 | 3493.89 | 361.85 | 0.00 | 361.85 | 0.00 | 0.00 |
Annual Sum or Average | 497.94 | 2098.54 | 1088.19 | 30.13 | 1058.07 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 983.46 | 361.85 | 0.00 | 361.85 | 0.00 | 0.00 |
Maximum of Months | 1255.11 | 3493.89 | 1868.94 | 139.05 | 1745.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 71.92 | 2101.15 | 456.19 | 115.68 | 340.51 | 0.00 | 0.00 |
February | 328.35 | 1803.42 | 837.05 | 297.10 | 539.95 | 0.00 | 0.00 |
March | 731.22 | 1463.33 | 1249.77 | 452.45 | 797.32 | 0.00 | 0.00 |
April | 1548.06 | 1135.13 | 1937.40 | 805.08 | 1132.33 | 0.00 | 0.00 |
May | 1735.30 | 926.64 | 2061.32 | 716.58 | 1344.74 | 0.00 | 0.00 |
June | 2317.97 | 715.73 | 2468.54 | 1073.91 | 1394.63 | 0.00 | 0.00 |
July | 2268.00 | 612.69 | 2298.72 | 1031.61 | 1267.11 | 0.00 | 0.00 |
August | 2376.92 | 584.82 | 2259.58 | 1130.33 | 1129.25 | 0.00 | 0.00 |
September | 1497.28 | 896.68 | 1670.88 | 770.73 | 900.15 | 0.00 | 0.00 |
October | 719.88 | 1283.28 | 1088.95 | 462.70 | 626.25 | 0.00 | 0.00 |
November | 149.97 | 1713.77 | 533.76 | 150.70 | 383.06 | 0.00 | 0.00 |
December | 98.41 | 2106.27 | 437.82 | 140.96 | 296.85 | 0.00 | 0.00 |
Annual Sum or Average | 1157.93 | 1276.05 | 1444.32 | 596.96 | 847.36 | 0.00 | 0.00 |
Minimum of Months | 71.92 | 584.82 | 437.82 | 115.68 | 296.85 | 0.00 | 0.00 |
Maximum of Months | 2376.92 | 2106.27 | 2468.54 | 1130.33 | 1394.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1456.35 | 2818.09 | 1880.87 | 1116.62 | 764.24 | 0.00 | 0.00 |
February | 2516.96 | 2545.67 | 2893.50 | 1791.15 | 1102.35 | 0.00 | 0.00 |
March | 2674.36 | 2253.97 | 3113.70 | 1661.08 | 1452.62 | 0.00 | 0.00 |
April | 2614.94 | 1856.49 | 3286.44 | 1427.11 | 1859.33 | 0.00 | 0.00 |
May | 2181.09 | 1495.10 | 3004.37 | 894.74 | 2109.63 | 0.00 | 0.00 |
June | 1919.16 | 1185.23 | 2748.68 | 737.69 | 2010.99 | 0.00 | 0.00 |
July | 2367.97 | 1059.94 | 2997.48 | 1097.51 | 1899.97 | 0.00 | 0.00 |
August | 2953.71 | 1017.34 | 3220.72 | 1501.74 | 1718.98 | 0.00 | 0.00 |
September | 3416.66 | 1430.13 | 3569.83 | 1971.89 | 1597.95 | 0.00 | 0.00 |
October | 3119.68 | 1953.72 | 3233.50 | 1996.78 | 1236.72 | 0.00 | 0.00 |
November | 1566.50 | 2413.36 | 1910.86 | 1094.92 | 815.94 | 0.00 | 0.00 |
December | 1750.00 | 2933.81 | 1999.04 | 1293.42 | 705.62 | 0.00 | 0.00 |
Annual Sum or Average | 2376.96 | 1910.48 | 2820.36 | 1379.50 | 1440.86 | 0.00 | 0.00 |
Minimum of Months | 1456.35 | 1017.34 | 1880.87 | 737.69 | 705.62 | 0.00 | 0.00 |
Maximum of Months | 3416.66 | 2933.81 | 3569.83 | 1996.78 | 2109.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 100.08 | 2239.80 | 481.18 | 141.92 | 339.27 | 0.00 | 0.00 |
February | 372.04 | 2027.46 | 862.70 | 324.25 | 538.45 | 0.00 | 0.00 |
March | 686.63 | 1727.37 | 1208.84 | 408.04 | 800.80 | 0.00 | 0.00 |
April | 1385.67 | 1408.21 | 1839.14 | 703.22 | 1135.92 | 0.00 | 0.00 |
May | 2114.71 | 1062.14 | 2366.17 | 961.08 | 1405.09 | 0.00 | 0.00 |
June | 2056.59 | 867.76 | 2275.54 | 883.31 | 1392.23 | 0.00 | 0.00 |
July | 2922.21 | 810.84 | 2811.05 | 1477.40 | 1333.65 | 0.00 | 0.00 |
August | 2441.26 | 803.06 | 2325.72 | 1187.54 | 1138.19 | 0.00 | 0.00 |
September | 1788.28 | 1044.28 | 1894.11 | 908.88 | 985.23 | 0.00 | 0.00 |
October | 710.38 | 1495.93 | 1078.27 | 439.34 | 638.93 | 0.00 | 0.00 |
November | 158.47 | 1987.07 | 537.00 | 151.48 | 385.52 | 0.00 | 0.00 |
December | 122.46 | 2467.64 | 451.47 | 154.74 | 296.74 | 0.00 | 0.00 |
Annual Sum or Average | 1244.16 | 1492.60 | 1514.89 | 647.55 | 867.33 | 0.00 | 0.00 |
Minimum of Months | 100.08 | 803.06 | 451.47 | 141.92 | 296.74 | 0.00 | 0.00 |
Maximum of Months | 2922.21 | 2467.64 | 2811.05 | 1477.40 | 1405.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.74 | 2895.66 | 425.83 | 0.00 | 425.83 | 0.00 | 0.00 |
February | 61.60 | 2600.34 | 662.61 | 0.00 | 662.61 | 0.00 | 0.00 |
March | 224.79 | 2110.62 | 976.25 | 0.00 | 976.25 | 0.00 | 0.00 |
April | 615.79 | 1663.91 | 1381.44 | 4.85 | 1376.59 | 0.00 | 0.00 |
May | 1025.47 | 1333.64 | 1777.50 | 52.68 | 1724.81 | 0.00 | 0.00 |
June | 1173.51 | 1011.01 | 1868.93 | 123.23 | 1745.70 | 0.00 | 0.00 |
July | 1313.71 | 899.60 | 1776.27 | 139.05 | 1637.22 | 0.00 | 0.00 |
August | 1161.08 | 892.54 | 1437.93 | 38.72 | 1399.22 | 0.00 | 0.00 |
September | 625.94 | 1331.97 | 1117.05 | 0.32 | 1116.73 | 0.00 | 0.00 |
October | 203.09 | 1831.18 | 765.37 | 0.00 | 765.37 | 0.00 | 0.00 |
November | 26.68 | 2381.91 | 482.11 | 0.00 | 482.11 | 0.00 | 0.00 |
December | 0.74 | 2935.86 | 361.85 | 0.00 | 361.85 | 0.00 | 0.00 |
Annual Sum or Average | 539.26 | 1820.13 | 1088.19 | 30.13 | 1058.06 | 0.00 | 0.00 |
Minimum of Months | 0.74 | 892.54 | 361.85 | 0.00 | 361.85 | 0.00 | 0.00 |
Maximum of Months | 1313.71 | 2935.86 | 1868.93 | 139.05 | 1745.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 83.43 | 1833.73 | 456.19 | 115.68 | 340.51 | 0.00 | 0.00 |
February | 362.15 | 1609.35 | 837.04 | 297.10 | 539.95 | 0.00 | 0.00 |
March | 765.71 | 1316.70 | 1249.76 | 452.44 | 797.32 | 0.00 | 0.00 |
April | 1572.15 | 1046.34 | 1937.40 | 805.07 | 1132.32 | 0.00 | 0.00 |
May | 1753.81 | 865.88 | 2061.32 | 716.58 | 1344.74 | 0.00 | 0.00 |
June | 2318.71 | 677.34 | 2468.53 | 1073.91 | 1394.62 | 0.00 | 0.00 |
July | 2272.25 | 583.00 | 2298.71 | 1031.61 | 1267.11 | 0.00 | 0.00 |
August | 2375.82 | 569.14 | 2259.57 | 1130.32 | 1129.24 | 0.00 | 0.00 |
September | 1511.94 | 833.06 | 1670.87 | 770.73 | 900.15 | 0.00 | 0.00 |
October | 748.55 | 1147.63 | 1088.94 | 462.70 | 626.25 | 0.00 | 0.00 |
November | 169.81 | 1501.29 | 533.76 | 150.70 | 383.06 | 0.00 | 0.00 |
December | 110.82 | 1857.77 | 437.82 | 140.96 | 296.85 | 0.00 | 0.00 |
Annual Sum or Average | 1174.63 | 1151.21 | 1444.32 | 596.96 | 847.36 | 0.00 | 0.00 |
Minimum of Months | 83.43 | 569.14 | 437.82 | 115.68 | 296.85 | 0.00 | 0.00 |
Maximum of Months | 2375.82 | 1857.77 | 2468.53 | 1130.32 | 1394.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1474.88 | 2610.45 | 1880.86 | 1116.62 | 764.24 | 0.00 | 0.00 |
February | 2535.15 | 2403.78 | 2893.49 | 1791.15 | 1102.34 | 0.00 | 0.00 |
March | 2683.29 | 2116.19 | 3113.69 | 1661.08 | 1452.62 | 0.00 | 0.00 |
April | 2637.87 | 1744.26 | 3286.43 | 1427.10 | 1859.33 | 0.00 | 0.00 |
May | 2195.83 | 1431.25 | 3004.35 | 894.73 | 2109.62 | 0.00 | 0.00 |
June | 1943.05 | 1122.11 | 2748.67 | 737.69 | 2010.98 | 0.00 | 0.00 |
July | 2392.85 | 1001.15 | 2997.47 | 1097.50 | 1899.96 | 0.00 | 0.00 |
August | 2970.79 | 972.83 | 3220.71 | 1501.74 | 1718.97 | 0.00 | 0.00 |
September | 3414.12 | 1382.53 | 3569.82 | 1971.88 | 1597.94 | 0.00 | 0.00 |
October | 3117.11 | 1849.36 | 3233.49 | 1996.77 | 1236.72 | 0.00 | 0.00 |
November | 1588.83 | 2231.36 | 1910.85 | 1094.92 | 815.94 | 0.00 | 0.00 |
December | 1772.59 | 2709.09 | 1999.03 | 1293.42 | 705.62 | 0.00 | 0.00 |
Annual Sum or Average | 2392.68 | 1794.83 | 2820.35 | 1379.50 | 1440.85 | 0.00 | 0.00 |
Minimum of Months | 1474.88 | 972.83 | 1880.86 | 737.69 | 705.62 | 0.00 | 0.00 |
Maximum of Months | 3414.12 | 2709.09 | 3569.82 | 1996.77 | 2109.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 113.72 | 1888.55 | 481.18 | 141.91 | 339.26 | 0.00 | 0.00 |
February | 417.08 | 1679.67 | 862.69 | 324.25 | 538.45 | 0.00 | 0.00 |
March | 752.51 | 1401.44 | 1208.83 | 408.03 | 800.80 | 0.00 | 0.00 |
April | 1478.36 | 1153.45 | 1839.14 | 703.22 | 1135.92 | 0.00 | 0.00 |
May | 2155.11 | 960.99 | 2366.16 | 961.08 | 1405.09 | 0.00 | 0.00 |
June | 2113.33 | 756.67 | 2275.54 | 883.31 | 1392.22 | 0.00 | 0.00 |
July | 2975.70 | 701.48 | 2811.04 | 1477.39 | 1333.64 | 0.00 | 0.00 |
August | 2508.75 | 676.66 | 2325.71 | 1187.53 | 1138.18 | 0.00 | 0.00 |
September | 1825.72 | 933.65 | 1894.10 | 908.87 | 985.22 | 0.00 | 0.00 |
October | 766.49 | 1233.24 | 1078.26 | 439.34 | 638.93 | 0.00 | 0.00 |
November | 188.21 | 1555.36 | 537.00 | 151.48 | 385.52 | 0.00 | 0.00 |
December | 147.53 | 1929.83 | 451.47 | 154.73 | 296.73 | 0.00 | 0.00 |
Annual Sum or Average | 1292.77 | 1237.16 | 1514.88 | 647.55 | 867.33 | 0.00 | 0.00 |
Minimum of Months | 113.72 | 676.66 | 451.47 | 141.91 | 296.73 | 0.00 | 0.00 |
Maximum of Months | 2975.70 | 1929.83 | 2811.04 | 1477.39 | 1405.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.38 | 2706.46 | 425.83 | 0.00 | 425.83 | 0.00 | 0.00 |
February | 76.58 | 2398.21 | 662.61 | 0.00 | 662.61 | 0.00 | 0.00 |
March | 257.73 | 1940.33 | 976.25 | 0.00 | 976.25 | 0.00 | 0.00 |
April | 650.66 | 1557.73 | 1381.44 | 4.85 | 1376.59 | 0.00 | 0.00 |
May | 1048.21 | 1263.96 | 1777.50 | 52.68 | 1724.81 | 0.00 | 0.00 |
June | 1179.36 | 979.67 | 1868.93 | 123.23 | 1745.70 | 0.00 | 0.00 |
July | 1311.24 | 877.06 | 1776.27 | 139.05 | 1637.22 | 0.00 | 0.00 |
August | 1162.97 | 863.24 | 1437.93 | 38.72 | 1399.22 | 0.00 | 0.00 |
September | 649.93 | 1243.69 | 1117.05 | 0.32 | 1116.73 | 0.00 | 0.00 |
October | 239.60 | 1661.94 | 765.37 | 0.00 | 765.37 | 0.00 | 0.00 |
November | 36.38 | 2148.52 | 482.11 | 0.00 | 482.11 | 0.00 | 0.00 |
December | 3.47 | 2688.81 | 361.85 | 0.00 | 361.85 | 0.00 | 0.00 |
Annual Sum or Average | 554.85 | 1690.67 | 1088.19 | 30.13 | 1058.06 | 0.00 | 0.00 |
Minimum of Months | 3.47 | 863.24 | 361.85 | 0.00 | 361.85 | 0.00 | 0.00 |
Maximum of Months | 1311.24 | 2706.46 | 1868.93 | 139.05 | 1745.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 90.99 | 1721.73 | 456.19 | 115.68 | 340.51 | 0.00 | 0.00 |
February | 385.99 | 1493.97 | 837.04 | 297.10 | 539.95 | 0.00 | 0.00 |
March | 791.65 | 1224.84 | 1249.76 | 452.44 | 797.32 | 0.00 | 0.00 |
April | 1593.95 | 990.89 | 1937.40 | 805.07 | 1132.32 | 0.00 | 0.00 |
May | 1765.40 | 831.38 | 2061.32 | 716.58 | 1344.74 | 0.00 | 0.00 |
June | 2316.25 | 663.50 | 2468.53 | 1073.91 | 1394.62 | 0.00 | 0.00 |
July | 2268.00 | 574.93 | 2298.71 | 1031.61 | 1267.11 | 0.00 | 0.00 |
August | 2373.42 | 557.49 | 2259.57 | 1130.32 | 1129.24 | 0.00 | 0.00 |
September | 1524.03 | 789.60 | 1670.87 | 770.73 | 900.15 | 0.00 | 0.00 |
October | 775.64 | 1059.03 | 1088.94 | 462.70 | 626.25 | 0.00 | 0.00 |
November | 183.48 | 1369.88 | 533.76 | 150.70 | 383.06 | 0.00 | 0.00 |
December | 120.48 | 1712.62 | 437.82 | 140.96 | 296.85 | 0.00 | 0.00 |
Annual Sum or Average | 1186.55 | 1080.52 | 1444.32 | 596.96 | 847.36 | 0.00 | 0.00 |
Minimum of Months | 90.99 | 557.49 | 437.82 | 115.68 | 296.85 | 0.00 | 0.00 |
Maximum of Months | 2373.42 | 1721.73 | 2468.53 | 1130.32 | 1394.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1508.20 | 2433.94 | 1880.86 | 1116.62 | 764.24 | 0.00 | 0.00 |
February | 2586.13 | 2224.13 | 2893.49 | 1791.15 | 1102.34 | 0.00 | 0.00 |
March | 2717.20 | 1961.54 | 3113.69 | 1661.08 | 1452.62 | 0.00 | 0.00 |
April | 2670.63 | 1645.23 | 3286.43 | 1427.10 | 1859.33 | 0.00 | 0.00 |
May | 2218.72 | 1363.46 | 3004.35 | 894.73 | 2109.62 | 0.00 | 0.00 |
June | 1950.17 | 1087.74 | 2748.67 | 737.69 | 2010.98 | 0.00 | 0.00 |
July | 2394.86 | 977.60 | 2997.47 | 1097.50 | 1899.96 | 0.00 | 0.00 |
August | 2975.55 | 942.79 | 3220.71 | 1501.74 | 1718.97 | 0.00 | 0.00 |
September | 3434.95 | 1301.35 | 3569.82 | 1971.88 | 1597.94 | 0.00 | 0.00 |
October | 3154.57 | 1703.21 | 3233.49 | 1996.77 | 1236.72 | 0.00 | 0.00 |
November | 1630.41 | 2037.02 | 1910.85 | 1094.92 | 815.94 | 0.00 | 0.00 |
December | 1809.61 | 2493.41 | 1999.03 | 1293.42 | 705.62 | 0.00 | 0.00 |
Annual Sum or Average | 2419.55 | 1678.27 | 2820.35 | 1379.50 | 1440.85 | 0.00 | 0.00 |
Minimum of Months | 1508.20 | 942.79 | 1880.86 | 737.69 | 705.62 | 0.00 | 0.00 |
Maximum of Months | 3434.95 | 2493.41 | 3569.82 | 1996.77 | 2109.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 118.59 | 1779.99 | 481.18 | 141.91 | 339.26 | 0.00 | 0.00 |
February | 431.76 | 1577.42 | 862.69 | 324.25 | 538.45 | 0.00 | 0.00 |
March | 767.84 | 1313.39 | 1208.83 | 408.03 | 800.80 | 0.00 | 0.00 |
April | 1494.04 | 1095.26 | 1839.14 | 703.22 | 1135.92 | 0.00 | 0.00 |
May | 2163.52 | 919.85 | 2366.16 | 961.08 | 1405.09 | 0.00 | 0.00 |
June | 2112.90 | 733.90 | 2275.54 | 883.31 | 1392.22 | 0.00 | 0.00 |
July | 2970.89 | 684.80 | 2811.04 | 1477.39 | 1333.64 | 0.00 | 0.00 |
August | 2508.41 | 657.21 | 2325.71 | 1187.53 | 1138.18 | 0.00 | 0.00 |
September | 1836.51 | 884.61 | 1894.10 | 908.87 | 985.22 | 0.00 | 0.00 |
October | 784.56 | 1147.63 | 1078.26 | 439.34 | 638.93 | 0.00 | 0.00 |
November | 197.56 | 1443.75 | 537.00 | 151.48 | 385.52 | 0.00 | 0.00 |
December | 153.65 | 1804.27 | 451.47 | 154.73 | 296.73 | 0.00 | 0.00 |
Annual Sum or Average | 1300.85 | 1168.26 | 1514.88 | 647.55 | 867.33 | 0.00 | 0.00 |
Minimum of Months | 118.59 | 657.21 | 451.47 | 141.91 | 296.73 | 0.00 | 0.00 |
Maximum of Months | 2970.89 | 1804.27 | 2811.04 | 1477.39 | 1405.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 259275.07 | 0.911248E+10 | 0.114055E+10 | 0.00 | 0.114055E+10 | 0.00 | 0.00 |
February | 88114299.42 | 0.734086E+10 | 0.160298E+10 | 0.00 | 0.160298E+10 | 0.00 | 0.00 |
March | 0.440665E+09 | 0.654974E+10 | 0.261479E+10 | 0.00 | 0.261479E+10 | 0.00 | 0.00 |
April | 0.138301E+10 | 0.493209E+10 | 0.358070E+10 | 12573675.36 | 0.356812E+10 | 0.00 | 0.00 |
May | 0.260611E+10 | 0.390059E+10 | 0.476087E+10 | 0.141109E+09 | 0.461976E+10 | 0.00 | 0.00 |
June | 0.290064E+10 | 0.285766E+10 | 0.484429E+10 | 0.319423E+09 | 0.452487E+10 | 0.00 | 0.00 |
July | 0.336169E+10 | 0.265151E+10 | 0.475757E+10 | 0.372427E+09 | 0.438514E+10 | 0.00 | 0.00 |
August | 0.296552E+10 | 0.263410E+10 | 0.385138E+10 | 0.103700E+09 | 0.374768E+10 | 0.00 | 0.00 |
September | 0.151560E+10 | 0.379360E+10 | 0.289540E+10 | 826149.50 | 0.289457E+10 | 0.00 | 0.00 |
October | 0.406366E+09 | 0.568345E+10 | 0.204998E+10 | 0.00 | 0.204998E+10 | 0.00 | 0.00 |
November | 35089764.61 | 0.736558E+10 | 0.124963E+10 | 0.00 | 0.124963E+10 | 0.00 | 0.00 |
December | 0.00 | 0.935802E+10 | 0.969175E+09 | 0.00 | 0.969175E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.157031E+11 | 0.661797E+11 | 0.343173E+11 | 0.950059E+09 | 0.333672E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.263410E+10 | 0.969175E+09 | 0.00 | 0.969175E+09 | 0.00 | 0.00 |
Maximum of Months | 0.336169E+10 | 0.935802E+10 | 0.484429E+10 | 0.372427E+09 | 0.461976E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.192636E+09 | 0.562773E+10 | 0.122187E+10 | 0.309830E+09 | 0.912035E+09 | 0.00 | 0.00 |
February | 0.794336E+09 | 0.436284E+10 | 0.202499E+10 | 0.718746E+09 | 0.130624E+10 | 0.00 | 0.00 |
March | 0.195849E+10 | 0.391937E+10 | 0.334738E+10 | 0.121183E+10 | 0.213555E+10 | 0.00 | 0.00 |
April | 0.401256E+10 | 0.294226E+10 | 0.502175E+10 | 0.208676E+10 | 0.293499E+10 | 0.00 | 0.00 |
May | 0.464782E+10 | 0.248192E+10 | 0.552105E+10 | 0.191929E+10 | 0.360176E+10 | 0.00 | 0.00 |
June | 0.600819E+10 | 0.185518E+10 | 0.639846E+10 | 0.278358E+10 | 0.361488E+10 | 0.00 | 0.00 |
July | 0.607460E+10 | 0.164102E+10 | 0.615689E+10 | 0.276306E+10 | 0.339383E+10 | 0.00 | 0.00 |
August | 0.636635E+10 | 0.156638E+10 | 0.605205E+10 | 0.302747E+10 | 0.302458E+10 | 0.00 | 0.00 |
September | 0.388096E+10 | 0.232420E+10 | 0.433092E+10 | 0.199773E+10 | 0.233319E+10 | 0.00 | 0.00 |
October | 0.192812E+10 | 0.343713E+10 | 0.291664E+10 | 0.123929E+10 | 0.167735E+10 | 0.00 | 0.00 |
November | 0.388723E+09 | 0.444209E+10 | 0.138351E+10 | 0.390610E+09 | 0.992898E+09 | 0.00 | 0.00 |
December | 0.263587E+09 | 0.564142E+10 | 0.117265E+10 | 0.377560E+09 | 0.795089E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.365164E+11 | 0.402416E+11 | 0.455482E+11 | 0.188258E+11 | 0.267224E+11 | 0.00 | 0.00 |
Minimum of Months | 0.192636E+09 | 0.156638E+10 | 0.117265E+10 | 0.309830E+09 | 0.795089E+09 | 0.00 | 0.00 |
Maximum of Months | 0.636635E+10 | 0.564142E+10 | 0.639846E+10 | 0.302747E+10 | 0.361488E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.390068E+10 | 0.754799E+10 | 0.503771E+10 | 0.299077E+10 | 0.204695E+10 | 0.00 | 0.00 |
February | 0.608903E+10 | 0.615848E+10 | 0.699996E+10 | 0.433316E+10 | 0.266680E+10 | 0.00 | 0.00 |
March | 0.716301E+10 | 0.603702E+10 | 0.833974E+10 | 0.444904E+10 | 0.389070E+10 | 0.00 | 0.00 |
April | 0.677793E+10 | 0.481201E+10 | 0.851846E+10 | 0.369906E+10 | 0.481940E+10 | 0.00 | 0.00 |
May | 0.584182E+10 | 0.400447E+10 | 0.804689E+10 | 0.239646E+10 | 0.565043E+10 | 0.00 | 0.00 |
June | 0.497447E+10 | 0.307213E+10 | 0.712458E+10 | 0.191210E+10 | 0.521249E+10 | 0.00 | 0.00 |
July | 0.634237E+10 | 0.283895E+10 | 0.802844E+10 | 0.293956E+10 | 0.508888E+10 | 0.00 | 0.00 |
August | 0.791122E+10 | 0.272484E+10 | 0.862638E+10 | 0.402227E+10 | 0.460411E+10 | 0.00 | 0.00 |
September | 0.885599E+10 | 0.370691E+10 | 0.925301E+10 | 0.511113E+10 | 0.414188E+10 | 0.00 | 0.00 |
October | 0.835575E+10 | 0.523284E+10 | 0.866060E+10 | 0.534817E+10 | 0.331244E+10 | 0.00 | 0.00 |
November | 0.406038E+10 | 0.625543E+10 | 0.495295E+10 | 0.283803E+10 | 0.211492E+10 | 0.00 | 0.00 |
December | 0.468721E+10 | 0.785791E+10 | 0.535423E+10 | 0.346430E+10 | 0.188993E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.749599E+11 | 0.602490E+11 | 0.889430E+11 | 0.435041E+11 | 0.454389E+11 | 0.00 | 0.00 |
Minimum of Months | 0.390068E+10 | 0.272484E+10 | 0.495295E+10 | 0.191210E+10 | 0.188993E+10 | 0.00 | 0.00 |
Maximum of Months | 0.885599E+10 | 0.785791E+10 | 0.925301E+10 | 0.534817E+10 | 0.565043E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.268067E+09 | 0.599908E+10 | 0.128879E+10 | 0.380105E+09 | 0.908689E+09 | 0.00 | 0.00 |
February | 0.900038E+09 | 0.490483E+10 | 0.208703E+10 | 0.784422E+09 | 0.130261E+10 | 0.00 | 0.00 |
March | 0.183907E+10 | 0.462660E+10 | 0.323775E+10 | 0.109288E+10 | 0.214487E+10 | 0.00 | 0.00 |
April | 0.359164E+10 | 0.365007E+10 | 0.476706E+10 | 0.182275E+10 | 0.294431E+10 | 0.00 | 0.00 |
May | 0.566404E+10 | 0.284483E+10 | 0.633756E+10 | 0.257416E+10 | 0.376340E+10 | 0.00 | 0.00 |
June | 0.533067E+10 | 0.224922E+10 | 0.589821E+10 | 0.228955E+10 | 0.360866E+10 | 0.00 | 0.00 |
July | 0.782684E+10 | 0.217174E+10 | 0.752912E+10 | 0.395707E+10 | 0.357205E+10 | 0.00 | 0.00 |
August | 0.653866E+10 | 0.215090E+10 | 0.622921E+10 | 0.318069E+10 | 0.304852E+10 | 0.00 | 0.00 |
September | 0.463522E+10 | 0.270678E+10 | 0.490953E+10 | 0.235581E+10 | 0.255371E+10 | 0.00 | 0.00 |
October | 0.190268E+10 | 0.400669E+10 | 0.288803E+10 | 0.117672E+10 | 0.171130E+10 | 0.00 | 0.00 |
November | 0.410749E+09 | 0.515047E+10 | 0.139191E+10 | 0.392635E+09 | 0.999279E+09 | 0.00 | 0.00 |
December | 0.328009E+09 | 0.660932E+10 | 0.120922E+10 | 0.414444E+09 | 0.794778E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.392357E+11 | 0.470705E+11 | 0.477734E+11 | 0.204213E+11 | 0.273522E+11 | 0.00 | 0.00 |
Minimum of Months | 0.268067E+09 | 0.215090E+10 | 0.120922E+10 | 0.380105E+09 | 0.794778E+09 | 0.00 | 0.00 |
Maximum of Months | 0.782684E+10 | 0.660932E+10 | 0.752912E+10 | 0.395707E+10 | 0.376340E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 4651350.86 | 0.775574E+10 | 0.114055E+10 | 0.00 | 0.114055E+10 | 0.00 | 0.00 |
February | 0.149022E+09 | 0.629075E+10 | 0.160298E+10 | 0.00 | 0.160298E+10 | 0.00 | 0.00 |
March | 0.602083E+09 | 0.565308E+10 | 0.261478E+10 | 0.00 | 0.261478E+10 | 0.00 | 0.00 |
April | 0.159614E+10 | 0.431286E+10 | 0.358068E+10 | 12573630.71 | 0.356811E+10 | 0.00 | 0.00 |
May | 0.274663E+10 | 0.357202E+10 | 0.476085E+10 | 0.141109E+09 | 0.461974E+10 | 0.00 | 0.00 |
June | 0.304173E+10 | 0.262053E+10 | 0.484427E+10 | 0.319422E+09 | 0.452485E+10 | 0.00 | 0.00 |
July | 0.351865E+10 | 0.240948E+10 | 0.475755E+10 | 0.372426E+09 | 0.438512E+10 | 0.00 | 0.00 |
August | 0.310983E+10 | 0.239059E+10 | 0.385136E+10 | 0.103699E+09 | 0.374766E+10 | 0.00 | 0.00 |
September | 0.162244E+10 | 0.345247E+10 | 0.289539E+10 | 826146.56 | 0.289456E+10 | 0.00 | 0.00 |
October | 0.543966E+09 | 0.490462E+10 | 0.204997E+10 | 0.00 | 0.204997E+10 | 0.00 | 0.00 |
November | 69149787.95 | 0.617392E+10 | 0.124963E+10 | 0.00 | 0.124963E+10 | 0.00 | 0.00 |
December | 1972862.73 | 0.786342E+10 | 0.969171E+09 | 0.00 | 0.969171E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.170063E+11 | 0.573995E+11 | 0.343172E+11 | 0.950056E+09 | 0.333671E+11 | 0.00 | 0.00 |
Minimum of Months | 1972862.73 | 0.239059E+10 | 0.969171E+09 | 0.00 | 0.969171E+09 | 0.00 | 0.00 |
Maximum of Months | 0.351865E+10 | 0.786342E+10 | 0.484427E+10 | 0.372426E+09 | 0.461974E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.223458E+09 | 0.491147E+10 | 0.122186E+10 | 0.309829E+09 | 0.912032E+09 | 0.00 | 0.00 |
February | 0.876118E+09 | 0.389335E+10 | 0.202498E+10 | 0.718743E+09 | 0.130624E+10 | 0.00 | 0.00 |
March | 0.205087E+10 | 0.352665E+10 | 0.334736E+10 | 0.121183E+10 | 0.213554E+10 | 0.00 | 0.00 |
April | 0.407501E+10 | 0.271212E+10 | 0.502173E+10 | 0.208675E+10 | 0.293498E+10 | 0.00 | 0.00 |
May | 0.469741E+10 | 0.231918E+10 | 0.552103E+10 | 0.191929E+10 | 0.360174E+10 | 0.00 | 0.00 |
June | 0.601009E+10 | 0.175565E+10 | 0.639844E+10 | 0.278357E+10 | 0.361487E+10 | 0.00 | 0.00 |
July | 0.608598E+10 | 0.156152E+10 | 0.615687E+10 | 0.276305E+10 | 0.339382E+10 | 0.00 | 0.00 |
August | 0.636339E+10 | 0.152438E+10 | 0.605202E+10 | 0.302746E+10 | 0.302457E+10 | 0.00 | 0.00 |
September | 0.391895E+10 | 0.215930E+10 | 0.433091E+10 | 0.199772E+10 | 0.233318E+10 | 0.00 | 0.00 |
October | 0.200492E+10 | 0.307380E+10 | 0.291663E+10 | 0.123929E+10 | 0.167734E+10 | 0.00 | 0.00 |
November | 0.440157E+09 | 0.389133E+10 | 0.138350E+10 | 0.390608E+09 | 0.992894E+09 | 0.00 | 0.00 |
December | 0.296828E+09 | 0.497585E+10 | 0.117264E+10 | 0.377558E+09 | 0.795086E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.370432E+11 | 0.363046E+11 | 0.455480E+11 | 0.188257E+11 | 0.267223E+11 | 0.00 | 0.00 |
Minimum of Months | 0.223458E+09 | 0.152438E+10 | 0.117264E+10 | 0.309829E+09 | 0.795086E+09 | 0.00 | 0.00 |
Maximum of Months | 0.636339E+10 | 0.497585E+10 | 0.639844E+10 | 0.302746E+10 | 0.361487E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.395033E+10 | 0.699184E+10 | 0.503770E+10 | 0.299076E+10 | 0.204694E+10 | 0.00 | 0.00 |
February | 0.613303E+10 | 0.581522E+10 | 0.699993E+10 | 0.433314E+10 | 0.266679E+10 | 0.00 | 0.00 |
March | 0.718691E+10 | 0.566801E+10 | 0.833971E+10 | 0.444902E+10 | 0.389069E+10 | 0.00 | 0.00 |
April | 0.683737E+10 | 0.452113E+10 | 0.851843E+10 | 0.369905E+10 | 0.481938E+10 | 0.00 | 0.00 |
May | 0.588130E+10 | 0.383346E+10 | 0.804686E+10 | 0.239646E+10 | 0.565041E+10 | 0.00 | 0.00 |
June | 0.503639E+10 | 0.290850E+10 | 0.712456E+10 | 0.191209E+10 | 0.521247E+10 | 0.00 | 0.00 |
July | 0.640902E+10 | 0.268148E+10 | 0.802841E+10 | 0.293955E+10 | 0.508886E+10 | 0.00 | 0.00 |
August | 0.795697E+10 | 0.260562E+10 | 0.862635E+10 | 0.402226E+10 | 0.460409E+10 | 0.00 | 0.00 |
September | 0.884939E+10 | 0.358353E+10 | 0.925297E+10 | 0.511111E+10 | 0.414186E+10 | 0.00 | 0.00 |
October | 0.834887E+10 | 0.495332E+10 | 0.866057E+10 | 0.534815E+10 | 0.331243E+10 | 0.00 | 0.00 |
November | 0.411826E+10 | 0.578367E+10 | 0.495293E+10 | 0.283802E+10 | 0.211491E+10 | 0.00 | 0.00 |
December | 0.474770E+10 | 0.725602E+10 | 0.535421E+10 | 0.346429E+10 | 0.188992E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.754555E+11 | 0.566018E+11 | 0.889426E+11 | 0.435039E+11 | 0.454387E+11 | 0.00 | 0.00 |
Minimum of Months | 0.395033E+10 | 0.260562E+10 | 0.495293E+10 | 0.191209E+10 | 0.188992E+10 | 0.00 | 0.00 |
Maximum of Months | 0.884939E+10 | 0.725602E+10 | 0.925297E+10 | 0.534815E+10 | 0.565041E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.304586E+09 | 0.505829E+10 | 0.128879E+10 | 0.380104E+09 | 0.908685E+09 | 0.00 | 0.00 |
February | 0.100901E+10 | 0.406346E+10 | 0.208703E+10 | 0.784419E+09 | 0.130261E+10 | 0.00 | 0.00 |
March | 0.201552E+10 | 0.375363E+10 | 0.323774E+10 | 0.109288E+10 | 0.214486E+10 | 0.00 | 0.00 |
April | 0.383190E+10 | 0.298975E+10 | 0.476704E+10 | 0.182274E+10 | 0.294430E+10 | 0.00 | 0.00 |
May | 0.577224E+10 | 0.257390E+10 | 0.633753E+10 | 0.257415E+10 | 0.376338E+10 | 0.00 | 0.00 |
June | 0.547775E+10 | 0.196129E+10 | 0.589819E+10 | 0.228954E+10 | 0.360865E+10 | 0.00 | 0.00 |
July | 0.797010E+10 | 0.187884E+10 | 0.752909E+10 | 0.395705E+10 | 0.357203E+10 | 0.00 | 0.00 |
August | 0.671943E+10 | 0.181237E+10 | 0.622919E+10 | 0.318068E+10 | 0.304851E+10 | 0.00 | 0.00 |
September | 0.473225E+10 | 0.242002E+10 | 0.490951E+10 | 0.235580E+10 | 0.255370E+10 | 0.00 | 0.00 |
October | 0.205297E+10 | 0.330310E+10 | 0.288801E+10 | 0.117672E+10 | 0.171130E+10 | 0.00 | 0.00 |
November | 0.487839E+09 | 0.403149E+10 | 0.139191E+10 | 0.392633E+09 | 0.999275E+09 | 0.00 | 0.00 |
December | 0.395138E+09 | 0.516885E+10 | 0.120922E+10 | 0.414442E+09 | 0.794775E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.407687E+11 | 0.390150E+11 | 0.477732E+11 | 0.204212E+11 | 0.273521E+11 | 0.00 | 0.00 |
Minimum of Months | 0.304586E+09 | 0.181237E+10 | 0.120922E+10 | 0.380104E+09 | 0.794775E+09 | 0.00 | 0.00 |
Maximum of Months | 0.797010E+10 | 0.516885E+10 | 0.752909E+10 | 0.395705E+10 | 0.376338E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 14408987.90 | 0.724899E+10 | 0.114055E+10 | 0.00 | 0.114055E+10 | 0.00 | 0.00 |
February | 0.185255E+09 | 0.580176E+10 | 0.160298E+10 | 0.00 | 0.160298E+10 | 0.00 | 0.00 |
March | 0.690300E+09 | 0.519699E+10 | 0.261478E+10 | 0.00 | 0.261478E+10 | 0.00 | 0.00 |
April | 0.168651E+10 | 0.403763E+10 | 0.358068E+10 | 12573630.71 | 0.356811E+10 | 0.00 | 0.00 |
May | 0.280753E+10 | 0.338538E+10 | 0.476085E+10 | 0.141109E+09 | 0.461974E+10 | 0.00 | 0.00 |
June | 0.305691E+10 | 0.253929E+10 | 0.484427E+10 | 0.319422E+09 | 0.452485E+10 | 0.00 | 0.00 |
July | 0.351202E+10 | 0.234911E+10 | 0.475755E+10 | 0.372426E+09 | 0.438512E+10 | 0.00 | 0.00 |
August | 0.311491E+10 | 0.231210E+10 | 0.385136E+10 | 0.103699E+09 | 0.374766E+10 | 0.00 | 0.00 |
September | 0.168461E+10 | 0.322364E+10 | 0.289539E+10 | 826146.56 | 0.289456E+10 | 0.00 | 0.00 |
October | 0.641749E+09 | 0.445133E+10 | 0.204997E+10 | 0.00 | 0.204997E+10 | 0.00 | 0.00 |
November | 94293881.38 | 0.556896E+10 | 0.124963E+10 | 0.00 | 0.124963E+10 | 0.00 | 0.00 |
December | 9294303.82 | 0.720172E+10 | 0.969171E+09 | 0.00 | 0.969171E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.174978E+11 | 0.533169E+11 | 0.343172E+11 | 0.950056E+09 | 0.333671E+11 | 0.00 | 0.00 |
Minimum of Months | 9294303.82 | 0.231210E+10 | 0.969171E+09 | 0.00 | 0.969171E+09 | 0.00 | 0.00 |
Maximum of Months | 0.351202E+10 | 0.724899E+10 | 0.484427E+10 | 0.372426E+09 | 0.461974E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.243710E+09 | 0.461148E+10 | 0.122186E+10 | 0.309829E+09 | 0.912032E+09 | 0.00 | 0.00 |
February | 0.933780E+09 | 0.361420E+10 | 0.202498E+10 | 0.718743E+09 | 0.130624E+10 | 0.00 | 0.00 |
March | 0.212034E+10 | 0.328061E+10 | 0.334736E+10 | 0.121183E+10 | 0.213554E+10 | 0.00 | 0.00 |
April | 0.413151E+10 | 0.256838E+10 | 0.502173E+10 | 0.208675E+10 | 0.293498E+10 | 0.00 | 0.00 |
May | 0.472845E+10 | 0.222677E+10 | 0.552103E+10 | 0.191929E+10 | 0.360174E+10 | 0.00 | 0.00 |
June | 0.600372E+10 | 0.171979E+10 | 0.639844E+10 | 0.278357E+10 | 0.361487E+10 | 0.00 | 0.00 |
July | 0.607461E+10 | 0.153990E+10 | 0.615687E+10 | 0.276305E+10 | 0.339382E+10 | 0.00 | 0.00 |
August | 0.635697E+10 | 0.149318E+10 | 0.605202E+10 | 0.302746E+10 | 0.302457E+10 | 0.00 | 0.00 |
September | 0.395027E+10 | 0.204665E+10 | 0.433091E+10 | 0.199772E+10 | 0.233318E+10 | 0.00 | 0.00 |
October | 0.207746E+10 | 0.283652E+10 | 0.291663E+10 | 0.123929E+10 | 0.167734E+10 | 0.00 | 0.00 |
November | 0.475569E+09 | 0.355072E+10 | 0.138350E+10 | 0.390608E+09 | 0.992894E+09 | 0.00 | 0.00 |
December | 0.322684E+09 | 0.458709E+10 | 0.117264E+10 | 0.377558E+09 | 0.795086E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.374191E+11 | 0.340753E+11 | 0.455480E+11 | 0.188257E+11 | 0.267223E+11 | 0.00 | 0.00 |
Minimum of Months | 0.243710E+09 | 0.149318E+10 | 0.117264E+10 | 0.309829E+09 | 0.795086E+09 | 0.00 | 0.00 |
Maximum of Months | 0.635697E+10 | 0.461148E+10 | 0.639844E+10 | 0.302746E+10 | 0.361487E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.403957E+10 | 0.651905E+10 | 0.503770E+10 | 0.299076E+10 | 0.204694E+10 | 0.00 | 0.00 |
February | 0.625636E+10 | 0.538062E+10 | 0.699993E+10 | 0.433314E+10 | 0.266679E+10 | 0.00 | 0.00 |
March | 0.727776E+10 | 0.525379E+10 | 0.833971E+10 | 0.444902E+10 | 0.389069E+10 | 0.00 | 0.00 |
April | 0.692226E+10 | 0.426445E+10 | 0.851843E+10 | 0.369905E+10 | 0.481938E+10 | 0.00 | 0.00 |
May | 0.594263E+10 | 0.365189E+10 | 0.804686E+10 | 0.239646E+10 | 0.565041E+10 | 0.00 | 0.00 |
June | 0.505485E+10 | 0.281941E+10 | 0.712456E+10 | 0.191209E+10 | 0.521247E+10 | 0.00 | 0.00 |
July | 0.641439E+10 | 0.261839E+10 | 0.802841E+10 | 0.293955E+10 | 0.508886E+10 | 0.00 | 0.00 |
August | 0.796971E+10 | 0.252518E+10 | 0.862635E+10 | 0.402226E+10 | 0.460409E+10 | 0.00 | 0.00 |
September | 0.890338E+10 | 0.337309E+10 | 0.925297E+10 | 0.511111E+10 | 0.414186E+10 | 0.00 | 0.00 |
October | 0.844921E+10 | 0.456189E+10 | 0.866057E+10 | 0.534815E+10 | 0.331243E+10 | 0.00 | 0.00 |
November | 0.422601E+10 | 0.527996E+10 | 0.495293E+10 | 0.283802E+10 | 0.211491E+10 | 0.00 | 0.00 |
December | 0.484686E+10 | 0.667834E+10 | 0.535421E+10 | 0.346429E+10 | 0.188992E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.763030E+11 | 0.529261E+11 | 0.889426E+11 | 0.435039E+11 | 0.454387E+11 | 0.00 | 0.00 |
Minimum of Months | 0.403957E+10 | 0.252518E+10 | 0.495293E+10 | 0.191209E+10 | 0.188992E+10 | 0.00 | 0.00 |
Maximum of Months | 0.890338E+10 | 0.667834E+10 | 0.925297E+10 | 0.534815E+10 | 0.565041E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.317632E+09 | 0.476752E+10 | 0.128879E+10 | 0.380104E+09 | 0.908685E+09 | 0.00 | 0.00 |
February | 0.104452E+10 | 0.381609E+10 | 0.208703E+10 | 0.784419E+09 | 0.130261E+10 | 0.00 | 0.00 |
March | 0.205659E+10 | 0.351778E+10 | 0.323774E+10 | 0.109288E+10 | 0.214486E+10 | 0.00 | 0.00 |
April | 0.387256E+10 | 0.283892E+10 | 0.476704E+10 | 0.182274E+10 | 0.294430E+10 | 0.00 | 0.00 |
May | 0.579477E+10 | 0.246372E+10 | 0.633753E+10 | 0.257415E+10 | 0.376338E+10 | 0.00 | 0.00 |
June | 0.547663E+10 | 0.190228E+10 | 0.589819E+10 | 0.228954E+10 | 0.360865E+10 | 0.00 | 0.00 |
July | 0.795724E+10 | 0.183418E+10 | 0.752909E+10 | 0.395705E+10 | 0.357203E+10 | 0.00 | 0.00 |
August | 0.671854E+10 | 0.176027E+10 | 0.622919E+10 | 0.318068E+10 | 0.304851E+10 | 0.00 | 0.00 |
September | 0.476023E+10 | 0.229290E+10 | 0.490951E+10 | 0.235580E+10 | 0.255370E+10 | 0.00 | 0.00 |
October | 0.210137E+10 | 0.307381E+10 | 0.288801E+10 | 0.117672E+10 | 0.171130E+10 | 0.00 | 0.00 |
November | 0.512070E+09 | 0.374221E+10 | 0.139191E+10 | 0.392633E+09 | 0.999275E+09 | 0.00 | 0.00 |
December | 0.411543E+09 | 0.483256E+10 | 0.120922E+10 | 0.414442E+09 | 0.794775E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.410237E+11 | 0.368422E+11 | 0.477732E+11 | 0.204212E+11 | 0.273521E+11 | 0.00 | 0.00 |
Minimum of Months | 0.317632E+09 | 0.176027E+10 | 0.120922E+10 | 0.380104E+09 | 0.794775E+09 | 0.00 | 0.00 |
Maximum of Months | 0.795724E+10 | 0.483256E+10 | 0.752909E+10 | 0.395705E+10 | 0.376338E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.11 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.09 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.03 | 5.25 | 4.23 | 1.21 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.01 | 7.49 | 3.85 | 3.74 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.79 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.40 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.56 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.54 | 10.74 | 2.23 | 5.46 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.18 | 7.19 | 4.02 | 2.09 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.12 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.11 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.56 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.48 | 7.20 | 8.40 | 3.88 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.15 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.40 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.20 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.35 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.72 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.76 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.67 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.67 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.47 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.93 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.42 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.42 | 0.00 | 0.00 | 3.88 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.76 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -1.9 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.18 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.56 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.56 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.48 | 11-JAN-21:00 | 11.10 | 10.00 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 12.41 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.44 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.27 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.57 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.72 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.16 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.12 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.96 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.04 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.70 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.48 | 11.10 | 6.70 | 0.00 | 6.35 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 28.90 | 15.70 | 6.70 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.48 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.34 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.09 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.76 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.92 | 2.10 | 6.88 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.00 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.09 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHWSYS1 WATER HEATER
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.253870E+11 | -.379299E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.129063E+10 | 67.74 | 0.00 | 0.00 |
February | 0.234214E+11 | -.347239E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.116137E+10 | 67.61 | 0.00 | 0.00 |
March | 0.279324E+11 | -.403597E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.125654E+10 | 66.61 | 0.00 | 0.00 |
April | 0.233749E+11 | -.356096E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.123465E+10 | 67.39 | 0.00 | 0.00 |
May | 0.239569E+11 | -.366080E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.127794E+10 | 67.41 | 0.00 | 0.00 |
June | 0.226319E+11 | -.349275E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.122541E+10 | 67.01 | 0.00 | 0.00 |
July | 0.193961E+11 | -.323111E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.129587E+10 | 68.17 | 0.00 | 0.00 |
August | 0.222996E+11 | -.350707E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.126842E+10 | 67.11 | 0.00 | 0.00 |
September | 0.197865E+11 | -.322399E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.124214E+10 | 67.67 | 0.00 | 0.00 |
October | 0.215301E+11 | -.343111E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.129326E+10 | 68.02 | 0.00 | 0.00 |
November | 0.227661E+11 | -.350098E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.125242E+10 | 68.04 | 0.00 | 0.00 |
December | 0.234721E+11 | -.361390E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.128876E+10 | 67.82 | 0.00 | 0.00 |
Annual Sum or Average | 0.275955E+12 | -.425240E+12 | 8760.00 | -.150874E+11 | 67.55 | |||||
Minimum of Months | 0.193961E+11 | -.403597E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.129587E+10 | 66.61 | 0.00 | 0.00 |
Maximum of Months | 0.279324E+11 | -.322399E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.116137E+10 | 68.17 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-09:00 | 2754.17 | 32.56 | 224.33 | 219.67 | 2172.58 | 33.67 | 226.67 | 187.33 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-08:39 | 4683.75 | 33.53 | 245.83 | 244.00 | 2037.56 | 29.24 | 224.00 | 219.00 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:40 | 7758.02 | 33.50 | 209.67 | 313.00 | 1667.04 | 22.67 | 202.83 | 267.83 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:10 | 2221.02 | 20.30 | 166.00 | 345.33 | 1217.70 | 21.72 | 247.33 | 308.33 |
May | 427.83 | 0.52 | 0.48 | 01-MAY-07:19 | 2041.29 | 20.16 | 155.67 | 386.00 | 1104.98 | 21.54 | 275.83 | 344.67 |
June | 375.17 | 0.53 | 0.48 | 01-JUN-06:10 | 1792.30 | 19.70 | 106.00 | 396.33 | 1021.41 | 21.11 | 262.83 | 346.17 |
July | 471.00 | 0.55 | 0.48 | 01-JUL-05:49 | 1593.83 | 18.53 | 113.00 | 395.67 | 927.66 | 19.92 | 189.33 | 341.00 |
August | 366.67 | 0.53 | 0.48 | 01-AUG-06:10 | 1883.44 | 19.58 | 113.67 | 374.50 | 1116.75 | 20.99 | 207.33 | 328.50 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 3014.12 | 22.33 | 141.17 | 320.17 | 1468.59 | 22.49 | 225.17 | 288.17 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:00 | 7200.64 | 34.94 | 223.83 | 285.00 | 1943.54 | 23.85 | 185.33 | 256.17 |
November | 242.67 | 0.51 | 0.48 | 01-NOV-08:20 | 3069.36 | 32.11 | 226.67 | 225.17 | 2439.02 | 33.29 | 230.50 | 194.00 |
December | 160.33 | 0.51 | 0.48 | 01-DEC-09:39 | 3696.99 | 35.78 | 149.50 | 207.33 | 3108.48 | 37.04 | 149.67 | 167.00 |
Annual Sum or Average | 3714.00 | 0.52 | 3130.99 | 25.09 | 2075.33 | 3712.17 | 1516.17 | 24.31 | 2626.83 | 3248.17 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 1593.83 | 18.53 | 106.00 | 207.33 | 927.66 | 19.92 | 149.67 | 167.00 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 7758.02 | 35.78 | 245.83 | 396.33 | 3108.48 | 37.04 | 275.83 | 346.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 01-JAN-10:09 | 933.79 | 21.17 | 70.17 | 200.67 | 573.83 | 22.50 | 93.50 | 132.33 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-08:39 | 1524.58 | 23.16 | 97.67 | 228.67 | 795.62 | 23.29 | 134.67 | 182.17 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-07:30 | 2743.31 | 25.59 | 116.50 | 304.17 | 1201.89 | 24.46 | 157.33 | 256.17 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 2863.78 | 24.30 | 145.83 | 348.00 | 1595.49 | 24.66 | 226.83 | 308.83 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-06:00 | 2943.91 | 23.60 | 158.17 | 391.50 | 1287.40 | 23.36 | 243.67 | 352.17 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:10 | 3095.65 | 23.50 | 106.50 | 404.33 | 1698.08 | 23.94 | 203.33 | 359.33 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-04:00 | 2909.04 | 23.72 | 168.67 | 410.83 | 1318.83 | 23.29 | 216.17 | 373.67 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:30 | 3385.40 | 24.39 | 127.33 | 379.50 | 1477.12 | 23.67 | 174.83 | 340.50 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2779.20 | 24.15 | 97.83 | 323.83 | 1544.03 | 24.49 | 161.33 | 286.33 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-07:49 | 2515.94 | 25.20 | 107.83 | 272.00 | 1103.41 | 24.01 | 138.33 | 227.83 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-08:09 | 1158.80 | 22.41 | 87.67 | 208.33 | 602.51 | 22.56 | 92.17 | 147.33 |
December | 160.33 | 0.55 | 0.48 | 01-DEC-09:39 | 1094.24 | 23.38 | 64.50 | 185.83 | 588.07 | 23.31 | 71.00 | 107.67 |
Annual Sum or Average | 3714.00 | 0.52 | 2510.87 | 23.76 | 1348.67 | 3657.67 | 1231.06 | 23.67 | 1913.17 | 3074.33 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 933.79 | 21.17 | 64.50 | 185.83 | 573.83 | 22.50 | 71.00 | 107.67 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 3385.40 | 25.59 | 168.67 | 410.83 | 1698.08 | 24.66 | 243.67 | 373.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.59 | 0.48 | 03-JAN-10:30 | 506.99 | 15.98 | 0.00 | 179.67 | 276.29 | 17.31 | 0.00 | 54.33 |
February | 259.50 | 0.55 | 0.48 | 01-FEB-11:09 | 645.09 | 17.17 | 0.00 | 215.50 | 364.88 | 18.58 | 1.17 | 132.33 |
March | 247.00 | 0.53 | 0.48 | 01-MAR-08:39 | 872.24 | 18.59 | 0.00 | 298.67 | 516.85 | 20.04 | 63.00 | 218.50 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:19 | 1022.27 | 19.27 | 0.50 | 349.00 | 592.53 | 20.61 | 154.67 | 302.50 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:19 | 1254.91 | 21.37 | 91.83 | 399.67 | 720.34 | 22.09 | 270.33 | 365.33 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:40 | 1333.96 | 22.43 | 124.00 | 413.83 | 759.16 | 22.42 | 257.67 | 381.00 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-05:10 | 1125.95 | 21.58 | 124.00 | 423.50 | 648.48 | 21.50 | 227.33 | 378.50 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:00 | 977.87 | 19.31 | 14.00 | 388.83 | 610.81 | 20.66 | 125.50 | 345.67 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:49 | 950.38 | 19.37 | 0.00 | 314.17 | 576.65 | 20.80 | 95.00 | 257.83 |
October | 245.33 | 0.55 | 0.48 | 01-OCT-08:39 | 708.11 | 17.65 | 0.00 | 260.67 | 428.71 | 19.17 | 10.50 | 171.50 |
November | 242.67 | 0.58 | 0.48 | 01-NOV-11:39 | 546.33 | 16.30 | 0.00 | 193.33 | 297.79 | 17.58 | 0.17 | 70.83 |
December | 160.33 | 0.61 | 0.48 | 01-DEC-10:20 | 475.57 | 15.99 | 0.00 | 155.50 | 277.33 | 17.58 | 0.00 | 41.67 |
Annual Sum or Average | 3714.00 | 0.53 | 938.71 | 19.29 | 354.33 | 3592.33 | 546.82 | 20.28 | 1205.33 | 2720.00 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 475.57 | 15.98 | 0.00 | 155.50 | 276.29 | 17.31 | 0.00 | 41.67 | |
Maximum of Months | 471.00 | 0.61 | 0.48 | 1333.96 | 22.43 | 124.00 | 423.50 | 759.16 | 22.42 | 270.33 | 381.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 01-JAN-13:20 | 1062.83 | 22.52 | 87.17 | 202.00 | 566.13 | 22.63 | 93.17 | 139.00 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-09:30 | 1509.65 | 23.13 | 93.83 | 232.17 | 775.83 | 23.20 | 124.83 | 184.50 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-08:39 | 2399.44 | 24.37 | 111.50 | 306.67 | 1282.45 | 24.56 | 150.33 | 254.00 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:49 | 2867.43 | 23.16 | 131.33 | 345.83 | 1253.80 | 22.60 | 206.00 | 308.83 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-08:09 | 2973.72 | 20.71 | 84.83 | 392.67 | 1593.27 | 20.91 | 217.83 | 357.50 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-06:19 | 3034.11 | 20.29 | 50.50 | 403.67 | 1372.29 | 20.66 | 184.33 | 363.17 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-09:00 | 3326.51 | 19.54 | 73.67 | 405.00 | 1462.18 | 19.60 | 152.67 | 364.00 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-06:49 | 3175.03 | 21.96 | 92.17 | 383.83 | 1826.61 | 22.64 | 157.00 | 346.00 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-08:09 | 3510.59 | 25.41 | 123.00 | 316.50 | 1952.50 | 25.47 | 177.83 | 274.33 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:00 | 2420.74 | 25.88 | 116.00 | 274.50 | 1078.23 | 24.66 | 151.50 | 228.00 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-10:20 | 1129.20 | 22.00 | 78.67 | 210.17 | 589.92 | 22.08 | 90.00 | 143.17 |
December | 160.33 | 0.55 | 0.48 | 01-DEC-10:09 | 1115.51 | 22.52 | 55.67 | 185.83 | 591.57 | 22.51 | 65.50 | 103.67 |
Annual Sum or Average | 3714.00 | 0.52 | 2576.99 | 22.31 | 1098.33 | 3658.83 | 1285.42 | 22.34 | 1771.00 | 3066.17 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 1062.83 | 19.54 | 50.50 | 185.83 | 566.13 | 19.60 | 65.50 | 103.67 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 3510.59 | 25.88 | 131.33 | 405.00 | 1952.50 | 25.47 | 217.83 | 364.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-09:00 | 2759.16 | 31.98 | 220.17 | 219.67 | 2234.52 | 33.11 | 221.33 | 190.33 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-08:39 | 4707.80 | 32.95 | 238.67 | 244.50 | 2130.85 | 27.43 | 156.50 | 223.17 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:40 | 7799.09 | 32.28 | 208.50 | 313.17 | 1779.05 | 17.90 | 8.33 | 272.17 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:10 | 2252.11 | 13.71 | 0.00 | 345.67 | 1301.27 | 17.21 | 0.67 | 312.50 |
May | 427.83 | 0.52 | 0.48 | 01-MAY-07:19 | 2066.99 | 13.71 | 0.00 | 386.67 | 1178.44 | 17.16 | 0.00 | 349.67 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-06:10 | 1824.43 | 13.57 | 0.00 | 396.50 | 1091.60 | 17.03 | 0.00 | 351.83 |
July | 471.00 | 0.54 | 0.48 | 01-JUL-05:40 | 1627.00 | 12.19 | 0.00 | 396.33 | 993.77 | 15.68 | 0.00 | 348.50 |
August | 366.67 | 0.53 | 0.48 | 01-AUG-06:10 | 1927.39 | 13.29 | 0.00 | 374.83 | 1199.57 | 16.85 | 1.17 | 333.00 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 3062.06 | 16.33 | 27.00 | 320.33 | 1575.11 | 18.06 | 10.17 | 292.00 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:00 | 7243.89 | 34.03 | 220.33 | 285.00 | 2055.05 | 19.29 | 26.17 | 258.83 |
November | 242.67 | 0.51 | 0.48 | 01-NOV-08:20 | 3082.55 | 31.48 | 221.33 | 225.50 | 2502.96 | 32.75 | 226.00 | 197.50 |
December | 160.33 | 0.51 | 0.48 | 01-DEC-09:39 | 3714.85 | 34.94 | 149.17 | 207.67 | 3196.68 | 36.41 | 149.67 | 171.17 |
Annual Sum or Average | 3714.00 | 0.52 | 3162.03 | 20.84 | 1285.17 | 3715.83 | 1598.74 | 20.79 | 800.00 | 3300.67 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 1627.00 | 12.19 | 0.00 | 207.67 | 993.77 | 15.68 | 0.00 | 171.17 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 7799.09 | 34.94 | 238.67 | 396.50 | 3196.68 | 36.41 | 226.00 | 351.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 01-JAN-10:09 | 950.09 | 18.29 | 61.33 | 202.33 | 597.89 | 20.60 | 71.33 | 138.67 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-08:30 | 1551.05 | 20.44 | 81.00 | 230.33 | 832.25 | 21.23 | 60.50 | 188.17 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-07:30 | 2792.09 | 23.07 | 91.50 | 304.67 | 1261.03 | 22.28 | 51.00 | 261.00 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 2914.16 | 21.44 | 118.33 | 348.83 | 1660.60 | 22.46 | 91.67 | 313.83 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-06:00 | 2986.94 | 20.33 | 132.50 | 393.00 | 1352.60 | 20.87 | 79.50 | 357.00 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:10 | 3146.66 | 20.32 | 98.83 | 405.33 | 1776.88 | 21.50 | 73.67 | 364.67 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-04:00 | 2950.78 | 19.98 | 148.50 | 411.00 | 1384.32 | 20.84 | 99.33 | 379.83 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:30 | 3440.88 | 21.46 | 116.33 | 380.67 | 1550.53 | 21.12 | 66.50 | 345.67 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2833.34 | 21.27 | 84.33 | 324.17 | 1608.63 | 22.26 | 61.17 | 290.50 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-07:49 | 2556.19 | 22.82 | 93.33 | 273.33 | 1155.41 | 21.95 | 57.00 | 232.33 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-08:09 | 1178.17 | 19.72 | 78.83 | 210.17 | 629.52 | 20.49 | 62.50 | 155.17 |
December | 160.33 | 0.54 | 0.48 | 01-DEC-09:39 | 1112.90 | 20.95 | 56.33 | 186.83 | 615.31 | 21.55 | 52.17 | 114.50 |
Annual Sum or Average | 3714.00 | 0.52 | 2552.15 | 20.80 | 1161.17 | 3670.67 | 1288.38 | 21.41 | 826.33 | 3141.33 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 950.09 | 18.29 | 56.33 | 186.83 | 597.89 | 20.49 | 51.00 | 114.50 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 3440.88 | 23.07 | 148.50 | 411.00 | 1776.88 | 22.46 | 99.33 | 379.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.59 | 0.48 | 02-JAN-11:30 | 512.13 | 9.38 | 0.00 | 180.17 | 293.10 | 12.90 | 0.00 | 68.33 |
February | 259.50 | 0.55 | 0.48 | 01-FEB-09:30 | 653.09 | 10.94 | 0.00 | 216.33 | 387.58 | 14.48 | 0.00 | 143.17 |
March | 247.00 | 0.53 | 0.48 | 01-MAR-08:30 | 886.19 | 12.83 | 0.00 | 298.83 | 549.88 | 16.35 | 0.00 | 229.50 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:19 | 1039.06 | 13.54 | 0.00 | 349.00 | 630.74 | 16.98 | 0.00 | 310.00 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:19 | 1291.77 | 16.06 | 39.00 | 399.83 | 771.12 | 19.24 | 43.33 | 371.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:40 | 1359.48 | 17.69 | 60.17 | 414.17 | 833.93 | 20.80 | 61.83 | 388.33 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-05:10 | 1153.23 | 16.65 | 78.00 | 424.00 | 720.70 | 19.81 | 79.67 | 389.33 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:00 | 1019.83 | 13.76 | 0.00 | 391.83 | 651.58 | 17.36 | 0.50 | 354.17 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:49 | 966.59 | 14.03 | 0.00 | 314.83 | 614.19 | 17.52 | 0.00 | 266.00 |
October | 245.33 | 0.55 | 0.48 | 01-OCT-08:30 | 718.88 | 11.95 | 0.00 | 261.83 | 456.10 | 15.53 | 0.00 | 187.00 |
November | 242.67 | 0.57 | 0.48 | 01-NOV-10:50 | 552.17 | 9.75 | 0.00 | 193.33 | 316.01 | 13.21 | 0.00 | 83.83 |
December | 160.33 | 0.60 | 0.48 | 01-DEC-10:09 | 480.26 | 9.66 | 0.00 | 156.17 | 294.28 | 13.40 | 0.00 | 51.33 |
Annual Sum or Average | 3714.00 | 0.53 | 959.28 | 13.69 | 177.17 | 3600.33 | 588.95 | 17.09 | 185.33 | 2842.17 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 480.26 | 9.38 | 0.00 | 156.17 | 293.10 | 12.90 | 0.00 | 51.33 | |
Maximum of Months | 471.00 | 0.60 | 0.48 | 1359.48 | 17.69 | 78.00 | 424.00 | 833.93 | 20.80 | 79.67 | 389.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.54 | 0.48 | 01-JAN-13:20 | 1080.38 | 19.93 | 79.00 | 203.83 | 591.32 | 20.66 | 63.33 | 145.50 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-09:30 | 1525.08 | 19.27 | 66.50 | 232.17 | 813.53 | 21.10 | 58.17 | 190.33 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-08:30 | 2437.51 | 21.54 | 78.17 | 307.67 | 1338.74 | 22.49 | 58.17 | 258.67 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:40 | 2915.77 | 20.12 | 105.33 | 346.50 | 1316.35 | 19.95 | 51.00 | 313.67 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:49 | 3010.49 | 16.74 | 52.17 | 392.83 | 1665.19 | 17.60 | 0.00 | 361.33 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:19 | 3081.74 | 16.36 | 42.83 | 404.00 | 1445.05 | 17.38 | 0.00 | 367.67 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-09:50 | 3376.13 | 15.48 | 58.83 | 406.33 | 1538.50 | 16.17 | 3.67 | 367.83 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-06:30 | 3209.36 | 18.43 | 75.83 | 384.00 | 1904.40 | 19.86 | 50.17 | 350.83 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:00 | 3546.70 | 22.34 | 100.50 | 316.67 | 2028.66 | 23.25 | 76.50 | 280.00 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:50 | 2431.95 | 22.15 | 89.83 | 275.17 | 1130.58 | 22.65 | 63.50 | 232.33 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-10:09 | 1148.52 | 19.24 | 70.50 | 211.50 | 617.22 | 19.95 | 51.33 | 150.17 |
December | 160.33 | 0.55 | 0.48 | 01-DEC-09:00 | 1133.98 | 19.83 | 48.67 | 186.67 | 618.66 | 20.60 | 44.50 | 111.50 |
Annual Sum or Average | 3714.00 | 0.52 | 2611.12 | 18.86 | 868.17 | 3667.33 | 1345.38 | 19.70 | 520.33 | 3129.83 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 1080.38 | 15.48 | 42.83 | 186.67 | 591.32 | 16.17 | 0.00 | 111.50 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 3546.70 | 22.34 | 105.33 | 406.33 | 2028.66 | 23.25 | 76.50 | 367.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-09:00 | 2760.32 | 31.97 | 220.17 | 219.67 | 2235.98 | 33.11 | 221.33 | 190.33 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-08:39 | 4709.58 | 32.94 | 238.67 | 244.50 | 2132.90 | 27.42 | 156.50 | 223.17 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:40 | 7802.12 | 32.27 | 208.50 | 313.33 | 1781.61 | 17.89 | 8.33 | 272.50 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:10 | 2255.49 | 13.68 | 0.00 | 345.67 | 1303.36 | 17.20 | 0.50 | 312.67 |
May | 427.83 | 0.52 | 0.48 | 01-MAY-07:19 | 2070.24 | 13.68 | 0.00 | 386.83 | 1180.35 | 17.14 | 0.00 | 349.67 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-06:10 | 1826.95 | 13.55 | 0.00 | 396.67 | 1093.16 | 17.02 | 0.00 | 352.00 |
July | 471.00 | 0.54 | 0.48 | 01-JUL-05:40 | 1629.21 | 12.17 | 0.00 | 396.33 | 995.13 | 15.67 | 0.00 | 349.00 |
August | 366.67 | 0.53 | 0.48 | 01-AUG-06:10 | 1929.83 | 13.26 | 0.00 | 375.17 | 1201.15 | 16.84 | 1.17 | 333.00 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 3065.15 | 16.30 | 27.00 | 320.33 | 1577.38 | 18.05 | 9.83 | 292.00 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:00 | 7245.84 | 34.02 | 220.33 | 285.00 | 2057.39 | 19.28 | 26.17 | 259.00 |
November | 242.67 | 0.51 | 0.48 | 01-NOV-08:20 | 3083.83 | 31.47 | 221.33 | 225.50 | 2504.61 | 32.75 | 226.00 | 197.50 |
December | 160.33 | 0.51 | 0.48 | 01-DEC-09:39 | 3715.59 | 34.93 | 149.17 | 207.83 | 3198.14 | 36.41 | 149.67 | 171.33 |
Annual Sum or Average | 3714.00 | 0.52 | 3164.42 | 20.82 | 1285.17 | 3716.83 | 1600.58 | 20.77 | 799.50 | 3302.17 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 1629.21 | 12.17 | 0.00 | 207.83 | 995.13 | 15.67 | 0.00 | 171.33 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 7802.12 | 34.93 | 238.67 | 396.67 | 3198.14 | 36.41 | 226.00 | 352.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 01-JAN-10:09 | 951.06 | 18.26 | 61.33 | 202.33 | 598.70 | 20.59 | 71.17 | 139.00 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-08:30 | 1552.25 | 20.41 | 80.83 | 230.33 | 833.30 | 21.21 | 60.00 | 188.17 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-07:30 | 2793.74 | 23.04 | 91.50 | 304.67 | 1262.48 | 22.27 | 50.83 | 261.50 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 2891.16 | 20.33 | 105.17 | 348.67 | 1662.20 | 22.45 | 91.67 | 314.17 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-06:00 | 2989.32 | 20.30 | 132.50 | 393.17 | 1354.30 | 20.86 | 79.50 | 357.00 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:10 | 3148.69 | 20.29 | 98.83 | 405.33 | 1778.57 | 21.48 | 73.67 | 364.67 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-04:00 | 2952.45 | 19.95 | 148.50 | 411.00 | 1385.63 | 20.83 | 99.33 | 380.00 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:30 | 3442.29 | 21.44 | 116.33 | 380.67 | 1551.92 | 21.11 | 66.50 | 345.83 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2830.31 | 21.04 | 82.67 | 324.00 | 1610.03 | 22.24 | 60.67 | 290.50 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-07:49 | 2518.03 | 21.36 | 83.00 | 273.33 | 1156.56 | 21.93 | 56.67 | 232.83 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-08:09 | 1179.24 | 19.70 | 78.83 | 210.33 | 630.39 | 20.48 | 62.50 | 155.50 |
December | 160.33 | 0.54 | 0.48 | 01-DEC-09:39 | 1113.62 | 20.93 | 56.33 | 186.83 | 616.08 | 21.54 | 52.17 | 115.00 |
Annual Sum or Average | 3714.00 | 0.52 | 2548.23 | 20.55 | 1135.83 | 3670.67 | 1289.71 | 21.39 | 824.67 | 3144.17 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 951.06 | 18.26 | 56.33 | 186.83 | 598.70 | 20.48 | 50.83 | 115.00 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 3442.29 | 23.04 | 148.50 | 411.00 | 1778.57 | 22.45 | 99.33 | 380.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.59 | 0.48 | 02-JAN-11:30 | 512.82 | 9.35 | 0.00 | 180.33 | 293.59 | 12.89 | 0.00 | 68.83 |
February | 259.50 | 0.55 | 0.48 | 01-FEB-09:30 | 653.88 | 10.91 | 0.00 | 216.33 | 388.18 | 14.47 | 0.00 | 143.50 |
March | 247.00 | 0.53 | 0.48 | 01-MAR-08:30 | 887.08 | 12.80 | 0.00 | 298.83 | 550.64 | 16.34 | 0.00 | 230.00 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:19 | 1040.21 | 13.51 | 0.00 | 349.00 | 631.63 | 16.97 | 0.00 | 310.17 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:19 | 1293.29 | 16.03 | 39.00 | 400.17 | 772.23 | 19.23 | 43.00 | 371.33 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:40 | 1360.73 | 17.67 | 60.17 | 414.17 | 834.98 | 20.79 | 61.83 | 388.50 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-05:10 | 1154.32 | 16.62 | 78.00 | 424.00 | 721.58 | 19.79 | 79.17 | 389.83 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:00 | 1020.68 | 13.72 | 0.00 | 391.83 | 652.35 | 17.34 | 0.50 | 354.17 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:49 | 967.45 | 14.00 | 0.00 | 314.83 | 614.97 | 17.51 | 0.00 | 266.67 |
October | 245.33 | 0.55 | 0.48 | 01-OCT-08:30 | 719.50 | 11.92 | 0.00 | 262.00 | 456.69 | 15.51 | 0.00 | 187.50 |
November | 242.67 | 0.57 | 0.48 | 01-NOV-10:39 | 552.93 | 9.72 | 0.00 | 193.50 | 316.54 | 13.20 | 0.00 | 84.33 |
December | 160.33 | 0.60 | 0.48 | 01-DEC-10:09 | 480.71 | 9.63 | 0.00 | 156.33 | 294.70 | 13.39 | 0.00 | 51.33 |
Annual Sum or Average | 3714.00 | 0.53 | 960.26 | 13.66 | 177.17 | 3601.33 | 589.74 | 17.08 | 184.50 | 2846.17 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 480.71 | 9.35 | 0.00 | 156.33 | 293.59 | 12.89 | 0.00 | 51.33 | |
Maximum of Months | 471.00 | 0.60 | 0.48 | 1360.73 | 17.67 | 78.00 | 424.00 | 834.98 | 20.79 | 79.17 | 389.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.54 | 0.48 | 01-JAN-13:20 | 1081.35 | 19.91 | 79.00 | 203.83 | 592.12 | 20.65 | 63.17 | 146.00 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-09:30 | 1526.27 | 19.24 | 66.50 | 232.33 | 814.58 | 21.09 | 57.50 | 190.50 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-08:30 | 2439.12 | 21.52 | 78.17 | 307.67 | 1340.23 | 22.48 | 58.17 | 259.00 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:40 | 2917.71 | 20.09 | 105.33 | 346.50 | 1317.96 | 19.93 | 51.00 | 314.17 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:49 | 3012.91 | 16.71 | 52.17 | 392.83 | 1667.02 | 17.58 | 0.00 | 361.50 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:19 | 3083.77 | 16.33 | 42.83 | 404.00 | 1446.72 | 17.37 | 0.00 | 367.67 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-09:50 | 3377.88 | 15.45 | 58.83 | 406.50 | 1539.93 | 16.15 | 3.67 | 368.00 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-06:30 | 3210.80 | 18.40 | 75.83 | 384.00 | 1905.82 | 19.85 | 50.17 | 351.00 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:00 | 3548.43 | 22.32 | 100.50 | 316.67 | 2030.38 | 23.23 | 76.50 | 280.83 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:50 | 2433.05 | 22.12 | 89.83 | 275.17 | 1131.78 | 22.64 | 63.33 | 232.50 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-10:09 | 1149.58 | 19.21 | 70.50 | 211.50 | 618.08 | 19.94 | 50.83 | 150.50 |
December | 160.33 | 0.55 | 0.48 | 01-DEC-09:00 | 1134.67 | 19.80 | 48.67 | 186.83 | 619.41 | 20.59 | 44.17 | 111.83 |
Annual Sum or Average | 3714.00 | 0.52 | 2612.73 | 18.84 | 868.17 | 3667.83 | 1346.78 | 19.69 | 518.50 | 3133.50 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 1081.35 | 15.45 | 42.83 | 186.83 | 592.12 | 16.15 | 0.00 | 111.83 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 3548.43 | 22.32 | 105.33 | 406.50 | 2030.38 | 23.23 | 76.50 | 368.00 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAWATERHEATC
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.970374E+10 | 433363.31 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182342E+09 | 272812.52 | 21-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 70744433.75 | 199335.62 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.995682E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.970374E+10 | 433363.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.498941E+10 | 74849.86 | 02-JAN-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.228725E+10 | 74832.05 | 13-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.531898E+09 | 74800.66 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33325624.65 | 22267.33 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.237407E+09 | 74724.60 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139093E+10 | 75347.40 | 27-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.317164E+10 | 74821.18 | 26-DEC-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126419E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.498941E+10 | 75347.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 10237171.68 | 1570.54 | 09-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10237171.68 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10237171.68 | 1570.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.146864E+09 | 8338.74 | 09-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 51184639.77 | 3390.13 | 13-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 369895.40 | 137.22 | 24-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1511336.84 | 225.58 | 30-NOV-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36101191.13 | 1382.08 | 22-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.236031E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.146864E+09 | 8338.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.233228E+09 | 13679.33 | 17-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 70506871.64 | 9749.81 | 21-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2020772.79 | 1053.64 | 06-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7221453.72 | 4468.30 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 44476030.59 | 10761.60 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.357453E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.233228E+09 | 13679.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1303884.61 | 302.43 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1303884.61 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1303884.61 | 302.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.276039E+11 | 101151.01 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130550E+11 | 102609.62 | 10-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384568E+10 | 104328.11 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115370E+10 | 99853.74 | 11-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 49523492.11 | 57981.81 | 18-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126547E+10 | 100274.93 | 30-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.732154E+10 | 102607.39 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176463E+11 | 100716.25 | 01-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.719411E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.276039E+11 | 104328.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.274003E+11 | 147055.50 | 06-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137679E+11 | 146975.14 | 13-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.466633E+10 | 147001.33 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142746E+10 | 146800.62 | 11-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.232032E+09 | 72156.65 | 18-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16312435.08 | 8269.73 | 14-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 68201271.61 | 16978.23 | 27-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.270428E+10 | 146821.04 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105255E+11 | 147774.49 | 27-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197286E+11 | 146985.03 | 27-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.805370E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.274003E+11 | 147774.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.230137E+11 | 196508.12 | 02-JAN-05:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.963428E+10 | 196175.20 | 14-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.327272E+10 | 196281.83 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125846E+10 | 170417.06 | 18-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110007E+09 | 86365.53 | 18-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125040E+10 | 144683.47 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.688230E+10 | 197324.00 | 27-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153656E+11 | 196255.03 | 27-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.607874E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.230137E+11 | 197324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.211354E+11 | 142495.18 | 03-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100822E+11 | 142446.21 | 21-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.327878E+10 | 142199.62 | 13-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101608E+10 | 81722.33 | 18-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.123792E+09 | 52715.57 | 18-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 611438.87 | 746.50 | 28-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165950E+10 | 79147.15 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.719778E+10 | 143073.97 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141093E+11 | 142532.39 | 16-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.586035E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.211354E+11 | 143073.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.558188E+10 | 11491.15 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.364791E+10 | 11887.41 | 24-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175949E+10 | 11484.18 | 06-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.714238E+09 | 11429.23 | 08-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148869E+09 | 11429.07 | 18-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13189314.98 | 8814.53 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 64422493.31 | 8519.88 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.952819E+09 | 11546.87 | 23-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.261352E+10 | 11726.81 | 27-NOV-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.459590E+10 | 11538.65 | 16-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200922E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.558188E+10 | 11887.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.447862E+10 | 16608.92 | 30-JAN-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275646E+10 | 16610.21 | 13-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138560E+10 | 16617.03 | 06-MAR-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.513547E+09 | 16593.31 | 19-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174323E+09 | 16548.10 | 18-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26505463.10 | 9061.00 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2727164.92 | 542.35 | 05-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120896E+09 | 7761.40 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.902941E+09 | 16601.48 | 31-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.236150E+10 | 16736.75 | 27-NOV-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.378736E+10 | 16615.12 | 11-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165105E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.447862E+10 | 16736.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.469013E+10 | 22779.67 | 30-JAN-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.273066E+10 | 22771.43 | 06-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154217E+10 | 22790.78 | 06-MAR-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.738205E+09 | 22755.61 | 17-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.223786E+09 | 22711.44 | 18-MAY-04:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31990840.21 | 9867.69 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76983330.97 | 8776.25 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.820761E+09 | 22760.71 | 28-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.241756E+10 | 22954.97 | 27-NOV-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.392336E+10 | 22795.08 | 18-DEC-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171956E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.469013E+10 | 22954.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.371978E+10 | 16882.57 | 18-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.222615E+10 | 16871.79 | 14-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120160E+10 | 16863.80 | 13-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.484477E+09 | 16833.61 | 11-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150313E+09 | 16831.46 | 18-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19148270.98 | 2974.86 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 61984598.61 | 2146.06 | 18-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.724774E+09 | 16871.40 | 23-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190377E+10 | 16982.96 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.296273E+10 | 16880.20 | 04-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134547E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.371978E+10 | 16982.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_HEATC
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.940431E+09 | 235174.31 | 01-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 46996039.57 | 234979.53 | 21-FEB-02:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 70499906.42 | 234999.35 | 27-MAR-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70600231.14 | 235334.10 | 30-APR-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.290787E+09 | 235378.09 | 29-MAY-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.117659E+09 | 235415.62 | 11-JUN-19:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.798706E+09 | 235414.30 | 16-JUL-23:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.699371E+09 | 235414.41 | 27-AUG-22:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100040E+10 | 235417.63 | 24-SEP-23:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.423213E+09 | 235362.56 | 09-OCT-20:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.658166E+09 | 235173.29 | 06-NOV-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.281979E+09 | 234997.17 | 25-DEC-20:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.539881E+10 | |||||||
Minimum of Months | 46996039.57 | 234979.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100040E+10 | 235417.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.512983E+10 | 23977.30 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.294095E+10 | 19551.60 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.383988E+09 | 14510.83 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 59442822.86 | 7914.13 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15287190.90 | 3683.52 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2989133.03 | 699.44 | 31-OCT-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.744178E+09 | 10853.30 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216122E+10 | 16331.33 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114379E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.512983E+10 | 23977.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109145E+12 | 269180.59 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.639689E+11 | 222428.51 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171585E+11 | 176868.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.655696E+10 | 126995.75 | 19-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.602039E+09 | 53982.27 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187084E+10 | 57070.18 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.343691E+11 | 173950.15 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.762939E+11 | 238851.51 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.309965E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109145E+12 | 269180.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131686E+11 | 30557.32 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.848439E+10 | 26969.16 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.355788E+10 | 22378.30 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138724E+10 | 17124.28 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.264961E+09 | 9432.44 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 129863.36 | 214.06 | 15-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1540.89 | 0.71 | 06-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1489.31 | 0.78 | 23-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32614292.38 | 3643.01 | 27-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.682144E+09 | 10081.28 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.551404E+10 | 21543.03 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108168E+11 | 27408.43 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.439088E+11 | |||||||
Minimum of Months | 1489.31 | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131686E+11 | 30557.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAELECHEATC
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2963085.03 | 2963085.03 | 9431.25 | 11-JAN-05:11 | 9431.25 | 0.00 |
February | 0.00 | 0.00 | 0.491220E+09 | 0.479754E+09 | 53024.34 | 24-FEB-05:11 | 35409.15 | 0.00 |
March | 0.00 | 0.00 | 0.143315E+09 | 0.130237E+09 | 38493.16 | 10-MAR-05:51 | 16850.26 | 0.00 |
April | 0.00 | 0.00 | 0.400997E+10 | 0.400256E+10 | 59085.00 | 27-APR-15:40 | 59085.00 | 0.04 |
May | 0.00 | 0.00 | 0.762608E+10 | 0.759553E+10 | 57099.84 | 15-MAY-16:00 | 57099.84 | 0.11 |
June | 0.00 | 0.00 | 0.158774E+11 | 0.157809E+11 | 77864.09 | 11-JUN-19:33 | 64265.50 | 0.22 |
July | 0.00 | 0.00 | 0.301503E+11 | 0.298040E+11 | 118994.32 | 30-JUL-17:42 | 105039.79 | 0.36 |
August | 0.00 | 0.00 | 0.417266E+11 | 0.411220E+11 | 123738.28 | 13-AUG-17:40 | 104188.64 | 0.42 |
September | 0.00 | 0.00 | 0.126515E+11 | 0.124258E+11 | 76919.07 | 01-SEP-03:01 | 43869.18 | 0.22 |
October | 0.00 | 0.00 | 0.182541E+10 | 0.178858E+10 | 66437.41 | 09-OCT-14:01 | 58852.16 | 0.02 |
November | 0.00 | 0.00 | 0.335827E+09 | 0.311433E+09 | 64112.73 | 05-NOV-16:41 | 46172.55 | 0.01 |
December | 0.00 | 0.00 | 9288233.40 | 8810054.96 | 16358.91 | 16-DEC-06:02 | 13471.95 | 0.00 |
Annual Sum or Average | 0.114850E+12 | 0.113453E+12 | 0.12 | |||||
Minimum of Months | 0.00 | 0.00 | 2963085.03 | 2963085.03 | 9431.25 | 9431.25 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.417266E+11 | 0.411220E+11 | 123738.28 | 105039.79 | 0.42 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 22387603.48 | 22387603.48 | 3157.99 | 11-JAN-14:00 | 3157.99 | 0.00 |
February | 0.00 | 0.00 | 0.100719E+10 | 0.100719E+10 | 55847.49 | 27-FEB-15:00 | 55847.49 | 0.02 |
March | 0.00 | 0.00 | 0.175433E+10 | 0.175433E+10 | 35256.30 | 18-MAR-16:00 | 35256.30 | 0.02 |
April | 0.00 | 0.00 | 0.112413E+11 | 0.112277E+11 | 106045.43 | 27-APR-15:20 | 102835.96 | 0.06 |
May | 0.00 | 0.00 | 0.187991E+11 | 0.184338E+11 | 87613.03 | 05-MAY-15:40 | 77979.83 | 0.18 |
June | 0.00 | 0.00 | 0.342141E+11 | 0.340662E+11 | 96007.20 | 28-JUN-16:00 | 96007.20 | 0.38 |
July | 0.00 | 0.00 | 0.622138E+11 | 0.582603E+11 | 124091.33 | 31-JUL-16:00 | 109491.01 | 0.56 |
August | 0.00 | 0.00 | 0.843891E+11 | 0.766819E+11 | 135932.06 | 29-AUG-14:40 | 119266.87 | 0.66 |
September | 0.00 | 0.00 | 0.300033E+11 | 0.276585E+11 | 109321.43 | 14-SEP-13:00 | 76402.87 | 0.38 |
October | 0.00 | 0.00 | 0.611641E+10 | 0.611336E+10 | 72609.40 | 04-OCT-15:00 | 72609.40 | 0.07 |
November | 0.00 | 0.00 | 0.104050E+10 | 0.966107E+09 | 47573.19 | 04-NOV-14:10 | 43355.40 | 0.03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.250802E+12 | 0.236192E+12 | 0.20 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.843891E+11 | 0.766819E+11 | 135932.06 | 119266.87 | 0.66 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.138767E+09 | 0.138767E+09 | 18047.11 | 11-JAN-16:00 | 18047.11 | 0.00 |
February | 0.00 | 0.00 | 0.695464E+10 | 0.695464E+10 | 377177.55 | 27-FEB-15:00 | 377177.55 | 0.02 |
March | 0.00 | 0.00 | 0.130663E+11 | 0.130663E+11 | 335720.18 | 18-MAR-14:00 | 335720.18 | 0.02 |
April | 0.00 | 0.00 | 0.840504E+11 | 0.839773E+11 | 872123.92 | 27-APR-15:20 | 854159.46 | 0.06 |
May | 0.00 | 0.00 | 0.162317E+12 | 0.158889E+12 | 783927.27 | 05-MAY-15:40 | 692072.07 | 0.19 |
June | 0.00 | 0.00 | 0.280439E+12 | 0.279477E+12 | 844696.66 | 28-JUN-16:00 | 844696.66 | 0.36 |
July | 0.00 | 0.00 | 0.487435E+12 | 0.456550E+12 | 1050511.75 | 31-JUL-16:00 | 909874.66 | 0.50 |
August | 0.00 | 0.00 | 0.639454E+12 | 0.581148E+12 | 1179980.72 | 29-AUG-14:40 | 1020604.48 | 0.55 |
September | 0.00 | 0.00 | 0.268418E+12 | 0.246564E+12 | 1011596.98 | 14-SEP-13:00 | 704963.52 | 0.38 |
October | 0.00 | 0.00 | 0.481784E+11 | 0.481784E+11 | 639862.16 | 04-OCT-15:00 | 639862.16 | 0.07 |
November | 0.00 | 0.00 | 0.945628E+10 | 0.869725E+10 | 472161.45 | 04-NOV-13:20 | 406034.45 | 0.04 |
December | 0.00 | 0.00 | 34375.43 | 34375.43 | 2.33 | 26-DEC-06:02 | 2.33 | 0.00 |
Annual Sum or Average | 0.199991E+13 | 0.188364E+13 | 0.18 | |||||
Minimum of Months | 0.00 | 0.00 | 34375.43 | 34375.43 | 2.33 | 2.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.639454E+12 | 0.581148E+12 | 1179980.72 | 1020604.48 | 0.55 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 12046481.72 | 12046481.72 | 1544.92 | 11-JAN-14:00 | 1544.92 | 0.00 |
February | 0.00 | 0.00 | 0.656995E+09 | 0.656995E+09 | 35312.21 | 27-FEB-15:00 | 35312.21 | 0.01 |
March | 0.00 | 0.00 | 0.122168E+10 | 0.122168E+10 | 32970.98 | 18-MAR-14:00 | 32970.98 | 0.02 |
April | 0.00 | 0.00 | 0.863747E+10 | 0.862678E+10 | 104863.05 | 27-APR-15:20 | 102214.53 | 0.05 |
May | 0.00 | 0.00 | 0.166153E+11 | 0.162902E+11 | 85832.91 | 04-MAY-15:00 | 85832.91 | 0.18 |
June | 0.00 | 0.00 | 0.296182E+11 | 0.295231E+11 | 103823.14 | 28-JUN-16:00 | 103823.14 | 0.35 |
July | 0.00 | 0.00 | 0.524538E+11 | 0.491230E+11 | 129572.93 | 27-JUL-15:40 | 99530.93 | 0.49 |
August | 0.00 | 0.00 | 0.677609E+11 | 0.618470E+11 | 134460.42 | 29-AUG-14:40 | 117648.82 | 0.54 |
September | 0.00 | 0.00 | 0.265246E+11 | 0.243862E+11 | 106174.70 | 14-SEP-13:00 | 74165.81 | 0.36 |
October | 0.00 | 0.00 | 0.431703E+10 | 0.431703E+10 | 63443.23 | 04-OCT-15:00 | 63443.23 | 0.05 |
November | 0.00 | 0.00 | 0.896845E+09 | 0.828063E+09 | 46188.96 | 04-NOV-13:30 | 40524.74 | 0.02 |
December | 0.00 | 0.00 | 10402.96 | 10402.96 | 89.43 | 26-DEC-04:17 | 89.43 | 0.00 |
Annual Sum or Average | 0.208715E+12 | 0.196832E+12 | 0.17 | |||||
Minimum of Months | 0.00 | 0.00 | 10402.96 | 10402.96 | 89.43 | 89.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.677609E+11 | 0.618470E+11 | 134460.42 | 117648.82 | 0.54 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.456543E+10 | 0.456525E+10 | 3192.55 | 09-JAN-12:00 | 3192.55 | 0.00 |
February | 0.00 | 0.00 | 0.216142E+11 | 0.215454E+11 | 207915.63 | 27-FEB-04:03 | 207915.63 | 0.00 |
March | 0.00 | 0.00 | 0.157405E+11 | 0.149723E+11 | 146182.70 | 18-MAR-16:00 | 146182.70 | 0.00 |
April | 0.00 | 0.00 | 0.108149E+12 | 0.991251E+11 | 382461.46 | 27-APR-14:50 | 382461.46 | 0.00 |
May | 0.00 | 0.00 | 0.830105E+11 | 0.825482E+11 | 139716.17 | 06-MAY-23:10 | 118863.83 | 0.00 |
June | 0.00 | 0.00 | 0.910128E+11 | 0.887757E+11 | 229938.53 | 12-JUN-01:10 | 207335.26 | 0.00 |
July | 0.00 | 0.00 | 0.247277E+12 | 0.205284E+12 | 342196.83 | 27-JUL-16:00 | 275441.89 | 0.00 |
August | 0.00 | 0.00 | 0.622920E+12 | 0.479255E+12 | 406789.31 | 30-AUG-13:00 | 275166.59 | 0.00 |
September | 0.00 | 0.00 | 0.156301E+11 | 0.146861E+11 | 143121.12 | 23-SEP-18:20 | 119524.45 | 0.00 |
October | 0.00 | 0.00 | 0.664412E+11 | 0.663115E+11 | 211606.89 | 20-OCT-21:13 | 207573.09 | 0.00 |
November | 0.00 | 0.00 | 0.164538E+12 | 0.162260E+12 | 345921.61 | 06-NOV-22:25 | 295480.35 | 0.00 |
December | 0.00 | 0.00 | 0.484957E+12 | 0.484276E+12 | 389115.55 | 03-DEC-14:27 | 389115.55 | 0.00 |
Annual Sum or Average | 0.192586E+13 | 0.172361E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.456543E+10 | 0.456525E+10 | 3192.55 | 3192.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.622920E+12 | 0.484276E+12 | 406789.31 | 389115.55 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.425658E+10 | 0.425658E+10 | 2300.63 | 05-JAN-16:20 | 2300.63 | 0.00 |
February | 0.00 | 0.00 | 0.873496E+10 | 0.873496E+10 | 4323.70 | 07-FEB-16:50 | 4323.70 | 0.00 |
March | 0.00 | 0.00 | 0.150448E+11 | 0.150448E+11 | 6318.46 | 14-MAR-17:20 | 6318.46 | 0.00 |
April | 0.00 | 0.00 | 0.195052E+11 | 0.195052E+11 | 8382.48 | 26-APR-18:20 | 8382.48 | 0.00 |
May | 0.00 | 0.00 | 0.547309E+10 | 0.547309E+10 | 2979.33 | 29-MAY-18:33 | 2979.33 | 0.00 |
June | 0.00 | 0.00 | 0.101966E+11 | 0.101966E+11 | 4691.54 | 18-JUN-18:56 | 4691.54 | 0.00 |
July | 0.00 | 0.00 | 0.155828E+11 | 0.155828E+11 | 7060.59 | 30-JUL-18:50 | 7060.59 | 0.00 |
August | 0.00 | 0.00 | 0.203662E+11 | 0.203662E+11 | 8470.99 | 06-AUG-19:23 | 8470.99 | 0.00 |
September | 0.00 | 0.00 | 0.536156E+10 | 0.536156E+10 | 2919.98 | 10-SEP-17:34 | 2919.98 | 0.00 |
October | 0.00 | 0.00 | 0.102118E+11 | 0.102118E+11 | 4702.30 | 03-OCT-17:00 | 4702.30 | 0.00 |
November | 0.00 | 0.00 | 0.144681E+11 | 0.144681E+11 | 6087.69 | 12-NOV-16:00 | 6087.69 | 0.00 |
December | 0.00 | 0.00 | 0.197250E+11 | 0.197250E+11 | 7917.87 | 05-DEC-16:00 | 7917.87 | 0.00 |
Annual Sum or Average | 0.148927E+12 | 0.148927E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.425658E+10 | 0.425658E+10 | 2300.63 | 2300.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.203662E+11 | 0.203662E+11 | 8470.99 | 8470.99 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.178478E+11 | 0.178478E+11 | 18062.13 | 20-JAN-16:20 | 18062.13 | 0.00 |
February | 0.00 | 0.00 | 0.658754E+11 | 0.658754E+11 | 39522.87 | 08-FEB-17:00 | 39522.87 | 0.00 |
March | 0.00 | 0.00 | 0.129049E+12 | 0.129049E+12 | 59098.56 | 14-MAR-17:20 | 59098.56 | 0.00 |
April | 0.00 | 0.00 | 0.176367E+12 | 0.176367E+12 | 79732.88 | 26-APR-18:10 | 79732.88 | 0.00 |
May | 0.00 | 0.00 | 0.447050E+11 | 0.447050E+11 | 27022.46 | 07-MAY-18:32 | 27022.46 | 0.00 |
June | 0.00 | 0.00 | 0.914537E+11 | 0.914537E+11 | 43809.76 | 22-JUN-19:00 | 43809.76 | 0.00 |
July | 0.00 | 0.00 | 0.144427E+12 | 0.144427E+12 | 65612.46 | 30-JUL-18:39 | 65612.46 | 0.00 |
August | 0.00 | 0.00 | 0.190940E+12 | 0.190940E+12 | 80483.62 | 06-AUG-19:12 | 80483.62 | 0.00 |
September | 0.00 | 0.00 | 0.443683E+11 | 0.443683E+11 | 26774.22 | 10-SEP-17:24 | 26774.22 | 0.00 |
October | 0.00 | 0.00 | 0.846744E+11 | 0.846744E+11 | 44277.25 | 04-OCT-17:00 | 44277.25 | 0.00 |
November | 0.00 | 0.00 | 0.120150E+12 | 0.120150E+12 | 55208.68 | 10-NOV-16:10 | 55208.68 | 0.00 |
December | 0.00 | 0.00 | 0.165986E+12 | 0.165986E+12 | 72593.74 | 05-DEC-16:10 | 72593.74 | 0.00 |
Annual Sum or Average | 0.127584E+13 | 0.127584E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.178478E+11 | 0.178478E+11 | 18062.13 | 18062.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.190940E+12 | 0.190940E+12 | 80483.62 | 80483.62 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.894914E+09 | 0.894914E+09 | 1750.91 | 05-JAN-16:20 | 1750.91 | 0.00 |
February | 0.00 | 0.00 | 0.519068E+10 | 0.519068E+10 | 3874.19 | 08-FEB-17:00 | 3874.19 | 0.00 |
March | 0.00 | 0.00 | 0.117456E+11 | 0.117456E+11 | 5925.67 | 14-MAR-17:20 | 5925.67 | 0.00 |
April | 0.00 | 0.00 | 0.169113E+11 | 0.169113E+11 | 8062.85 | 26-APR-18:10 | 8062.85 | 0.00 |
May | 0.00 | 0.00 | 0.397672E+10 | 0.397672E+10 | 2796.79 | 07-MAY-18:30 | 2796.79 | 0.00 |
June | 0.00 | 0.00 | 0.892475E+10 | 0.892475E+10 | 4474.39 | 22-JUN-19:00 | 4474.39 | 0.00 |
July | 0.00 | 0.00 | 0.143005E+11 | 0.143005E+11 | 6729.24 | 30-JUL-18:33 | 6729.24 | 0.00 |
August | 0.00 | 0.00 | 0.189172E+11 | 0.189172E+11 | 8147.62 | 06-AUG-19:04 | 8147.62 | 0.00 |
September | 0.00 | 0.00 | 0.389789E+10 | 0.389789E+10 | 2716.98 | 08-SEP-17:40 | 2716.98 | 0.00 |
October | 0.00 | 0.00 | 0.740042E+10 | 0.740042E+10 | 4458.06 | 04-OCT-17:00 | 4458.06 | 0.00 |
November | 0.00 | 0.00 | 0.105962E+11 | 0.105962E+11 | 5401.39 | 10-NOV-16:10 | 5401.39 | 0.00 |
December | 0.00 | 0.00 | 0.148987E+11 | 0.148987E+11 | 7116.82 | 05-DEC-16:10 | 7116.82 | 0.00 |
Annual Sum or Average | 0.117655E+12 | 0.117655E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.894914E+09 | 0.894914E+09 | 1750.91 | 1750.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.189172E+11 | 0.189172E+11 | 8147.62 | 8147.62 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 6787.43 | 37526.89 | 01-JAN-08:50 | 13318.00 | 52063.91 | 31-JAN-12:40 |
February | 6409.74 | 37475.12 | 26-FEB-09:20 | 13474.03 | 52120.91 | 10-FEB-12:40 |
March | 5193.24 | 37533.81 | 26-MAR-08:10 | 14414.51 | 51950.95 | 01-MAR-12:40 |
April | 6274.73 | 37664.84 | 30-APR-22:11 | 12929.57 | 50802.46 | 03-APR-12:00 |
May | 6206.37 | 37790.97 | 29-MAY-07:25 | 12917.15 | 49263.99 | 01-MAY-11:20 |
June | 5603.84 | 37893.86 | 25-JUN-07:27 | 12743.41 | 47354.51 | 01-JUN-11:50 |
July | 7245.02 | 37970.63 | 30-JUL-07:18 | 11130.61 | 45745.74 | 03-JUL-11:50 |
August | 5586.21 | 37977.34 | 13-AUG-07:20 | 12274.90 | 45093.08 | 31-AUG-12:00 |
September | 6555.99 | 37959.85 | 03-SEP-07:40 | 11593.92 | 46055.67 | 29-SEP-11:40 |
October | 7104.15 | 37889.69 | 01-OCT-07:50 | 11941.27 | 47800.13 | 31-OCT-11:40 |
November | 7121.18 | 37751.04 | 05-NOV-07:50 | 12639.07 | 49635.85 | 30-NOV-12:40 |
December | 6913.47 | 37630.11 | 03-DEC-09:10 | 12592.07 | 51144.45 | 29-DEC-12:50 |
Annual Sum or Average | 6417.14 | 12659.44 | ||||
Minimum of Months | 5193.24 | 37475.12 | 11130.61 | 45093.08 | ||
Maximum of Months | 7245.02 | 37977.34 | 14414.51 | 52120.91 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 96998.83 | 1743411.44 | 28-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 55908.75 | 1702436.18 | 16-FEB-05:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15844.82 | 1786334.83 | 13-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5997.86 | 1254188.55 | 11-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 1006.17 | 2753747.24 | 23-MAY-03:04 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 71.76 | 333965.32 | 19-JUN-01:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 316.96 | 302519.33 | 02-JUL-19:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 261.63 | 236161.83 | 06-AUG-21:20 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 460.00 | 315291.62 | 24-SEP-23:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 4919.46 | 1867842.01 | 02-OCT-01:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 32254.69 | 1746294.50 | 24-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 65016.88 | 1677818.15 | 18-DEC-05:11 |
Annual Sum or Average | 0.00 | 23135.02 | ||||
Minimum of Months | 0.00 | 0.00 | 71.76 | 236161.83 | ||
Maximum of Months | 0.00 | 0.00 | 96998.83 | 2753747.24 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 84.31 | 22821.86 | 11-JAN-16:00 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 3817.60 | 540495.15 | 27-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 6087.14 | 405147.64 | 18-MAR-14:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 43250.95 | 1399417.97 | 26-APR-15:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 80036.45 | 1387971.87 | 04-MAY-15:50 | 0.00 | 0.00 | 01-MAY-00:02 |
June | 142341.64 | 1349714.93 | 21-JUN-15:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 248715.96 | 1369776.03 | 31-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 328204.03 | 1518742.15 | 29-AUG-14:40 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 135757.31 | 1295067.70 | 11-SEP-14:10 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 23138.76 | 933619.55 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 4599.75 | 582080.70 | 04-NOV-13:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 36.89 | 22296.39 | 16-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 85372.03 | 0.00 | ||||
Minimum of Months | 36.89 | 22296.39 | 0.00 | 0.00 | ||
Maximum of Months | 328204.03 | 1518742.15 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 48.07 | 21218.20 | 11-JAN-16:00 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 3753.98 | 563620.12 | 27-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 5990.53 | 404039.65 | 18-MAR-14:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 43389.40 | 1694216.52 | 27-APR-12:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 79754.46 | 1512440.72 | 05-MAY-15:30 | 0.00 | 0.00 | 01-MAY-00:02 |
June | 143023.69 | 1676028.71 | 21-JUN-15:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 248767.52 | 1578836.92 | 19-JUL-15:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 328670.41 | 2291329.47 | 30-AUG-15:50 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 136343.51 | 2117701.53 | 11-SEP-15:20 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 22902.78 | 937033.14 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 4513.37 | 581371.54 | 04-NOV-13:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 6.85 | 25796.68 | 16-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 85461.83 | 0.00 | ||||
Minimum of Months | 6.85 | 21218.20 | 0.00 | 0.00 | ||
Maximum of Months | 328670.41 | 2291329.47 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15563.93 | 32058.97 | 20-JAN-16:30 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 54662.67 | 307082.24 | 26-FEB-16:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 82535.45 | 492221.28 | 18-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 185044.29 | 1345364.59 | 27-APR-15:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 84536.05 | 523611.66 | 05-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:02 |
June | 146230.72 | 879593.51 | 28-JUN-17:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 331892.28 | 1320432.01 | 24-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 643587.16 | 1590163.82 | 10-AUG-17:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 60651.50 | 525341.88 | 22-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 82519.70 | 507215.77 | 08-OCT-16:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 151511.35 | 613106.52 | 04-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 318042.02 | 576974.37 | 10-DEC-16:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 181240.18 | 0.00 | ||||
Minimum of Months | 15563.93 | 32058.97 | 0.00 | 0.00 | ||
Maximum of Months | 643587.16 | 1590163.82 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 18.06 | 19262.06 | 11-JAN-16:00 | 416.59 | 94723.69 | 21-JAN-07:40 |
February | 5216.61 | 732513.01 | 27-FEB-16:00 | 502.92 | 109826.65 | 01-FEB-05:11 |
March | 8947.68 | 577246.37 | 18-MAR-14:20 | 425.32 | 79024.63 | 01-MAR-10:10 |
April | 60589.72 | 1953624.13 | 27-APR-12:50 | 764.09 | 81054.38 | 01-APR-05:03 |
May | 114474.04 | 2030400.64 | 05-MAY-15:40 | 708.33 | 63794.34 | 27-MAY-06:00 |
June | 202406.22 | 1884970.48 | 21-JUN-16:10 | 426.16 | 48338.99 | 05-JUN-09:20 |
July | 373967.11 | 3241097.79 | 31-JUL-16:00 | 432.49 | 53922.69 | 03-JUL-08:40 |
August | 539017.34 | 3881186.08 | 29-AUG-14:30 | 345.81 | 45766.21 | 05-AUG-07:50 |
September | 200227.29 | 2419021.46 | 14-SEP-13:10 | 328.48 | 46416.38 | 06-SEP-11:40 |
October | 32714.65 | 1252099.49 | 04-OCT-15:00 | 568.54 | 69586.99 | 31-OCT-17:10 |
November | 6229.23 | 825178.47 | 04-NOV-13:30 | 635.87 | 86648.37 | 13-NOV-06:40 |
December | 1.79 | 3577.79 | 12-DEC-15:20 | 478.42 | 95207.11 | 26-DEC-04:10 |
Annual Sum or Average | 129789.04 | 502.36 | ||||
Minimum of Months | 1.79 | 3577.79 | 328.48 | 45766.21 | ||
Maximum of Months | 539017.34 | 3881186.08 | 764.09 | 109826.65 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143610E+11 | 0.80 | 9430.69 | 01-JAN-00:37 | 1.41 |
February | 0.126673E+11 | 0.78 | 9430.69 | 01-FEB-05:11 | 1.40 |
March | 0.152409E+11 | 0.85 | 9430.69 | 01-MAR-04:01 | 1.41 |
April | 0.142507E+11 | 0.82 | 9430.69 | 01-APR-04:11 | 1.41 |
May | 0.150593E+11 | 0.84 | 9430.69 | 01-MAY-00:02 | 1.40 |
June | 0.150957E+11 | 0.87 | 9430.69 | 01-JUN-03:01 | 1.40 |
July | 0.149961E+11 | 0.83 | 9430.69 | 01-JUL-03:01 | 1.41 |
August | 0.160629E+11 | 0.89 | 9430.69 | 01-AUG-03:01 | 1.40 |
September | 0.149443E+11 | 0.86 | 9430.69 | 01-SEP-03:01 | 1.40 |
October | 0.151136E+11 | 0.84 | 9430.69 | 01-OCT-23:21 | 1.40 |
November | 0.146685E+11 | 0.84 | 9430.69 | 01-NOV-03:01 | 1.40 |
December | 0.143441E+11 | 0.80 | 9430.69 | 01-DEC-05:11 | 1.41 |
Annual Sum or Average | 0.176804E+12 | 0.83 | |||
Minimum of Months | 0.126673E+11 | 0.78 | 9430.69 | 1.40 | |
Maximum of Months | 0.160629E+11 | 0.89 | 9430.69 | 1.41 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.378110E+10 | 0.31 | 12213.70 | 09-JAN-06:01 | 1.33 |
February | 0.419965E+10 | 0.34 | 10807.22 | 28-FEB-05:11 | 1.22 |
March | 0.630261E+10 | 0.41 | 13657.81 | 11-MAR-05:11 | 1.41 |
April | 0.690913E+10 | 0.44 | 13831.51 | 03-APR-04:11 | 1.43 |
May | 0.555372E+10 | 0.39 | 15079.74 | 30-MAY-05:01 | 1.51 |
June | 0.600351E+10 | 0.42 | 19722.92 | 19-JUN-05:01 | 1.79 |
July | 0.656583E+10 | 0.44 | 15026.69 | 24-JUL-05:01 | 1.50 |
August | 0.761725E+10 | 0.50 | 16080.58 | 28-AUG-05:01 | 1.56 |
September | 0.529457E+10 | 0.38 | 15524.73 | 25-SEP-05:01 | 1.53 |
October | 0.560347E+10 | 0.38 | 13831.51 | 02-OCT-05:01 | 1.43 |
November | 0.511545E+10 | 0.36 | 13831.51 | 04-NOV-04:11 | 1.42 |
December | 0.521358E+10 | 0.36 | 12281.69 | 30-DEC-05:11 | 1.33 |
Annual Sum or Average | 0.681599E+11 | 0.39 | |||
Minimum of Months | 0.378110E+10 | 0.31 | 10807.22 | 1.22 | |
Maximum of Months | 0.761725E+10 | 0.50 | 19722.92 | 1.79 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.304065E+11 | 0.32 | 52949.53 | 02-JAN-05:11 | 0.86 |
February | 0.292129E+11 | 0.32 | 98442.15 | 10-FEB-06:02 | 1.25 |
March | 0.386755E+11 | 0.34 | 155181.44 | 27-MAR-05:01 | 1.66 |
April | 0.380311E+11 | 0.34 | 116613.17 | 19-APR-05:03 | 1.39 |
May | 0.427530E+11 | 0.36 | 98804.50 | 05-MAY-05:02 | 1.24 |
June | 0.438251E+11 | 0.37 | 94392.53 | 01-JUN-05:03 | 1.21 |
July | 0.448904E+11 | 0.37 | 144481.14 | 24-JUL-05:01 | 1.57 |
August | 0.506212E+11 | 0.40 | 155875.63 | 14-AUG-05:03 | 1.65 |
September | 0.434334E+11 | 0.36 | 94708.27 | 12-SEP-05:02 | 1.21 |
October | 0.383534E+11 | 0.33 | 94392.53 | 02-OCT-05:01 | 1.21 |
November | 0.307002E+11 | 0.31 | 94392.53 | 03-NOV-05:03 | 1.21 |
December | 0.303265E+11 | 0.30 | 44957.46 | 06-DEC-13:10 | 0.79 |
Annual Sum or Average | 0.461229E+12 | 0.34 | |||
Minimum of Months | 0.292129E+11 | 0.30 | 44957.46 | 0.79 | |
Maximum of Months | 0.506212E+11 | 0.40 | 155875.63 | 1.66 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.332627E+10 | 0.34 | 4828.14 | 02-JAN-04:01 | 0.78 |
February | 0.288525E+10 | 0.32 | 4828.14 | 06-FEB-05:11 | 0.78 |
March | 0.318029E+10 | 0.31 | 4828.14 | 06-MAR-05:11 | 0.78 |
April | 0.322155E+10 | 0.30 | 7950.57 | 27-APR-05:03 | 1.04 |
May | 0.373600E+10 | 0.33 | 7950.57 | 05-MAY-05:02 | 1.04 |
June | 0.405236E+10 | 0.34 | 7950.57 | 01-JUN-05:03 | 1.04 |
July | 0.437177E+10 | 0.34 | 14478.19 | 24-JUL-05:01 | 1.50 |
August | 0.485116E+10 | 0.37 | 9820.15 | 14-AUG-05:03 | 1.18 |
September | 0.366904E+10 | 0.32 | 7950.57 | 01-SEP-05:03 | 1.04 |
October | 0.303931E+10 | 0.29 | 5543.59 | 04-OCT-14:40 | 0.85 |
November | 0.268748E+10 | 0.29 | 4828.14 | 13-NOV-05:01 | 0.78 |
December | 0.296133E+10 | 0.30 | 4828.14 | 04-DEC-05:11 | 0.79 |
Annual Sum or Average | 0.419818E+11 | 0.32 | |||
Minimum of Months | 0.268748E+10 | 0.29 | 4828.14 | 0.78 | |
Maximum of Months | 0.485116E+10 | 0.37 | 14478.19 | 1.50 |
Report: FanReportMonthly
For: DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.955846E+11 | 1.37 | 35687.21 | 01-JAN-00:03 | 1.37 |
February | 0.863345E+11 | 1.37 | 35687.21 | 01-FEB-00:10 | 1.37 |
March | 0.955846E+11 | 1.38 | 35687.21 | 01-MAR-00:10 | 1.38 |
April | 0.925013E+11 | 1.38 | 35687.21 | 01-APR-00:10 | 1.37 |
May | 0.955846E+11 | 1.37 | 35687.21 | 01-MAY-00:02 | 1.37 |
June | 0.925013E+11 | 1.37 | 35687.21 | 01-JUN-00:10 | 1.37 |
July | 0.955846E+11 | 1.37 | 35687.21 | 01-JUL-00:10 | 1.37 |
August | 0.955846E+11 | 1.37 | 35687.21 | 01-AUG-00:05 | 1.37 |
September | 0.925013E+11 | 1.37 | 35687.21 | 01-SEP-00:03 | 1.37 |
October | 0.955846E+11 | 1.37 | 35687.21 | 01-OCT-00:10 | 1.37 |
November | 0.925013E+11 | 1.37 | 35687.21 | 01-NOV-00:10 | 1.37 |
December | 0.955846E+11 | 1.38 | 35687.21 | 01-DEC-00:10 | 1.37 |
Annual Sum or Average | 0.112543E+13 | 1.37 | |||
Minimum of Months | 0.863345E+11 | 1.37 | 35687.21 | 1.37 | |
Maximum of Months | 0.955846E+11 | 1.38 | 35687.21 | 1.38 |
Report: FanReportMonthly
For: DATACENTER BOT SUPPLY FAN
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149159E+10 | 0.93 | 556.89 | 01-JAN-00:03 | 0.93 |
February | 0.134724E+10 | 0.93 | 556.89 | 01-FEB-00:10 | 0.93 |
March | 0.149159E+10 | 0.93 | 556.89 | 01-MAR-00:10 | 0.93 |
April | 0.144347E+10 | 0.93 | 556.89 | 01-APR-00:10 | 0.93 |
May | 0.149159E+10 | 0.93 | 556.89 | 01-MAY-00:02 | 0.93 |
June | 0.144347E+10 | 0.93 | 556.89 | 01-JUN-00:10 | 0.93 |
July | 0.149159E+10 | 0.93 | 556.89 | 01-JUL-00:10 | 0.93 |
August | 0.149159E+10 | 0.93 | 556.89 | 01-AUG-00:05 | 0.93 |
September | 0.144347E+10 | 0.93 | 556.89 | 01-SEP-00:03 | 0.93 |
October | 0.149159E+10 | 0.93 | 556.89 | 01-OCT-00:10 | 0.93 |
November | 0.144347E+10 | 0.93 | 556.89 | 01-NOV-00:10 | 0.93 |
December | 0.149159E+10 | 0.93 | 556.89 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.175622E+11 | 0.93 | |||
Minimum of Months | 0.134724E+10 | 0.93 | 556.89 | 0.93 | |
Maximum of Months | 0.149159E+10 | 0.93 | 556.89 | 0.93 |
Report: FanReportMonthly
For: DATACENTER MID SUPPLY FAN
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142939E+11 | 0.93 | 5336.73 | 01-JAN-00:03 | 0.93 |
February | 0.129106E+11 | 0.93 | 5336.73 | 01-FEB-00:10 | 0.93 |
March | 0.142939E+11 | 0.93 | 5336.73 | 01-MAR-00:10 | 0.93 |
April | 0.138328E+11 | 0.93 | 5336.73 | 01-APR-00:10 | 0.93 |
May | 0.142939E+11 | 0.93 | 5336.73 | 01-MAY-00:02 | 0.93 |
June | 0.138328E+11 | 0.93 | 5336.73 | 01-JUN-00:20 | 0.93 |
July | 0.142939E+11 | 0.93 | 5336.73 | 01-JUL-00:10 | 0.93 |
August | 0.142939E+11 | 0.93 | 5336.73 | 01-AUG-00:05 | 0.93 |
September | 0.138328E+11 | 0.93 | 5336.73 | 01-SEP-00:05 | 0.93 |
October | 0.142939E+11 | 0.93 | 5336.73 | 01-OCT-00:30 | 0.93 |
November | 0.138328E+11 | 0.93 | 5336.73 | 01-NOV-00:10 | 0.93 |
December | 0.142939E+11 | 0.93 | 5336.73 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.168299E+12 | 0.93 | |||
Minimum of Months | 0.129106E+11 | 0.93 | 5336.73 | 0.93 | |
Maximum of Months | 0.142939E+11 | 0.93 | 5336.73 | 0.93 |
Report: FanReportMonthly
For: DATACENTER TOP SUPPLY FAN
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144994E+10 | 0.93 | 541.35 | 01-JAN-00:03 | 0.93 |
February | 0.130963E+10 | 0.93 | 541.35 | 01-FEB-00:10 | 0.93 |
March | 0.144994E+10 | 0.93 | 541.35 | 01-MAR-00:10 | 0.93 |
April | 0.140317E+10 | 0.93 | 541.35 | 01-APR-00:10 | 0.93 |
May | 0.144994E+10 | 0.93 | 541.35 | 01-MAY-00:02 | 0.93 |
June | 0.140317E+10 | 0.93 | 541.35 | 01-JUN-00:10 | 0.93 |
July | 0.144994E+10 | 0.93 | 541.35 | 01-JUL-00:10 | 0.93 |
August | 0.144994E+10 | 0.93 | 541.35 | 01-AUG-00:05 | 0.93 |
September | 0.140317E+10 | 0.93 | 541.35 | 01-SEP-00:03 | 0.93 |
October | 0.144994E+10 | 0.93 | 541.35 | 01-OCT-00:10 | 0.93 |
November | 0.140317E+10 | 0.93 | 541.35 | 01-NOV-00:10 | 0.93 |
December | 0.144994E+10 | 0.93 | 541.35 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.170719E+11 | 0.93 | |||
Minimum of Months | 0.130963E+10 | 0.93 | 541.35 | 0.93 | |
Maximum of Months | 0.144994E+10 | 0.93 | 541.35 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 29840762.48 | 26856686.24 | 1171.79 | 02-JAN-06:01 | 1054.61 | 1054.61 | 69.22 | 21.00 |
February | 10465071.87 | 9418564.69 | 719.74 | 21-FEB-06:03 | 647.77 | 647.77 | 64.68 | 16.78 |
March | 2538959.84 | 2285063.86 | 395.69 | 06-MAR-06:03 | 356.12 | 356.12 | 59.78 | 12.58 |
April | 831579.85 | 748421.87 | 259.27 | 11-APR-05:03 | 233.34 | 233.34 | 52.56 | 10.19 |
May | 3248669.02 | 2923802.12 | 1417.32 | 26-MAY-04:53 | 1275.59 | 1275.59 | 81.44 | 22.72 |
June | 53061.84 | 47755.66 | 99.37 | 11-JUN-19:30 | 89.44 | 89.44 | 71.24 | 5.99 |
July | 337728.30 | 303955.47 | 99.52 | 31-JUL-03:30 | 89.57 | 89.57 | 72.65 | 5.99 |
August | 296202.71 | 266582.44 | 99.52 | 13-AUG-18:30 | 89.57 | 89.57 | 72.68 | 5.99 |
September | 436030.03 | 392427.03 | 99.52 | 04-SEP-20:50 | 89.57 | 89.57 | 72.66 | 5.99 |
October | 951585.25 | 856426.72 | 1397.30 | 11-OCT-03:02 | 1257.57 | 1257.57 | 70.98 | 22.72 |
November | 5291441.96 | 4762297.76 | 398.87 | 27-NOV-06:02 | 358.98 | 358.98 | 58.03 | 12.64 |
December | 12990429.11 | 11691386.20 | 560.35 | 26-DEC-06:02 | 504.32 | 504.32 | 64.40 | 14.88 |
Annual Sum or Average | 67281522.27 | 60553370.04 | ||||||
Minimum of Months | 53061.84 | 47755.66 | 99.37 | 89.44 | 89.44 | 52.56 | 5.99 | |
Maximum of Months | 29840762.48 | 26856686.24 | 1417.32 | 1275.59 | 1275.59 | 81.44 | 22.72 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 60843.95 | 54759.55 | 7.83 | 11-JAN-14:00 | 7.05 | 7.05 | 6.70 | 1.35 |
February | 5331794.93 | 4798615.43 | 658.68 | 27-FEB-16:00 | 592.81 | 592.81 | 6.71 | 17.58 |
March | 6274079.80 | 5646671.82 | 157.47 | 18-MAR-12:00 | 141.72 | 141.72 | 6.70 | 8.72 |
April | 0.109366E+09 | 98429810.48 | 8764.23 | 27-APR-12:30 | 7887.80 | 7887.80 | 10.07 | 52.97 |
May | 0.180211E+09 | 0.162190E+09 | 4855.28 | 04-MAY-14:40 | 4369.75 | 4369.75 | 8.59 | 41.78 |
June | 0.389500E+09 | 0.350550E+09 | 7258.03 | 21-JUN-15:30 | 6532.23 | 6532.23 | 10.07 | 49.14 |
July | 0.723753E+09 | 0.651378E+09 | 7719.57 | 19-JUL-15:00 | 6947.61 | 6947.61 | 9.70 | 50.37 |
August | 0.104997E+10 | 0.944970E+09 | 10581.18 | 30-AUG-15:50 | 9523.07 | 9523.07 | 11.47 | 57.05 |
September | 0.394761E+09 | 0.355285E+09 | 10639.92 | 11-SEP-15:20 | 9575.93 | 9575.93 | 11.38 | 57.18 |
October | 34924270.25 | 31431843.22 | 743.56 | 04-OCT-15:00 | 669.21 | 669.21 | 6.71 | 18.59 |
November | 7099896.85 | 6389907.17 | 458.72 | 04-NOV-13:30 | 412.85 | 412.85 | 6.71 | 14.84 |
December | 5239.80 | 4715.82 | 7.67 | 16-DEC-06:02 | 6.90 | 6.90 | 6.70 | 1.33 |
Annual Sum or Average | 0.290125E+10 | 0.261113E+10 | ||||||
Minimum of Months | 5239.80 | 4715.82 | 7.67 | 6.90 | 6.90 | 6.70 | 1.33 | |
Maximum of Months | 0.104997E+10 | 0.944970E+09 | 10639.92 | 9575.93 | 9575.93 | 11.47 | 57.18 |
Report: PumpReportMonthly
For: SHWSYS1 PUMP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871592.27 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 73.94 | 0.44 |
February | 0.101979E+09 | 30593696.24 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 66.25 | 0.44 |
March | 0.112905E+09 | 33871592.27 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 66.34 | 0.44 |
April | 0.109263E+09 | 32778960.26 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 66.51 | 0.44 |
May | 0.112905E+09 | 33871592.27 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 77.70 | 0.44 |
June | 0.109263E+09 | 32778960.26 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 66.25 | 0.44 |
July | 0.112905E+09 | 33871592.27 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 65.08 | 0.44 |
August | 0.112905E+09 | 33871592.27 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 67.06 | 0.44 |
September | 0.109263E+09 | 32778960.26 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 68.85 | 0.44 |
October | 0.112905E+09 | 33871592.27 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 74.71 | 0.44 |
November | 0.109263E+09 | 32778960.26 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 66.65 | 0.44 |
December | 0.112905E+09 | 33871592.27 | 56.21 | 01-DEC-06:02 | 16.86 | 16.86 | 64.50 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398811E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593696.24 | 56.21 | 16.86 | 16.86 | 64.50 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871592.27 | 56.21 | 16.86 | 16.86 | 77.70 | 0.44 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.107873E+09 | 97085661.32 | 1864.06 | 01-JAN-05:40 | 1677.65 | 1677.65 | 6.71 | 29.23 |
February | 0.184187E+09 | 0.165769E+09 | 1864.06 | 01-FEB-05:11 | 1677.65 | 1677.65 | 6.72 | 29.23 |
March | 0.293701E+09 | 0.264331E+09 | 1864.06 | 01-MAR-06:03 | 1677.65 | 1677.65 | 6.86 | 29.23 |
April | 0.876573E+09 | 0.788915E+09 | 1864.06 | 01-APR-05:03 | 1677.65 | 1677.65 | 6.71 | 29.23 |
May | 0.156340E+10 | 0.140706E+10 | 1864.06 | 01-MAY-00:02 | 1677.65 | 1677.65 | 6.83 | 29.23 |
June | 0.228140E+10 | 0.205326E+10 | 1864.06 | 01-JUN-03:01 | 1677.65 | 1677.65 | 7.48 | 29.23 |
July | 0.303936E+10 | 0.273542E+10 | 1864.06 | 01-JUL-03:01 | 1677.65 | 1677.65 | 7.72 | 29.23 |
August | 0.335869E+10 | 0.302282E+10 | 1864.06 | 01-AUG-00:52 | 1677.65 | 1677.65 | 6.86 | 29.23 |
September | 0.198608E+10 | 0.178747E+10 | 1864.06 | 01-SEP-00:03 | 1677.65 | 1677.65 | 6.80 | 29.23 |
October | 0.765981E+09 | 0.689383E+09 | 1864.06 | 01-OCT-13:10 | 1677.65 | 1677.65 | 6.79 | 29.23 |
November | 0.263130E+09 | 0.236817E+09 | 1864.06 | 01-NOV-03:01 | 1677.65 | 1677.65 | 6.78 | 29.23 |
December | 89306953.01 | 80376257.71 | 1864.06 | 01-DEC-12:00 | 1677.65 | 1677.65 | 6.72 | 29.23 |
Annual Sum or Average | 0.148097E+11 | 0.133287E+11 | ||||||
Minimum of Months | 89306953.01 | 80376257.71 | 1864.06 | 1677.65 | 1677.65 | 6.71 | 29.23 | |
Maximum of Months | 0.335869E+10 | 0.302282E+10 | 1864.06 | 1677.65 | 1677.65 | 7.72 | 29.23 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 6.71 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.71 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.97 | 0.00 |
April | 35789887.24 | 32210898.52 | 1864.06 | 26-APR-14:00 | 1677.65 | 1677.65 | 14.85 | 14.62 |
May | 29079283.38 | 26171355.05 | 1864.06 | 04-MAY-14:50 | 1677.65 | 1677.65 | 14.97 | 14.62 |
June | 43618925.08 | 39257032.57 | 1864.06 | 09-JUN-15:30 | 1677.65 | 1677.65 | 14.73 | 14.62 |
July | 0.258358E+09 | 0.232522E+09 | 1864.06 | 07-JUL-12:30 | 1677.65 | 1677.65 | 15.47 | 14.62 |
August | 0.581026E+09 | 0.522924E+09 | 1864.06 | 07-AUG-11:00 | 1677.65 | 1677.65 | 15.45 | 14.62 |
September | 0.147074E+09 | 0.132367E+09 | 1864.06 | 11-SEP-14:00 | 1677.65 | 1677.65 | 15.28 | 14.62 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 6.78 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.71 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.109495E+10 | 0.985452E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.71 | 0.00 | |
Maximum of Months | 0.581026E+09 | 0.522924E+09 | 1864.06 | 1677.65 | 1677.65 | 15.47 | 14.62 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.892724E+10 | 0.803452E+10 | 3333.05 | 01-JAN-00:03 | 2999.75 | 2999.75 | 18.47 | 13.92 |
February | 0.806332E+10 | 0.725698E+10 | 3333.05 | 01-FEB-00:10 | 2999.75 | 2999.75 | 19.15 | 13.92 |
March | 0.892724E+10 | 0.803452E+10 | 3333.05 | 01-MAR-00:10 | 2999.75 | 2999.75 | 19.89 | 13.92 |
April | 0.863927E+10 | 0.777534E+10 | 3333.05 | 01-APR-00:10 | 2999.75 | 2999.75 | 20.38 | 13.92 |
May | 0.892724E+10 | 0.803452E+10 | 3333.05 | 01-MAY-00:02 | 2999.75 | 2999.75 | 19.58 | 13.92 |
June | 0.863927E+10 | 0.777534E+10 | 3333.05 | 01-JUN-00:10 | 2999.75 | 2999.75 | 19.41 | 13.92 |
July | 0.892724E+10 | 0.803452E+10 | 3333.05 | 01-JUL-00:10 | 2999.75 | 2999.75 | 19.99 | 13.92 |
August | 0.892724E+10 | 0.803452E+10 | 3333.05 | 01-AUG-00:05 | 2999.75 | 2999.75 | 26.18 | 13.92 |
September | 0.863927E+10 | 0.777534E+10 | 3333.05 | 01-SEP-00:03 | 2999.75 | 2999.75 | 21.74 | 13.92 |
October | 0.892724E+10 | 0.803452E+10 | 3333.05 | 01-OCT-00:10 | 2999.75 | 2999.75 | 19.31 | 13.92 |
November | 0.863927E+10 | 0.777534E+10 | 3333.05 | 01-NOV-00:10 | 2999.75 | 2999.75 | 19.74 | 13.92 |
December | 0.892724E+10 | 0.803452E+10 | 3333.05 | 01-DEC-00:10 | 2999.75 | 2999.75 | 29.57 | 13.92 |
Annual Sum or Average | 0.105111E+12 | 0.946000E+11 | ||||||
Minimum of Months | 0.806332E+10 | 0.725698E+10 | 3333.05 | 2999.75 | 2999.75 | 18.47 | 13.92 | |
Maximum of Months | 0.892724E+10 | 0.803452E+10 | 3333.05 | 2999.75 | 2999.75 | 29.57 | 13.92 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.639052E+09 | 0.575147E+09 | 11044.26 | 11-JAN-16:00 | 9939.83 | 9939.83 | 21.19 | 52.36 |
February | 0.109163E+10 | 0.982466E+09 | 11070.18 | 27-FEB-16:00 | 9963.16 | 9963.16 | 24.45 | 52.36 |
March | 0.174085E+10 | 0.156677E+10 | 11064.53 | 18-MAR-14:20 | 9958.08 | 9958.08 | 23.74 | 52.36 |
April | 0.537783E+10 | 0.484005E+10 | 22159.71 | 27-APR-12:50 | 19943.74 | 19943.74 | 25.56 | 104.72 |
May | 0.939942E+10 | 0.845948E+10 | 22162.97 | 05-MAY-15:40 | 19946.67 | 19946.67 | 25.74 | 104.72 |
June | 0.137407E+11 | 0.123666E+11 | 22156.79 | 21-JUN-16:10 | 19941.12 | 19941.12 | 25.41 | 104.72 |
July | 0.194750E+11 | 0.175275E+11 | 22214.46 | 31-JUL-16:00 | 19993.01 | 19993.01 | 28.50 | 104.72 |
August | 0.232755E+11 | 0.209479E+11 | 22220.11 | 24-AUG-14:40 | 19998.10 | 19998.10 | 28.82 | 104.72 |
September | 0.126039E+11 | 0.113435E+11 | 22179.47 | 14-SEP-13:10 | 19961.52 | 19961.52 | 26.63 | 104.72 |
October | 0.454118E+10 | 0.408707E+10 | 11091.53 | 04-OCT-15:00 | 9982.38 | 9982.38 | 26.82 | 52.36 |
November | 0.155944E+10 | 0.140349E+10 | 11073.55 | 04-NOV-13:30 | 9966.20 | 9966.20 | 24.87 | 52.36 |
December | 0.529051E+09 | 0.476146E+09 | 11043.69 | 12-DEC-15:20 | 9939.32 | 9939.32 | 21.12 | 52.36 |
Annual Sum or Average | 0.939735E+11 | 0.845761E+11 | ||||||
Minimum of Months | 0.529051E+09 | 0.476146E+09 | 11043.69 | 9939.32 | 9939.32 | 21.12 | 52.36 | |
Maximum of Months | 0.232755E+11 | 0.209479E+11 | 22220.11 | 19998.10 | 19998.10 | 28.82 | 104.72 |
Report: CondLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 6787.43 | 37526.89 | 01-JAN-08:50 | 80.31 | 82.22 | 13318.00 | 52063.91 | 31-JAN-12:40 |
February | 6409.74 | 37475.12 | 26-FEB-09:20 | 80.28 | 82.22 | 13474.03 | 52120.91 | 10-FEB-12:40 |
March | 5193.24 | 37533.81 | 26-MAR-08:10 | 80.31 | 82.22 | 14414.51 | 51950.95 | 01-MAR-12:40 |
April | 6274.73 | 37664.84 | 30-APR-22:11 | 80.38 | 82.22 | 12929.57 | 50802.46 | 03-APR-12:00 |
May | 6206.37 | 37790.97 | 29-MAY-07:25 | 80.45 | 82.22 | 12917.15 | 49263.99 | 01-MAY-11:20 |
June | 5603.84 | 37893.86 | 25-JUN-07:27 | 80.51 | 82.22 | 12743.41 | 47354.51 | 01-JUN-11:50 |
July | 7245.02 | 37970.63 | 30-JUL-07:18 | 80.55 | 82.22 | 11130.61 | 45745.74 | 03-JUL-11:50 |
August | 5586.21 | 37977.34 | 13-AUG-07:20 | 80.55 | 82.22 | 12274.90 | 45093.08 | 31-AUG-12:00 |
September | 6555.99 | 37959.85 | 03-SEP-07:40 | 80.54 | 82.22 | 11593.92 | 46055.67 | 29-SEP-11:40 |
October | 7104.15 | 37889.69 | 01-OCT-07:50 | 80.50 | 82.22 | 11941.27 | 47800.13 | 31-OCT-11:40 |
November | 7121.18 | 37751.04 | 05-NOV-07:50 | 80.43 | 82.22 | 12639.07 | 49635.85 | 30-NOV-12:40 |
December | 6913.47 | 37630.11 | 03-DEC-09:10 | 80.36 | 82.22 | 12592.07 | 51144.45 | 29-DEC-12:50 |
Annual Sum or Average | 6417.14 | 12659.44 | ||||||
Minimum of Months | 5193.24 | 37475.12 | 80.28 | 82.22 | 11130.61 | 45093.08 | ||
Maximum of Months | 7245.02 | 37977.34 | 80.55 | 82.22 | 14414.51 | 52120.91 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 54.41 | 54.41 | 96998.83 | 1743411.44 | 28-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 47.56 | 47.56 | 55908.75 | 1702436.18 | 16-FEB-05:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 44.40 | 44.40 | 15844.82 | 1786334.83 | 13-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 43.59 | 43.59 | 5997.86 | 1254188.55 | 11-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 56.12 | 56.12 | 1006.17 | 2753747.24 | 23-MAY-03:04 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 71.84 | 71.84 | 71.76 | 333965.32 | 19-JUN-01:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 69.53 | 69.53 | 316.96 | 302519.33 | 02-JUL-19:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 72.65 | 72.65 | 261.63 | 236161.83 | 06-AUG-21:20 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 72.66 | 72.66 | 460.00 | 315291.62 | 24-SEP-23:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 58.83 | 58.83 | 4919.46 | 1867842.01 | 02-OCT-01:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 43.16 | 43.16 | 32254.69 | 1746294.50 | 24-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 49.06 | 49.06 | 65016.88 | 1677818.15 | 18-DEC-05:11 |
Annual Sum or Average | 0.00 | 23135.02 | ||||||
Minimum of Months | 0.00 | 0.00 | 43.16 | 43.16 | 71.76 | 236161.83 | ||
Maximum of Months | 0.00 | 0.00 | 72.66 | 72.66 | 96998.83 | 2753747.24 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 84.31 | 22821.86 | 11-JAN-16:00 | 6.89 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 3817.60 | 540495.15 | 27-FEB-16:00 | 11.11 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 6087.14 | 405147.64 | 18-MAR-14:10 | 10.01 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 43250.95 | 1399417.97 | 26-APR-15:20 | 12.42 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 80036.45 | 1387971.87 | 04-MAY-15:50 | 12.37 | 6.70 | 0.00 | 0.00 | 01-MAY-00:02 |
June | 142341.64 | 1349714.93 | 21-JUN-15:10 | 12.21 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 248715.96 | 1369776.03 | 31-JUL-16:00 | 12.29 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 328204.03 | 1518742.15 | 29-AUG-14:40 | 12.90 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 135757.31 | 1295067.70 | 11-SEP-14:10 | 11.99 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 23138.76 | 933619.55 | 04-OCT-15:00 | 14.33 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 4599.75 | 582080.70 | 04-NOV-13:30 | 11.45 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 36.89 | 22296.39 | 16-DEC-06:02 | 6.88 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 85372.03 | 0.00 | ||||||
Minimum of Months | 36.89 | 22296.39 | 6.88 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 328204.03 | 1518742.15 | 14.33 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 48.07 | 21218.20 | 11-JAN-16:00 | 10.48 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 3753.98 | 563620.12 | 27-FEB-16:00 | 14.36 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 5990.53 | 404039.65 | 18-MAR-14:10 | 18.73 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 43389.40 | 1694216.52 | 27-APR-12:30 | 14.34 | 10.11 | 0.00 | 0.00 | 01-APR-00:10 |
May | 79754.46 | 1512440.72 | 05-MAY-15:30 | 16.30 | 9.34 | 0.00 | 0.00 | 01-MAY-00:02 |
June | 143023.69 | 1676028.71 | 21-JUN-15:30 | 14.85 | 10.24 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 248767.52 | 1578836.92 | 19-JUL-15:10 | 16.73 | 8.92 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 328670.41 | 2291329.47 | 30-AUG-15:50 | 16.30 | 11.71 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 136343.51 | 2117701.53 | 11-SEP-15:20 | 15.55 | 11.35 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 22902.78 | 937033.14 | 04-OCT-15:00 | 18.75 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 4513.37 | 581371.54 | 04-NOV-13:30 | 16.07 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 6.85 | 25796.68 | 16-DEC-06:02 | 11.33 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 85461.83 | 0.00 | ||||||
Minimum of Months | 6.85 | 21218.20 | 10.48 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 328670.41 | 2291329.47 | 18.75 | 11.71 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15563.93 | 32058.97 | 20-JAN-16:30 | 18.99 | 18.33 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 54662.67 | 307082.24 | 26-FEB-16:30 | 24.66 | 18.33 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 82535.45 | 492221.28 | 18-MAR-16:00 | 28.44 | 22.88 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 185044.29 | 1345364.59 | 27-APR-15:10 | 45.53 | 32.63 | 0.00 | 0.00 | 01-APR-00:10 |
May | 84536.05 | 523611.66 | 05-MAY-16:00 | 29.08 | 26.19 | 0.00 | 0.00 | 01-MAY-00:02 |
June | 146230.72 | 879593.51 | 28-JUN-17:00 | 36.27 | 29.50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 331892.28 | 1320432.01 | 24-JUL-15:00 | 45.03 | 34.87 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 643587.16 | 1590163.82 | 10-AUG-17:00 | 50.33 | 37.32 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 60651.50 | 525341.88 | 22-SEP-16:00 | 29.12 | 26.20 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 82519.70 | 507215.77 | 08-OCT-16:00 | 28.75 | 22.54 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 151511.35 | 613106.52 | 04-NOV-15:00 | 30.90 | 23.95 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 318042.02 | 576974.37 | 10-DEC-16:00 | 30.16 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 181240.18 | 0.00 | ||||||
Minimum of Months | 15563.93 | 32058.97 | 18.99 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 643587.16 | 1590163.82 | 50.33 | 37.32 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 18.06 | 19262.06 | 11-JAN-16:00 | 21.19 | 20.77 | 416.59 | 94723.69 | 21-JAN-07:40 |
February | 5216.61 | 732513.01 | 27-FEB-16:00 | 24.45 | 21.72 | 502.92 | 109826.65 | 01-FEB-05:11 |
March | 8947.68 | 577246.37 | 18-MAR-14:20 | 23.74 | 21.59 | 425.32 | 79024.63 | 01-MAR-10:10 |
April | 60589.72 | 1953624.13 | 27-APR-12:50 | 25.56 | 22.17 | 764.09 | 81054.38 | 01-APR-05:03 |
May | 114474.04 | 2030400.64 | 05-MAY-15:40 | 25.74 | 22.62 | 708.33 | 63794.34 | 27-MAY-06:00 |
June | 202406.22 | 1884970.48 | 21-JUN-16:10 | 25.41 | 22.09 | 426.16 | 48338.99 | 05-JUN-09:20 |
July | 373967.11 | 3241097.79 | 31-JUL-16:00 | 28.50 | 24.86 | 432.49 | 53922.69 | 03-JUL-08:40 |
August | 539017.34 | 3881186.08 | 29-AUG-14:30 | 29.97 | 25.90 | 345.81 | 45766.21 | 05-AUG-07:50 |
September | 200227.29 | 2419021.46 | 14-SEP-13:10 | 26.63 | 23.26 | 328.48 | 46416.38 | 06-SEP-11:40 |
October | 32714.65 | 1252099.49 | 04-OCT-15:00 | 26.82 | 21.10 | 568.54 | 69586.99 | 31-OCT-17:10 |
November | 6229.23 | 825178.47 | 04-NOV-13:30 | 24.87 | 21.80 | 635.87 | 86648.37 | 13-NOV-06:40 |
December | 1.79 | 3577.79 | 12-DEC-15:20 | 21.12 | 20.54 | 478.42 | 95207.11 | 26-DEC-04:10 |
Annual Sum or Average | 129789.04 | 502.36 | ||||||
Minimum of Months | 1.79 | 3577.79 | 21.12 | 20.54 | 328.48 | 45766.21 | ||
Maximum of Months | 539017.34 | 3881186.08 | 29.97 | 25.90 | 764.09 | 109826.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.96 | 7.48 |
February | 0.32 | 6.18 |
March | 0.12 | 7.48 |
April | 0.67 | 7.48 |
May | 0.43 | 3.86 |
June | 0.62 | 5.65 |
July | 1.60 | 6.11 |
August | 0.64 | 5.37 |
September | 1.53 | 6.19 |
October | 1.15 | 6.49 |
November | 0.64 | 7.48 |
December | 0.33 | 7.48 |
Annual Sum or Average | 9.01 | 6.40 |
Minimum of Months | 0.12 | 3.86 |
Maximum of Months | 1.60 | 7.48 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.54 | 13.25 |
February | 1.60 | 11.62 |
March | 1.31 | 6.23 |
April | 6.81 | 3.44 |
May | 2.23 | 4.16 |
June | 4.86 | 2.98 |
July | 10.30 | 3.33 |
August | 15.22 | 1.87 |
September | 2.54 | 2.46 |
October | 1.96 | 3.58 |
November | 1.15 | 5.10 |
December | 0.89 | 8.10 |
Annual Sum or Average | 50.42 | 3.64 |
Minimum of Months | 0.89 | 1.87 |
Maximum of Months | 15.22 | 13.25 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.22 | 11.76 |
February | 0.76 | 11.36 |
March | 0.39 | 12.48 |
April | 0.97 | 9.88 |
May | 1.76 | 10.01 |
June | 2.99 | 10.46 |
July | 1.88 | 7.91 |
August | 2.44 | 6.91 |
September | 2.23 | 10.32 |
October | 1.15 | 10.60 |
November | 0.70 | 11.20 |
December | 0.32 | 10.61 |
Annual Sum or Average | 15.81 | 9.66 |
Minimum of Months | 0.22 | 6.91 |
Maximum of Months | 2.99 | 12.48 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.33 | 10.08 |
March | 0.47 | 12.65 |
April | 1.32 | 11.38 |
May | 2.33 | 11.60 |
June | 2.12 | 10.33 |
July | 1.94 | 7.92 |
August | 2.22 | 8.78 |
September | 1.89 | 10.33 |
October | 1.06 | 13.08 |
November | 0.28 | 9.40 |
December | 0.00 | 0.00 |
Annual Sum or Average | 13.95 | 10.32 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.33 | 13.08 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.11 | 0.84 |
April | 2.01 | 0.48 |
May | 1.04 | 0.38 |
June | 1.82 | 0.52 |
July | 3.59 | 0.47 |
August | 5.75 | 0.31 |
September | 1.03 | 0.43 |
October | 0.49 | 0.55 |
November | 0.28 | 0.67 |
December | 0.00 | 0.00 |
Annual Sum or Average | 16.11 | 0.42 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 5.75 | 0.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 1.09 |
February | 0.43 | 0.75 |
March | 0.90 | 0.49 |
April | 3.67 | 0.39 |
May | 2.59 | 0.39 |
June | 3.92 | 0.41 |
July | 5.86 | 0.32 |
August | 8.84 | 0.20 |
September | 2.84 | 0.59 |
October | 1.28 | 0.44 |
November | 0.62 | 0.50 |
December | 0.19 | 0.54 |
Annual Sum or Average | 31.31 | 0.36 |
Minimum of Months | 0.17 | 0.20 |
Maximum of Months | 8.84 | 1.09 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 0.84 |
February | 0.32 | 0.84 |
March | 0.54 | 0.54 |
April | 2.69 | 0.48 |
May | 1.53 | 0.46 |
June | 2.49 | 0.57 |
July | 4.52 | 0.46 |
August | 7.31 | 0.29 |
September | 1.42 | 0.60 |
October | 0.74 | 0.59 |
November | 0.36 | 0.71 |
December | 0.06 | 0.84 |
Annual Sum or Average | 22.06 | 0.45 |
Minimum of Months | 0.06 | 0.29 |
Maximum of Months | 7.31 | 0.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.53 | 0.96 |
February | 1.47 | 0.81 |
March | 2.76 | 0.62 |
April | 8.53 | 0.31 |
May | 4.22 | 0.54 |
June | 5.50 | 0.30 |
July | 11.96 | 0.31 |
August | 18.87 | 0.19 |
September | 5.61 | 0.38 |
October | 3.54 | 0.52 |
November | 2.64 | 0.56 |
December | 1.97 | 0.70 |
Annual Sum or Average | 68.61 | 0.36 |
Minimum of Months | 1.47 | 0.19 |
Maximum of Months | 18.87 | 0.96 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.10 | 0.36 |
February | 0.04 | 0.84 |
March | 0.00 | 0.00 |
April | 0.06 | 0.84 |
May | 0.36 | 0.78 |
June | 0.46 | 0.69 |
July | 0.47 | 0.57 |
August | 0.44 | 1.00 |
September | 0.48 | 1.13 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 2.41 | 0.82 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.48 | 1.13 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.21 | 0.54 |
February | 0.25 | 0.54 |
March | 0.06 | 0.54 |
April | 0.55 | 0.71 |
May | 2.29 | 0.59 |
June | 2.26 | 0.58 |
July | 2.05 | 0.37 |
August | 2.07 | 0.61 |
September | 2.38 | 0.78 |
October | 0.58 | 0.78 |
November | 0.11 | 0.54 |
December | 0.00 | 0.00 |
Annual Sum or Average | 12.80 | 0.60 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.38 | 0.78 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.21 | 0.84 |
February | 0.00 | 0.00 |
March | 0.14 | 1.35 |
April | 0.27 | 0.58 |
May | 1.14 | 0.62 |
June | 1.32 | 0.92 |
July | 1.40 | 0.71 |
August | 1.14 | 0.84 |
September | 1.94 | 1.22 |
October | 0.37 | 1.22 |
November | 0.25 | 0.84 |
December | 0.00 | 0.00 |
Annual Sum or Average | 8.18 | 0.91 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.94 | 1.35 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.12 | 0.54 |
February | 0.08 | 1.09 |
March | 0.39 | 1.01 |
April | 1.07 | 0.76 |
May | 2.26 | 0.77 |
June | 2.81 | 0.72 |
July | 3.16 | 0.57 |
August | 3.15 | 0.67 |
September | 2.76 | 0.81 |
October | 0.83 | 0.92 |
November | 0.33 | 0.68 |
December | 0.00 | 0.00 |
Annual Sum or Average | 16.97 | 0.72 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.16 | 1.09 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.23 | 0.54 |
February | 0.46 | 0.59 |
March | 0.25 | 0.28 |
April | 0.06 | 0.84 |
May | 0.31 | 0.84 |
June | 0.32 | 0.84 |
July | 0.71 | 0.60 |
August | 0.61 | 1.11 |
September | 0.31 | 1.30 |
October | 0.00 | 0.00 |
November | 0.27 | 0.60 |
December | 0.78 | 0.45 |
Annual Sum or Average | 5.30 | 0.68 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.23 | 1.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.86 | 0.34 |
February | 0.26 | 0.43 |
March | 0.28 | 0.27 |
April | 0.46 | 0.54 |
May | 1.57 | 0.40 |
June | 2.03 | 0.60 |
July | 2.68 | 0.47 |
August | 2.55 | 0.60 |
September | 1.93 | 0.65 |
October | 0.09 | 0.75 |
November | 0.18 | 0.42 |
December | 0.32 | 0.42 |
Annual Sum or Average | 13.22 | 0.52 |
Minimum of Months | 0.09 | 0.27 |
Maximum of Months | 2.68 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.69 | 2.28 |
February | 0.21 | 0.84 |
March | 0.19 | 0.24 |
April | 0.22 | 0.84 |
May | 1.28 | 0.73 |
June | 1.49 | 0.96 |
July | 1.89 | 0.85 |
August | 2.08 | 1.14 |
September | 1.46 | 1.02 |
October | 0.25 | 0.84 |
November | 0.10 | 0.48 |
December | 0.12 | 0.60 |
Annual Sum or Average | 9.99 | 1.02 |
Minimum of Months | 0.10 | 0.24 |
Maximum of Months | 2.08 | 2.28 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.18 | 0.38 |
February | 0.17 | 0.54 |
March | 0.14 | 0.54 |
April | 0.87 | 0.57 |
May | 1.89 | 0.62 |
June | 2.38 | 0.77 |
July | 3.08 | 0.59 |
August | 2.44 | 0.71 |
September | 2.79 | 0.69 |
October | 0.25 | 0.54 |
November | 0.24 | 0.54 |
December | 0.00 | 0.00 |
Annual Sum or Average | 14.43 | 0.66 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.08 | 0.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.940431E+09 | 0.00 | 2963085.03 | 0.143610E+11 | 0.00 | 0.00 |
February | 46996039.57 | 0.00 | 0.491220E+09 | 0.126673E+11 | 0.00 | 0.00 |
March | 70499906.42 | 0.00 | 0.143315E+09 | 0.152409E+11 | 0.00 | 0.00 |
April | 70600231.14 | 0.00 | 0.400997E+10 | 0.142507E+11 | 0.00 | 0.00 |
May | 0.290787E+09 | 0.00 | 0.762608E+10 | 0.150593E+11 | 0.00 | 0.00 |
June | 0.117659E+09 | 0.00 | 0.158774E+11 | 0.150957E+11 | 0.00 | 0.00 |
July | 0.798706E+09 | 0.00 | 0.301503E+11 | 0.149961E+11 | 0.00 | 0.00 |
August | 0.699371E+09 | 0.00 | 0.417266E+11 | 0.160629E+11 | 0.00 | 0.00 |
September | 0.100040E+10 | 0.00 | 0.126515E+11 | 0.149443E+11 | 0.00 | 0.00 |
October | 0.423213E+09 | 0.00 | 0.182541E+10 | 0.151136E+11 | 0.00 | 0.00 |
November | 0.658166E+09 | 0.00 | 0.335827E+09 | 0.146685E+11 | 0.00 | 0.00 |
December | 0.281979E+09 | 0.00 | 9288233.40 | 0.143441E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.539881E+10 | 0.00 | 0.114850E+12 | 0.176804E+12 | 0.00 | 0.00 |
Minimum of Months | 46996039.57 | 0.00 | 2963085.03 | 0.126673E+11 | 0.00 | 0.00 |
Maximum of Months | 0.100040E+10 | 0.00 | 0.417266E+11 | 0.160629E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.552146E+10 | 0.00 | 22387603.48 | 0.378110E+10 | 0.00 | 0.00 |
February | 0.306264E+10 | 0.00 | 0.100719E+10 | 0.419965E+10 | 0.00 | 0.00 |
March | 0.386379E+09 | 0.00 | 0.175433E+10 | 0.630261E+10 | 0.00 | 0.00 |
April | 59442822.86 | 0.00 | 0.112413E+11 | 0.690913E+10 | 0.00 | 0.00 |
May | 15287190.90 | 0.00 | 0.187991E+11 | 0.555372E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.342141E+11 | 0.600351E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.622138E+11 | 0.656583E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.843891E+11 | 0.761725E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.300033E+11 | 0.529457E+10 | 0.00 | 0.00 |
October | 2989133.03 | 0.00 | 0.611641E+10 | 0.560347E+10 | 0.00 | 0.00 |
November | 0.752911E+09 | 0.00 | 0.104050E+10 | 0.511545E+10 | 0.00 | 0.00 |
December | 0.224179E+10 | 0.00 | 0.00 | 0.521358E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.120429E+11 | 0.00 | 0.250802E+12 | 0.681599E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.378110E+10 | 0.00 | 0.00 |
Maximum of Months | 0.552146E+10 | 0.00 | 0.843891E+11 | 0.761725E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.218002E+12 | 0.00 | 0.138767E+09 | 0.304065E+11 | 0.00 | 0.00 |
February | 0.110691E+12 | 0.00 | 0.695464E+10 | 0.292129E+11 | 0.00 | 0.00 |
March | 0.322220E+11 | 0.00 | 0.130663E+11 | 0.386755E+11 | 0.00 | 0.00 |
April | 0.114127E+11 | 0.00 | 0.840504E+11 | 0.380311E+11 | 0.00 | 0.00 |
May | 0.111739E+10 | 0.00 | 0.162317E+12 | 0.427530E+11 | 0.00 | 0.00 |
June | 16312435.08 | 0.00 | 0.280439E+12 | 0.438251E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.487435E+12 | 0.448904E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.639454E+12 | 0.506212E+11 | 0.00 | 0.00 |
September | 68812710.48 | 0.00 | 0.268418E+12 | 0.434334E+11 | 0.00 | 0.00 |
October | 0.875048E+10 | 0.00 | 0.481784E+11 | 0.383534E+11 | 0.00 | 0.00 |
November | 0.662963E+11 | 0.00 | 0.945628E+10 | 0.307002E+11 | 0.00 | 0.00 |
December | 0.143214E+12 | 0.00 | 34375.43 | 0.303265E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.591791E+12 | 0.00 | 0.199991E+13 | 0.461229E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 34375.43 | 0.292129E+11 | 0.00 | 0.00 |
Maximum of Months | 0.218002E+12 | 0.00 | 0.639454E+12 | 0.506212E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.366284E+11 | 0.00 | 12046481.72 | 0.332627E+10 | 0.00 | 0.00 |
February | 0.221328E+11 | 0.00 | 0.656995E+09 | 0.288525E+10 | 0.00 | 0.00 |
March | 0.997865E+10 | 0.00 | 0.122168E+10 | 0.318029E+10 | 0.00 | 0.00 |
April | 0.387103E+10 | 0.00 | 0.863747E+10 | 0.322155E+10 | 0.00 | 0.00 |
May | 0.962252E+09 | 0.00 | 0.166153E+11 | 0.373600E+10 | 0.00 | 0.00 |
June | 90963752.63 | 0.00 | 0.296182E+11 | 0.405236E+10 | 0.00 | 0.00 |
July | 1540.89 | 0.00 | 0.524538E+11 | 0.437177E+10 | 0.00 | 0.00 |
August | 2728654.23 | 0.00 | 0.677609E+11 | 0.485116E+10 | 0.00 | 0.00 |
September | 0.356900E+09 | 0.00 | 0.265246E+11 | 0.366904E+10 | 0.00 | 0.00 |
October | 0.432085E+10 | 0.00 | 0.431703E+10 | 0.303931E+10 | 0.00 | 0.00 |
November | 0.162013E+11 | 0.00 | 0.896845E+09 | 0.268748E+10 | 0.00 | 0.00 |
December | 0.292578E+11 | 0.00 | 10402.96 | 0.296133E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.123804E+12 | 0.00 | 0.208715E+12 | 0.419818E+11 | 0.00 | 0.00 |
Minimum of Months | 1540.89 | 0.00 | 10402.96 | 0.268748E+10 | 0.00 | 0.00 |
Maximum of Months | 0.366284E+11 | 0.00 | 0.677609E+11 | 0.485116E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.561857E+10 | 0.190389E+12 | 0.00 | 33.91 |
February | 0.00 | 0.00 | 0.265093E+11 | 0.222833E+12 | 0.00 | 47.94 |
March | 0.00 | 0.00 | 0.198279E+11 | 0.282523E+12 | 0.00 | 66.87 |
April | 0.00 | 0.00 | 0.138279E+12 | 0.283156E+12 | 0.00 | 57.98 |
May | 0.00 | 0.00 | 0.101215E+12 | 0.147020E+12 | 0.00 | 8.51 |
June | 0.00 | 0.00 | 0.113187E+12 | 0.147822E+12 | 0.00 | 7.70 |
July | 0.00 | 0.00 | 0.314975E+12 | 0.192159E+12 | 0.00 | 7.98 |
August | 0.00 | 0.00 | 0.794821E+12 | 0.276251E+12 | 0.00 | 0.34 |
September | 0.00 | 0.00 | 0.192069E+11 | 0.103378E+12 | 0.00 | 0.65 |
October | 0.00 | 0.00 | 0.810449E+11 | 0.163396E+12 | 0.00 | 17.62 |
November | 0.00 | 0.00 | 0.200652E+12 | 0.233530E+12 | 0.00 | 33.47 |
December | 0.00 | 0.00 | 0.591315E+12 | 0.326600E+12 | 0.00 | 44.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.240665E+13 | 0.256906E+13 | 0.00 | 327.64 |
Minimum of Months | 0.00 | 0.00 | 0.561857E+10 | 0.103378E+12 | 0.00 | 0.34 |
Maximum of Months | 0.00 | 0.00 | 0.794821E+12 | 0.326600E+12 | 0.00 | 66.87 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.518614E+10 | 0.260398E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.106456E+11 | 0.347772E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.183331E+11 | 0.499035E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.238595E+11 | 0.590153E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.668521E+10 | 0.291189E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.125063E+11 | 0.399511E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.193370E+11 | 0.545475E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.256374E+11 | 0.684736E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.655650E+10 | 0.284207E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.124474E+11 | 0.397148E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.176314E+11 | 0.481178E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.240302E+11 | 0.591743E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.182856E+12 | 0.537254E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.518614E+10 | 0.260398E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.256374E+11 | 0.684736E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.217453E+11 | 0.192687E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.802853E+11 | 0.293220E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.157255E+12 | 0.446838E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.215765E+12 | 0.544806E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.546216E+11 | 0.260584E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.112194E+12 | 0.368885E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.179259E+12 | 0.512053E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.240436E+12 | 0.647228E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.542748E+11 | 0.255611E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.103215E+12 | 0.351383E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.146422E+12 | 0.422615E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.202216E+12 | 0.521759E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.156769E+13 | 0.481767E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.217453E+11 | 0.192687E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.240436E+12 | 0.647228E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.109039E+10 | 0.170775E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.632619E+10 | 0.262581E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.143130E+11 | 0.424679E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.206927E+11 | 0.533198E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.486158E+10 | 0.250877E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.109522E+11 | 0.366421E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.177568E+11 | 0.512146E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.238319E+11 | 0.647150E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.477124E+10 | 0.244756E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.902132E+10 | 0.329494E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.129137E+11 | 0.394622E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.181508E+11 | 0.489958E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.144682E+12 | 0.462666E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.109039E+10 | 0.170775E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.238319E+11 | 0.647150E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143610E+11 | 2963085.03 | 0.940431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126673E+11 | 0.491220E+09 | 46996039.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152409E+11 | 0.143315E+09 | 70499906.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142507E+11 | 0.400997E+10 | 70600231.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150593E+11 | 0.762608E+10 | 0.290787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150957E+11 | 0.158774E+11 | 0.117659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149961E+11 | 0.301503E+11 | 0.798706E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160629E+11 | 0.417266E+11 | 0.699371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149443E+11 | 0.126515E+11 | 0.100040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151136E+11 | 0.182541E+10 | 0.423213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146685E+11 | 0.335827E+09 | 0.658166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143441E+11 | 9288233.40 | 0.281979E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176804E+12 | 0.114850E+12 | 0.539881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126673E+11 | 2963085.03 | 46996039.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160629E+11 | 0.417266E+11 | 0.100040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.378110E+10 | 22387603.48 | 0.552146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.419965E+10 | 0.100719E+10 | 0.306264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.630261E+10 | 0.175433E+10 | 0.386379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.690913E+10 | 0.112413E+11 | 59442822.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.555372E+10 | 0.187991E+11 | 15287190.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.600351E+10 | 0.342141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.656583E+10 | 0.622138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.761725E+10 | 0.843891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.529457E+10 | 0.300033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.560347E+10 | 0.611641E+10 | 2989133.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.511545E+10 | 0.104050E+10 | 0.752911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.521358E+10 | 0.00 | 0.224179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.681599E+11 | 0.250802E+12 | 0.120429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.378110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.761725E+10 | 0.843891E+11 | 0.552146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.304065E+11 | 0.138767E+09 | 0.218002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.292129E+11 | 0.695464E+10 | 0.110691E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.386755E+11 | 0.130663E+11 | 0.322220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.380311E+11 | 0.840504E+11 | 0.114127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.427530E+11 | 0.162317E+12 | 0.111739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.438251E+11 | 0.280439E+12 | 16312435.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.448904E+11 | 0.487435E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.506212E+11 | 0.639454E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.434334E+11 | 0.268418E+12 | 68812710.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.383534E+11 | 0.481784E+11 | 0.875048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.307002E+11 | 0.945628E+10 | 0.662963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.303265E+11 | 34375.43 | 0.143214E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.461229E+12 | 0.199991E+13 | 0.591791E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.292129E+11 | 34375.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.506212E+11 | 0.639454E+12 | 0.218002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.332627E+10 | 12046481.72 | 0.366284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288525E+10 | 0.656995E+09 | 0.221328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.318029E+10 | 0.122168E+10 | 0.997865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.322155E+10 | 0.863747E+10 | 0.387103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.373600E+10 | 0.166153E+11 | 0.962252E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.405236E+10 | 0.296182E+11 | 90963752.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.437177E+10 | 0.524538E+11 | 1540.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.485116E+10 | 0.677609E+11 | 2728654.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.366904E+10 | 0.265246E+11 | 0.356900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.303931E+10 | 0.431703E+10 | 0.432085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.268748E+10 | 0.896845E+09 | 0.162013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.296133E+10 | 10402.96 | 0.292578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.419818E+11 | 0.208715E+12 | 0.123804E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.268748E+10 | 10402.96 | 1540.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.485116E+10 | 0.677609E+11 | 0.366284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.955846E+11 | 0.466727E+10 | 0.00 | 0.00 | 0.00 | 0.907399E+11 | 0.00 | 0.00 |
February | 0.863345E+11 | 0.222495E+11 | 0.00 | 0.00 | 0.00 | 0.128295E+12 | 0.00 | 0.00 |
March | 0.955846E+11 | 0.157240E+11 | 0.00 | 0.00 | 0.00 | 0.178956E+12 | 0.00 | 0.00 |
April | 0.925013E+11 | 0.108985E+12 | 0.00 | 0.00 | 0.00 | 0.155161E+12 | 0.00 | 0.00 |
May | 0.955846E+11 | 0.862733E+11 | 0.00 | 0.00 | 0.00 | 0.227701E+11 | 0.00 | 0.00 |
June | 0.925013E+11 | 0.940917E+11 | 0.00 | 0.00 | 0.00 | 0.205955E+11 | 0.00 | 0.00 |
July | 0.955846E+11 | 0.253374E+12 | 0.00 | 0.00 | 0.00 | 0.213649E+11 | 0.00 | 0.00 |
August | 0.955846E+11 | 0.636453E+12 | 0.00 | 0.00 | 0.00 | 0.917132E+09 | 0.00 | 0.00 |
September | 0.925013E+11 | 0.162417E+11 | 0.00 | 0.00 | 0.00 | 0.173639E+10 | 0.00 | 0.00 |
October | 0.955846E+11 | 0.689945E+11 | 0.00 | 0.00 | 0.00 | 0.471600E+11 | 0.00 | 0.00 |
November | 0.925013E+11 | 0.170773E+12 | 0.00 | 0.00 | 0.00 | 0.895672E+11 | 0.00 | 0.00 |
December | 0.955846E+11 | 0.503636E+12 | 0.00 | 0.00 | 0.00 | 0.119536E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.112543E+13 | 0.198146E+13 | 0.00 | 0.00 | 0.00 | 0.876800E+12 | 0.00 | 0.00 |
Minimum of Months | 0.863345E+11 | 0.466727E+10 | 0.00 | 0.00 | 0.00 | 0.917132E+09 | 0.00 | 0.00 |
Maximum of Months | 0.955846E+11 | 0.636453E+12 | 0.00 | 0.00 | 0.00 | 0.178956E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149159E+10 | 0.440755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134724E+10 | 0.904477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149159E+10 | 0.155784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144347E+10 | 0.201971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149159E+10 | 0.566721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144347E+10 | 0.105583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149159E+10 | 0.161355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149159E+10 | 0.210909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144347E+10 | 0.555172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149159E+10 | 0.105740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144347E+10 | 0.149813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149159E+10 | 0.204246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175622E+11 | 0.154211E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134724E+10 | 0.440755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149159E+10 | 0.210909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142939E+11 | 0.184808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129106E+11 | 0.682119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142939E+11 | 0.133626E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138328E+11 | 0.182622E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142939E+11 | 0.462906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138328E+11 | 0.946974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142939E+11 | 0.149550E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142939E+11 | 0.197728E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138328E+11 | 0.459419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142939E+11 | 0.876777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138328E+11 | 0.124411E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142939E+11 | 0.171874E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168299E+12 | 0.132111E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129106E+11 | 0.184808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.142939E+11 | 0.197728E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144994E+10 | 0.926670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130963E+10 | 0.537479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144994E+10 | 0.121622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140317E+10 | 0.175111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144994E+10 | 0.411777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140317E+10 | 0.924129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144994E+10 | 0.148078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144994E+10 | 0.195897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140317E+10 | 0.403614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144994E+10 | 0.766290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140317E+10 | 0.109721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144994E+10 | 0.154272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170719E+11 | 0.121830E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130963E+10 | 0.926670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144994E+10 | 0.195897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.143610E+11 | 0.940431E+09 | 2963085.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126673E+11 | 46996039.57 | 0.491220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152409E+11 | 70499906.42 | 0.143315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142507E+11 | 70600231.14 | 0.400997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150593E+11 | 0.290787E+09 | 0.762608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150957E+11 | 0.117659E+09 | 0.158774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149961E+11 | 0.798706E+09 | 0.301503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160629E+11 | 0.699371E+09 | 0.417266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149443E+11 | 0.100040E+10 | 0.126515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151136E+11 | 0.423213E+09 | 0.182541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146685E+11 | 0.658166E+09 | 0.335827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143441E+11 | 0.281979E+09 | 9288233.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176804E+12 | 0.539881E+10 | 0.114850E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.126673E+11 | 46996039.57 | 2963085.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160629E+11 | 0.100040E+10 | 0.417266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.378110E+10 | 0.552146E+10 | 22387603.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.419965E+10 | 0.306264E+10 | 0.100719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.630261E+10 | 0.386379E+09 | 0.175433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.690913E+10 | 59442822.86 | 0.112413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.555372E+10 | 15287190.90 | 0.187991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.600351E+10 | 0.00 | 0.342141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.656583E+10 | 0.00 | 0.622138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.761725E+10 | 0.00 | 0.843891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.529457E+10 | 0.00 | 0.300033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.560347E+10 | 2989133.03 | 0.611641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.511545E+10 | 0.752911E+09 | 0.104050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.521358E+10 | 0.224179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.681599E+11 | 0.120429E+11 | 0.250802E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.378110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.761725E+10 | 0.552146E+10 | 0.843891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.304065E+11 | 0.218002E+12 | 0.138767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.292129E+11 | 0.110691E+12 | 0.695464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.386755E+11 | 0.322220E+11 | 0.130663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.380311E+11 | 0.114127E+11 | 0.840504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.427530E+11 | 0.111739E+10 | 0.162317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.438251E+11 | 16312435.08 | 0.280439E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.448904E+11 | 0.00 | 0.487435E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.506212E+11 | 0.00 | 0.639454E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.434334E+11 | 68812710.48 | 0.268418E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.383534E+11 | 0.875048E+10 | 0.481784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.307002E+11 | 0.662963E+11 | 0.945628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.303265E+11 | 0.143214E+12 | 34375.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.461229E+12 | 0.591791E+12 | 0.199991E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.292129E+11 | 0.00 | 34375.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.506212E+11 | 0.218002E+12 | 0.639454E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.332627E+10 | 0.366284E+11 | 12046481.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288525E+10 | 0.221328E+11 | 0.656995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.318029E+10 | 0.997865E+10 | 0.122168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.322155E+10 | 0.387103E+10 | 0.863747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.373600E+10 | 0.962252E+09 | 0.166153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.405236E+10 | 90963752.63 | 0.296182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.437177E+10 | 1540.89 | 0.524538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.485116E+10 | 2728654.23 | 0.677609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.366904E+10 | 0.356900E+09 | 0.265246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.303931E+10 | 0.432085E+10 | 0.431703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.268748E+10 | 0.162013E+11 | 0.896845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.296133E+10 | 0.292578E+11 | 10402.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.419818E+11 | 0.123804E+12 | 0.208715E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.268748E+10 | 1540.89 | 10402.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.485116E+10 | 0.366284E+11 | 0.677609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.955846E+11 | 0.00 | 0.561857E+10 | 0.00 | 0.365603E+10 | 0.00 | 0.00 | 0.00 | 0.911484E+11 | 0.00 | 0.00 | 0.00 |
February | 0.863345E+11 | 0.00 | 0.265093E+11 | 0.00 | 0.762529E+10 | 0.00 | 0.00 | 0.00 | 0.128873E+12 | 0.00 | 0.00 | 0.00 |
March | 0.955846E+11 | 0.00 | 0.198279E+11 | 0.00 | 0.717699E+10 | 0.00 | 0.00 | 0.00 | 0.179762E+12 | 0.00 | 0.00 | 0.00 |
April | 0.925013E+11 | 0.00 | 0.138279E+12 | 0.00 | 0.347959E+11 | 0.00 | 0.00 | 0.00 | 0.155859E+12 | 0.00 | 0.00 | 0.00 |
May | 0.955846E+11 | 0.00 | 0.101215E+12 | 0.00 | 0.285628E+11 | 0.00 | 0.00 | 0.00 | 0.228726E+11 | 0.00 | 0.00 | 0.00 |
June | 0.925013E+11 | 0.00 | 0.113187E+12 | 0.00 | 0.346324E+11 | 0.00 | 0.00 | 0.00 | 0.206882E+11 | 0.00 | 0.00 | 0.00 |
July | 0.955846E+11 | 0.00 | 0.314975E+12 | 0.00 | 0.751129E+11 | 0.00 | 0.00 | 0.00 | 0.214611E+11 | 0.00 | 0.00 | 0.00 |
August | 0.955846E+11 | 0.00 | 0.794821E+12 | 0.00 | 0.179745E+12 | 0.00 | 0.00 | 0.00 | 0.921261E+09 | 0.00 | 0.00 | 0.00 |
September | 0.925013E+11 | 0.00 | 0.192069E+11 | 0.00 | 0.913276E+10 | 0.00 | 0.00 | 0.00 | 0.174421E+10 | 0.00 | 0.00 | 0.00 |
October | 0.955846E+11 | 0.00 | 0.810449E+11 | 0.00 | 0.204388E+11 | 0.00 | 0.00 | 0.00 | 0.473723E+11 | 0.00 | 0.00 | 0.00 |
November | 0.925013E+11 | 0.00 | 0.200652E+12 | 0.00 | 0.510579E+11 | 0.00 | 0.00 | 0.00 | 0.899704E+11 | 0.00 | 0.00 | 0.00 |
December | 0.955846E+11 | 0.00 | 0.591315E+12 | 0.00 | 0.110941E+12 | 0.00 | 0.00 | 0.00 | 0.120074E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112543E+13 | 0.00 | 0.240665E+13 | 0.00 | 0.562878E+12 | 0.00 | 0.00 | 0.00 | 0.880747E+12 | 0.00 | 0.00 | |
Minimum of Months | 0.863345E+11 | 0.00 | 0.561857E+10 | 0.00 | 0.365603E+10 | 0.00 | 0.00 | 0.00 | 0.921261E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.955846E+11 | 0.00 | 0.794821E+12 | 0.00 | 0.179745E+12 | 0.00 | 0.00 | 0.00 | 0.179762E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.149159E+10 | 0.00 | 0.518614E+10 | 0.00 | 0.111239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134724E+10 | 0.00 | 0.106456E+11 | 0.00 | 0.213048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149159E+10 | 0.00 | 0.183331E+11 | 0.00 | 0.349876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144347E+10 | 0.00 | 0.238595E+11 | 0.00 | 0.445806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149159E+10 | 0.00 | 0.668521E+10 | 0.00 | 0.142030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144347E+10 | 0.00 | 0.125063E+11 | 0.00 | 0.255164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149159E+10 | 0.00 | 0.193370E+11 | 0.00 | 0.396316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149159E+10 | 0.00 | 0.256374E+11 | 0.00 | 0.535577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144347E+10 | 0.00 | 0.655650E+10 | 0.00 | 0.139860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149159E+10 | 0.00 | 0.124474E+11 | 0.00 | 0.247989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144347E+10 | 0.00 | 0.176314E+11 | 0.00 | 0.336831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149159E+10 | 0.00 | 0.240302E+11 | 0.00 | 0.442584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175622E+11 | 0.00 | 0.182856E+12 | 0.00 | 0.361632E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.134724E+10 | 0.00 | 0.518614E+10 | 0.00 | 0.111239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149159E+10 | 0.00 | 0.256374E+11 | 0.00 | 0.535577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.142939E+11 | 0.00 | 0.217453E+11 | 0.00 | 0.497485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129106E+11 | 0.00 | 0.802853E+11 | 0.00 | 0.164114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142939E+11 | 0.00 | 0.157255E+12 | 0.00 | 0.303899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138328E+11 | 0.00 | 0.215765E+12 | 0.00 | 0.406478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142939E+11 | 0.00 | 0.546216E+11 | 0.00 | 0.117645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138328E+11 | 0.00 | 0.112194E+12 | 0.00 | 0.230557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142939E+11 | 0.00 | 0.179259E+12 | 0.00 | 0.369114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142939E+11 | 0.00 | 0.240436E+12 | 0.00 | 0.504289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138328E+11 | 0.00 | 0.542748E+11 | 0.00 | 0.117283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142939E+11 | 0.00 | 0.103215E+12 | 0.00 | 0.208444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138328E+11 | 0.00 | 0.146422E+12 | 0.00 | 0.284287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142939E+11 | 0.00 | 0.202216E+12 | 0.00 | 0.378820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168299E+12 | 0.00 | 0.156769E+13 | 0.00 | 0.313468E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.129106E+11 | 0.00 | 0.217453E+11 | 0.00 | 0.497485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.142939E+11 | 0.00 | 0.240436E+12 | 0.00 | 0.504289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.144994E+10 | 0.00 | 0.109039E+10 | 0.00 | 0.257812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130963E+10 | 0.00 | 0.632619E+10 | 0.00 | 0.131619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144994E+10 | 0.00 | 0.143130E+11 | 0.00 | 0.279685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140317E+10 | 0.00 | 0.206927E+11 | 0.00 | 0.392881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144994E+10 | 0.00 | 0.486158E+10 | 0.00 | 0.105882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140317E+10 | 0.00 | 0.109522E+11 | 0.00 | 0.226104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144994E+10 | 0.00 | 0.177568E+11 | 0.00 | 0.367152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144994E+10 | 0.00 | 0.238319E+11 | 0.00 | 0.502155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140317E+10 | 0.00 | 0.477124E+10 | 0.00 | 0.104439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144994E+10 | 0.00 | 0.902132E+10 | 0.00 | 0.184500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140317E+10 | 0.00 | 0.129137E+11 | 0.00 | 0.254305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144994E+10 | 0.00 | 0.181508E+11 | 0.00 | 0.344964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170719E+11 | 0.00 | 0.144682E+12 | 0.00 | 0.291947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.130963E+10 | 0.00 | 0.109039E+10 | 0.00 | 0.257812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144994E+10 | 0.00 | 0.238319E+11 | 0.00 | 0.502155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.482573E+09 | 0.00 | 0.00 | 0.127196E+09 | 0.00 | 0.00 | 0.691308E+11 | 0.00 | 0.59 |
February | 0.387990E+09 | 0.00 | 0.00 | 0.114403E+09 | 0.00 | 0.00 | 0.634941E+11 | 0.00 | 0.69 |
March | 0.298031E+09 | 0.00 | 0.00 | 0.147266E+09 | 0.00 | 0.00 | 0.790547E+11 | 0.00 | 0.87 |
April | 0.274320E+09 | 21539190.69 | 0.00 | 0.143209E+09 | 0.00 | 0.00 | 0.709147E+11 | 0.00 | 0.97 |
May | 0.220887E+09 | 13487852.31 | 0.00 | 0.143142E+09 | 0.00 | 0.00 | 0.705370E+11 | 0.00 | 1.19 |
June | 0.116173E+09 | 15722381.28 | 0.00 | 0.153587E+09 | 1385586.80 | 0.00 | 0.644064E+11 | 0.00 | 1.42 |
July | 0.154901E+09 | 0.135403E+09 | 0.00 | 0.166228E+09 | 3449827.85 | 0.00 | 0.512327E+11 | 0.00 | 1.39 |
August | 0.109496E+09 | 0.389679E+09 | 0.00 | 0.166688E+09 | 169330.43 | 0.00 | 0.473840E+11 | 0.00 | 1.36 |
September | 0.242365E+09 | 0.00 | 0.00 | 0.160064E+09 | 0.00 | 0.00 | 0.655431E+11 | 0.00 | 1.37 |
October | 0.295230E+09 | 0.00 | 0.00 | 0.162983E+09 | 0.00 | 0.00 | 0.780778E+11 | 0.00 | 1.07 |
November | 0.313912E+09 | 0.00 | 0.00 | 0.157253E+09 | 0.00 | 0.00 | 0.769266E+11 | 0.00 | 0.83 |
December | 0.511141E+09 | 0.00 | 0.00 | 0.143112E+09 | 0.00 | 0.00 | 0.738802E+11 | 0.00 | 0.65 |
Annual Sum or Average | 0.340702E+10 | 0.575832E+09 | 0.00 | 0.178513E+10 | 5004745.08 | 0.00 | 0.810582E+12 | 0.00 | 1.03 |
Minimum of Months | 0.109496E+09 | 0.00 | 0.00 | 0.114403E+09 | 0.00 | 0.00 | 0.473840E+11 | 0.00 | 0.59 |
Maximum of Months | 0.511141E+09 | 0.389679E+09 | 0.00 | 0.166688E+09 | 3449827.85 | 0.00 | 0.790547E+11 | 0.00 | 1.42 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.278167E+10 | 0.00 | 0.00 | 60631392.83 | 0.00 | 0.00 | 0.451099E+11 | 0.00 | 0.39 |
February | 0.186175E+10 | 0.00 | 0.00 | 71068197.09 | 0.00 | 0.00 | 0.457528E+11 | 0.00 | 0.49 |
March | 0.175960E+10 | 0.00 | 0.00 | 0.108416E+09 | 0.00 | 0.00 | 0.614636E+11 | 0.00 | 0.65 |
April | 0.467143E+10 | 10370562.56 | 0.00 | 0.109018E+09 | 491996.42 | 0.00 | 0.558238E+11 | 0.00 | 0.77 |
May | 0.334175E+10 | 9150582.46 | 0.00 | 92641382.21 | 0.00 | 0.00 | 0.491037E+11 | 0.00 | 0.78 |
June | 0.344544E+10 | 9099734.53 | 0.00 | 0.106685E+09 | 5216216.58 | 0.00 | 0.447928E+11 | 0.00 | 0.90 |
July | 0.600590E+10 | 0.445634E+09 | 0.00 | 0.100117E+09 | 37768878.43 | 0.00 | 0.316837E+11 | 0.00 | 0.88 |
August | 0.675071E+10 | 0.125045E+10 | 0.00 | 99036741.35 | 15781973.76 | 0.00 | 0.286955E+11 | 0.00 | 0.93 |
September | 0.317332E+10 | 51286771.06 | 0.00 | 92504682.99 | 3062287.93 | 0.00 | 0.405693E+11 | 0.00 | 0.80 |
October | 0.255050E+10 | 0.00 | 0.00 | 98938015.96 | 0.00 | 0.00 | 0.545959E+11 | 0.00 | 0.72 |
November | 0.198063E+10 | 0.00 | 0.00 | 92639169.99 | 0.00 | 0.00 | 0.552086E+11 | 0.00 | 0.58 |
December | 0.182089E+10 | 0.00 | 0.00 | 91665324.32 | 0.00 | 0.00 | 0.549319E+11 | 0.00 | 0.48 |
Annual Sum or Average | 0.401436E+11 | 0.177599E+10 | 0.00 | 0.112336E+10 | 62321353.12 | 0.00 | 0.567731E+12 | 0.00 | 0.70 |
Minimum of Months | 0.175960E+10 | 0.00 | 0.00 | 60631392.83 | 0.00 | 0.00 | 0.286955E+11 | 0.00 | 0.39 |
Maximum of Months | 0.675071E+10 | 0.125045E+10 | 0.00 | 0.109018E+09 | 37768878.43 | 0.00 | 0.614636E+11 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.239222E+12 | 0.00 | 0.00 | 97124033.11 | 0.00 | 0.248614E+10 | 0.103506E+12 | 0.00 | 0.30 |
February | 0.163905E+12 | 0.00 | 0.00 | 0.192173E+09 | 0.00 | 20254520.52 | 0.163301E+12 | 0.00 | 0.35 |
March | 0.118747E+12 | 0.00 | 0.00 | 0.396742E+09 | 0.00 | 0.00 | 0.286367E+12 | 0.00 | 0.43 |
April | 0.803495E+11 | 0.110526E+09 | 0.00 | 0.416307E+09 | 0.105994E+09 | 0.00 | 0.288076E+12 | 0.00 | 0.48 |
May | 0.511850E+11 | 12074879.63 | 0.00 | 0.526317E+09 | 0.147280E+09 | 0.00 | 0.349528E+12 | 0.00 | 0.62 |
June | 0.306260E+11 | 89105557.17 | 0.00 | 0.600577E+09 | 56726872.29 | 0.00 | 0.327153E+12 | 0.00 | 0.69 |
July | 0.275529E+11 | 0.364320E+10 | 0.00 | 0.544064E+09 | 0.105855E+10 | 0.00 | 0.224565E+12 | 0.00 | 0.64 |
August | 0.219420E+11 | 0.112088E+11 | 0.00 | 0.543431E+09 | 0.287861E+09 | 0.00 | 0.202777E+12 | 0.00 | 0.64 |
September | 0.478555E+11 | 0.265620E+09 | 0.00 | 0.532246E+09 | 0.451504E+09 | 0.00 | 0.286792E+12 | 0.00 | 0.65 |
October | 0.900531E+11 | 0.00 | 0.00 | 0.428994E+09 | 0.00 | 0.00 | 0.295616E+12 | 0.00 | 0.51 |
November | 0.133423E+12 | 0.00 | 0.00 | 0.268778E+09 | 0.00 | 0.00 | 0.215399E+12 | 0.00 | 0.37 |
December | 0.191807E+12 | 0.00 | 0.00 | 0.178076E+09 | 0.00 | 18930556.87 | 0.158139E+12 | 0.00 | 0.31 |
Annual Sum or Average | 0.119667E+13 | 0.153293E+11 | 0.00 | 0.472483E+10 | 0.210791E+10 | 0.252532E+10 | 0.290122E+13 | 0.00 | 0.50 |
Minimum of Months | 0.219420E+11 | 0.00 | 0.00 | 97124033.11 | 0.00 | 0.00 | 0.103506E+12 | 0.00 | 0.30 |
Maximum of Months | 0.239222E+12 | 0.112088E+11 | 0.00 | 0.600577E+09 | 0.105855E+10 | 0.248614E+10 | 0.349528E+12 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.289697E+11 | 0.00 | 0.00 | 338491.12 | 0.00 | 0.111223E+10 | 0.104960E+10 | 0.00 | 0.29 |
February | 0.240668E+11 | 0.00 | 0.00 | 3040126.13 | 0.00 | 0.583735E+09 | 0.374821E+10 | 0.00 | 0.32 |
March | 0.208612E+11 | 0.00 | 0.00 | 12257361.27 | 0.00 | 0.160289E+09 | 0.125914E+11 | 0.00 | 0.38 |
April | 0.128722E+11 | 0.00 | 0.00 | 25058859.12 | 3368980.11 | 1851916.33 | 0.194630E+11 | 0.00 | 0.44 |
May | 0.997069E+10 | 182310.25 | 0.00 | 39075799.32 | 3102971.47 | 0.00 | 0.273520E+11 | 0.00 | 0.58 |
June | 0.748730E+10 | 1181698.31 | 0.00 | 51637765.39 | 3842814.24 | 0.00 | 0.275550E+11 | 0.00 | 0.68 |
July | 0.608797E+10 | 0.297732E+09 | 0.00 | 50208143.39 | 43904597.68 | 0.00 | 0.191478E+11 | 0.00 | 0.64 |
August | 0.527896E+10 | 0.864560E+09 | 0.00 | 46608426.63 | 25169105.67 | 0.00 | 0.157779E+11 | 0.00 | 0.63 |
September | 0.103385E+11 | 736944.93 | 0.00 | 35229352.39 | 23589247.84 | 0.00 | 0.185018E+11 | 0.00 | 0.59 |
October | 0.163571E+11 | 0.00 | 0.00 | 16423677.80 | 0.00 | 39299458.66 | 0.142414E+11 | 0.00 | 0.43 |
November | 0.230090E+11 | 0.00 | 0.00 | 3960816.87 | 0.00 | 0.418996E+09 | 0.499173E+10 | 0.00 | 0.33 |
December | 0.272993E+11 | 0.00 | 0.00 | 615903.13 | 0.00 | 0.831866E+09 | 0.164263E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.192599E+12 | 0.116439E+10 | 0.00 | 0.284455E+09 | 0.102978E+09 | 0.314826E+10 | 0.166062E+12 | 0.00 | 0.47 |
Minimum of Months | 0.527896E+10 | 0.00 | 0.00 | 338491.12 | 0.00 | 0.00 | 0.104960E+10 | 0.00 | 0.28 |
Maximum of Months | 0.289697E+11 | 0.864560E+09 | 0.00 | 51637765.39 | 43904597.68 | 0.111223E+10 | 0.275550E+11 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.420334E+10 | 0.00 | 0.00 | 57806.68 | 0.00 | 0.00 | 0.202476E+09 | 0.00 | 0.28 |
February | 0.330260E+10 | 0.00 | 0.00 | 880020.27 | 0.00 | 0.00 | 0.874646E+09 | 0.00 | 0.34 |
March | 0.247575E+10 | 0.00 | 0.00 | 3591657.01 | 0.00 | 0.00 | 0.292295E+10 | 0.00 | 0.45 |
April | 0.176353E+10 | 1580861.49 | 0.00 | 5742497.08 | 0.00 | 0.00 | 0.407954E+10 | 0.00 | 0.62 |
May | 0.143375E+10 | 1522362.76 | 0.00 | 7005737.36 | 0.00 | 0.00 | 0.441644E+10 | 0.00 | 0.73 |
June | 0.806497E+09 | 1451123.25 | 0.00 | 9682713.51 | 656664.58 | 0.00 | 0.480728E+10 | 0.00 | 0.88 |
July | 0.885081E+09 | 72318062.96 | 0.00 | 9855910.80 | 4754688.44 | 0.00 | 0.367306E+10 | 0.00 | 0.91 |
August | 0.105772E+10 | 0.200156E+09 | 0.00 | 8921812.64 | 1986777.77 | 0.00 | 0.305919E+10 | 0.00 | 0.92 |
September | 0.150874E+10 | 7024675.79 | 0.00 | 5904094.98 | 0.00 | 0.00 | 0.309779E+10 | 0.00 | 0.71 |
October | 0.220251E+10 | 0.00 | 0.00 | 3822136.67 | 0.00 | 0.00 | 0.292151E+10 | 0.00 | 0.52 |
November | 0.257354E+10 | 0.00 | 0.00 | 1984751.48 | 0.00 | 0.00 | 0.197371E+10 | 0.00 | 0.38 |
December | 0.327071E+10 | 0.00 | 0.00 | 724299.76 | 0.00 | 0.00 | 0.112857E+10 | 0.00 | 0.29 |
Annual Sum or Average | 0.254838E+11 | 0.284053E+09 | 0.00 | 58173438.23 | 7398130.79 | 0.00 | 0.331571E+11 | 0.00 | 0.59 |
Minimum of Months | 0.806497E+09 | 0.00 | 0.00 | 57806.68 | 0.00 | 0.00 | 0.202476E+09 | 0.00 | 0.28 |
Maximum of Months | 0.420334E+10 | 0.200156E+09 | 0.00 | 9855910.80 | 4754688.44 | 0.00 | 0.480728E+10 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.450896E+10 | 0.00 | 0.00 | 8217.86 | 0.00 | 2920155.93 | 11203200.35 | 0.00 | 0.45 |
February | 0.379722E+10 | 0.00 | 0.00 | 535113.78 | 0.00 | 409725.86 | 0.434045E+09 | 0.00 | 0.53 |
March | 0.310728E+10 | 0.00 | 0.00 | 2758702.83 | 0.00 | 0.00 | 0.218162E+10 | 0.00 | 0.67 |
April | 0.230737E+10 | 1137466.87 | 0.00 | 5299574.02 | 63581.40 | 0.00 | 0.355996E+10 | 0.00 | 0.94 |
May | 0.184244E+10 | 1223297.88 | 0.00 | 6552770.99 | 0.00 | 0.00 | 0.392148E+10 | 0.00 | 1.09 |
June | 0.127210E+10 | 1041039.33 | 0.00 | 9184316.44 | 674099.08 | 0.00 | 0.461236E+10 | 0.00 | 1.37 |
July | 0.148778E+10 | 54619457.49 | 0.00 | 8837461.05 | 5872062.63 | 0.00 | 0.305999E+10 | 0.00 | 1.35 |
August | 0.157551E+10 | 0.149935E+09 | 0.00 | 8177533.69 | 1913585.93 | 0.00 | 0.260846E+10 | 0.00 | 1.41 |
September | 0.191921E+10 | 6429267.66 | 0.00 | 6047938.42 | 0.00 | 0.00 | 0.294522E+10 | 0.00 | 1.14 |
October | 0.299773E+10 | 0.00 | 0.00 | 3115857.49 | 0.00 | 0.00 | 0.213693E+10 | 0.00 | 0.80 |
November | 0.410356E+10 | 0.00 | 0.00 | 293264.53 | 0.00 | 0.00 | 0.370116E+09 | 0.00 | 0.57 |
December | 0.444221E+10 | 0.00 | 0.00 | 58937.41 | 0.00 | 0.00 | 59982944.69 | 0.00 | 0.47 |
Annual Sum or Average | 0.333614E+11 | 0.214386E+09 | 0.00 | 50869688.52 | 8523329.03 | 3329881.79 | 0.259014E+11 | 0.00 | 0.90 |
Minimum of Months | 0.127210E+10 | 0.00 | 0.00 | 8217.86 | 0.00 | 0.00 | 11203200.35 | 0.00 | 0.45 |
Maximum of Months | 0.450896E+10 | 0.149935E+09 | 0.00 | 9184316.44 | 5872062.63 | 2920155.93 | 0.461236E+10 | 0.00 | 1.41 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.444293E+10 | 0.00 | 0.00 | 2328794.82 | 0.00 | 0.108277E+09 | 0.160654E+10 | 0.00 | 0.39 |
February | 0.350622E+10 | 0.00 | 0.00 | 5324816.76 | 0.00 | 30820972.67 | 0.339302E+10 | 0.00 | 0.58 |
March | 0.305122E+10 | 0.00 | 0.00 | 8875335.79 | 0.00 | 0.00 | 0.628742E+10 | 0.00 | 0.80 |
April | 0.242557E+10 | 3411648.69 | 0.00 | 8961513.35 | 0.00 | 0.00 | 0.588805E+10 | 0.00 | 0.91 |
May | 0.210507E+10 | 2268575.70 | 0.00 | 8359689.90 | 0.00 | 0.00 | 0.507084E+10 | 0.00 | 0.91 |
June | 0.163868E+10 | 1599815.28 | 0.00 | 9631666.87 | 805394.24 | 0.00 | 0.464589E+10 | 0.00 | 1.00 |
July | 0.168580E+10 | 95179352.19 | 0.00 | 10148930.96 | 5831590.15 | 0.00 | 0.354435E+10 | 0.00 | 1.07 |
August | 0.160896E+10 | 0.317180E+09 | 0.00 | 10303609.92 | 2205664.08 | 0.00 | 0.328308E+10 | 0.00 | 1.17 |
September | 0.190205E+10 | 22147746.98 | 0.00 | 12617336.74 | 0.00 | 0.00 | 0.502354E+10 | 0.00 | 1.21 |
October | 0.260082E+10 | 0.00 | 0.00 | 10545047.10 | 0.00 | 0.00 | 0.647135E+10 | 0.00 | 0.98 |
November | 0.360026E+10 | 0.00 | 0.00 | 4202397.49 | 0.00 | 288397.94 | 0.290537E+10 | 0.00 | 0.55 |
December | 0.410133E+10 | 0.00 | 0.00 | 4155939.35 | 0.00 | 18256763.83 | 0.286436E+10 | 0.00 | 0.48 |
Annual Sum or Average | 0.326689E+11 | 0.441787E+09 | 0.00 | 95455079.08 | 8842648.48 | 0.157643E+09 | 0.509838E+11 | 0.00 | 0.84 |
Minimum of Months | 0.160896E+10 | 0.00 | 0.00 | 2328794.82 | 0.00 | 0.00 | 0.160654E+10 | 0.00 | 0.39 |
Maximum of Months | 0.444293E+10 | 0.317180E+09 | 0.00 | 12617336.74 | 5831590.15 | 0.108277E+09 | 0.647135E+10 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.490332E+10 | 0.00 | 0.00 | 264839.76 | 0.00 | 0.00 | 0.523661E+09 | 0.00 | 0.54 |
February | 0.267945E+10 | 0.00 | 0.00 | 2770844.10 | 0.00 | 0.00 | 0.273433E+10 | 0.00 | 0.69 |
March | 0.854254E+09 | 0.00 | 0.00 | 9050340.26 | 0.00 | 0.00 | 0.690226E+10 | 0.00 | 1.03 |
April | 0.676220E+09 | 2628372.23 | 0.00 | 14943271.57 | 0.00 | 0.00 | 0.831306E+10 | 0.00 | 1.51 |
May | 0.102920E+10 | 1667868.66 | 0.00 | 12677567.51 | 0.00 | 0.00 | 0.603245E+10 | 0.00 | 1.43 |
June | 0.535717E+09 | 4701459.01 | 0.00 | 15617793.71 | 652392.97 | 0.00 | 0.630708E+10 | 0.00 | 1.75 |
July | 0.773194E+09 | 0.150022E+09 | 0.00 | 19077740.65 | 210018.36 | 0.00 | 0.540698E+10 | 0.00 | 2.04 |
August | 0.863470E+09 | 0.331054E+09 | 0.00 | 19807683.12 | 2309604.76 | 0.00 | 0.493105E+10 | 0.00 | 2.06 |
September | 0.109580E+10 | 11601996.87 | 0.00 | 10206205.30 | 0.00 | 0.00 | 0.453658E+10 | 0.00 | 1.44 |
October | 0.132792E+10 | 0.00 | 0.00 | 7057588.31 | 0.00 | 0.00 | 0.527708E+10 | 0.00 | 1.07 |
November | 0.126797E+10 | 0.00 | 0.00 | 5476559.21 | 0.00 | 0.00 | 0.470156E+10 | 0.00 | 0.77 |
December | 0.116290E+10 | 0.00 | 0.00 | 5562436.96 | 0.00 | 0.00 | 0.496896E+10 | 0.00 | 0.64 |
Annual Sum or Average | 0.171694E+11 | 0.501676E+09 | 0.00 | 0.122513E+09 | 3172016.09 | 0.00 | 0.606351E+11 | 0.00 | 1.25 |
Minimum of Months | 0.535717E+09 | 0.00 | 0.00 | 264839.76 | 0.00 | 0.00 | 0.523661E+09 | 0.00 | 0.54 |
Maximum of Months | 0.490332E+10 | 0.331054E+09 | 0.00 | 19807683.12 | 2309604.76 | 0.00 | 0.831306E+10 | 0.00 | 2.06 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.223560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204136E+11 | 0.00 | 0.00 | 0.29 |
February | 0.286429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.996996E+10 | 0.00 | 0.00 | 0.32 |
March | 0.389984E+11 | 0.00 | 0.00 | 166836.03 | 0.00 | 0.317775E+10 | 0.477634E+09 | 0.00 | 0.36 |
April | 0.295089E+11 | 15554423.21 | 0.00 | 9221941.55 | 13311401.78 | 0.824886E+09 | 0.735166E+10 | 0.00 | 0.40 |
May | 0.219480E+11 | 20541222.24 | 0.00 | 32824421.73 | 0.00 | 3736665.41 | 0.207228E+11 | 0.00 | 0.55 |
June | 0.150152E+11 | 12665716.49 | 0.00 | 49885435.98 | 7124141.95 | 0.00 | 0.243646E+11 | 0.00 | 0.64 |
July | 0.111150E+11 | 0.651350E+09 | 0.00 | 51691321.03 | 71619269.23 | 0.00 | 0.184143E+11 | 0.00 | 0.63 |
August | 0.116384E+11 | 0.180762E+10 | 0.00 | 42344170.43 | 16653160.44 | 0.00 | 0.135852E+11 | 0.00 | 0.61 |
September | 0.220342E+11 | 33485031.62 | 0.00 | 25884289.93 | 56702942.22 | 0.00 | 0.127586E+11 | 0.00 | 0.56 |
October | 0.357335E+11 | 0.00 | 0.00 | 3067970.56 | 0.00 | 0.697026E+09 | 0.319870E+10 | 0.00 | 0.41 |
November | 0.341483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506364E+10 | 0.00 | 0.00 | 0.33 |
December | 0.270174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146551E+11 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.298156E+12 | 0.254121E+10 | 0.00 | 0.215086E+09 | 0.165411E+09 | 0.548057E+11 | 0.100873E+12 | 0.00 | 0.45 |
Minimum of Months | 0.111150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.389984E+11 | 0.180762E+10 | 0.00 | 51691321.03 | 71619269.23 | 0.204136E+11 | 0.243646E+11 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.229554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235692E+11 | 0.00 | 0.00 | 0.49 |
February | 0.320160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100360E+11 | 0.00 | 0.00 | 0.55 |
March | 0.392652E+11 | 0.00 | 0.00 | 8282125.04 | 0.00 | 0.272644E+10 | 0.565126E+10 | 0.00 | 0.62 |
April | 0.245672E+11 | 14532594.93 | 0.00 | 31626180.98 | 14490773.36 | 0.749964E+09 | 0.215567E+11 | 0.00 | 0.77 |
May | 0.237226E+11 | 20913003.58 | 0.00 | 45025415.21 | 977121.35 | 33155197.26 | 0.266450E+11 | 0.00 | 1.00 |
June | 0.152624E+11 | 12103246.37 | 0.00 | 73774810.92 | 7755330.97 | 0.00 | 0.361681E+11 | 0.00 | 1.25 |
July | 0.129708E+11 | 0.576804E+09 | 0.00 | 76955860.66 | 0.131831E+09 | 0.00 | 0.235588E+11 | 0.00 | 1.17 |
August | 0.115174E+11 | 0.165113E+10 | 0.00 | 68618129.93 | 44896138.38 | 0.00 | 0.204697E+11 | 0.00 | 1.19 |
September | 0.243560E+11 | 79829155.40 | 0.00 | 44030309.33 | 13117672.27 | 6736456.93 | 0.189213E+11 | 0.00 | 1.06 |
October | 0.352272E+11 | 0.00 | 0.00 | 13447119.00 | 0.00 | 0.891066E+09 | 0.887373E+10 | 0.00 | 0.73 |
November | 0.362300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648688E+10 | 0.00 | 0.00 | 0.56 |
December | 0.282252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171719E+11 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 0.306315E+12 | 0.235531E+10 | 0.00 | 0.361760E+09 | 0.213068E+09 | 0.616713E+11 | 0.161845E+12 | 0.00 | 0.82 |
Minimum of Months | 0.115174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.392652E+11 | 0.165113E+10 | 0.00 | 76955860.66 | 0.131831E+09 | 0.235692E+11 | 0.361681E+11 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.336036E+11 | 0.00 | 0.00 | 14083372.49 | 0.00 | 0.155599E+11 | 0.100886E+11 | 0.00 | 0.41 |
February | 0.320448E+11 | 0.00 | 0.00 | 46275158.07 | 0.00 | 0.759237E+10 | 0.257832E+11 | 0.00 | 0.56 |
March | 0.344741E+11 | 0.00 | 0.00 | 68303949.75 | 0.00 | 0.208491E+10 | 0.452277E+11 | 0.00 | 0.72 |
April | 0.268833E+11 | 78633933.80 | 0.00 | 59451666.27 | 0.00 | 0.765889E+09 | 0.372411E+11 | 0.00 | 0.73 |
May | 0.263660E+11 | 37185783.44 | 0.00 | 61044222.45 | 0.00 | 39020791.70 | 0.349712E+11 | 0.00 | 0.81 |
June | 0.207575E+11 | 15727504.91 | 0.00 | 65199523.67 | 9118321.02 | 0.00 | 0.301676E+11 | 0.00 | 0.84 |
July | 0.158327E+11 | 0.102021E+10 | 0.00 | 70582994.24 | 0.101496E+09 | 0.00 | 0.233115E+11 | 0.00 | 0.86 |
August | 0.143340E+11 | 0.348709E+10 | 0.00 | 70950314.49 | 21314687.99 | 0.00 | 0.203639E+11 | 0.00 | 0.92 |
September | 0.221574E+11 | 0.338780E+09 | 0.00 | 0.117032E+09 | 1106560.29 | 0.00 | 0.403204E+11 | 0.00 | 1.17 |
October | 0.294799E+11 | 0.00 | 0.00 | 93396347.63 | 0.00 | 0.448133E+09 | 0.509267E+11 | 0.00 | 0.91 |
November | 0.381881E+11 | 0.00 | 0.00 | 26132312.14 | 0.00 | 0.479683E+10 | 0.146538E+11 | 0.00 | 0.50 |
December | 0.330673E+11 | 0.00 | 0.00 | 26100439.04 | 0.00 | 0.128909E+11 | 0.174775E+11 | 0.00 | 0.45 |
Annual Sum or Average | 0.327189E+12 | 0.497762E+10 | 0.00 | 0.718553E+09 | 0.133036E+09 | 0.441779E+11 | 0.350533E+12 | 0.00 | 0.74 |
Minimum of Months | 0.143340E+11 | 0.00 | 0.00 | 14083372.49 | 0.00 | 0.00 | 0.100886E+11 | 0.00 | 0.41 |
Maximum of Months | 0.381881E+11 | 0.348709E+10 | 0.00 | 0.117032E+09 | 0.101496E+09 | 0.155599E+11 | 0.509267E+11 | 0.00 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.315420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170793E+11 | 0.00 | 0.00 | 0.52 |
February | 0.349613E+11 | 0.00 | 0.00 | 2541739.16 | 0.00 | 0.733720E+10 | 0.201001E+10 | 0.00 | 0.58 |
March | 0.406822E+11 | 0.00 | 0.00 | 9984693.55 | 0.00 | 0.177598E+10 | 0.848298E+10 | 0.00 | 0.68 |
April | 0.309750E+11 | 34996643.69 | 0.00 | 27149956.53 | 5078649.27 | 0.241796E+09 | 0.167788E+11 | 0.00 | 0.82 |
May | 0.244355E+11 | 22901380.58 | 0.00 | 74377475.26 | 0.00 | 17318459.43 | 0.277940E+11 | 0.00 | 1.11 |
June | 0.182937E+11 | 47709659.10 | 0.00 | 66889999.06 | 8118493.16 | 0.00 | 0.267323E+11 | 0.00 | 1.21 |
July | 0.122806E+11 | 0.147236E+10 | 0.00 | 78837605.53 | 6371555.38 | 0.00 | 0.233704E+11 | 0.00 | 1.31 |
August | 0.127935E+11 | 0.282958E+10 | 0.00 | 61949110.88 | 22962646.00 | 0.00 | 0.162180E+11 | 0.00 | 1.17 |
September | 0.255349E+11 | 0.111092E+09 | 0.00 | 48385546.84 | 16721909.26 | 0.00 | 0.172746E+11 | 0.00 | 1.14 |
October | 0.388201E+11 | 0.00 | 0.00 | 12119259.92 | 0.00 | 0.323094E+09 | 0.814876E+10 | 0.00 | 0.78 |
November | 0.400908E+11 | 0.00 | 0.00 | 694753.16 | 0.00 | 0.404785E+10 | 0.538918E+09 | 0.00 | 0.58 |
December | 0.370768E+11 | 0.00 | 0.00 | 109198.48 | 0.00 | 0.101450E+11 | 0.228293E+09 | 0.00 | 0.51 |
Annual Sum or Average | 0.347486E+12 | 0.451863E+10 | 0.00 | 0.383039E+09 | 59253253.08 | 0.409675E+11 | 0.147577E+12 | 0.00 | 0.87 |
Minimum of Months | 0.122806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.406822E+11 | 0.282958E+10 | 0.00 | 78837605.53 | 22962646.00 | 0.170793E+11 | 0.277940E+11 | 0.00 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272924E+10 | 0.00 | 0.00 | 0.29 |
February | 0.170495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189933E+10 | 0.00 | 0.00 | 0.32 |
March | 0.330529E+10 | 0.00 | 0.00 | 1460.24 | 0.00 | 0.775778E+09 | 14131832.23 | 0.00 | 0.36 |
April | 0.276416E+10 | 0.00 | 0.00 | 857874.65 | 423128.24 | 0.361926E+09 | 0.567007E+09 | 0.00 | 0.40 |
May | 0.243550E+10 | 413404.45 | 0.00 | 2860763.07 | 0.00 | 58552407.28 | 0.178281E+10 | 0.00 | 0.55 |
June | 0.167736E+10 | 178457.60 | 0.00 | 4844046.66 | 482639.60 | 2280938.48 | 0.236131E+10 | 0.00 | 0.65 |
July | 0.114632E+10 | 50066932.29 | 0.00 | 5412505.59 | 3693125.64 | 0.00 | 0.192765E+10 | 0.00 | 0.65 |
August | 0.116786E+10 | 0.137652E+09 | 0.00 | 4328667.02 | 2682432.49 | 0.00 | 0.130057E+10 | 0.00 | 0.63 |
September | 0.241695E+10 | 94641.97 | 0.00 | 2119986.39 | 2962699.84 | 27345722.26 | 0.895985E+09 | 0.00 | 0.55 |
October | 0.308598E+10 | 0.00 | 0.00 | 125834.43 | 0.00 | 0.445842E+09 | 0.130318E+09 | 0.00 | 0.40 |
November | 0.205533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153211E+10 | 0.00 | 0.00 | 0.33 |
December | 0.129366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250805E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.243140E+11 | 0.188405E+09 | 0.00 | 20551138.05 | 10244025.80 | 0.103405E+11 | 0.897979E+10 | 0.00 | 0.45 |
Minimum of Months | 0.114632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.330529E+10 | 0.137652E+09 | 0.00 | 5412505.59 | 3693125.64 | 0.272924E+10 | 0.236131E+10 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.150847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267010E+10 | 0.00 | 0.00 | 0.48 |
February | 0.204809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174286E+10 | 0.00 | 0.00 | 0.53 |
March | 0.344633E+10 | 0.00 | 0.00 | 405616.28 | 0.00 | 0.621428E+09 | 0.308205E+09 | 0.00 | 0.60 |
April | 0.217305E+10 | 0.00 | 0.00 | 2821387.65 | 449660.61 | 0.248855E+09 | 0.192269E+10 | 0.00 | 0.73 |
May | 0.224187E+10 | 457258.21 | 0.00 | 4269925.59 | 0.00 | 65358315.75 | 0.260241E+10 | 0.00 | 0.97 |
June | 0.146862E+10 | 135697.34 | 0.00 | 7299412.91 | 512903.65 | 9799394.97 | 0.364221E+10 | 0.00 | 1.24 |
July | 0.117457E+10 | 42849311.53 | 0.00 | 7853004.81 | 5362724.60 | 0.00 | 0.250090E+10 | 0.00 | 1.18 |
August | 0.106186E+10 | 0.123333E+09 | 0.00 | 7115696.20 | 3695306.99 | 0.00 | 0.198773E+10 | 0.00 | 1.20 |
September | 0.221168E+10 | 2892133.19 | 0.00 | 4140589.54 | 341087.03 | 17538043.00 | 0.176786E+10 | 0.00 | 1.02 |
October | 0.299614E+10 | 0.00 | 0.00 | 890478.86 | 0.00 | 0.401983E+09 | 0.585895E+09 | 0.00 | 0.68 |
November | 0.225719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153342E+10 | 0.00 | 0.00 | 0.54 |
December | 0.156685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242923E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.241547E+11 | 0.169667E+09 | 0.00 | 34796111.84 | 10361682.88 | 0.974058E+10 | 0.153179E+11 | 0.00 | 0.80 |
Minimum of Months | 0.106186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.344633E+10 | 0.123333E+09 | 0.00 | 7853004.81 | 5362724.60 | 0.267010E+10 | 0.364221E+10 | 0.00 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.243500E+10 | 0.00 | 0.00 | 791175.86 | 0.00 | 0.245082E+10 | 0.621443E+09 | 0.00 | 0.40 |
February | 0.246105E+10 | 0.00 | 0.00 | 3151729.55 | 0.00 | 0.145519E+10 | 0.199715E+10 | 0.00 | 0.54 |
March | 0.306582E+10 | 0.00 | 0.00 | 5408260.99 | 0.00 | 0.754786E+09 | 0.384778E+10 | 0.00 | 0.69 |
April | 0.254239E+10 | 917153.33 | 0.00 | 5543295.47 | 0.00 | 0.418139E+09 | 0.347698E+10 | 0.00 | 0.72 |
May | 0.285018E+10 | 803212.81 | 0.00 | 5550906.59 | 0.00 | 85713658.66 | 0.340020E+10 | 0.00 | 0.81 |
June | 0.234175E+10 | 214271.55 | 0.00 | 6237187.73 | 644575.47 | 4936951.48 | 0.304958E+10 | 0.00 | 0.87 |
July | 0.169025E+10 | 71711624.83 | 0.00 | 7306830.13 | 6165268.37 | 0.00 | 0.252085E+10 | 0.00 | 0.90 |
August | 0.151906E+10 | 0.248677E+09 | 0.00 | 7452593.38 | 3868448.29 | 0.00 | 0.206289E+10 | 0.00 | 0.96 |
September | 0.249747E+10 | 12724724.44 | 0.00 | 11096104.44 | 0.00 | 37844878.51 | 0.377367E+10 | 0.00 | 1.15 |
October | 0.268977E+10 | 0.00 | 0.00 | 7130912.25 | 0.00 | 0.392180E+09 | 0.430999E+10 | 0.00 | 0.85 |
November | 0.294028E+10 | 0.00 | 0.00 | 1608336.33 | 0.00 | 0.135985E+10 | 0.901970E+09 | 0.00 | 0.49 |
December | 0.231034E+10 | 0.00 | 0.00 | 1586069.61 | 0.00 | 0.216713E+10 | 0.111993E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.293434E+11 | 0.335048E+09 | 0.00 | 62863402.32 | 10678292.13 | 0.912659E+10 | 0.310824E+11 | 0.00 | 0.74 |
Minimum of Months | 0.151906E+10 | 0.00 | 0.00 | 791175.86 | 0.00 | 0.00 | 0.621443E+09 | 0.00 | 0.40 |
Maximum of Months | 0.306582E+10 | 0.248677E+09 | 0.00 | 11096104.44 | 6165268.37 | 0.245082E+10 | 0.430999E+10 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.214796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245523E+10 | 0.00 | 0.00 | 0.52 |
February | 0.269656E+10 | 0.00 | 0.00 | 175197.51 | 0.00 | 0.136701E+10 | 0.131835E+09 | 0.00 | 0.59 |
March | 0.371100E+10 | 0.00 | 0.00 | 787769.21 | 0.00 | 0.545848E+09 | 0.742297E+09 | 0.00 | 0.69 |
April | 0.295544E+10 | 554018.86 | 0.00 | 2708158.87 | 80319.70 | 0.231345E+09 | 0.165824E+10 | 0.00 | 0.84 |
May | 0.270499E+10 | 484604.99 | 0.00 | 6827883.79 | 0.00 | 36151996.19 | 0.273583E+10 | 0.00 | 1.13 |
June | 0.214269E+10 | 586414.77 | 0.00 | 6666415.07 | 566845.43 | 304250.47 | 0.265377E+10 | 0.00 | 1.27 |
July | 0.138032E+10 | 0.110119E+09 | 0.00 | 8838438.76 | 438707.23 | 0.00 | 0.244903E+10 | 0.00 | 1.37 |
August | 0.140706E+10 | 0.203709E+09 | 0.00 | 6326692.88 | 3693067.62 | 0.00 | 0.155642E+10 | 0.00 | 1.21 |
September | 0.273727E+10 | 2641950.83 | 0.00 | 4642478.77 | 1266028.60 | 343658.34 | 0.156062E+10 | 0.00 | 1.15 |
October | 0.350792E+10 | 0.00 | 0.00 | 989124.93 | 0.00 | 0.302670E+09 | 0.669113E+09 | 0.00 | 0.77 |
November | 0.305176E+10 | 0.00 | 0.00 | 30819.49 | 0.00 | 0.109395E+10 | 35119985.15 | 0.00 | 0.59 |
December | 0.238107E+10 | 0.00 | 0.00 | 447.05 | 0.00 | 0.201520E+10 | 5843146.26 | 0.00 | 0.52 |
Annual Sum or Average | 0.308240E+11 | 0.318095E+09 | 0.00 | 37993426.35 | 6044968.59 | 0.804805E+10 | 0.141981E+11 | 0.00 | 0.89 |
Minimum of Months | 0.138032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.371100E+10 | 0.203709E+09 | 0.00 | 8838438.76 | 3693067.62 | 0.245523E+10 | 0.273583E+10 | 0.00 | 1.37 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:58:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.565341E+09 | 0.00 | 0.00 | 0.416934E+12 | 0.00 | 9.08 |
February | 0.00 | 0.00 | 0.00 | 0.967186E+09 | 0.00 | 0.00 | 0.625867E+12 | 0.00 | 16.71 |
March | 0.00 | 0.00 | 0.00 | 0.163202E+10 | 0.00 | 0.00 | 0.985250E+12 | 0.00 | 27.29 |
April | 0.00 | 66512.39 | 0.00 | 0.243362E+10 | 0.00 | 0.00 | 0.107968E+13 | 0.00 | 37.38 |
May | 0.00 | 0.00 | 0.00 | 0.466957E+09 | 0.00 | 0.00 | 0.270920E+12 | 0.00 | 13.02 |
June | 0.00 | 0.00 | 0.00 | 0.111391E+10 | 0.00 | 0.00 | 0.486677E+12 | 0.00 | 28.05 |
July | 0.00 | 0.118087E+10 | 0.00 | 0.213676E+10 | 0.00 | 0.00 | 0.594059E+12 | 0.00 | 39.17 |
August | 0.00 | 0.313600E+10 | 0.00 | 0.286579E+10 | 0.00 | 0.00 | 0.437712E+12 | 0.00 | 40.15 |
September | 0.00 | 0.00 | 0.00 | 0.594614E+09 | 0.00 | 0.00 | 0.310669E+12 | 0.00 | 18.16 |
October | 0.00 | 0.00 | 0.00 | 0.108558E+10 | 0.00 | 0.00 | 0.557046E+12 | 0.00 | 20.88 |
November | 0.00 | 0.00 | 0.00 | 0.143947E+10 | 0.00 | 0.00 | 0.715913E+12 | 0.00 | 21.88 |
December | 0.00 | 0.00 | 0.00 | 0.133729E+10 | 0.00 | 0.00 | 0.683921E+12 | 0.00 | 16.67 |
Annual Sum or Average | 0.00 | 0.431693E+10 | 0.00 | 0.166385E+11 | 0.00 | 0.00 | 0.716464E+13 | 0.00 | 24.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.466957E+09 | 0.00 | 0.00 | 0.270920E+12 | 0.00 | 9.08 |
Maximum of Months | 0.00 | 0.313600E+10 | 0.00 | 0.286579E+10 | 0.00 | 0.00 | 0.107968E+13 | 0.00 | 40.15 |